HomeMy WebLinkAboutRES16_CCD-004.2 Civil Construction Permit Revisions_Street Lighting_signed (1)
CAPITAL PLANNING & CONSTRUCTION
RSD CCD-2020-2
PROJECT: RENTON ELEMENTARY SCHOOL #16 CCD NO.: CCD-004.2
CONTRACTOR: CORNERSTONE GENERAL CONTRACTORS DATE: 10/24/2022
CONSTRUCTION CHANGE DIRECTIVE
Item.: Civil Construction Permit Revisions – Street Lighting
Ref. Drawing and/or Spec.: See attachments
In order to expedite the work and avoid delays in the work, the Contract documents are hereby amended
as described below and/or detailed on the attachments referred to:
In addition to revisions per CCD-004 and CCD-004.1 provide modifications to Contract Documents for
Right-of-Way street lighting per attached documents. Refer to attached updated sheets for clouded scope
revisions.
Attachments:
Narrative for electrical drawing revisions.
Civil Drawings (updated): C6.2, C6.3, C6.4
Electrical Drawings (updated): E0.04, E1.00
You are directed to proceed with this work immediately.
Performance of this Construction Change Directive will be accomplished:
☐ With no change to the Contract Sum / Contract Time.
☐ With a lump sum increase / decrease of $ to the Contract Sum, per COR- .
☐ With a unit price / labor and materials basis with a maximum allowable increase / decrease of $
to the Contract Sum. Costs to be sustained in accordance with the General Conditions (Submit Change
in Work Cost Summary Form).
☒ With work to start immediately and determination of any change to the Contract Sum and/or Contract
Time to be negotiated within twenty-one (21) calendar days after authorization (Submit Change in Work
Cost Summary Form).
CAPITAL PLANNING & CONSTRUCTION
RSD CCD-2020-2
☐ With a Contract Time increase / decrease of calendar days.
☐
ARCHITECT/ENGINEER SIGNATURE: DATE:
CONTRACTOR SIGNATURE: DATE:
OWNER SIGNATURE: DATE: ET 10-24-2022
OCTOBER 19, 2022
Hutteball + Oremus Architecture
4010 Lake Washington Blvd NE #320
Kirkland, WA 98033
ATTENTION Ingrida Sanders
REGARDING Renton ES #16 CCD-004.2
In addition to the contents of CCD-004 and CCD-004.1, revise the contract documents as follows:
E0.04
Add type SL4 as indicated on attached full-sized sheet.
E1.00
Revise the two fixtures as indicated on attached full-sized sheet.
On behalf of HARGIS ENGINEERS,
Taylor VanderKley
m:\jobs\20\20095\ca\contract changes\ccd\ccd-004 - civil permit comments\20095eccd 20221019 - ccd-
004.2 - civil permit comments.docx
1932 First AveSuite 201Seattle, WA 98101p. 206.725.1211f. 206.973.5344www.lpdengineering.comengineering pllcIN COMPLIANCE WITH CITY OF RENTON STANDARDS1932 First AveSuite 201Seattle, WA 98101p. 206.725.1211f. 206.973.5344www.lpdengineering.comengineering pllcTED-40-4192
LUA:21-000167PR:20-000097C:21-004289R-41924010 LAKE WASHINGTON BLVD NESUITE 320KIRKLAND, WA 98033425.828.8948HOARCH.COMPROJECT INFORMATIONCONSULTANT STAMPARCHITECT STAMPSCHOOL DISTRICT LOGOPROJECT NUMBER:SHEET NAMESHEET NUMBER1HZ(OHPHQWDU\1R.1075 Duvall Avenue NERenton, WA 98059R(17O16CHOO/',67R,C71O.11.4.2020SCHEMATIC DESIGN1.21.202150% DESIGN DEVELOPMENT3.26.2021100% DESIGN DEVELOPMENT8.27.2021PERMIT SUBMITTAL11.12.202175% CONTRACT DOCUMENTS12.3.202190% CONTRACT DOCUMENTS12.20.2021PERMIT RESUBMITTAL1.20.2022BP-06.11.24.2022BID SET2.17.2022ADDENDUM NO.32.24.2022ADDENDUM NO.43.4.2022CONFORMED SET5.26.2022PERMIT RESUBMITTALCO1)ORM('6(73.4.20222014PR114510.07.2022CCD 004.2C.)RO17A*(3/A1'89A//A9(1(Know what's below.Call before you dig.Dial 811
1932 First AveSuite 201Seattle, WA 98101p. 206.725.1211f. 206.973.5344www.lpdengineering.comengineering pllcIN COMPLIANCE WITH CITY OF RENTON STANDARDS1932 First AveSuite 201Seattle, WA 98101p. 206.725.1211f. 206.973.5344www.lpdengineering.comengineering pllcTED-40-4192
LUA:21-000167PR:20-000097C:21-004289R-41924010 LAKE WASHINGTON BLVD NESUITE 320KIRKLAND, WA 98033425.828.8948HOARCH.COMPROJECT INFORMATIONCONSULTANT STAMPARCHITECT STAMPSCHOOL DISTRICT LOGOPROJECT NUMBER:SHEET NAMESHEET NUMBER1HZ(OHPHQWDU\1R.1075 Duvall Avenue NERenton, WA 98059R(17O16CHOO/',67R,C71O.11.4.2020SCHEMATIC DESIGN1.21.202150% DESIGN DEVELOPMENT3.26.2021100% DESIGN DEVELOPMENT8.27.2021PERMIT SUBMITTAL11.12.202175% CONTRACT DOCUMENTS12.3.202190% CONTRACT DOCUMENTS12.20.2021PERMIT RESUBMITTAL1.20.2022BP-06.11.24.2022BID SET2.17.2022ADDENDUM NO.32.24.2022ADDENDUM NO.43.4.2022CONFORMED SET5.26.2022PERMIT RESUBMITTALCO1)ORM('6(73.4.20222014PR114510.07.2022CCD 004.2C.)RO17A*(3/A1'89A//A9(1(Know what's below.Call before you dig.Dial 811
PARCEL B-1 OF LOT 7STA 918+34.3, 35.0'L4'x4' OFFLINE TBBUSTA 919+00.3, 38.5'LTTRENCH DRAIN END4" IE=419.424"-45° VERT BND (PVC)STA 918+03.1, 38.5'LTTRENCH DRAIN ENDSEE DETAIL4" IE=421.624"-45° VERT BND (PVC)STA 917+87.1, 38.5'LTTRENCH DRAIN BEGINSEE DETAILIE=421.851932 First AveSuite 201Seattle, WA 98101p. 206.725.1211f. 206.973.5344www.lpdengineering.comengineering pllcIN COMPLIANCE WITH CITY OF RENTON STANDARDS1932 First AveSuite 201Seattle, WA 98101p. 206.725.1211f. 206.973.5344www.lpdengineering.comengineering pllcTED-40-4192
LUA:21-000167PR:20-000097C:21-004289R-41924010 LAKE WASHINGTON BLVD NESUITE 320KIRKLAND, WA 98033425.828.8948HOARCH.COMPROJECT INFORMATIONCONSULTANT STAMPARCHITECT STAMPSCHOOL DISTRICT LOGOPROJECT NUMBER:SHEET NAMESHEET NUMBER1HZ(OHPHQWDU\1R.1075 Duvall Avenue NERenton, WA 98059R(17O16CHOO/',67R,C71O.11.4.2020SCHEMATIC DESIGN1.21.202150% DESIGN DEVELOPMENT3.26.2021100% DESIGN DEVELOPMENT8.27.2021PERMIT SUBMITTAL11.12.202175% CONTRACT DOCUMENTS12.3.202190% CONTRACT DOCUMENTS12.20.2021PERMIT RESUBMITTAL1.20.2022BP-06.11.24.2022BID SET2.17.2022ADDENDUM NO.32.24.2022ADDENDUM NO.43.4.2022CONFORMED SET5.26.2022PERMIT RESUBMITTALCO1)ORM('6(73.4.20222014PR114510.07.2022CCD 004.2C.)RO17A*(3/A1'89A//A9(1(Know what's below.Call before you dig.Dial 811
