Press Alt + R to read the document text or Alt + P to download or print.
This document contains no pages.
HomeMy WebLinkAboutCS_WATERSHED - FIREALARM - SUBMITTALS_20221222_V1
11409 58Th Ave E- Puyallup, WA. 98373
FIRE ALARM
SUBMITTALS
Watershed
625 Williams AVE S
Renton WA, 98057
GAMEWELL-FCI12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118Specifications are for information only, are not intended for installation purposes, and are subject to change without notice. No responsibility is assumed by Gamewell-FCI for their use.
©2016 by Honeywell International Inc. All rights reserved. www.gamewell-fci.com 9020-0637 Rev. R page 1 of 2
E3 Series®
Control Panel
Approved
City of
Denver7165-1703:0125 3025415
APPROVED
FM
Reference Certificate of ComplianceVMA-45894-02C(Revision 1)
FDNY #: 6175COA # 231-06-E
MEAApproved
SIGNALING
S1869 12Class
High Rise
Class
City of
ChicagoApproved
Description
The E3 Series® Expandable Emergency Evacuation Sys-
tem by Gamewell-FCI is in the forefront of the latest gener-
ation of fire alarm control panels. Employing the new high-
speed Velociti® sensors, the E3 Series provides previously
unattainable polling speed and response together with the
flexibility demanded by today’s emergency evacuation sys-
tems. In addition to their high-speed polling rate, the Veloc-
iti Series of sensors feature bi-polar LEDs that flash green
for normal polling, and light red steadily to indicate an
alarm.
The E3 Series is equipped with an 80-character LCD-E3
alphanumeric LCD display that allows 40 characters to be
user-defined for custom installations. Up to six keyboard
LCD displays may also be remotely located. In addition,
you can install five of the familiar LCD-7100/RAN-7100
remote displays. The displays show instant system status
information and can be connected in any desired area of
an installation.
A high-speed 32-bit processor easily tackles a wide array
of applications from small office buildings to multi-complex,
high-rise installations.
The 64 node networking is made possible by 625K baud/
ARCNET communications using twisted-pair copper cable,
fiber-optic cable, or a combination of both. In addition, the
Addressable Node Expander (ANX) board expands the
network to 122 nodes.
The basic E3 Series is equipped with an ILI-MB-E3/ILI95-
MB-E3 Intelligent Loop Interface-Main Board, ILI-S-E3/
ILI95-S-E3 Intelligent Loop Interface Expansion Board,
ANX, and ASM-16 Addressable Switch Module that fea-
tures 16 software programmable switches, each accompa-
nied by red, green and yellow LEDs that can be
programmed to indicate operation of the switches. Addi-
tional ASM-16 modules may be added to expand the oper-
ation to a plateau previously unimagined.
The Intelligent Loop Interface - Expansion Board (ILI-S-E3/
ILI95-S-E3 provides the E3 Series control panel with two
additional electrically isolated signaling line circuits. The
layout is similar to the ILI-MB-E3/ILI95-MB-E3 with the
exception that a number of components are omitted. It
occupies one node on the Broadband network.
E3 Series® and Velociti® are registered trademarks of Honeywell
International Inc.
UL® is a registered trademark of Underwriters Laboratories Inc.
Features
• IBC Seismic Certified.
• Listed under UL® Standard 864, 9th Edition.
• UL Listed for smoke control (dedicated and non-dedi-
cated) when properly configured.
• UL Listed and FM Approved for Pre-action/Deluge and
Agent Releasing.
• Styles 4, 6, or 7* signaling line circuits.
• Two to 244 SLCs each supporting 159 sensors, 159
modules and 159 addressable sounder bases.
• 625K baud ARCNET communications using wire, fiber,
or mixed configurations for installation flexibility.
• High-speed 32 bit processor and 8100 event history log.
• Advanced Boolean logic-based programming such as
AND, OR, NOT, time delay and calendar functions
configurable via computer programming.
• Supports up to (16), ASM-16 addressable switch or
ANU-48 LED driver modules per ILI-MB-E3/ILI95-MB-E3.
• Two Class A, Style Z or Class B, Style Y, notification
appliance circuits rated at 2.0 amps. per circuit.
• Integral city connection.
• Flexible 115,200 baud high speed RS-232 interface.
• 40 character user-defined text per device.
• 15 LCD-SLP displays/annunciators, 6 LCD-E3 displays/
annunciators, 5 LCD-7100/RAN-7100 remote LED
annunciators per ILI-MB-E3/ILI95-MB-E3.
*Style 7 wiring requires the use of System Sensor M500X
Isolator Modules.
Expandable Emergency
Evacuation System
E3 Series
GAMEWELL-FCI
12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-71189020-0637 Rev. R page 2 of 2 www.gamewell-fci.com
Description (Continued)
Each ILI-MB-E3/ILI95-MB-E3 can support as many as six-
teen ANU-48 LED Driver modules supporting hundreds of
LEDs on a 3rd party graphic annunciator for remote annun-
ciation. The ANU-48 modules may be installed in any
Listed remote annunciator. It can be remotely located via
an RS-485 serial interface.
An array of cabinets allows for neat, compact, attractive
installations.
Installation
The E3 Series expandable emergency evacuation system
offers four cabinet size options. A typical cabinet includes a
backbox, an inner door, and an outer door. The E3 Series
cabinet assembly is a compact 19 3/8” (49 cm) wide. wall-
mounted enclosure.
Cabinet A includes the following four options:
• Cabinet A1 inner door mounted to the backbox. The
backbox houses one NGA module.
• Cabinet A2 inner door mounted to the backbox. The
backbox houses one LCD-E3 module.
• Two or three-bay inner door mounted to the backbox.
The backbox typically houses one LCD-E3, or one
NGA, and one or two ASM-16 modules.
Cabinet B contains a space for the ILI-MB-E3/ILI95-MB-E3,
PM-9/PM-9G modules and batteries set inside the back-
box. Additional module options mounted on the backbox
include the DACT-E3, and RPT-E3 or ILI-S-E3/ILI95-S-E3/
ANX. The 2-bay inner door houses one LCD-E3 module
and one ASM-16 module.
Both Cabinets C and D include the following:
• Pre-assembled outer door that gives visibility to the fire
fighter’s phone handset and a microphone voice
messaging system.
• Two inner door panel selections that may contain
optional modules to meet the facility operation
requirements.
In the Cabinet B, C and D backboxes, the ANX appears in
the same place as the ILI-MB-E3/ILI95-MB-E3 and PM-9/
PM-9G. For information on the installation instructions for
any of the E3 Series cabinets, refer to the E3 Series®
Expandable Emergency Evacuation Manual
Part Number: LS10080-051GF-E.
Features (Continued)
Velociti® Intelligent Sensor Features:
• Poll 318 devices in less than two seconds.
• Activate up to 159 outputs in less than five seconds.
• LED’s blink associated device address during Walk Test.
• Fully digital, hi-precision protocol.
• Up to 9 levels of sensitivity adjustment.
• Pre-Alarm adjustable between 15 levels for both Alert
and Action.
• Day/night automatic sensing adjustment.
• Sensitivity windows:
- Ion .05 to 2% obscuration.
- Photo 1 to 3% obscuration.
- Laser .02 to 2% obscuration.
- MCS Acclimate2F .5 to 4%, also self-adjustable
options 1 to 2%, 2 to 3%, and 3 to 4%.
- HARSH 1 to 3% obscuration.
• Drift compensation.
• Each Loop Card has its own integral processor
providing maximum survivability on loss of any other
component. SLC provides full response on loss of any
other system processor.
• Optional programmable switches can be configured to
enable, disable or group any combination of output
devices.
• Integrated point or Grouped Cross Zoning allows for
numerous devices installed at any location to cooperate
and determine alarm condition.
• Automatic detector sensitivity testing.
• DIRTY and VERY DIRTY detector maintenance alerts.
Specifications
Operating Voltage:24 VDC
Operating Temperature: Not to exceed the range of
32° to 120° F (0 to 49° C)
Relative Humidity:Not to exceed 93% non-con-
densing at 90° F (32° C)
Ordering Information
Part Number Description
ILI-MB-E3 Intelligent Loop Interface-Main Board
ILI95-MB-E3 Intelligent Loop Interface-Main Board
ILI-S-E3 Intelligent Loop Interface-Expansion Board
ILI95-S-E3 Intelligent Loop Interface-Expansion Board
ANX-SR Addressable Node Expander-Single Ring
ANX-MR-FO Addressable Node Expander-Multi-Ring Fiber Optic
ANX-MR-UTP Addressable Node Expander-Multi-Ring Twisted-pair
LCD-E3 LCD-E3, LCD Keypad Display
RPT-E3-UTP Network Repeater, unshielded, twisted-pair
FML-E3 Multi-Mode Fiber-Optic Module
FSL-E3 Single-Mode Fiber-Optic Module
DACT-E3 Digital Alarm Communicator Transmitter
ANU-48 ANU-48 LED Driver Module
ASM-16 Addressable Switch Module
NGA LCD Network Graphic Annunciator
PM-9 Power Supply Module
PM-9G Power Supply Module
LCD-7100 Remote LCD Display
RAN-7100 Remote LCD Display
For additional information on the cabinets, refer to the E3 Series Cabinets data sheet (Part Number: 9020-0649).
