Loading...
HomeMy WebLinkAboutCA_Limelite SP - Lot 5 Sprinkler Calcs_20190402_V1        MATERIAL SUBMITTAL   AND   HYDRAULIC CALCULATIONS      FOR      LIMELITE SP – LOT 5  16214 114TH AVENUE SE  RENTON, WA 98055    BY     LIBERTY PLUMBING  26116 112TH STREET EAST  BUCKLEY, WA 98321  PR14000070 F19001679RECEIVED 04/02/2019 lwalker BUILDING DIVISION By: ccappelletti Date: 04/08/2019 FIRE DEPARTMENT For Construction Subject to Corrections Noted in Red APPROVED LIMELITE LOT 5 RESIDENCE  TABLE OF CONTENTS  FIRE SPRINKLERS  RELIABLE MODEL RFC49 RESIDENTIAL CONCEALED SPRINKLER  RELIABLE MODEL G5‐56 CONCEALED SPRINKLER  FIRE SPRINKLER VALVES  AMES 200OB BACKFLOW PREVENTER  PIPE AND FITTINGS  HARVEL CPVC FIRE SPRINKLER PIPE  SPEARS FLAMEGUARD CPVC FITTINGS  HANGERS   TOLCO FIGURE 24 CPVC HANGER  TOLCO FIGURE 28 “STAND‐OFF” CPVC HANGER  TOLCO FIGURE 28M OFFSET CPVC HANGER  HYDRAULIC CALCULATIONS  BEDROOM – TWO SPRINKLER CALCULATION (RESIDENTIAL)  PR14000070 F19001679RECEIVED 04/02/2019 lwalker BUILDING DIVISION FIRE SPRINKLERS PR14000070 F19001679RECEIVED 04/02/2019 lwalker BUILDING DIVISION Reliable Automatic Sprinkler Co., Inc., 103 Fairview Park Drive, Elmsford, New York 10523 Bulletin 006 Rev. IBulletin 006 Rev. I Model RFC30 (SIN RA0611) Model RFC43 (SIN RA0612) Model RFC49 (SIN RA0616) Residential Flat Concealed Sprinklers A Residential Flat Concealed Sprinkler engineered for a minimum design density of 0.05 gpm/ft2 with low GPM requirements. Features 1. Very low water flow requirements. 2.Cover plate attachment (Plain or Perforated) with ½” (13mm) Total adjustment. 3. Thread-On/Thread-Off or Push-On/Thread Off cover attachment option. 4. Smooth aesthetic ceiling profile. 5. Available in brass, chrome and black plated or painted finishes. Listings & Approval 1. Listed by Underwriters Laboratories, and certified by UL for Canada (cULus) UL Listing Categories Residential Automatic Sprinklers UL Guide Number VKKW Product Description Model RFC30, RFC43 and RFC49 Concealed Residen- tial Sprinklers are fast response residential fusible solder link automatic sprinklers. Residential sprinklers differ from standard sprinklers primarily in their response time and water distribution patterns. Model RFC30, RFC43 and RFC49 sprinklers discharge water in a hemispherical pattern below the sprinkler de- flector. Residential distribution patterns are higher and generally contain a finer droplet size than standard sprin- kler patterns. The combination of speed of operation and high dis- charge pattern required for residential sprinklers has demonstrated, in fire testing, an ability for controlling residential fires, and thereby providing significant evacu- ation time for occupants. The RFC30, RFC43 and RFC49 Sprinklers provide the best form of fire protection by combining an attractive ap- pearance and ½” (13mm) of cover adjustment for ease of installation. The small diameter cover plate is easily and positively attached and blends into the ceiling, con- cealing the most dependable fire protection available, an automatic sprinkler system. The RFC30, RFC43 and RFC49 are UL Listed Residen- tial Sprinklers to be installed in the residential portions of any occupancy in accordance with NFPA 13, 13R, & 13D. The RFC30, RFC43 and RFC49 can reduce the need for precise cutting of drop nipples. The threaded cover plate assembly can be adjusted without tools to fit ac- curately against the ceiling. The fire protection system need not be shut down to adjust or remove the cover plate assembly. Plain Cover Plate Perforated Cover Plate PR14000070 F19001679RECEIVED 04/02/2019 lwalker BUILDING DIVISION 2. Application and Installation The RFC30, RFC43 and RFC49, for residential instal- lations, use a 165°F (74°C) fusible solder link in a tun- ing fork style sprinkler frame with a drop-down deflector. This assembly is recessed into the ceiling and concealed by a flat cover plate. The cover plate is attached to the skirt, using 135°F (57°C) ordinary temperature classifica- tion solder. When the ceiling temperature rises, the solder holding the cover plate releases the cover allowing the deflector to drop into position and exposing the sprinkler inside to ceiling temperature. The subsequent operation of the solder link opens the waterway and causes the de- flector to drop into position to distribute the discharging water in a hemispherical pattern below the sprinkler de- flector. Any adjustment of thread engagement between the cover plate and cup will assure that the drop-down