1. VERIFY EXIT SIGN COLOR WITH AHJ PRIOR TO ORDERING.
2. SEE SHEET E1.00 FOR POLE LOCATIONS WITH DOUBLE, TRIPLE, OR QUADRUPLE HEADS.
3. SEE CITY OF RENTON STREET LIGHTING DETAILS ON SHEETS E7.08 AND E7.09 FOR ADDITIONAL INFORMATION.
4. POLE HEIGHT SHALL BE 3'-0" FROM TOP OF HIGHEST LUMINAIRE MOUNTING BRACKET.
5. PROGRAM OCCUPANCY SENSOR TIME DELAY SETTING DURATION OF 15 MINUTES. IF COMBINATION PHOTOCELL IS
PROVIDED, FACTORY DISABLE PHOTOCELL INPUT.
LIGHT FIXTURE SCHEDULE NOTES
LIGHT FIXTURE SCHEDULE
TYPE DESCRIPTION MANUFACTURER MODEL SERIES
LIGHT
SOURCE
COLOR
TEMP
DELIVERED
LUMENS
INPUT
WATTS FINISH REMARKS CO-LISTED FIXTURE
D1 6" RECESSED LED ROUND DOWNLIGHT WITH SEMI-SPECULAR REFLECTOR NON-CONDUCTIVE TRIM WHITE FLANGE AND SATINE LENS WITH MEDIUM DISTRIBUTION GOTHAM LIGHTING EVO6 LED SERIES LED 3,500 1,500 15 WHITE COOPER LIGHING - PORTOFLIO
LD6B
E1 7" PROFILE X 13"X 26" 24' TALL ARM-MOUNTED SITE FIXTURE, DIECAST ALUMINUM HOUSING, IP66 RATED, ANSI C136.31 VIBRATION RATED, 40-DEGREE AMBIENT TEMP RATED, 50-100% OCCUPANCY SENSOR INTEGRAL TO HEAD WITH SAME
FINISH AS FIXTURE - TYPE II MEDIUM DISTRIBUTION 1050mA DRIVE CURRENT 20 LED COUNT. PROVIDE 5" DIAMETER STRAIGHT ROUND STEEL POLE SEVEN-GAUGE POLE THICKNESS MINIMUM AND 9.0 EPA RATING AT 90 MPH WITH AN
ADDITIONAL CAPACITY OF 100LBS FOR CAMERA EQUIPMENT. PROVIDE METAL BOLT COVER SHROUD AND TAMPERPROOF FASTENERS
LITHONIA LIGHTING DSX0 LED SERIES LED 3,500 8,200 71 BRONZE 2,5 MCGRAW-EDISON - GALLEON I
E2 7" PROFILE X 13"X 26" 24' TALL ARM-MOUNTED SITE FIXTURE, DIECAST ALUMINUM HOUSING, IP66 RATED, ANSI C136.31 VIBRATION RATED, 40-DEGREE AMBIENT TEMP RATED, 50-100% OCCUPANCY SENSOR INTEGRAL TO HEAD WITH SAME
FINISH AS FIXTURE - TYPE II MEDIUM DISTRIBUTION 700 mA DRIVE CURRENT 40 LED COUNT. PROVIDE 5" DIAMETER STRAIGHT ROUND STEEL POLE SEVEN-GAUGE POLE THICKNESS MINIMUM AND9.0 EPA RATING AT 90 MPH WITH AN
ADDITIONAL CAPACITY OF 100LBS FOR CAMERA EQUIPMENT. PROVIDE METAL BOLT COVER SHROUD AND TAMPERPROOF FASTENERS
LITHONIA LIGHTING DSX0 LED SERIES LED 3,500 10,876 89 BRONZE 2,5 MCGRAW-EDISON - GALLEON I
E3 7" PROFILE X 13"X 26" 24' TALL ARM-MOUNTED SITE FIXTURE, DIECAST ALUMINUM HOUSING, IP66 RATED, ANSI C136.31 VIBRATION RATED, 40-DEGREE AMBIENT TEMP RATED, 50-100% OCCUPANCY SENSOR INTEGRAL TO HEAD WITH SAME
FINISH AS FIXTURE - TYPE III MEDIUM DISTRIBUTION WITH EXTERNAL HOUSE SIDE SHIELDS AND EXTERNAL GLARE SHIELDS 700 mA DRIVE CURRENT 40 LED COUNT. PROVIDE 5" DIAMETER STRAIGHT ROUND STEEL POLE SEVEN-GAUGE
POLE THICKNESS MINIMUM AND 9.0 EPA RATING AT 90 MPH WITH AN ADDITIONAL CAPACITY OF 100LBS FOR CAMERA EQUIPMENT. PROVIDE METAL BOLT COVER SHROUD AND TAMPERPROOF FASTENERS
LITHONIA LIGHTING DSX0 LED SERIES LED 3,500 10,849 89 BRONZE 2,5 MCGRAW-EDISON - GALLEON I
E4 7" PROFILE X 13"X 26" 24' TALL ARM-MOUNTED SITE FIXTURE, DIECAST ALUMINUM HOUSING, IP66 RATED, ANSI C136.31 VIBRATION RATED, 40-DEGREE AMBIENT TEMP RATED, 50-100% OCCUPANCY SENSOR INTEGRAL TO HEAD WITH SAME
FINISH AS FIXTURE - TYPE IV MEDIUM DISTRIBUTION 700 mA DRIVE CURRENT 40 LED COUNT. PROVIDE 5" DIAMETER STRAIGHT ROUND STEEL POLE SEVEN-GAUGE POLE THICKNESS MINIMUM AND 9.0 EPA RATING AT 90 MPH WITH AN
ADDITIONAL CAPACITY OF 100LBS FOR CAMERA EQUIPMENT. PROVIDE METAL BOLT COVER SHROUD AND TAMPERPROOF FASTENERS
LITHONIA LIGHTING DSX0 LED SERIES LED 3,500 10,613 89 BRONZE 2,5 MCGRAW-EDISON - GALLEON I
E5 24"X4"X24" 13' TALL POLE TOP SITE FIXTURE, DIECAST ALUMINUM HOUSING, IP66 RATED. PROVIDE 4" DIAMETER STRAIGHT ROUND STEEL POLE, ELEVEN-GAUGE POLE THICKNESS MINIMUM WITH METAL BOLT COVER SHROUD. PROVIDE