Seismic Battery Bracket Kits
For information on the types of Seismic Battery Bracket Kits that are available, the Seismic Battery Bracket Kit Part Numbers and the installation instructions, refer to the following documents:
• Seismic Battery Bracket Installation Guide, P/N: 53839
• E3 Series Cabinets Data Sheet, P/N: 9020-0649
LCD-SLP
LCD Touchscreen Annunciator Display
GAMEWELL-FCI12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118Specifications are for information only, are not intended for installation purposes, and are subject to change without notice. No responsibility is assumed by Gamewell-FCI for their use.
©2016 by Honeywell International Inc. All rights reserved. www.gamewell-fci.com 9021-60782 Rev. E page 1 of 1
FDNY: COA-#6162
MEA
S1869
SIGNALING
7165-1703:0176
City ofChicago
Approved
Class 1Reference Certificate of Compliance
VMA-45894-02C
APPROVED
FM
Description
The Gamewell-FCI, Liquid Crystal Display, Smart LoopPanel (LCD-SLP) is a touchscreen annunciator displayused with the S3 Series and E3 Series® Systems. TheLCD-SLP provides an easy-to-use, intuitive interface forthe operator’s control. The 4.3” (10.92 cm) color touchscreendisplay shows the following:• System Status • Service modes• Event details
The following identify the LED Indicators that display on
the panel.
• AC (green) • Supervisory (yellow)
• Fire Alarm (red) • Trouble (yellow)
• Hazard (blue) • Silenced (yellow)
The five fully-programmable front panel switch/LED combi-nations provide a direct access to perform the followingtasks:
• Device Bypass • Lamp Test• Enable/Disable Groups or Devices
The display features the following physical switches.
•Menu •System Reset
• Five Programmable Switches •Drift Walk Test
Installation
The LCD-SLP is adaptable for installation in the S3, E3®
Series or Retrofit cabinets. For additional information, referto the E3 Series Cabinets Data Sheet, P/N:9020-0649
• S3 Series Cabinets
- SLP-BB basic system enclosure
- S3BB-BB/S3BB-RB system enclosure
• E3 Series
® Cabinets
- AA size cabinet (E3BB-BAA, E3BB-RAA)
- A2 size cabinet (E3BB-BA2, E3BB-RA2)- A size flush cabinet (E3BB-FLUSH-LCD)- B-Slim cabinet (E3BB-RBSLIM)- B size cabinet (E3BB-BB, E3BB-RB)
- C size cabinet (E3BB-BC/INCC, E3BB-RC/INCC)
- D size cabinet (E3BB-BD/INCC, E3BB-RD/INCC)
• Retrofit Cabinets
- IF600-RETROFIT - 7200-B-RETROFIT
- 7200-C-RETROFIT
Specifications
Operating Voltage:24 VDC FWR
Operating Current:0.030 amp
Alarm Current:0.065 amp
Operating Temperature: 32° to 120° F (0° to 49° C)
Relative Humidity:0 to 93%,non-condensing at 90° F (32° C)
E3 Series® is a registered trademark of Honeywell International Inc.
UL® is a registered trademark of Underwriter’s Laboratories Inc.
Features
LCD-SLP
• Listed per ANSI/UL
® Standard 864 9th Edition.
• UL Listed and FM approved for Pre-Action/Deluge and
Agent Releasing.
• Provides 4.3” (10.92 cm) color touchscreen display of
System Events.
• Includes five custom function buttons with LEDs for
direct access to system controls.
• Offers the following installation options:
- Locally mounted in the S3 Series panels.
- Remotely mounted in the E3 Series, A2 cabinet or LCD Flush enclosure.
• Displays the following six LED indicators:
- Alarm - Hazard
- Trouble - NAC Silence
- Supervisory - AC Power
• Shows the Hazard LED to indicate gas, carbon
monoxide or other toxic gases.
• Both the E3 Series (ILI-MB-E3/ILI95-MB-E3) and the
S3 Series (SLP) support up to 15 LCD-SLP displays via
the RS-485 serial interface.
Ordering Information
Part Number Description
LCD-SLP LCD Touchscreen display unit
E3BB-BA2 Remote enclosure with inner door, black, one LCD slot
E3BB-RA2 Remote enclosure with inner door, red, one LCD slot
E3BB-FLUSH-LCD Remote flush mounting enclosure, black, LCD slot
GAMEWELL-FCI12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118Specifications are for information only, are not intended for installation purposes, and are subject to change without notice. No responsibility is assumed by Gamewell-FCI for their use.
©2015 by Honeywell International Inc. All rights reserved. www.gamewell-fci.com 9020-0555 Rev. P page 1 of 1
PM-9
PM-9 Power Supply
S1869 Vol. 14
S1949 Vol. 19
APPROVED
FM
3017416 7165-1703:0125
Approved
City of DENVERApproved
Class 1
Class 2
High Rise
Chicago
City ofSIGNALING
FDNY:
COA #6077
MEAApproved
Description
•The Gamewell-FCI, PM-9 Power Supply is a switching
power supply that provides 9 amperes of filtered and regu-
lated 24 VDC (nominal). It provides the power to the INX
Transponder assembly and all of the E3 Series compo-
nents. It is a component of the following systems.
• E3 Series® Expandable Emergency Evacuation System
• E3 Series Combined Fire and Mass Notification System
• E3 Series Broadband Voice Evacuation System
• NetSOLO
® System
•The PM-9 has an internal battery charging circuit capable
of maintaining up to 55 A/H batteries. This module is
designed for use with the Gamewell-FCI distributed audio
networks.
•Installation
Typically, the PM-9 Module can be mounted in the follow-
ing E3 Series cabinets:
• Cabinet B and D, backbox
• Cabinet C, INX-E3 sub-assembly plate
• Cabinet C, INCC-E3 sub-assembly plate
• Cabinet D, E3-INX-D Plate
• Cabinet D, E3-ILI-D Plate
•For information on the installation of the PM-9, refer to the
following documents:
• E3 Series Expandable Emergency Evacuation Manual,
P/N: LS10080-000GF-E
• PM-9 Installation Instructions, P/N: 9000-0548
• Mass Notification System Manual, P/N:LS10013-000GF-E
•Specifications
•Input Voltage:120 VAC 60 Hz
@ 3.5 A. max.
Output Voltage:24 VDC (nominal) FWR
Output Current:9 amperes
Output Current:1 ampere battery charging
current
Alarm Current:0.050 amp
Operating Temperature:32° to 120° F (0° to 49° C)
Relative Humidity:0 to 93% (non-condensing) at
90° F (32° C)
Dimensions:10 1/2” W x 5” H x 2” D
(27 x 13 x 5 cm)
E3 Series® and NetSOLO® are registered trademarks of Honeywell International Inc.
UL® is a registered trademark of Underwriter’s Laboratories Inc.
Features
• Listed under UL
® Standard 864, 9th Edition.
• Listed under UL Standard UL2572 for Mass
Notification.
• Includes 9 ampere, filtered, regulated power
supply.
• Provides 1 ampere battery charging current.
• Offers energy and space saving switching
technology.
• Contains an integral battery charger capable of
recharging up to 55 AH batteries.
(Batteries not furnished).
Ordering Information
Part Number Description
PM-9 Power supply
29229 AC Line Filter Kit
PM-9
GAMEWELL-FCI12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118Specifications are for information only, are not intended for installation purposes, and are subject to change without notice. No responsibility is assumed by Gamewell-FCI for their use.
©2015 by Honeywell International Inc. All rights reserved. www.gamewell-fci.com 9021-60901 Rev. A page 1 of 1
PRN-7
Printer
Printer
S35611 E351188
Description
General
The PRN-7 printer is used with the Gamewell-FCI fire
alarm control panels (FACPs) and provides printer capabil-
ity to produce a written record of system events and status
changes. In the Gamewell-FCI applications, the PRN-7
can be used with the following systems.
•E3 Series® System • S3 Series System
• 7100 Series System • 600 Series System
Applications
Printed transaction records reduce the man-hours required
to install and maintain a system. A printed record of all sys-
tem events (alarms, troubles, etc.) and status changes can
be especially valuable in the event of a disputed incident.
Construction and Operation
The printer is housed in its own separate enclosure and is
suitable for placement on a desktop, counter, or table.
Installation
Install the PRN-7 printer in a location no further than 20 ft/
6.10 m (actual cable length) from the fire alarm control
panel. The PRN-7 should be placed in a secure area to
prevent theft of the printer and/or printed records.
