HomeMy WebLinkAboutRS_Redline_Letter_From_Renton_180930_v2September 27, 2018
Mr. Russ Sorkness
JK Monarch
424 29th St NE, Suite C
Puyallup, WA 98372
RE: Building Permit Structural Plan Review – First Submittal
830 Chelan Place NE (B18004548)
Dear Mr. Sorkness:
We reviewed the proposed project for compliance with the structural provisions of
the 2015 International Residential Code (IRC) and 2015 International Building Code
(IBC) as amended and adopted by the state of Washington and the City of Renton.
The design team should address the comments below.
Responses to these review comments should be made in an itemized letter form and
any changes to the drawings should be clouded. We recommend that the permit
applicant have the architect, structural engineer, and truss engineer respond and
resubmit for additional review.
All information should be submitted directly to the City of Renton.
Geotechnical
1. Geotechnical special inspections. Special inspections and tests should be
provided by a qualified geotechnical engineer as recommended in the
geotechnical report by Associated Earth Sciences, dated June 20, 2013. See IRC
Section R401.4. The following is a summary:
a. Site excavation and grading.
b. Overexcavation for placement of structural fill.
c. Construction dewatering, see Page 4 of the geotechnical report.
d. Placement of structural fill and soil compaction.
e. Verification of soil-bearing capacity.
D08-053
B18004548
V2
REVISION
Received: 10/04/2018 / aalexander
BUILDING DIVISION
Mr. Sorkness
Page 2 of 7
September 27, 2018
No response from the applicant is required for this comment. This
comment is for the building official and for reference.
Architectural
1. Special Inspection Form. Due to the geotechnical inspection requirements
indicated on Pages 5 and 8 of the submitted geotechnical report, please
complete and submit the City of Renton’s special inspection form. An
electronic copy of this form may be found at:
https://edocs.rentonwa.gov/Documents/0/edoc/955944/Special%20Inspection
%20Form.pdf
2. Our review of the site plan indicates the roof projects within 5 feet of the
property line on the south and north sides of the structure. By IRC Section
302.1 and Table 302.1(1), either the underside roof shall have a 1-hour fire-
resistance rating or if fire blocking is applied between the top of wall and
underside of the roof. We note the “2x solid blocking” note in the Typical Wall
Section on Sheet A-4, but it is not clear if opening are to be placed in the
blocking to allow for venting; i.e. how is the roof being vented? Please revise
the drawings to be consistent with the IRC requirements and resubmit the
drawings for review. This may affect the roof ventilation calculations. Please
verify. See IRC Section 106.1.1.
Structural
General
1. Structural special inspections. Structural special inspections. Special
inspections by qualified special inspectors do not appear warranted for this
project. If it is determined otherwise, the applicable special inspections are
noted below. See IBC Sections 1704.1 and 1704.2.
Mr. Sorkness
Page 3 of 7
September 27, 2018
a. Installation of concrete expansion, adhesive, and screw anchors, where
applicable: in accordance with qualifying report of evaluation service (e.g.,
ICC-ES). See also IRC Section 301.1.3 as well as IBC Section 1705.1.1.
No response from the applicant is required for this comment. This
comment is for the building official and for reference.
2. The drawings do not include information relating to the proposed wood
trusses. The drawings should be revised and resubmitted indicating the
following:
a. The truss live loading shall be per IRC Section 301.5 and Table 301.5,
especially noting footnotes b and g.
b. The truss design shall be per IRC Sections 502.11.1 and 802.10.2, especially
indicating the truss design and manufacturing shall be per ANSI/TPI 1.
c. The truss temporary and permanent bracing shall be per IRC Sections
502.11.2 and 802.10.3 as well as the Truss Plate Institute’s Building
Component Safety Information. Please note, we see Note 8 under the
Manufactured Wood Trusses on Sheet S-0 indicates bracing per the truss
engineer, but does not indicate to what standard the bracing is to satisfy.
d. Truss alterations shall not occur unless the approval of a design
professional as indicated in IRC Sections 502.11.3 and 802.10.4.