TAMPERPROOF FASTENERS
LITHONIA LIGHTING RADEAN ARM MOUNT LED 3,500 6,781 65 BRONZE VISIONAIRE LIGHTING - LUSSO
MEDIUM
E6 7" PROFILE X 15"X 22" 24' TALL ARM-MOUNTED SITE FIXTURE, DIECAST ALUMINUM HOUSING, IP66 RATED, ANSI C136.31 VIBRATION RATED, 40 DEGREE AMBIENT TEMP RATED, 50-100% OCCUPANCY SENSOR INTEGRAL TO HEAD WITH SAME
FINISH AS FIXTURE - LCCO DISTRIBUTION OPTIC SHALL BE ORIENTED TO AVOID LIGHT SPILL OFF AT WEST PORTION OF SITE, 1050 mA DRIVE CURRENT 20 LED COUNT. PROVIDE 5" DIAMETER STRAIGHT ROUND STEEL POLE SEVEN-GAUGE
POLE THICKNESS MINIMUM AND 9.0 EPA RATING AT 90 MPH WITH AN ADDITIONAL CAPACITY OF 100LBS FOR CAMERA EQUIPMENT. PROVIDE METAL BOLT COVER SHROUD AND TAMPERPROOF FASTENERS
LITHONIA LIGHTING DSX0 LED SERIES LED 3,500 4,784 71 BRONZE MCGRAW-EDISON - GALLEON I
E7 12"X4.5"X4" EXTERIOR WALL-MOUNTED ARCHITECTURAL LED FIXTURE. WET LOCATION RATED, DIECAST ALUMINUM HOUSING WITH MATTE SAFETY GLASS LENS BEGA LIGHTING 22360 LED SERIES LED 3,500 1,024 16 BRONZE PERFORMANCE IN LIGHTING -
QUASAR 30 TECH
E8 9"X18"X12" EXTERIOR WALL-MOUNTED QUARTER SPHERE LED FIXTURE. IP65 RATED WITH INTEGRAL MOTION SENSOR THE SAME FINISH AS FIXTURE FOR 50-100% DIMMING. TYPE III DISTRIBUTION AND 600 mA DRIVER CURRENT LITHONIA LIGHTING WSQ LED SERIES LED 3,500 3,129 29 BRONZE MCGRAW-EDISON - IMPACT
ELITE LED QUARTER SPHERE
E9 12"X12"X5" DIE CAST ALUMINUM BASE, SURFACE-MOUNTED, WET RATED, TAMPERPROOF LED FIXTURE WITH CLEAR POLYCARBONATE LENS LUMINAIRE LED LIGHTING SWP 1212 LED SERIES LED 3,500 2,900 25 BRONZE FAIL-SAFE - G12
E10 3.5"X3.5"X4' LED SURFACE-MOUNTED LIGHT FIXTURE. EXTRUDED DIFFUSE ACRYLIC CONTINUOUS HE TECH LENS. HYBRID ALUMINUM HOUSING WITH ALUMINUM END CAPS AND POWDER COAT FINISH. 0-10V DIMMING DRIVER A-LIGHT ARCHITECTURAL LIGHTING D3 LED SURFACE SERIES LED 3,500 400 LM/FT 18 BRONZE PINNACLE - EDGE EX3WET
E11 12"X12"X6" CYLINDER LED FLOOD LIGHT FIXTURE, 30 DEGREE BEAM ANGLE WITH 360 DEGREE GLARE SHIELD AND 5"DIAMETER POLE-MOUNT ARM MOUNTED TO E5 LUMINAIRE LIGHT POLE AT +12' AFG LUMINIS SC655 SERIES SCOPO LED LED 4,000 4,102 48 BRONZE HK USA LIGHTING GROUP -
ZXL30i
F1 3.5"X3.5"X4' LED RECESSED FLANGE-MOUNTED LIGHT FIXTURE. EXTRUDED DIFFUSE ACRYLIC CONTINUOUS HE TECH LENS. HYBRID ALUMINUM HOUSING WITH ALUMINUM END CAPS AND POWDER COAT FINISH. 0-10V DIMMING DRIVER A-LIGHT ARCHITECTURAL LIGHTING D5 LED RECESSED SERIES LED 3,500 400 LM/FT 18 WHITE PINNACLE - EDGE EV3D
F1X SAME AS TYPE F1 WITH INTEGRAL EMERGENCY LIGHTING TRANSFER DEVICE A-LIGHT ARCHITECTURAL LIGHTING D5 LED RECESSED SERIES LED 3,500 400 LM/FT 18 WHITE PINNACLE - EDGE EV3D
F2 3.5"X3.5"X8' LED RECESSED FLANGE-MOUNTED LIGHT FIXTURE. EXTRUDED DIFFUSE ACRYLIC CONTINUOUS HE TECH LENS. HYBRID ALUMINUM HOUSING WITH ALUMINUM END CAPS AND POWDER COAT FINISH. 0-10V DIMMING DRIVER A-LIGHT ARCHITECTURAL LIGHTING D5 LED RECESSED SERIES LED 3,500 400 LM/FT 36 WHITE PINNACLE - EDGE EV3D
F3 3.5"X3.5"X4' LED RECESSED FLANGE-MOUNTED LIGHT FIXTURE. EXTRUDED DIFFUSE ACRYLIC CONTINUOUS HE TECH LENS. HYBRID ALUMINUM HOUSING WITH ALUMINUM END CAPS AND POWDER COAT FINISH. 0-10V DIMMING DRIVER A-LIGHT ARCHITECTURAL LIGHTING D5 LED RECESSED SERIES LED 3,500 750 LM/FT 38 WHITE PINNACLE - EDGE EV3D
F3X SAME AS TYPE F3 WITH INTEGRAL EMERGENCY LIGHTING TRANSFER DEVICE A-LIGHT ARCHITECTURAL LIGHTING D5 LED RECESSED SERIES LED 3,500 750 LM/FT 38 WHITE PINNACLE - EDGE EV3D