For information on the proper method and PIN numbers
required to complete the electrical connection to the fire
alarm control panel, refer to the Gamewell-FCI module
specific documentation located on the Gamewell-FCI Web-
site, www.gamewell-fci.com.
NOTE: During a primary power failure, if it is necessary to
use the printer, Gamewell-FCI recommends that you use a
separate UL-Listed Uninterruptible Power Supply (UPS)
system.
Specifications
Printer Method:Serial printing with a 24-pin
matrix print head.
Printing Speed (copy draft):333 cps at 10 cpi.
Character Density:10 cpi standard.
(12, 15, 17.1, and 20 cpi
available via front panel).
Graphic Resolution (VxH):Up to 360 x 360 dpi.
Ribbon Life (approx.):6 million characters (DPQ).
Acoustic Noise Level:52 dBA (approx.).
E3 Series® is a registered trademark of Honeywell International Inc.
UL® is a registered trademark of Underwriters Laboratories, Inc.
Features
• Produces a hard copy printout of all system events and status changes.
• Registers the time stamps printed on the record of each event and status change including the current time-of-day and date.
• Uses standard 9” x 11” tractor-feed fan-fold paper.
• Prints 80 columns of data at 10 characters per inch.
• Provides printed records of the system configuration and the addressable device parameters.
• Includes a 24-pin print head.
• Offers accoustic noise levels of approximately 52 dBA.
Ordering Information
Part Number Description
PRN-7 24-pin dot-matrix printer, 110-230 VAC
power.
PRN-7 Printer
GAMEWELL-FCI12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118Specifications are for information only, are not intended for installation purposes, and are subject to change without notice. No responsibility is assumed by Gamewell-FCI for their use.
©2013 by Honeywell International Inc. All rights reserved.www.gamewell-fci.com 9020-0554 Rev. O page 1 of 1
ASM-16
ASM-16 Addressable
Switch Module
Rear View Front View
APPROVED
FM
3017416S1869
SIGNALING
Approved
City of
Chicago
Class 1
Class 2High Rise
7165-1703:01257170-1703:0126
FDNY:
COA # 231-06-E
MEAApproved
City of Denver
Approved
Description
•The Gamewell-FCI, ASM-16 Addressable Switch Module
serves as the point of interface between an operator and
the system’s audio evacuation, fire fighter intercom, and
building control circuits. It is a component of the following
systems:
• E3 Series
® Expandable Emergency Evacuation System
•E3 Series Combined Fire and Mass Notification System
• E3 Series Broadband Voice Evacuation System•NetSOLO® System
•The ASM-16 is a configurable switch input sub-assembly
with 16 switches and 48 status LEDs. It may be remotely
located via the RS-485 serial interface. Each ASM-16
addressable switch module has 16 push-button switches
that can be programmed to serve any function the applica-
tion demands.
•An ASM-16 switch can be programmed to operate as any
of the following functions:• speaker circuit switch • fire fighter phone switch
• auxiliary control switch (using a bank of 2 switches
(1 switch each for on-off-auto functions).
• switches with custom-defined
functions: - system reset
- system silence
- system acknowledge- all-call, phone patch- lamp test, alarm tone on
- manual select, etc.
•Each ASM-16 switch also has 3 fully programmable LEDs
that appear in red, yellow, and green. These LEDs can be
programmed to work in concert with their associated push-
button switch or they can be programmed to work inde-
pendently as status indicators (e.g. on, off, normal, etc.).
•An INI-VGC assembly or ILI-MB-E3/ILI95-MB-E3 can
accommodate up to 16 ASM-16 modules for a total of 256
switches and 768 LEDs.
•Specifications
•Operating Voltage:24 VDC (nominal) (from the
PM-9/PM-9G power supply)
Operating Current:0.011 amp. (with no LEDs lit)Operating Temperature:32° to 120° F (0° to 49° C)Relative Humidity:0 to 93% (non-condensing)
at 90° F (32° C)
E3 Series® and NetSOLO® are registered trademarks of Honeywell International Inc.
UL® is a registered trademark of Underwriters Laboratories Inc.
Features
• Listed under UL
® Standard 864, 9th Edition.
• Listed under UL
® Standard UL2572 for Mass
Notification.
• Each INI-VGC supports up to 16 ASM-16 switch
modules for a total of 256 switches.
• Each ILI-MB-E3/ILI95-MB-E3 supports up to 16
ASM-16 switch modules for a total of 256 switches.
• Each ASM-16 switch has 3 fully programmable status,
indicating LEDS: red, yellow, and green.
• All switch functions are fully software programmable.
• Slip-in label inserts allow easily modified switch
designations.
Ordering Information
Part Number Description
1100-0455 Programmable Addressable Switch
Module
MS-7 Series
MS-7 Series
Manual Fire Alarm Pull Stations
Addressable Devices
General
The Gamewell-FCI, MS-7 Series manual fire alarm pull stations are available in a wide
variety of configurations. The pull stations comply with the Americans with Disabilities
Act (ADA) 5-lb. maximum pull force requirement. Operating instructions and Braille
text are engraved in the handle. All pull stations include a key lock/reset which is keyed
alike with the Gamewell-FCI fire alarm control panels and other manual fire alarm pull
stations.
MS-7AF Velociti Addressable Station
The MS-7AF Velociti® Series addressable station is a double action pull station
designed for installation in the signaling line circuit of Gamewell-FCI analog
addressable control panels. Activation of the pull station causes its assigned address
to register at the fire alarm control panel. The door contains an LED which flashes
green in normal condition and lights steady red when the station has been activated.*
The station features screw terminals.
MS-7ASF Velociti Addressable Station
The MS-7ASF Velociti® Series addressable pull station is a single action station
designed for installation in the signaling line circuit of Gamewell-FCI analog
addressable control panels. Activation of the station causes its assigned address to
register at the control panel. The door contains an LED which flashes green in normal condition and lights steady red when the pull station is
activated.* The station features screw terminals.
The Velociti® Series pull stations use a communication protocol that substantially increases the speed of communication between the sensors
and certain Gamewell-FCI analog addressable fire alarm controls. These devices operate in a grouped fashion. If one of the devices in the
group has a status change, the panel’s microprocessor stops the group poll and focuses on the single device. The net effect offers a response
speed up to five times greater than earlier designs.
MS-7 Double Action Station
The MS-7 double action pull station is used with conventional fire alarm control panels. It features a set of single pole contacts and screw
terminals for connection to an initiating circuit.
FEATURES & BENEFITS
• Addressable stations
compatible with all
Gamewell-FCI analog
addressable fire alarm
controls
• Conventional stations
suitable for use with
any UL® Listed control
panel
• The pull stations (MS-
7LOB) are Listed for
outdoor applications
• Complies with ADA pull
force requirements
• Offers surface or semi-
flush mounting
• Shock and vibration
resistant
• Both single and double
action pull stations
available
• Includes a tumbler lock
for test and reset keyed
alike with analog
addressable fire alarm
controls
*Only the red LED is
operative in panels that
do not operate in Velociti
mode
2
MS-7S Single Action Station
The MS-7S single action pull station is used with
conventional fire alarm control panels. It features a set
of single pole contacts and wire leads for connection to
an initiating circuit.
MS-7SP Double Action Station
The MS-7SP is a double action pull station similar to
the MS-7 station, with the additional feature of
including both English and Spanish instructions
molded into the unit.
MS-7LR Dual-action Agent Release Station
The MS-7LR is designed for use with the Gamewell-FCI
fire alarm control panels with releasing capabilities
and Flex Series releasing systems. It features a set of
single pole contacts and screw terminals used to
connect to an initiating circuit.
MS-7LRA Agent Release Station with Abort
The MS-7LRA is designed for use with the Gamewell-
FCI fire alarm control panels with releasing capabilities
and Flex Series releasing systems where system abort
capabilities are required. It consists of the following:
• An MS-7LR mounted on a plate with an abort switch
• LED indicators that signal system normal and
system activated status
MS-7LOB Double Action Station (Listed for Outdoor
Applications)
The MS-7LOB station must be mounted on a Model
SB-I/O backbox. In retrofit applications, the pull
station is UL Listed for use with the WP-10 backbox. It
is intended for use with conventional control panels
and has a set of single pole contacts and screw
terminals.
Mounting
The MS-7 interior pull stations may be surface
mounted or semi-flush mounted on a standard
double-gang, or 4-inch (10.2 cm) square electrical box.
An optional trim ring (BG12TR) may also be used for
semi-flush mounting.
NYC-Plate
The NYC-Plate provides the backplate for the manual
pull station. (See Figure 1).