deflector is properly located below the ceiling. The resi- dential distribution pattern contains a finer droplet size than a standard sprinkler, and the pattern produces sig- nificantly higher wall wetting. After a 25/8 inch diameter hole is cut in the ceiling, the sprinkler is to be installed with the Model FC Wrench. When installing a sprinkler, the wrench is first positioned into the sprinkler/cup assembly and around the hexago- nal body of the sprinkler frame. The Wrench must bottom out against the cup in order to ensure proper, safe instal- lation. The sprinkler is then tightened into the pipe fitting. When inserting or removing the wrench from the sprin- kler/cup assembly, care should be taken to prevent dam- age to the sprinkler. DO NOT WRENCH ON ANY OTHER PART OF THE SPRINKLER/CUP ASSEMBLY. MODEL RFC30, RFC43 AND RFC49 CONCEALED SPRINKLERS MUST BE INSTALLED ONLY WITH 135°F RATED COV- ERS. Note: A leak tight ½” NPT (R1/2) sprinkler joint can be ob- tained with a torque of 8-18 ft-lbs (10,8 - 24,4 N-m). Do not tighten sprinklers over maximum recommended torque. It may cause leakage or impairment of the sprinklers. Cover assemblies provide up to 1/2” (13mm) of adjust- ment. Turn the cover clockwise until the flange is in con- tact with the ceiling. For the push-on/thread-off option, the cover assembly is pushed onto the cup and final ad- justment is made by turning the cover clockwise until the skirt flange makes full contact with the ceiling. Cover re- moval requires turning in the counter-clockwise direction. In ceilings that have a plenum space above the sprinkler, the plenum space may have neutral or neg- ative pressurization but must not be positively pres- surized. Inspect all sprinklers after installation to en- sure that the gap between the cover plate and ceiling and the 4 slots in the cup are all open and free from any air fl ow impediment. Model (SIN) Thread Size Inch (mm) Nominal Orifi ce Inch (mm) Sprinkler Temp Rating CCP Assembly Temp. Rating Max. Ambient Temp. K Factor Max. Pressure psi (bar)°F °C °F °C °F °C RFC 30 (RA0611)½” (15)21/64 (8,2) 165 74 135 57 100 38 3.0 (43.2) 175 (12) RFC 43 (RA0612)½” (15)3/8 (10) 165 74 135 57 100 38 4.3 (62) 175 (12) RFC 49 (RA0616)½” (15)7/16 (11) 165 74 135 57 100 38 4.9 (70.6) 175 (12) Note: 1 bar = 100 Kpa RFC 30 Max. Coverage area Ft x Ft (m x m) Max. Spacing Ft (m) Ordinary Temp. Rating (165°F/74°C)Top of Defl ector to Ceiling Inch (mm) Installation Type Minimum Spacing Ft (m)Flow GPM (L/min) Pressure PSI (bar) 12 x 12 (3,6 x 3,6) 12 (3,6) 9 (34,1) 9.0 (0,62) Smooth Ceilings ½ to 1 (13 to 25.4) Beamed Ceilings per NFPA 13D, 13R or13 installed in beams ½ to 1 (13 to 25.4)Concealed 8 (2,4) 14 x 14 (4,3 x 4,3) 14 (4,3) 10 (37,8) 11.0 (0,76) For Ceiling types refer to NFPA 13, 13R or 13D PR14000070 F19001679RECEIVED 04/02/2019 lwalker BUILDING DIVISION 3. Maintenance Model RFC30, RFC43 and RFC49 Concealed Sprin- klers should be inspected and the sprinkler system maintained in accordance with NFPA 25. Do not clean sprinklers with soap and water, ammonia or any other cleaning fluids. Remove dust by using a soft brush or gentle vacuuming. Remove any sprinkler cover plate as- sembly which has been painted (other than factory ap- plied) or damaged in any way. A stock of spare sprin- klers should be maintained to allow quick replacement of damaged or operated sprinklers. Prior to installation, sprinklers should be maintained in the original cartons and packaging until used to minimize the potential for damage to sprinklers that would cause improper opera- tion or non-operation. Model RFC30, RFC43 and RFC49 Residential Concealed Sprinkler Specifi cation Sprinklers shall be cULus Listed low flow residential con- cealed sprinklers with drop-down deflector and adjust- able flat cover plate engineered for a minimum design density of 0.05 gpm/ft2. Sprinkler frame and deflector shall be of bronze frame construction having a ½” NPT thread. Thermal element shall consist of an approved black-painted beryllium-nickel fusible solder link with symmetric lever mechanism, maintaining a Teflon-coated Belleville spring washer and machined brass cap water seal assembly containing no plastic parts. Sprinkler K- factor shall be nominal 3.0 (43.2), 4.3 (62), and 4.9 (70.6) having a 5/16”, 3/8” and 7/16” orifice. Temperature rating shall be Ordinary 165°F (74°C); cover plate temperature rating to be 135°F (57°C). Cover plate assembly shall consist of a brass cover plate and copper alloy retainer flange