F4X 3.5"X3.5"X6' LED RECESSED FLANGE-MOUNTED LIGHT FIXTURE. EXTRUDED DIFFUSE ACRYLIC CONTINUOUS HE TECH LENS. HYBRID ALUMINUM HOUSING WITH ALUMINUM END CAPS AND POWDER COAT FINISH. 0-10V DIMMING DRIVER AND
INTEGRAL EMERGENCY LIGHTING TRANSFER DEVICE
A-LIGHT ARCHITECTURAL LIGHTING D5 LED RECESSED SERIES LED 3,500 400 LM/FT 27 WHITE PINNACLE - EDGE EV3D
G1 2'X4' RECESSED GRID-MOUNTED LED TROFFER FIXTURE. HYBRID ALUMINUM STEEL DOOR FRAME, SOFT-WHITE ACRYLIC LENS. TWO-CHANNEL TUNABLE LIGHTING CONTROLS FROM 2700K-6500K WITH 0-10V DIMMING DRIVER MARK ARCHITECTURAL LIGHTING WHSPR TUNABLE LED SERIES LED TUNABLE 4,800 39 WHITE PINNACLE - LUCEN LU24 LED
G2 2'X4' RECESSED GRID-MOUNTED LED TROFFER FIXTURE. HYBRID ALUMINUM STEEL DOOR FRAME, SOFT-WHITE ACRYLIC LENS AND 0-10V DIMMING DRIVER MARK ARCHITECTURAL LIGHTING WHSPR LED SERIES LED 3,500 4,879 41 WHITE PINNACLE - LUCEN LU24 LED
G3 2'X2' RECESSED GRID-MOUNTED LED TROFFER FIXTURE. HYBRID ALUMINUM STEEL DOOR FRAME, SOFT-WHITE ACRYLIC LENS. TWO-CHANNEL TUNABLE LIGHTING CONTROLS FROM 2700K-6500K WITH 0-10V DIMMING DRIVER MARK ARCHITECTURAL LIGHTING WHSPR TUNABLE LED SERIES LED TUNABLE 4,000 39 WHITE PINNACLE - LUCEN LU22 LED
G4 2'X2' RECESSED GRID-MOUNTED LED TROFFER FIXTURE. HYBRID ALUMINUM STEEL DOOR FRAME, SOFT-WHITE ACRYLIC LENS AND 0-10V DIMMING DRIVER MARK ARCHITECTURAL LIGHTING WHSPR LED SERIES LED 3,500 4,879 45 WHITE PINNACLE - LUCEN LU22 LED
G5 3.5"X3.5"X4' LED RECESSED GRID-MOUNTED LIGHT FIXTURE. EXTRUDED DIFFUSE ACRYLIC CONTINUOUS HE TECH LENS. HYBRID ALUMINUM HOUSING. 0-10V DIMMING DRIVER A-LIGHT ARCHITECTURAL LIGHTING D5 LED RECESSED SERIES LED 3,500 750 LM/FT 38 WHITE PINNACLE - EDGE EV3D
G6 2'X4' RECESSED GRID-MOUNTED LED TROFFER FIXTURE. HYBRID ALUMINUM STEEL DOOR FRAME, SOFT-WHITE ACRYLIC LENS AND 0-10V DIMMING DRIVER MARK ARCHITECTURAL LIGHTING WHSPR LED SERIES LED 3,500 6,086 53 WHITE PINNACLE - LUCEN LU24 LED
G7 2'X4' RECESSED GRID-MOUNTED GASKETED LED FIXTURE WITH INVERTED PRISMATIC LENS AND ALUMINUM DOOR FRAME LITHONIA LIGHTING 2GTL LED SERIES LED 3,500 4,879 41 WHITE COOPER LIGHTING - METALUX
24GR
H1 23"X14"X2" SUSPENDED HIGH-BAY LED LIGHT FIXTURE. FROSTED WIDE DISTRIBUTION LENS, CABLE-READY MOUNTING AND 0-10V DIMMING DRIVER LITHONIA LIGHTING IBG SERIES LED 3,500 21,743 129 WHITE FLEX LIGHTING - ESSENTIALS
ES40P LED SERIES
P1 3.5"X5.5"X4' LED SUSPENSION PENDANT-MOUNTED LIGHT FIXTURE. EXTRUDED DIFFUSE ACRYLIC CONTINUOUS BOTTOM LENS AND RIGID DIFFUSE TOP DUST COVER. DIRECT SYMMETRIC/INDIRECT SYMMETRIC WIDE OPTICS. ALUMINUM
HOUSING WITH ALUMINUM END CAPS AND POWDER COAT FINISH. 0-10V DIMMING DRIVER
A-LIGHT ARCHITECTURAL LIGHTING ACCOLADE D2 LED PENDANT
SERIES
LED 3,500 950 LM/FT
DOWN - 412
LM/FT UP
59 TBD PINNACLE - EDGE EX3DI
P2 19" DIAMETER X 11" TALL HOLLOW CYLINDRICAL STEM-MOUNTED INDIRECT/DIRECT LED LIGHT FIXTURE. ALUMINUM HOUSING, POWDER COAT FINISH, POLYETHYLENE LENS AND INTEGRAL 0-10V DIMMING DRIVER LUMINIS LIGHTING HOLLOWCORE HC1600 LED
SERIES
LED 3,500 6,338 UP/2,144
DOWN
76 TBD BETA CALCO - TRIPLE
P3 19" DIAMETER X 11" TALL HOLLOW CYLINDRICAL STEM-MOUNTED INDIRECT/DIRECT LED LIGHT FIXTURE. ALUMINUM HOUSING, POWDER COAT FINISH, POLYETHYLENE LENS AND INTEGRAL 0-10V DIMMING DRIVER LUMINIS LIGHTING HOLLOWCORE HC1600 LED
SERIES
LED 3,500 9,731
DOWN/2,144 UP
123 TBD BETA CALCO - TRIPLE
P4 6"x3" DIE-CAST ALUMINUM CYLINDRICAL PENDANT LED FIXTURE AND THREE-PLY OPAL GLASS WITH 0-10V DIMMING DRIVER BEGA LIGHTING 50 702 LED 3,500 512 6 WHITE LITON - LCMPD5RP
P5 3.5"X5.5"X8' LED SUSPENSION PENDANT-MOUNTED LIGHT FIXTURE. EXTRUDED DIFFUSE ACRYLIC CONTINUOUS BOTTOM LENS AND RIGID DIFFUSE TOP DUST COVER. DIRECT SYMMETRIC WIDE OPTICS. ALUMINUM HOUSING WITH ALUMINUM