Figure 1 NYC-Plate
Ordering Information
MS-7: Double action station
MS-7AF**: Velociti addressable double action station
MS-7ASF**: Velociti addressable single action station
MS-7S: Single action station, wire leads
MS-7SP: Double action station, English and Spanish
instructions
MS-7LR: Agent release station, dual-action
MS-7LRA: Agent release station with abort switch,
LED indicators, dual- action
MS-7LOB: Double action station, outdoor use
(Includes SB-I/O - Indoor/outdoor use backbox)
SB-I/O: Indoor/outdoor use backbackbox
SB-10: Surface backbox
BG12TR: Trim ring for semi-flush mount, plastic
NY-PLATE: NYC backplate for manual pull station
**For use with the Gamewell-FCI analog addressable
control panels only.
MS-7 Series Technical Specifications
9020-0616 | F | 11/17
©2017 Honeywell International Inc.
For a complete listing of all
compliance approvals and
certifications, please visit:
http://www.gamewell-
fci.com/en-US/
documentation/Pages/
Listings.aspx
LEXAN® is a registered
trademark of GE Plastics, a
subsidiary of General Electric
Company.
Velociti® and Gamewell-FCI
are registered trademarks of
Honeywell International Inc.
UL® is a registered trademark
of Underwriter’s Laboratories
Inc.
This document is not intended
to be used for installation
purposes. We try to keep our
product information up-to-
date and accurate. We cannot
cover all specific applications
or anticipate all requirements.
All specifications are subject to
change without notice.
Honeywell Gamewell-FCI
12 Clintonville Road
Northford, CT 06472-1610
203.484.7161
www.honeywell.com
For more information
Learn more about Gamewell-FCI’s MS-7 Series and other
products available by visiting www.Gamewell-FCI.com
SYSTEMS
Material: Lexan®
Contact Ratings: 0.25 amps. @ 30 VAC/VDC (resistive)
Dimensions: 5 5/8” H x 4 1/4” W x 1 1/4” D
(14 x 10.1 x 3.2 cm)
Operating Temperature:
(MS-7AF, MS-7ASF): 32° to 120° F (0° to 49° C)
(MS-7LOB): -30° to 150° F (-35° to 66° C)
Relative Humidity :
(MS-7AF, MS-7ASF): 10 to 93% (non-condensing)
(MS-7LOB): 85% ± 5% @ 86° ± 3.6° (30° ± 2° C)
Alarm Current: .0030 amp. 0.007 for LED
Supervisory Current:
(MS-7AF, MS-7ASF): .00030 amps.
TEMPERATURE AND HUMIDITY RANGES
This system meets NFPA requirements for operation at 0
– 49°C/32 – 120°F and at a relative humidity 93% ± 2%
RH (noncondensing) at 32°C ± 2°C (90°F ± 3°F).
However, the useful life of the system's standby batteries
and the electronic components may be adversely affected
by extreme temperature ranges and humidity. Therefore,
it is recommended that this system and its peripherals be
installed in an environment with a normal room
temperature of 15 – 27°C/60 – 80°F.
STANDARDS
The MS-7 Series is designed to comply with the following
standard:
UL Standard: UL 864 9th Edition
AGENCY LISTINGS AND APPROVALS
These listings and approvals apply to the modules
specified in this document. In some cases, certain
modules or applications may not be listed by certain
approval agencies, or listing may be in process.
Consult factory for latest listing status.
UL: S2465
FM: 3023594
MEA FDNY: 67-02-E Vol. VII
CSFM:
7160-1703:0119
7160-1703:0170
7160-1703:0109
ISO 9001 Certification
AMM-2F
AMM-2F
Addressable Monitor Module
Addressable Devices
General
The Gamewell-FCI Velociti® Series, addressable monitor module AMM-2F is a single
Style B, Class B initiating device circuit (IDC) with a 47KW end-of-line resistor. This
module provides an address for any device or group of devices connected to this
circuit on the signaling line circuit (SLC) of the Gamewell-FCI addressable series fire
alarm control panel. Any initiating device with normally open (N.O.) dry contacts may
be made addressable when connected to the AMM-2F module.
The Velociti® Seriems use a communication protocol that substantially increases the
speed of communication between the sensors and certain Gamewell-FCI analog
addressable fire alarm controls. These devices operate in a grouped fashion. If one of
the devices in the group has a status change, the panel’s microprocessor stops the
group poll and concentrates on the single device. The net effect is response speed up
to five times greater than earlier designs.
The AMM-2F module can be programmed to provide a wide variety of input functions
to the Gamewell-FCI addressable series fire alarm control panels. It can be identified
as a manual station, heat detector, plenum detector, waterflow switch, tamper switch,
N.O. contact, smoke detector, projected beam smoke detector, sub loop, remote zone,
etc. It can also serve as a remote system silence, system reset, system acknowledge or
drill switch. It is even possible to customize its device type to meet specific job
requirements.
The initiating device circuit of the AMM-2F can support a maximum line resistance of
up to 40 ohms allowing the use of linear heat detection devices. The compact size
facilitates the installation of the module inside manual stations, or mounting boxes of
various types of alarm initiating devices.
Ordering Information
AMM-2F: Addressable monitor module, single circuit, Style B, Class B
FEATURES & BENEFITS
•Compact size allows
easy installation
• Class B, Style B,
initiating circuit
• 40 Ohm line resistance
for each initiating
device circuit
• Connects to any
normally open dry
contact device
AMM-2F Technical Specifications
9020-0626 | F | 11/17
©2017 Honeywell International Inc.
For a complete listing of all
compliance approvals and
certifications, please visit:
http://www.gamewell-
fci.com/en-US/
documentation/Pages/
Listings.aspx
Velociti® and Gamewell-FCI®
are registered trademarks of
Honeywell International Inc.
UL® is a registered trademark
of Underwriters Laboratories
Inc.
This document is not intended
to be used for installation
purposes. We try to keep our
product information up-to-
date and accurate. We cannot
cover all specific applications
or anticipate all requirements.
All specifications are subject to
change without notice.
Honeywell Gamewell-FCI
12 Clintonville Road
Northford, CT 06472-1610
203.484.7161
www.honeywell.com
For more information
Learn more about Gamewell-FCI’s AMM-2F and other products
available by visiting www.Gamewell-FCI.com
System
Supervisory Current: .000375 amps
Alarm Current: .00060 amps
Operating Temperature: 32° to 120° F (0° to 49° C)
Relative Humidity: 10 to 93% (non-condensing)
End-of-Line Resistance: 47K ohms
Dimensions: 1.3” L x 2.5” W x 0.5” D
(3.3 x 6.4 x 1.3 cm)
TEMPERATURE AND HUMIDITY RANGES
This system meets NFPA requirements for operation at 0
– 49°C/32 – 120°F and at a relative humidity 93% ± 2%
RH (noncondensing) at 32°C ± 2°C (90°F ± 3°F).
However, the useful life of the system's standby batteries
and the electronic components may be adversely affected
by extreme temperature ranges and humidity. Therefore,
it is recommended that this system and its peripherals be
installed in an environment with a normal room
temperature of 15 – 27°C/60 – 80°F.
STANDARDS
The E3 Series Control Panel is designed to comply with
the following standard:
UL Standard: UL 864 9th Edition
AGENCY LISTINGS AND APPROVALS
These listings and approvals apply to the modules
specified in this document. In some cases, certain
modules or applications may not be listed by certain
approval agencies, or listing may be in process.
Consult factory for latest listing status.
UL: S1949
FM: 3023594
MEA FDNY: 227-03-E VOL. IV
CSFM: 7300-1703:0102
ISO 9001 Certification
AMM-2IF
Velociti® Series AMM-2IF
Addressable Dual Monitor Module
Addressable Devices
General
The Gamewell-FCI Velociti® Series, addressable dual monitor module, AMM-2IF,
features two Style B, Class B initiating device circuits, each with an end-of-line
resistor. This module provides addresses for any device or group of devices connected
to each circuit. Any alarm initiating devices with normally open (N.O.) dry contacts,
such as heat detectors, 4-wire projected beam smoke detectors, 4-wire smoke
detectors, water flow switches, tamper switches, manual stations, etc. may be installed
in these circuits.
The Velociti® Series use a communication protocol that substantially increases the
speed of communication between the sensors and certain Gamewell-FCI analog
addressable fire alarm controls. These devices operate in a grouped fashion. If one of
the devices in the group has a status change, the panel’s microprocessor stops the
group poll and concentrates on the single device. The net effect is response speed up
to five times greater than earlier designs.
The first circuit address is set via a rotary switch. The second circuit is automatically
assigned the next higher address. The module has a single panel-controlled red LED.
The AMM-2IF module is designed for installation in the signaling line circuit of any
Gamewell-FCI addressable control panel. The AMM-2IF is designed to mount in a 4”
square junction box, 2 1/8” deep. The initiating device circuit of the AMM-2IF can
support a maximum line resistance of up to 40 ohms allowing the use of linear heat
detection devices.
