Conditions for Permit B21003522
Fire
1 Fire Lanes/Fire Zones Shall Be Marked Per City Ordinance. Fire Department Access Roads Shall Be Paved A
Minimum Of 20-Feet Wide And Shall Provide A Minimum Height Clearance Of 13.5-Feet. Applicant Shall Provide
An 8.5 X 11-Inch Site Plan Showing Placement Of Required Fire Lanes For Fire Department Permanent Record
Prior To Certificate Of Occupancy.
2 Street Address Shall Be Posted On Building. Contrasting Color Minimum 12-Inches.
3 Dry Standpipes Are Required. Plans Shall Be Submitted For Approval. Roof outlets are required.
4 Portable Fire Extinguishers Required, 2A10Bc Minimum Rating.
5 Fire Alarm System Required. Plans To Be Submitted To Renton Fire Prevention Bureau For Approval
(425)430-7024. Both An Electrical And Fire Alarm Permit Are Required For This Installation. System Shall Be
Monitored By An Approved Ul-Listed Central Station. Full Detection And Fully Addressable Required.
6 SPRINKLER SYSTEM IS REQUIRED. PLANS SHALL BE STAMPED BY A STATE CERTIFIED SPRINKLER
CONTRACTOR. PLANS TO BE SUBMITTED TO RENTON FIRE PREVENTION BUREAU FOR REVIEW AND
PERMITTING(425)430-7024. A PLUMBING PERMIT FOR A BACKFLOW PREVENTION DEVICE IS ALSO
REQUIRED PRIOR TO ISSUANCE OF SPRINKLER PERMIT.
7 Required Fire Flow 4,750 Gpm. Proposed Hydrant Layout Is Acceptable.
8 The building shall comply with the City of Renton Emergency Radio Coverage ordinance. Testing shall verify both
incoming and outgoing minimum emergency radio signal coverage. If inadequate the building shall be enhanced
with amplification equipment in order to meet minimum coverage. Separate plans and permits are required for any
proposed amplification systems.
Planning
9 Planning General Conditions
Arctic white change is approved however original ground floor base exterior brick color was changed in this
revision and will need to return to color as shown in approved building permit set and land use decision.