END CAPS AND POWDER COAT FINISH. 0-10V DIMMING DRIVER
A-LIGHT ARCHITECTURAL LIGHTING ACCOLADE D2 LED PENDANT
SERIES
LED 3,500 950 LM/FT 80 TBD PINNACLE - EDGE EX3D
S1 2"X4' INDUSTRIAL LED FLAT DIFFUSED LENSED STRIP FIXTURE WITH SQUARE/FLAT FULL FROST LENS LITHONIA LIGHTING ZL1N LED SERIES LED 3,500 900 LM/FT 35 WHITE METALUX - SNLED LENSED
S1BX SAME AS TYPE S1X WITH 120V DRIVER AND EMERGENCY LIGHTING TRANSFER DEVICE LITHONIA LIGHTING ZL1N LED SERIES LED 3,500 900 LM/FT 35 WHITE METALUX - SNLED LENSED
S1X SAME AS TYPE S1 WITH INTEGRAL EMERGENCY LIGHTING TRANSFER DEVICE LITHONIA LIGHTING ZL1N LED SERIES LED 3,500 900 LM/FT 35 WHITE METALUX - SNLED LENSED
S2X NEMA-4X RATED INDUSTRIAL LED STRIP FIXTURE WITH 120V DRIVER AND INTEGRAL BATTERY LITHONIA LIGHTING LITHONIA FEM ELD SERIES LED 4,000 1000 LM/FT 30 WHITE METALUX - VAPORTITE LED
SL1 TYPE III LED DOME STYLE STREET LIGHT FIXTURE, MAXIMUM 750mA DRIVE CURRENT, PROVIDE 10" BASE ALUMINUM HEAT TREATED POLE AND FOUNDATION WITH REINFORCED ALUMINUM HANDHOLE, GROUND CONNECTOR WITH ALUMINUM
DOOR AND GASKET, DECORATIVE POLEBASE, UTILITY DECAL NUMBERING, 10' ALUMINUM LUMINAIRE ARM, AND ROUND POLE CAP PER CITY OF RENTON MUNICIPAL CODE AND ENGINEERING STANDARDS. FIXTURE MOUNTING HEIGHT IS 35'-0"
ABOVE ROADWAY FINISHED GRADE
CYCLONE LIGHTING DOMIA PENDANT CY55P1A LED
SERIES
LED 4,000 14,700 120 RAL 9005TX,
JET BLACK
2,3,4 KING LUMINAIRE K831 LED
SERIES
SL2 TYPE II LED DOME STYLE STREET LIGHT FIXTURE, MAXIMUM 750mA DRIVE CURRENT, PROVIDE 6" BASE ALUMINUM HEAT TREATED POLE AND FOUNDATION WITH REINFORCED ALUMINUM HANDHOLE, GROUND CONNECTOR WITH ALUMINUM
DOOR AND GASKET, DECORATIVE POLEBASE, UTILITY DECAL NUMBERING, 4' ALUMINUM LUMINAIRE ARM, AND ROUND POLE CAP PER CITY OF RENTON MUNICIPAL CODE AND ENGINEERING STANDARDS. FIXTURE MOUNTING HEIGHT IS 16'-6"
ABOVE ROADWAY FINISHED GRADE
CYCLONE LIGHTING DOMIA PENDANT CY55P1A LED
SERIES
LED 4,000 4,500 40 RAL 9005TX,
JET BLACK
2,3,4 KING LUMINAIRE K731 LED
SERIES
SL3 TYPE II LED DOME STYLE STREET LIGHT FIXTURE, MAXIMUM 750mA DRIVE CURRENT, PROVIDE 6" BASE ALUMINUM HEAT TREATED POLE AND FOUNDATION WITH REINFORCED ALUMINUM HANDHOLE, GROUND CONNECTOR WITH ALUMINUM
DOOR AND GASKET, DECORATIVE POLEBASE, UTILITY DECAL NUMBERING, 4' ALUMINUM LUMINAIRE ARM, AND ROUND POLE CAP PER CITY OF RENTON MUNICIPAL CODE AND ENGINEERING STANDARDS. FIXTURE MOUNTING HEIGHT IS 16'-6"
ABOVE ROADWAY FINISHED GRADE
CYCLONE LIGHTING DOMIA PENDANT CY55P1A LED
SERIES
LED 4,000 4,500 40 RAL 9005TX,
JET BLACK
2,3,4 KING LUMINAIRE K731 LED
SERIES
SL4 TYPE III LED DOME STYLE STREET LIGHT FIXTURE, MAXIMUM 750mA DRIVE CURRENT, PROVIDE 10" BASE ALUMINUM HEAT TREATED POLE AND FOUNDATION WITH REINFORCED ALUMINUM HANDHOLE, GROUND CONNECTOR WITH ALUMINUM
DOOR AND GASKET, DECORATIVE POLEBASE, UTILITY DECAL NUMBERING, 4' ALUMINUM LUMINAIRE ARM, AND ROUND POLE CAP PER CITY OF RENTON MUNICIPAL CODE AND ENGINEERING STANDARDS. FIXTURE MOUNTING HEIGHT IS 35'-0"
ABOVE ROADWAY FINISHED GRADE
CYCLONE LIGHTING DOMIA PENDANT CY55P1A LED
SERIES
LED 4,000 14,700 120 RAL 9005TX,
JET BLACK
2,3,4 KING LUMINAIRE K831 LED
SERIES
T1 C CLAMP-MOUNTED LED PERFORMANCE SPOT TYPE TRACK LIGHTING FIXTURE 12-DEGREE BEAM SPREAD 0-10V DIMMING DRIVER TIMES SQUARE LIGHTING CXT30 LED 3,000 2,850 32 BLACK LEVITON LIGHTING - MB3G2 LED
SERIES
U1 7'X1"X1" LONG LINEAR TAPE LIGHT WITH ALUMINUM EXTRUSION HOUSING AND REMOTE DRIVER LOCATED IN ACCESSIBLE CEILING SPACE AION LED AT 401 LED SERIES LED 3,500 427 LM/FT 35 WHITE LUMINII LIGHTING - KENDO S