Ordering Information
AMM-2IF: Monitor module, two circuit, Style B, Class B
FEATURES & BENEFITS
• Supports Class B, Style
B, initiating device
circuits
• Provides a visual rotary,
decimal switch
addressing (01-159)
• Offers 40 ohm line
resistance for each
initiating circuit
• Accommodates any
normally open contact
device
• Displays bi-color LEDs
flash green whenever
the module is
addressed, and light
steady red on alarm*
• Includes a compact
size allows easy
installation
*Note: Only the red LED
is operative in panels that
do not operate in Velociti®
mode.
Velociti® Series AMM-2IF Technical Specifications
9020-0629 | F | 11/17
©2017 Honeywell International Inc.
For a complete listing of all
compliance approvals and
certifications, please visit:
http://www.gamewell-
fci.com/en-US/
documentation/Pages/
Listings.aspx
Velociti®, E3 Series® and
Gamewell-FCI are registered
trademarks of Honeywell
International Inc.
This document is not intended
to be used for installation
purposes. We try to keep our
product information up-to-
date and accurate. We cannot
cover all specific applications
or anticipate all requirements.
All specifications are subject to
change without notice.
Honeywell Gamewell-FCI
12 Clintonville Road
Northford, CT 06472-1610
203.484.7161
www.honeywell.com
For more information
Learn more about Gamewell-FCI’s Velociti® Series AMM-2IF and
other products available by visiting www.Gamewell-FCI.com
SYSTEMS
Supervisory Current: 0.0075 amp.
Alarm Current: .0057 amp. (LED lit)
Operating Temperature: 32° to 120° F (0° to 49° C)
Relative Humidity: 10 to 93% (non-condensing)
Dimensions: 4 1/2” H x 4” mW x 1 1/4” D
(11 H x 10.2 W x 3 D cm)
(Mounts in a 4” square by 2 1/8” deep box).
End-of-line Resistor: 47 K ohms
TEMPERATURE AND HUMIDITY RANGES
This system meets NFPA requirements for operation at 0
– 49°C/32 – 120°F and at a relative humidity 93% ± 2%
RH (noncondensing) at 32°C ± 2°C (90°F ± 3°F).
However, the useful life of the system's standby batteries
and the electronic components may be adversely affected
by extreme temperature ranges and humidity. Therefore,
it is recommended that this system and its peripherals be
installed in an environment with a normal room
temperature of 15 – 27°C/60 – 80°F.
STANDARDS
The Velociti® Series AMM-2IF is designed to comply with
the following standards:
UL Standards: UL 864 9th Edition
UL 2572 for Mass Notification
AGENCY LISTINGS AND APPROVALS
These listings and approvals apply to the modules
specified in this document. In some cases, certain
modules or applications may not be listed by certain
approval agencies, or listing may be in process. Consult
factory for latest listing status.
UL: S1949
2572 for Mass Notification
FM: 3023594
MEA FDNY: 227-03-E Vol. IV
CSFM: 7300-1703:0107
ISO 9001 Certification
AOM-2RF
Velociti® Series AOM-2RF
Addressable Output Relay Control Module
Addressable Devices
General
The Gamewell-FCI Velociti® Series, addressable output relay control module (AOM-
2RF) allows a Gamewell-FCI analog addressable fire alarm control panel to switch
discrete relay contacts by code command. The relay provides two isolated sets of
Form-C contacts which transfer simultaneously. Circuit connections to the relay
contacts are not supervised by the module.
The Velociti® Series use a communication protocol that substantially increases the
speed of communication between the SLC devices and certain Gamewell-FCI analog
addressable fire alarm control panels. These devices operate in a grouped fashion. If
one of the devices in the group has a status change, the panel’s microprocessor stops
the group poll and concentrates on the single device. The net result produces a
superior response speed up to five times greater than earlier designs.
The AOM-2RF Module is designed for installation in the signaling line circuit of any
Gamewell-FCI analog addressable fire alarm control panel. The module contains a
panel controlled LED. The AOM-2RF is designed to mount in a 4” (10.16 cm) square
junction box 2 1/8” (5.53 cm) deep.
Ordering Information
AOM-2RF: Addressable output relay control module
Table 1 lists the relay contact ratings.
FEATURES & BENEFITS
• Listed under UL
®
Standard 864
• Offers two sets of Form
“C” contacts
• Provides visual rotary,
decimal switch
addressing (01-159)
•Includes a bi-color LED
that flashes green
whenever the module is
addressed, and lights
steady red upon
activation*
• Designed as a compact
size to allow easy
installation
Note: Only the red LED is
operative in panels that
do not operate in Velociti®
mode
CURRENT
RATING
MAXIMUM
VOLTAGE
LOAD
DESCRIPTION APPLICATION
3A 30 VDC Resistive Non-Coded
2A 30 VDC Resistive Coded
0.9A 110 VDC Resistive Non-Coded
0.5A 125 VAC Resistive Non-Coded
0.5A 30 VDC Inductive
(L/R=5ms)
Coded
1A 30 VDC Inductive
(L/R=2ms)
Coded
0.5A 125 VAC Inductive
(PF=.35)
Non-Coded
0.7A 75 VAC Inductive Non-Coded
Table 1: Relay Contact Ratings
Velociti® Series AOM-2RF Technical Specifications
9020-0625 | G | 11/17
©2018 Honeywell International Inc.
For a complete listing of all
compliance approvals and
certifications, please visit:
http://www.gamewell-
fci.com/en-US/
documentation/Pages/
Listings.aspx
Velociti® Series and Gamewell-
FCI® are registered trademarks
of Honeywell International Inc.
UL® is a registered trademark
of Underwriter’s Laboratories
Inc.
This document is not intended
to be used for installation
purposes. We try to keep our
product information up-to-
date and accurate. We cannot
cover all specific applications
or anticipate all requirements.
All specifications are subject to
change without notice.
Honeywell Gamewell-FCI
12 Clintonville Road
Northford, CT 06472-1610
203.484.7161
www.honeywell.com
For more information
Learn more about Gamewell-FCI’s Velociti® Series AOM-2RF and
other products available by visiting www.Gamewell-FCI.com
SYSTEMS
Supervisory Current: .000375 amps.
Alarm Current: .0065 amps.
Operating Temperature: 32° to 120° F (0° to 49° C)
Relative Humidity: 10 to 93% relative humidity (non-
condensing)
Dimensions: 4 1/2” H x 4” W x 1 1/4”
(11.4 x 10.2 x 3.2 cm)
TEMPERATURE AND HUMIDITY RANGES
This system meets NFPA requirements for operation at 0
– 49°C/32 – 120°F and at a relative humidity 93% ± 2%
RH (noncondensing) at 32°C ± 2°C (90°F ± 3°F).
However, the useful life of the system's standby batteries
and the electronic components may be adversely affected
by extreme temperature ranges and humidity. Therefore,
it is recommended that this system and its peripherals be
installed in an environment with a normal room
temperature of 15 – 27°C/60 – 80°F.
STANDARDS
The Velociti Series® AOM-2RF is designed to comply with
the following standard:
UL Standard: UL 864 9th Edition
AGENCY LISTINGS AND APPROVALS
These listings and approvals apply to the modules
specified in this document. In some cases, certain
modules or applications may not be listed by certain
approval agencies, or listing may be in process. Consult
factory for latest listing status.
UL: S1913
FM: 3023594
MEA FDNY: 219-02-E Vol. VI
CSFM: 7300-1703:0102
ISO 9001 Certification
Intrusion Alarm Systems | D126 Standby Battery (12 V, 7 Ah)
D126 Standby Battery (12 V, 7 Ah)
www.boschsecurity.com
u 12 VDC sealed lead-acid
u Fully rechargeable
u Maintenance‑free
u For use as secondary power source
u Long service life
This battery is a maintenance‑free, sealed lead‑acid,
standby and auxiliary power source that provides long
service life and dependability.
The battery is for use only with charging circuits
calibrated for lead‑acid batteries. It is suitable for
supplying backup power for fire, security, and access
control systems during AC power failures.
The D126 fits in any of the currently offered
enclosures and connects to the two color‑coded
battery leads supplied with the control panel or
module. Use a D122 Dual Battery Harness to connect
two D126 batteries in parallel and double the amp
hour capacity.
Certifications and approvals
Region Certification
USA CSFM California State Fire Marshal (see ourwebsite)
Installation/configuration notes
Standby power requirementsRefer to the appropriate control panel installation
manual for information on calculating the standby
battery requirements for the system. Total continuous
and intermittent current requirements must not
exceed the amp hour capacity of the battery.
CompatibilityThe battery is compatible with all Bosch control
panels.
Parts included
Quantity Component
1 12 V battery
Technical specifications
Capacity
Capacity
(25 °C)
12 V, 7.2 Ah 20 hour rate
Internal
resistance
Fully charged battery (25 °C)21 MΩ
Temperature
dependency of
capacity (20
hour rate)
40 °C (104 °F)
25 °C (77 °F)
0 °C (32 °F)
-15 °C (5 °F)
102%
100%
85%
65%
Properties
Dimensions 15 cm x 6.5 cm x 9.4 cm (6 in. x 2.5 in. x 3.7 in.)
