Loading...
HomeMy WebLinkAboutHeating_System_Sizing_Worksheet_2301_190710_v3Simple Heating System Size: Washington State Project Information Contact Information Heating System Type: To see detailed instructions for each section, place your cursor on the word "Instructions". Design Temperature Instructions Design Temperature Difference (∆T)46 ∆T = Indoor (70 degrees) - Outdoor Design Temp Area of Building Conditioned Floor Area Instructions Conditioned Floor Area (sq ft)2,301 Average Ceiling Height Conditioned Volume Instructions Average Ceiling Height (ft)8.5 19,559 Glazing and Doors U-Factor X Area =UA Instructions 0.280 363 101.64 Skylights U-Factor X Area =UA Instructions 0.50 0 --- Insulation Attic U-Factor X Area =UA Instructions 0.026 1,175 30.55 Single Rafter or Joist Vaulted Ceilings U-Factor X Area UA Instructions No selection 0 --- Above Grade Walls (see Figure 1)U-Factor X Area UA Instructions 0.056 1,996 111.78 Floors U-Factor X Area UA Instructions 0.025 1,115 27.88 Below Grade Walls (see Figure 1)U-Factor X Area UA Instructions No selection 0 --- Slab Below Grade (see Figure 1)F-Factor X Length UA Instructions 0.303 0 --- Slab on Grade (see Figure 1)F-Factor X Length UA Instructions ---0 ________ Location of Ducts Instructions Duct Leakage Coefficient 1.10 Sum of UA 271.84 Envelope Heat Load 12,505 Btu / Hour Sum of UA X ∆T Air Leakage Heat Load 9,717 Btu / Hour Volume X 0.6 X ∆T X .018 Building Design Heat Load 22,221 Btu / Hour Air Leakage + Envelope Heat Loss Building and Duct Heat Load 24,443 Btu / Hour Ducts in unconditioned space: Sum of Building Heat Loss X 1.10 Ducts in conditioned space: Sum of Building Heat Loss X 1 Maximum Heat Equipment Output 34,221 Btu / Hour Building and Duct Heat Loss X 1.40 for Forced Air Furnace Building and Duct Heat Loss X 1.25 for Heat Pump This heating system sizing calculator is based on the Prescriptive Requirements of the 2015 Washington State Energy Code (WSEC) and ACCA Manuals J and S. This calculator will calculate heating loads only. ACCA procedures for sizing cooling systems should be used to determine cooling loads. Please fill out all of the green drop-downs and boxes that are applicable to your project. As you make selections in the drop-downs for each section, some values will be calculated for you. If you do not see the selection you need in the drop-down options, please call the WSU Energy Extension Program at (360) 956-2042 for assistance. Plan 2301 Rueppell, Inc. (253) 297-8040 Above Grade Below Grade Figure 1. All Other Systems Heat Pump (07/01/13) D08-053 B19001161 V3 REVISION Received: 07/18/2019 / aalexander BUILDING DIVISION APPROVEDBUILDING DIVISION THIS SET OF APPROVED PLANS MUST BE ON THE JOB AT ALLTIMES DURING CONSTRUCTION. THIS BUILDING IS NOT TO BEOCCUPIED UNTIL AFTER FINAL INSPECTION BY THE RENTONBUILDING DIVISION AND RECEIPT OF CERTIFICATE OFOCCUPANCY. APPROVAL SHALL NOT BE CONSTRUED AS THE AUTHORITY TOVIOLATE OR CANCEL ANY PROVISIONS OF CODES, ORDINANCES,OR OTHER REGULATIONS ENFORCED BY THIS CITY. DATE: 08/05/2019