LED SERIES
U2 2'X1"X1" LONG LINEAR TAPE LIGHT WITH ALUMINUM EXTRUSION HOUSING AND REMOTE DRIVER LOCATED IN ACCESSIBLE CEILING SPACE AION LED AT 401 LED SERIES LED 3,500 427 LM/FT 35 WHITE LUMINII LIGHTING - KENDO S
LED SERIES
W1 19"DIAMETER X 2.5"TALL ROUND WALL-MOUNTED LED FIXTURE WITH BLUE COLORED NOISE REDUCING FELT AND WHITE STEEL FRONT PLATE EUREKA LIGHTING - OSLO 3038-19 OSLO 3038-19 LED 3,500 617 23 BLUE/WHITE LUXXBOX - WDB-S
X1 DIECAST ALUMINUM SINGLE-SIDED EXIT SIGN WITH GREEN LETTERING, BRUSHED ALUMINUM FACE LITHONIA LIGHTING LE LED SERIES LED - - 3 BRUSHED
ALUMINUM
1 EMERGI-LITE - PRECEPTOR
SERIES
X2 SAME AS TYPE X1 BUT DOUBLE-SIDED LITHONIA LIGHTING LE LED SERIES LED - - 3 BRUSHED
ALUMINUM
1 EMERGI-LITE - PRECEPTOR
SERIES
1201 third avenue, ste 600
seattle, wa 98101
206.448.3376
www.hargis.biz
4010 LAKE WASHINGTON BLVD NE
SUITE 320
KIRKLAND, WA 98033
425.828.8948
HOARCH.COM
ARCHITECT STAMP
CONSULTANT STAMP
PROJECT INFORMATION
SCHOOL DISTRICT LOGO
SHEET NAME
SHEET NUMBER
50% DESIGN DEVELOPMENT
100% DESIGN DEVELOPMENT
PERMIT SUBMITTAL
75% CONTRACT DOCUMENTS
90% CD
PERMIT RESUBMITTAL
BP-06.1
BID SET
ADDENDUM NO. 1
CONFORMED SET
1.21.2021
3.26.2021
8.27.2021
10.15.2021
12.3.2021
12.20.2021
1.20.2022
1.24.2022
2.3.2022
3.4.2022
1
SCHEMATIC DESIGN11.4.2020
PR1
2
3ADDENDUM NO. 22.10.2022
4ADDENDUM NO. 32.17.2022
ADDENDUM NO. 42.24.2022 5
10/19/2022 10:50:26 AME0.04
Light Fixture Schedule
PROJECT NUMBER: 2014
CONFORMED SET
3.4.2022
New
Elementary
No. 16
1075 Duvall Avenue NE
Renton, WA 98059
RENTON SCHOOL DISTRICT
No. 403
004.2 CCD
TRTRTR44444444430.82429.34428.48430.86429.50427.98427.25xxxxxxxxxxxxx4444444444444444444444444
4
444444444444444444444GENERATORGENERATORBACKUPFUEL TANKUTILITYTRANSFORMER& VAULTE7.0214"C - UTILITY PRIMARYFURNISHED BY UTILITYINSTALLED BY CONTRACTOR(E) UTILITY POLE W/ (E)POLE-MOUNT XFMR(E) UTILITY POLE W/(E) POLE-MOUNTXFMR TO REMAIN(E) UTILITY POLE W/(E) POLE-MOUNTXFMR TO REMAIN(E) OVERHEADSERVICE LATERAL -POWER & TV(E) UTILITY POLE(E) OVERHEADSERVICE LATERAL -POWER(E)WEATHERHEAD(E) STREETLUMINAIRE (TYP OF 2)(E) STREETLUMINIARE MOUNTEDTO UTILITY POLE(E) STREET LIGHTINGPEDESTAL(E) 37.5 KVA PAD-MOUNTEDUTILITY TRANSFORMER(E) TV PEDESTAL(E) TELEPHONE PEDESTAL(E) STREETLUMINAIRE (TYP OF 2)(E) UTILITYTHREE-PHASEOVERHEADDISTRIBUTION(E) UTILITYTHREE-PHASEOVERHEADDISTRIBUTION(E) UTILITYTHREE-PHASEOVERHEADDISTRIBUTION(E) UTILITY POLE(E) STREET LIGHTINGHANDHOLE (TYP)(E) SIGNALIZATIONPEDESTAL(E) STREET LIGHTINGPEDESTAL(E) UTILITY POWERMETER(E) TELEPHONEPEDESTAL(E) CATV AND PHONESERVICE AERIAL CABLINGTO REMAIN(E) OVERHEADSERVICE - CATVUTILITY JUNCTION VAULTFURNISHED BY UTILITYINSTALLED BY CONTRACTOR (1) 4"C - FURNISHED BYUTILITY INSTALLED BYCONTRACTORNEW THREE-PHASEOVERHEAD UTILITYDISTRIBUTION BY PSEE3E1E1E1E3E3E6E2E2E2E5E5 E5E5FGFGFGFGFG(2) 2-1/2"C - POWER(1) 2"C - FIRE ALARMV4V4(2) 1"C - FUTURE EVCHARGING STATIONS(1) 2"C - READERBOARDV3READERBOARDFAAPFAAP FACPGENERATORMANUALTRANSFERSWITCHNEW RENTONELEMENTARYSCHOOL #161(E) SERVICE1(E) SERVICE1222124"C - UTILITY PRIMARYFURNISHED BY UTILITYINSTALLED BY CONTRACTOR(E) SERVICE12(E) SERVICE12FUTURE EVCHARGINGSTATIONSFUTUREPORTABLESE5FGV3(1) 1"C - LIGHTING(1) 1"C - POWER(N) 2" CONDUIT RISERFURNISHED ANDINSTALLED BY UTILITY4(N) UTILITY POLE WITH (E) POLE-TOPTRANSFORMER AND (N) CONDUIT RISERSFURNISHED AND INSTALLED BY UTILITYNEW THREE-PHASEOVERHEAD UTILITYDISTRIBUTION BY PSE12(1) 2"C - POWERE2E4E4E3E3E5FGE5E5FG(2) 1"C - LIGHTINGV3FGE5E5E5FGFG(1) 