Total height
with terminals
10 cm (4 in.)
Weight 2.5 kg (5.5 lb)
Terminal Faston .187
Ordering information
D126 Standby Battery (12 V, 7 Ah)
A rechargeable sealed lead‑acid power supply used as
a secondary power supply or in auxiliary or ancillary
functions.
Order number D126
2 | D126 Standby Battery (12 V, 7 Ah)
Represented by:
Europe, Middle East, Africa:Germany:North America:Asia-Pacific:Bosch Security Systems B.V.
P.O. Box 800025600 JB Eindhoven, The NetherlandsPhone: + 31 40 2577 284emea.securitysystems@bosch.com
emea.boschsecurity.com
Bosch Sicherheitssysteme GmbH
Robert-Bosch-Ring 585630 GrasbrunnGermanywww.boschsecurity.com
Bosch Security Systems, Inc.
130 Perinton ParkwayFairport, New York, 14450, USAPhone: +1 800 289 0096Fax: +1 585 223 9180
onlinehelp@us.bosch.comwww.boschsecurity.us
Robert Bosch (SEA) Pte Ltd, Security Systems
11 Bishan Street 21Singapore 573943Phone: +65 6571 2808Fax: +65 6571 2699
apr.securitysystems@bosch.comwww.boschsecurity.asia
© Bosch Security Systems 2016 | Data subject to change without notice
2548450571 | en, V11, 28. Nov 2016
ASD-PL2F/ASD-PTL2F
ASD-PL2FR
Velociti® Series 3 Detectors
Photoelectric Detectors
Addressable Devices
Photoelectric Detector
Description
The Gamewell-FCI, Velociti® Series 3 intelligent photoelectric detectors with integral
communication provide point location for alarm communication and selective
maintenance. Designed in a modern bright white color, the Velociti Series 3 is
aesthetically pleasing for today's contemporary buildings.
The Velociti Series 3 smoke detectors are intelligent addressable detectors with point
ID capability that enable each detector address to be set with rotary address switches
providing exact device locations. The photoelectric detector continually monitors the
detected temperature and reports it to the fire alarm control panel. The modern
design and expanded color options support a variety of contemporary aesthetic
demands. In addition, each detector is constructed for exceptional installation and
maintenance efficiency.
The Gamewell-FCI, ASD-PL3 photoelectric detector's re-designed optical sensing
chamber is engineered to sense smoke produced by a wide range of combustion
sources in accordance with more stringent code standards. The sensitivity of Velociti
series detectors can be programmed using the control panel software to suit the
environment. The ASD-PL3R photoelectric detector is also remote test capable that
may be used with a DNR (DNRW) duct smoke detector housing. The ASD-PTL3 multi-
sensor detector offers either photoelectric detection or thermal detection through
dual electronic thermistors at 135°F fixed temperature thermal sensing.
For legacy installations, service detectors are available in the classic ivory color that
will operate in both Velociti and CLIP protocol for backwards compatibility. Service
models are designated by the -IV part number after the detector model.
Note: Although the E3 Series® and S3 Series panels support both the Velociti® and
CLIP™ protocols, the GWF-7075 panel does not support the CLIP protocol. To obtain
a complete list of panels that are listed to Velociti Series 3 detectors, refer to the
Compatibility Addendum for Gamewell-FCI Manuals, P/N:9000-0427-L8.
FEATURES & BENEFITS
• Complies with UL®
Standard 268 7th
Edition
• Designed with a new
profile to offer modern
and improved
aesthetics
• Contains a built-in
functional test switch
activated by external
magnet
• Supports a low standby
current
• Provides rotary address
switches (01-159)
• Supplies optional relay,
isolator, or sounder
bases (standard or low
frequency)
• Includes dual LEDs for
360° visibility
• Offers expanded color
options
2
Ordering Information
NOTE: "-IV" suffix indicates Ivory color model.
NOTE: "-BL" suffix indicates Black color model.
NOTE: “WH” suffix indicates Bright White color model.
ASD-PL3: Photoelectric smoke detector, bright white,
Velociti
ASD-PL3R: Photoelectric smoke detector, remote test
capable, for use with DNR(W) duct smoke detectors, bright
white, Velociti
ASD-PTL3: Photoelectric smoke detector with thermal
sensing, bright white, Velociti
ASD-PL3-IV : Photoelectric smoke detector, ivory, Velociti/
CLIP
ASD-PL3R-IV: Photoelectric smoke detector, remote test
capable, for use with DNR(W) duct smoke detectors, ivory,
Velociti/CLIP
ASD-PTL3-IV : Photoelectric smoke detector with thermal
sensing, ivory, Velociti/CLIP
Intelligent Bases
For details on intelligent bases, refer to Data Sheet
P/N: 9021-60540.
Note: “IV” suffix indicates Flashscan and CLIP devices.
“WH” suffix indicates bright white
B501-WHITE: 4” Flangeless mounting base, bright white
B501-WHITE-BP: 4” Flangeless mounting base bulk pack,
bright white
B501-IV: 4” Flangeless mounting base, ivory
B300-6: 6” Flanged mounting base, bright white
B300-6-IV: 6” Flanged mounting base, ivory
B300-6-BP: 6” Flanged mounting base bulk (Pack of 10)
B200SR-WH: Standard sounder base, bright white
B200SR-IV: Standard sounder base, ivory
B200S-WH: Intelligent addressable sounder base, bright
white
B200S-IV: Intelligent addressable sounder base, ivory
B200SR-LF-WH: Standard low frequency sounder base,
bright white
B200SR-LF-IV: Standard low frequency sounder base,
ivory
B200S-LF-WH: Intelligent addressable low frequency
sounder base, bright white
B200S-LF-IV: Intelligent addressable low frequency
sounder base, ivory
B224RB-WH: Relay base, bright white
B224RB-IV: Relay base, ivory
B224BI-WH: Isolator base, bright white
B224BI-IV: Isolator base, ivory
DNR: Intelligent duct detector housing, non-relay
DNRW: Intelligent duct detector housing, non-relay,
watertight
Ordering Information
Accessories
SMB600: Surface Mounting Kit (flanged)
TR300: Accessory Flange Ring for B300 6” Base, bright
white
TR300-IV: Accessory Flange Ring for B300 6” Base, ivory
RA100Z: Remote LED annunciator, 3-32 VDC
The annunciator mounts to a U.S. single-gang electrical
box. For use with B501 and B300-6.
CK300: Bright White detector kit (Pack of 10)
CK300-IR: White, detector color kit for use with MCS-COF
Series Detectors. (Pack of 10)
CK300-IV: Ivory, detector color kit. (Pack of 10)
CK300-IR-IV: Ivory, detector color kit for use with
MCSCOF Series detectors. (Pack of 10)
CK300-BL: Black detector kit. (Pack of 10)
CK300-IR-Bl: Black, detector color kit for use with
MCSCOF Series detectors. (Pack of 10)
M02-04-01: Detector test magnet.
M02-09-00: Test magnet with telescoping handle.
XR2B: Detector removal tool. Allows the installation and/
or removal of the detector heads from the bases in high
ceiling applications.
XP-4: Extension pole for XR2B. Shipped with three, 5-foot
(1.524,m) sections.
Velociti® Series 3 Detectors Technical Specifications
9020-0617 | K | 04/2018
©2018 Honeywell International Inc.
For a complete listing of all
compliance approvals and
certifications, please visit:
http://www.gamewell-
fci.com/en-US/
documentation/Pages/
Listings.aspx
E3 Series®, Velociti® and
Gamewell-FCI® are registered
trademarks of Honeywell
International Inc.
UL® is a registered trademark
of Underwriter’s Laboratories
Inc.
This document is not intended
to be used for installation
purposes. We try to keep our
product information up-to-
date and accurate. We cannot
cover all specific applications
or anticipate all requirements.
All specifications are subject to
change without notice.