Lateral
3. Detail 6/SD-1 indicates a pinned connection where the floor joist run parallel
to the wall with respect to out of plane wall loads; in that the proposed
connection transfers shear but don’t provide calculate-able moment
resistance. Below is image with redlined comments. Please revise the detail to
resolve this pinned condition and resubmit for review. Please note, the City of
Renton notes per AWC SDPWS-15 Section 4.1.5.1.2 sheathing cannot be used
to transfer tensile loads. See IRC Sections 106.1.1 and 301.1.3 as well as IBC
Sections 2305.1 and 2306.1.
Mr. Sorkness
Page 4 of 7
September 27, 2018
4. Currently Detail 23/SD-2 indicates the diagonal bracing passing its load directly
to the truss’s top chord for which the truss has not be designed. Please revise
the detail to establish a positive load path to the roof. Below are some images
with our redlined comments. See IBC Section 107.2.1, 1604.2, and 2306.1.
Mr. Sorkness
Page 5 of 7
September 27, 2018
5. Our review indicates that a “flat” 2x member, needs to be connected to the 2x
diagonal wood bracing shown in Detail 23/SD-2 which braces the top of wall at
the end gable truss. This to stiffen the diagonal brace and prevent the
diagonal from buckling under loading when the brace length exceeds 6 feet 3
inches. The drawings should be revised to indicate this requirement and
resubmitted for review. See IRC Sections 106.1.1, 301.1, and 301.1.3 as well as
IBC Sections 107.2.1, 2305.1, 2306.1, and 2307.1 as well as AWC NDS-15
Section 3.7.1.
6. Sheet S-2 indicates plans showing the proposed shear walls, but the shear wall
schedule which details the construction requirement of the shear walls is on
another sheet, Sheet S-0. The City of Renton requires the shear wall schedule
and the plans showing the shear walls to be on the same sheet(s). Please
revise the drawings to meet this requirement and resubmit the drawings for
review. See IRC Sections 104.1, 106.1.1, and 109.1.4.
7. The drawings, such as Sheet S-0, indicate walls that have sheathing on both
sides of the wall (i.e., shear wall types 2W3 and 2W2), but the drawings do not
indicate how this loading from both sides of the wall is transferred to the
below wall/structure. Is there addition blocking/ rim joists below the double
sheathed wall with additional nailing and light gage connections? Please revise
the drawings to clarify the design intent for this load path and resubmit for
review. See IRC Section 301.1.3 as well as IBC Sections 107.2.1, 1604.2, and
2305.1.
Mr. Sorkness
Page 6 of 7
September 27, 2018
8. The Upper Floor Framing/ Main Floor SW Plan indicates 2x6 HF Stud Grade
studs at 16 inches on-center balloon framing to the north of the proposed
stairs. Please submit substantiating data, such as additional calculations which
indicate the proposed studs have the capacity to resist the required IBC
loadings, especially the combined wind and gravity components and cladding
loads. The proposed design may need to be revised. Please verify. See IRC
Section 301.1.3 and IBC Sections 107.2.1, 1604.2, 1605.3, and 2306.1.
9. Please revise the drawings to indicate a positive load path from the W4 shear
wall at the south side/ entrance of the house to the foundation. Below is an
image from Sheet S-2 with our redlined comment. Please resubmit the revised
drawings for review. See IRC Sections 106.1.1 and 301.1.3 as well as IBC
Section 1604.2.
Truss Submittal
1. The truss layout and design should be revised to match Sheet S-2. Below are
images from the truss layout drawings with our redlined comments. These
redlined notes are to be consistent with Sheet S-2 which appears to use these
drag trusses as part of the chord system for the roof. Please resubmit the
Mr. Sorkness
Page 7 of 7
September 27, 2018
revised layout drawing and revised truss engineering package for review. See
IBC Section 107.2.1, 1604.2, 1609.1, and 1613.1.
Corrections and comments made during the review process do not relieve the permit
applicant or the designers from compliance with code requirements, conditions of
approval, and permit requirements; nor are the designers relieved of responsibility for
a complete design in accordance with the laws of the state of Washington. This
review is for general compliance with the International Residential Code and
International Building Code as they relate to the project. See IRC Section 105.4.
If you have any questions or need additional clarification, please contact us.
Sincerely,
Alan D. Findlay, P.E.
Building Plan Reviewer, City of Renton
cc: File