1"C - POWER(1) 1"C - LIGHTINGV3(1) 1"C - LIGHTINGIRRIGATIONBOOSTER PUMPSEE CONTINUATIONTO IRRIGATIONCONTROLLER ONSHEET E3.12E5E5FGFGE4E2E4E6E5FGE4E4SL1SL1SL1SL1SL1E11GFWPGFWPFAAP LB1-9LB1-9LB1-9LB1-9LB1-9LB1-9LB1-7LB1-7LB1-7LB1-8LB1-8LB1-8LB1-8LB1-8LB1-8LB1-8LB1-8LB1-8LB1-11LA1-12LA1-12LA1-12LA1-12LA1-12LA1-12LA1-12LA1-12LA1-12LA1-10LA1-10LA1-10LA1-10LA1-10LA1-10LA1-10LA1-10P3A-43MA1-30,32,34P1A-26P1A-26SL2SL2SL1SL2SL1STREETLIGHTING PEDESTALSL2SL2SL2SL2SL2SL2SL2SL2SL2SL2SL2E7.091,2E7.083,4E7.085,6E7.081,2(TYP)(TYP)(TYP)V5V5V5V5V5V5V5V5V5V5V5V5V5V5E7.086(TYP)E7.093DUVALL AVE NECHELAN AVE NESTREET LIGHTINGSERVICE LATERALSTREET LIGHTINGSERVICE POINT(IN 1324 HANDHOLE)335677FAAP
(3) 10AFJ PIV1"C TOFACP(1) 2"C - POWERV5(1) SPARE 2"C FOR COMM8SL3V5SL2V5V5(1) SPARE 2"C FOR COMM8SL4SL2V5SL49101111004CCD004CCD004R1CCD004R1CCD004R1CCD004R1CCD004.2CCD004.2CCDVAULT SCHEDULEVAULT TYPEMANUFACTURERVAULT MODELCOVER MODELCOVER RATINGCOVER LABELVAULT DIMENSIONSNOTES(L X W X D)V1V2OLDCASTLE444-BL44-332PMEDIUM DUTY: H-20 OFF STREET4'-0" X 4'-0" X 4'-0"V3OLDCASTLEB1324 BOXN1324-51JHHEAVY DUTY: H-20 ROADWAYELECTRIC29-1/2" X 18-3/4" X 12"V4OLDCASTLE233-BL23-2436PMEDIUM DUTY: H-20 OFF STREETELECTRIC3'-8" X 2'-8" X 3'-6"V5OLDCASTLETYPE-1-MEDIUM DUTY: H-20 OFF STREETLT22"X17"X12"1NOTES1.COORDINATE WITH CITY OF RENTON REQUIREMENTS STANDARDS 119,120.2.3.FLAG NOTES:SHEET NOTES:1.REFER TO CIVIL, LANDSCAPE AND SURVEY DRAWINGS FOR ADDITIONAL INFORMATION.2.COORDINATE PLACEMENT OF SITE LIGHTING, VAULTS AND RACEWAY WITH DIVISION 31, CIVIL AND DIVISION 32,LANDSCAPE CONTRACTORS. COORDINATE WITH TREE PROTECTION PLANS AND AVOID CRITICAL ROOT ZONES OFEXISTING TREES. CONFLICTS SHALL BE COMMUNICATED TO THE ARCHITECT FOR RESOLUTION PRIOR TOCOMMENCEMENT OF SITE WORK.3.COORDINATE ELECTRICAL UTILITY SERVICE AND OFF-SITE UTILITY ELECTRICAL WORK WITH PUGET SOUND ENERGYPRIOR TO COMMENCING WORK. INSTALLATION SHALL COMPLY WITH POWER COMPANY'S ELECTRICAL INSTALLATIONREQUIREMENTS. CONTACT JENNY CHAU WITH PUGET SOUND ENERGY AT 253-208-9480, JENNY.CHAU@PSE.COM FORADDITIONAL REQUIREMENTS.4.MINIMUM CONDUIT SIZE SHALL BE 1 INCH. MINIMUM CONDUCTOR SIZE SHALL BE #10 AWG FOR BRANCH CIRCUIT WORKSHOWN ON THIS SHEET.5.PROVIDE #8 AWG CONDUCTORS FOR LIGHTING BRANCH CIRCUIT WORK SHOWN ON THIS SHEET.6.PROVIDE A WATER-TIGHT SEAL FOR EACH UNDERGROUND RACEWAY ENTERING THE ELECTRICAL ROOM AFTERCONDUCTORS HAVE BEEN INSTALLED. REFER TO RACEWAY SPECIFICATION SECTION 260533 FOR ADDITIONALINFORMATION.7.REFER TO ONE-LINE DIAGRAM ON SHEET E9.01 FOR ADDITIONAL INFORMATION.8.ROUTE SITE LIGHTING CIRCUITS TO PANELS INDICATED VIA ASSOCIATED LIGHTING CONTROL PANELS. REFER TO E2SERIES DRAWINGS FOR SITE LIGHTING CONTROL REQUIREMENTS. PROVIDE WIRING AND CONTROL DEVICES REQUIREDFOR COMPLETE SYSTEM.9.INSTALL UNDERGROUND CONDUIT PER TRENCHING DETAIL. REFER TO DETAIL 3, SHEET E7.03.10.PROVIDE CONCRETE BASE FOR SITE LIGHTING POLES. REFER TO DETAILS 1 AND 2, SHEET E7.03 FOR ADDITIONALINFORMATION.11.REFER TO VAULT SCHEDULE ON THIS SHEET FOR VAULT AND HANDHOLE TYPES. REFER TO SPECIFICATIONSECTION 260543 FOR ADDITIONAL INFORMATION.12.PRIMARY CABLING IS PROVIDED BY UTILITY.COORDINATE RECONNECTION OF EXISTING SERVICES TO REMAIN FROM DEMOLISHED UTILITY POLETO BE FED FROM NEW RELOCATED POLE-TOP TRANSFORMER/UTILITY PRIMARY.NEW CONDUCTORS PROVIDED BY UTILITY TO RECONNECT EXISTING SERVICES TO REMAIN.MATERIAL SHALL BE FURNISHED AND INSTALLED BY UTILITY FROM EXISTING UTILITY POLE TOSERVICE POINT. PROVIDE EXCAVATION, TRENCHING, AND BACKFILL REQUIRED BY