Honeywell Gamewell-FCI
12 Clintonville Road
Northford, CT 06472-1610
203.484.7161
www.honeywell.com
For more information
Learn more about Gamewell-FCI’s Velociti® Series 3 Detectors
and other products available by visiting www.Gamewell-FCI.com
SYSTEMS
Photoelectric Intelligent Detector:
Physical Specifications
Height: 2.0 inches (51 mm) installed in B300-6 base
Diameter:
6.1 inches (15.49 cm) installed in B300-6 base
4 inches (10.16 cm) installed in B501 base
Shipping Weight: 3.4 oz (96.4 g)
Operating Temperature Range:
Photo: 32° F to 122° F (0° C to 50° C)
Photo in Duct Applications: -4° F to 158° F
(-20° C to 70° C)
Photo with Thermal: 32° F to 100° F (0° C to 38° C)
Operating Humidity Range: 10% to 93%
non-condensing
Rate-of-Rise Detection: Responds to greater than
15°F/minute or 135°F (8.3° C/minute or 57°C
Air Velocity Range: 0 to 4,000 ft/min
(0 to 1219.2 m/min)
Electrical Specifications
Voltage Range: 15 to 32 VDC
Standby Current (@ 24 VDC): 200 UA (one
communication every 5 seconds with green LED
enabled)
Max Alarm Current (max.): 2 mA @ 24 VDC (one
communication every 5 seconds with red LED
enabled)
Max Current (max.): 4.5 mA @ 24 VDC (one
communication every 5 seconds with amber LED
enabled)
Isolator Load Rating: 0.0063
STANDARDS
The Velociti® Series 3 Photoelectric Detectors are
designed to comply with the following standard:
UL Standard: UL 268
AGENCY LISTINGS AND APPROVALS
These listings and approvals apply to the modules
specified in this document. In some cases, certain
modules or applications may not be listed by certain
approval agencies, or listing may be in process.
Consult factory for latest listing status.
UL: S2332
FM: 3023594
MEA FDNY: COA-219-02-E Vol. VI
CSFM: 7272-1703:0501
ISO 9001 Certification
Thermal Detector
Velociti® Series 3 Detectors
Thermal Detectors
Addressable Devices
Description
The Gamewell-FCI, Velociti® Series 3 intelligent thermal detectors with integral
communication provide point location for alarm communication and selective
maintenance. Designed in a modern bright white color, the Velociti Series 3 is
aesthetically pleasing for today's contemporary buildings.
The Velociti Series 3 heat detectors are intelligent addressable detectors with point ID
capability that enable each detector address to be set with rotary address switches
providing exact device locations. The thermal detector continually monitors the
detected temperature and reports it to the fire alarm control panel. The modern
design and expanded color options support a variety of contemporary aesthetic
demands. In addition, each detector is constructed for exceptional installation and
maintenance efficiency. Velociti Series 3 thermal detectors provide cost-effective,
intelligent property protection using the following single thermistor:
• ATD-L3 offers 135°F fixed thermal detection.
• ATD-L3R offers 135°F fixed and rate-of-rise thermal detection.
• ATD-L3H provides fixed high-temperature detection at 190°F .
For legacy installations, service detectors are available in the classic ivory color that
will operate in both Velociti and CLIP protocol for backwards compatibility. Service
models are designated by the -IV part number that appears after the detector model.
Note: The E3 Series® and S3 Series panels support both the Velociti® and CLIP™
protocols, and the GWF-7075 panel supports only the Velociti® protocol. To obtain a
complete list of panels that are listed to Velociti Series 3 detectors, refer to the
Compatibility Addendum for Gamewell-FCI Manuals, P/N:9000-0427-L8.
FEATURES & BENEFITS
• Complies with UL® 268
7th Edition
• Designed with a new
profile to offer modern
and improved
aesthetics
• Contains a built-in
functional test switch
activated by an
external magnet
• Supports a low standby
current
• Provides rotary address
switches (01-159)
• Supplies optional relay,
isolator, or sounder
bases (standard or low
frequency)
•Includes dual LEDs
used for 360° visibility
• Offers expanded color
options
2
Ordering Information
NOTE: "-IV" suffix indicates Ivory color model.
NOTE: "-BL" suffix indicates Black color model.
NOTE: “WH” suffix indicates Bright White color model.
ATD-L3: Thermal heat detector, 135°F fixed, bright white,
Velociti
ATD-L3-IV: Thermal heat detector, 135°F fixed, ivory,
Velociti/CLIP
ATD-L3R: Thermal heat detector, 135°F rate of rise, bright
white, Velociti
ATD-L3R-IV: Thermal heat detector, 135°F rate of rise,
ivory, Velociti/CLIP
ATD-L3H: Thermal heat detector, 190°F high temp, bright
white, Velociti
ATD-L3H-IV: Thermal heat detector, 190°F high temp,
ivory, Velociti/CLIP
Intelligent Bases
For details on intelligent bases, refer to Data Sheet
P/N: 9021-60540.
B501-White: 4" Flangeless mounting base, bright white
B501-White-BP: 4" Flangeless mounting base bulk pack,
bright white
B501-IV: 4" Flangeless mounting base, ivory
B501-BL
4" Flangeless mounting base,
B300-6: 6" Flanged mounting base, bright white
B300-6-IV: 6" Flanged mounting base, ivory
B300-6-BP: 6" Flanged mounting base bulk pack
B200SR-WH: Standard sounder base, bright white
B200SR-IV: Standard sounder base, ivory
B200S-WH: Intelligent addressable sounder base, bright
white
B200S-IV: Intelligent addressable sounder base, ivory
B200SR-LF-WH: Standard low frequency sounder base,
bright white
B200SR-LF-IV: Standard low frequency sounder base,
ivory
B200S-LF-WH: Intelligent addressable low frequency
sounder base, bright white
B200S-LF-IV: Intelligent addressable low frequency
sounder base, ivory
B224RB-WH: Relay base, bright white
B224RB-IV: Relay base, ivory
B224BI-WH: Isolator base, bright white
B224BI-IV: Isolator base, ivory
Ordering Information
Accessories
SMB600: Surface Mounting Kit (flanged)
TR300: Accessory Flange Ring for B300 6" Base, bright
white
TR300-IV: Accessory Flange Ring for B300 6" Base, ivory
RA100Z: Remote LED annunciator, 3-32 VDC
The annunciator mounts to a U.S. single-gang electrical
box. For use with B501 and B300-6.
CK300: Bright White detector kit (Pack of 10)
CK300-IR: White, detector color kit for use with MCS-COF
Series Detectors. (Pack of 10)
CK300-IV: Ivory, detector color kit. (Pack of 10)
CK300-IR-IV: Ivory, detector color kit for use with MCS-
COF Series detectors. (Pack of 10)
CK300-BL: Black detector kit (Pack of 10)
CK300-IR-Bl: Black, detector color kit for use with MCS-
COF Series detectors. (Pack of 10)
M02-04-01: Detector test magnet.
M02-09-00: Test magnet with telescoping handle.
XR2B: Detector removal tool. Allows the installation
and/or removal of the detector heads from the bases in
high ceiling applications.
XP-4: Extension pole for XR2B. Shipped with three, 5-
foot (1.524,m) sections.
Velociti® Series 3 Detectors Technical Specifications
9020-0620 | G | 04/2018
©2018 Honeywell International Inc.
For a complete listing of all
compliance approvals and
certifications, please visit:
http://www.gamewell-
fci.com/en-US/
documentation/Pages/
Listings.aspx
E3 Series®, Velociti® and
Gamewell-FCI® are registered
trademarks and CLIP™ is a
trademark of Honeywell
International Inc.
UL® is a registered trademark
of Underwriter’s Laboratories
Inc.
This document is not intended
to be used for installation
purposes. We try to keep our
product information up-to-
date and accurate. We cannot
cover all specific applications
or anticipate all requirements.
All specifications are subject to
change without notice.
Honeywell Gamewell-FCI
12 Clintonville Road
Northford, CT 06472-1610
203.484.7161
www.honeywell.com
For more information
Learn more about Gamewell-FCI’s Velociti® Series 3 Detectors
and other products available by visiting www.Gamewell-FCI.com
SYSTEMS
Thermal Intelligent Detector
Physical Specifications
Height: 2.0 inches (51 mm) installed in B300-6 base
Diameter:
6.1 inches (15.6 cm) installed in B300-6 base
4 inches (10.2 cm) installed in B501 base
Shipping Weight: 3.4 oz (95 g)
Operating Temperature Range:
Thermal 135° F fixed: -4° F to 100° F
(-20° C to 38° C)
Thermal 135° F rate-of-rise: -4° F to 100° F
(-20° C to 38° C)
Thermal 190° F rate-of-rise: -4° F to 135° F
(-20° C to 57° C)
Operating Humidity Range: 10% to 93% non-
condensing
Rate-of-Rise Detection: : Responds to greater than
15°F/minute or 135°F (8.3° C/minute or 57°C
Electrical Specifications
Voltage Range: : 15 to 32 VDC
Standby Current (@ 24 VDC): 200 uA (one
communication every 5 seconds with green LED
enabled)
Max Alarm Current (max.): : 2 mA @ 24 VDC (one
communication every 5 seconds with red LED
enabled)
Max Current (max.): : 4.5 mA @ 24 VDC (one
communication every 5 seconds with amber LED
enabled)
Isolator Load Rating: : 0.0063
STANDARDS
The Velociti® Series 3 Thermal Detectors are designed to
comply with the following standard:
UL Standard: UL 268
AGENCY LISTINGS AND APPROVALS
These listings and approvals apply to the modules
specified in this document. In some cases, certain
modules or applications may not be listed by certain
approval agencies, or listing may be in process.