UTILITY. SEEONE-LINE DIAGRAM FOR ADDITIONAL INFORMATION.UTILITY SHALL PROVIDE REFEED OF PRIMARY SIDE OF EXISTING POLE-TOP TRANSFORMER.COORDINATE FINAL LOCATION WITH LANDSCAPE.COORDINATE FINAL LOCATION WITH CIVIL.PROVIDE ADDITIONAL HANDHOLE AT +24" TO CENTER INTEGRAL TO POLE FOR RECEPTACLEINDICATED.1234STREET LIGHTING NOTES:1.THE CONTRACTOR SHALL ACQUIRE AN ELECTRICAL PERMIT FROM THE CITY'S BUILDING DEPARTMENT. THE ELECTRICALPERMIT SHALL BE KEPT IN THE UPPER BAY OF THE SERVICE CABINET.2.UPON COMPLETION OF UNDERGROUND INSTALLATION OF POWER FROM POWER VAULT OR POLE TO SERVICE CABINET,NOTIFY THE BUILDING DEPARTMENT. UPON FINAL ELECTRICAL PERMIT APPROVAL, ELECTRICAL INSPECTOR WILL PLACEAN APPROVAL TAG NEXT TO THE METER BASE SO ELECTRICAL SERVICE CAN BE AUTHORIZED.3.COORDINATE POWER SOURCE AND SERVICE LOCATION WITH UTILITY.4.CONTACT THE UTILITIES UNDERGROUND LOCATION CENTER AT LEAST 3 DAYS PRIOR TO COMMENCING EARTHWORK.5.SEE CITY OF RENTON MUNICIPAL CODE AND SECTION J ILLUMINATION DESIGN STANDARDS FOR ADDITIONALINFORMATION.6.SEE STREET LIGHTING DETAILS ON SHEETS E7.08 AND E7.09 FOR ADDITIONAL INFORMATION.7.COORDINATE FINAL LOCATION OF STREET LIGHTING LUMINAIRE WITH CIVIL AND LANDSCAPE DRAWINGS. POLE SHALL BECENTERED IN CONCRETE HOUSEKEEPING PAD. CENTER OF POLE BASE SHALL BE 3'-0" FROM EDGE OF SIDEWALK AND 7'-0"FROM EDGE OF DUVALL AVENUE. LOCATE LIGHT POLE BASES, JUNCTION BOXES, AND CONCRETE PADS IN ACCORDANCEWITH CITY OF RENTON MUNICIPAL STANDARDS AND ALLOWING FOR LUMINAIRES TO ADHERE TO MAXIMUM ARM LENGTHREQUIREMENTS AND TO OVERHANG ROADWAY OR SIDEWALK BY MAXIMUM 2 FEET.8.DURING CONSTRUCTION, EXISTING ILLUMINATION LEVELS SHALLB E MAINTAINED BY KEEPING EXISTING ILLUMINATIONSYSTEM OPERTAIONAL, OR BY PROVIDING TEMP LIGHTING.9.FOR ILLUMINATION SYSTEMS COORDINATION WITH THE CITY OF RENTON, CONTRACTOR SHALL CONTACTTRANSPORTATION MAINTENANCE DEPARTMENT REPRESENTATIVE ERIC CUTSHALL AT (425) 430-7423.10.REFER TO GEOTECHNICAL REPORT AND WSDOT STANDARD PLAN J-28.30-03 FOR STREET LIGHTING POLE BASEFOUNDATION DESIGN.567004CCD004CCDFLAG NOTES:PROVIDE CONDUIT IN EXISTING LANDSCAPE BUFFER ON DUVALL SIDE OF EXISTING SIDEWALK.PROVIDE TRENCHING, COMPACTION, AND BACKFILL. COORDINATE INSTALLATION WITH EXISTINGUTILITIES & LANDSCAPE. INSTALL CONDUIT FROM V5 VAULT AT 10TH ST NE TO V5 VAULT AT 12TH STNECOORDINATE RECONNECTION OF EXISTING SERVICES TO REMAIN FROM DEMOLISHED UTILITY POLETO BE FED FROM NEW RELOCATED POLE-TOP TRANSFORMER/UTILITY PRIMARY.PROVIDE 5'X4'X17" (LXWXD) WORK PIT, 5-1/3 CUBIC YARD 6" CRUSHED ROCK PER UTILITY STANDARDS.PROVIDE TRENCHING, BACKFILL, COMPACTION, AND RESTORATION.COORDINATE TERMINATION OF STREET LIGHTING SERVICE SECONDARY.COORDINATE FINAL LOCATION OF STREET LIGHTING LUMINAIRE WITH CIVIL AND LANDSCAPEDRAWINGS. POLE SHALL BE CENTERED IN CONCRETE HOUSEKEEPING PAD.910118004CCD004R1CCD4010 LAKE WASHINGTON BLVD NESUITE 320KIRKLAND, WA 98033425.828.8948HOARCH.COMPROJECT INFORMATIONCONSULTANT STAMPARCHITECT STAMPSCHOOL DISTRICT LOGOPROJECT NUMBER:SHEET NAMESHEET NUMBER3.4.2022CONFORMED SETNewElementaryNo. 16ADDENDUM NO. 4Renton, WA 98059RENTON SCHOOL DISTRICTNO. 40311.4.2020SCHEMATIC DESIGN1.21.202150% DESIGN DEVELOPMENT3.26.2021100% DESIGN DEVELOPMENT8.27.2021PERMIT SUBMITTAL10.15.202175% CONTRACT DOCUMENTS12.3.202190% CD12.20.2021PERMIT RESUBMITTAL1.20.2022BP-06.11.24.2022BID SET2.3.2022ADDDENDUM NO. 12.10.2022ADDENDUM NO. 22.17.2022ADDENDUM NO. 32.24.2022ADDENDUM NO. 4CONFORMED SET3.4.2022201412345PR1ELECTRICAL SITE PLAN1SCALE: 1" = 40'-0"RONHTE1.00ElectricalSite Plan