Consult factory for latest listing status.
UL: S2332
FM: 3023594
MEA-FDNY: 219-02-E Vol. VI
CSFM: 7270-1703-0502
ISO 9001 Certification
Figure 1 B501 Mounting Base Figure 2 B210LP
Mounting Base
Figure 3 B224BI Mounting Base Figure 4 B224RB
Mounting Base
Intelligent Bases
B501, B210LP, B224BI, B224RB and Mounting Kits and Accessories
Addressable Devices
General
The Intelligent Velociti® and CLIP™ mounting bases and kits provide a variety of ways
to install Gamewell-FCI detectors in any application. These mounting bases are non-
addressable and are available in both the Velociti and CLIP protocols. The intelligent
detectors can be mounted in any of the following devices, depending on the junction
box selection (see Table 1 - Junction Box Selection Guide).
•flanged bases
• flangeless bases
•plastic rings
Note: The E3 Series® and S3 Series panels support both the Velociti® and CLIP™
protocols, and the GWF-7075 panel supports only the Velociti protocol.
Relay, isolator, and sounder bases can be used to meet local code requirements. Relay
bases provide one Form-C contact relay for the control of auxiliary functions such as
door closure and elevator recall. Isolator bases allow loops to continue to operate
under fault conditions and automatically restore when the fault is removed. Sounder
bases are available in a combination temporal 3 and continuous tone model.
The Intelligent Bases provide a variety of mounting options to meet your installation
challenges. The bases are available in flanged or flangeless versions, so that you can
mount the bases to a variety of junction boxes. See Table 1 for the Junction Box
Selection Guide. You can use the SMB600 surface mounting box to mount the
following bases:
• B210LP relay base
• B224BI isolator base
• B224RB relay base
FEATURES & BENEFITS
All sounder bases offer
the following features.
•Complies with UL®
Standards 268 and 464
•Includes the following
three types of bases
that comply with local
code requirements:
- Relay
- Isolator
- Sounder
Relay Base Feature
• Relay bases provide
one Form-C contact
relay
Isolator Base Feature
• Isolator bases include
data communications
lines to operate under
fault condition
Installation Features
The bases offer the
following flexible
installation
characteristics:
• Offers multiple
accessory options
• Includes an installation
mounting kit and
accessories for several
types of model options
• Uses 12-24 AWG
gauge wire ranges to
provide the bases with
flexible installation
• Contains bases that
enable quick and
secure detector plug-in
• Provides SEMS screws
for easy wiring
connections
• Available in temporal
and non-temporal
pattern versions
2
Ordering Information
NOTE: “WH” suffix indicates Bright White color model.
NOTE: "-IV" suffix indicates Ivory color model.
NOTE: "-BL" suffix indicates Black color model.
Intelligent Bases
B501-WHITE: Flangeless mounting base, bright white
Dimensions: 4” (10.2 cm) diameter x 0.74” (18.8 mm)
height
B501-WHITE-BP: Flangeless mounting base bulk
pack, bright white
B501-IV: Standard European flangeless mounting
base, ivory
B501-BL: Standard European flangeless mounting
base, black
B224BI-WH: Plug-in Isolator detector base, bright
white
Dimensions: 6.85 (17.4 cm) diameter x 1.61” (4.1 cm)
height
B224BI-IV: Plug-in Isolator detector base, ivory
B224RB-WH: Plug-in Relay detector base, bright
white
Dimensions: 6.85” (17.4 cm) diameter x 1.61”
(4.1 cm) height
B224RB-IV: Plug-in Relay detector base, ivory
B300-6 : Standard flanged low-profile mounting base,
white
Dimensions: 6.1" (15.49 cm) diameter
B300-6-BP: Bulk pack of B200-6 package contains 10
B300-6-IV: Standard flanged low-profile mounting
base, ivory
Ordering Information
Mounting Kits and Accessories:
BCK-200B: Detector kit, black
CK300: Detector color kit, white Pack of 10
CK300-IR: Detector color kit for use with MCS-COF
Series Detectors, white. Pack of 10
CK300-IV: Detector color kit, ivory. Pack of 10.
CK300-IR-IV: Detector color kit for use with MCS-COF
Series detectors, ivory. Pack of 10.
CK300-BL: Detector color kit, black. Pack of 10.
CK300-IR-Bl: Detector color kit for use with MCS-COF
Series detectors, black. Pack of 10.
TR300: Accessory flange ring for B300-6, bright white
TR300-IV: Accessory flange ring for B300-6m ivory
M02-04-01: Detector test magnet.
M02-09-00: Test magnet with telescoping handle.
RA100Z: Remote LED annunciator. 3-32 VDC. Mounts
to a U.S. single-gang electrical box. For use with B401
and B300-6.
SMB600: Surface mounting kit, flanged.
TR300: Replacement flange for B210LP base, white
TR300-IV: Replacement flange for B210LP base, ivory
WCK-200B: Detector kit, white
Mounting Kits and Accessories
Table 1 lists the mounting kits and accessories assigned to each model.
SINGLE-
GANG
3.5"
OCTAGONA
L
4.0"
OCTAGONA
L
4.0"
SQUARE
4.0"
SQUARE
WITH 3.0"
MUD RING
50 MM 60 MM 70 MM 75 MM
B501 No Yes No No Yes Yes Yes Yes No
B210LP Yes Yes Yes Yes Yes No No No No
B224BI No Yes Yes Yes Yes No Yes Yes Yes
B224RB No Yes Yes Yes Yes No Yes Yes Yes
NOTE: The box depth is contingent on the base and the wire size.
For information on applicable local codes for appropriate recommendation, refer to the National Electrical Code.
Table 1: Intelligent Bases Mounting Kits
Intelligent Bases Technical Specifications
9021-60540 | J | 07/2018
©2018 Honeywell International Inc.
For a complete listing of all
compliance approvals and
certifications, please visit:
http://www.gamewell-
fci.com/en-US/
documentation/Pages/
Listings.aspx
Gamewell-FCI®, E3 Series® and
Velociti® are registered
trademarks and Clip™ is a
trademark of Honeywell
International Inc.
UL® is a registered trademark
of Underwriters Laboratories
Inc.
ULC® is a registered trademark
of Underwriters Laboratories
of Canada Inc.
This document is not intended
to be used for installation
purposes. We try to keep our
product information up-to-
date and accurate. We cannot
cover all specific applications
or anticipate all requirements.
All specifications are subject to
change without notice.
Honeywell Gamewell-FCI
12 Clintonville Road
Northford, CT 06472-1610
203.484.7161
www.honeywell.com
For more information
Learn more about Gamewell-FCI’s Intelligent Bases and other
products available by visiting www.Gamewell-FCI.com
SYSTEM
Temperature Range:
For B224RB, B224BI, and B210LP: 32°F to 120°F
(0°C to 49° C)
For B210LP, B300-6, B501: -4° F to 150°F (-20°C to
66°C)
Humidity Range: 10% to 93% RH, non-condensing
Wire Gauge:
For B224BI, B224RB: 14 to 24 AWG
For B210LP, B300-6, B501: 12 to 24 AWG
Electrical Ratings:
For B501, B224RB, B224BI:
Operating Voltage: 15 to 32 VDC (powered by SLC)
Standby Ratings:
B501: 150 uA
B224BI: 450 uA maximum
B224RB: 170 uA
Set Time (B224RB only):
Short delay: 55-90 m seconds
Long delay: 6 to 9 seconds
Reset Time (B224RB only): 20 m seconds maximum
Relay Characteristics (B224RB only): Two-coil Latching
Relay One Form-C Contact
Ratings (UL/CSA):
0.9 A @ 125 VAC (resistive)
0.9 A @ 110 VDC (inductive)
3.0 A @ 30 VDC (resistive)
TEMPERATURE AND HUMIDITY RANGES
This system meets NFPA requirements for operation at 0
– 49°C/32 – 120°F and at a relative humidity 93% ± 2%
RH (noncondensing) at 32°C ± 2°C (90°F ± 3°F).
However, the useful life of the system's standby batteries
and the electronic components may be adversely affected
by extreme temperature ranges and humidity. Therefore,
it is recommended that this system and its peripherals be
installed in an environment with a normal room
temperature of 15 – 27°C/60 – 80°F.
STANDARDS
The Intelligent Bases are designed to comply with the
following standards:
UL Standards: UL 268
UL 464
AGENCY LISTINGS AND APPROVALS
These listings and approvals apply to the modules
specified in this document. In some cases, certain
modules or applications may not be listed by certain
approval agencies, or listing may be in process.
Consult factory for latest listing status.
UL: S911
FM: 3035027
CSFM: 7135-1653:0213
7300-1653:0109
7300-1653:0126
7300-1653:0238
ISO 9001 Certification