allowing a ½” cover plate adjustment. Any secure engagement between the cover plate and the cup will assure that the drop-down deflector is properly located below the ceiling. A plastic protective cap shall be provided and factory installed inside the sprinkler cup to protect the drop-down sprinkler deflector from dam- age, which could occur during construction before the cover plate is installed. Standard cover finish: [Chrome] [White] [Specialty – specify]. Residential concealed sprinklers shall be Reliable Model RFC30, SIN RA0611 (Bulletin 006), Model RFC43, SIN RA0612 (Bulletin 006) or Model RFC49, SIN RA0616 (Bulletin 006). RFC 43 Max. Coverage area Ft x Ft (m x m) Max. Spacing Ft (m) Ordinary Temp. Rating (165°F/74°C)Top of Defl ector to Ceiling Inch (mm) Installation Type Minimum Spacing Ft (m)Flow GPM (L/min) Pressure PSI (bar) 12 x 12 (3,6 x 3,6) 12 (3,6) 12 (4,5) 7.8 (0,54) Smooth Ceilings ½ to 1 (13 to 25.4) Beamed Ceilings per NFPA 13D, 13R or 13 installed in beams ½ to 1 (13 to 25.4) Concealed 8 (2,4) 14 x 14 (4,3 x 4,3) 14 (4,3) 13 (49) 9.1 (0,63) 16 x 16 (4,9 x 4,9) 16 (4,9) 13 (49) 9.1 (0,63) 18 x 18 (5,5 x 5,5) 18 (5,5) 18 (68) 17.5 (1,21) 20 x 20 (6,1 x 6,1) 20 (6,1) 21 (79) 23.8 (1,64) For Ceiling types refer to NFPA 13, 13R or 13D RFC 49 Max. Coverage area Ft x Ft (m x m) Max. Spacing Ft (m) Ordinary Temp. Rating (165°F/74°C)Top of Defl ector to Ceiling Inch (mm) Installation Type Minimum Spacing Ft (m)Flow GPM (L/min) Pressure PSI (bar) 12 x 12 (3,6 x 3,6) 12 (3,6) 13 (49) 7.0 (0,48) Smooth Ceilings ½ to 1 (13 to 25.4)Beamed Ceilings per NFPA 13D, 13R or 13 installed in beams ½ to 1 (13 to 25.4) Concealed 8 (2,4) 14 x 14 (4,3 x 4,3) 14 (4,3) 13 (49) 7.0 (0,48) 16 x 16 (4,9 x 4,9) 16 (4,9) 13 (49) 7.0 (0,48) 18 x 18 (5,5 x 5,5) 18 (5,5) 17 (64,3) 12.0 (0,83) 20 x 20 (6,1 x 6,1) 20 (6,1) 20 (75,73) 16.7 (1,14) For Ceiling types refer to NFPA 13, 13R or 13D PR14000070 F19001679RECEIVED 04/02/2019 lwalker BUILDING DIVISION Reliable Automatic Sprinkler Co., Inc. (800) 431-1588 Sales Offices(800) 848-6051 Sales Fax (914) 829-2042 Corporate Offices www.reliablesprinkler.com Internet Address Manufactured by Recycled Paper Revision lines indicate updated or new data. EG. Printed in U.S.A. 11/14 P/N 9999970261 The equipment presented in this bulletin is to be installed in accordance with the latest published Standards of the National Fire Protection Association, Factory Mutual Research Corporation, or other similar organizations and also with the provisions of governmental codes or ordinances whenever applicable. Products manufactured and distributed by Reliable have been protecting life and property for over 90 years, and are installed and serviced by the most highly qualified and reputable sprinkler contractors located throughout the United States, Canada and foreign countries. Ordering Information Specify: 1. Sprinkler Model 2. Cover Plate Finish 3. Thread-On or Push-On Feature Cover Plate Finishes(1) Standard Finishes Chrome White Paint Special Application Finishes(2) Bright Brass Finished Bronze Black Plating Black Paint Off White Satin Chrome (1)Other finishes and colors are available on special order. Consult factory for details. Coverplate custom paint issemi-gloss, unless specified otherwise. (2)For the perforated style cover- plate, consult factory for avail- ability on these and other cus-tom finishes. PR14000070 F19001679RECEIVED 04/02/2019 lwalker BUILDING DIVISION FIRE SPRINKLER VALVES PR14000070 F19001679RECEIVED 04/02/2019 lwalker BUILDING DIVISION Series 2000B Double Check Valve Assemblies are designed to protect drinking water sup-plies for dangerous cross-connections in accordance with national plumbing codes and water authority requirements for non-health-hazard non-potable service applications such as irrigation, fire line, or industrial processing. These valves meet the requirements of ASSE Std. 1015 and AWWA Std. C510 and are approved by the Foun da tion for Cross-Con nec tion Control and Hy drau lic Re search at the University of South ern California. Specifications A Double Check Valve Assembly shall be installed at each not ed lo ca tion. The as sem bly shall con sist of two positive seat ing check mod ules with cap tured springs and rubber seat discs. The check module seats and seat discs shall be re place able. Ser vice of all internal com po nents shall be through a sin gle ac cess cover se cured with stainless steel bolts. The as sem bly shall also in clude two resilient seat ed iso la tion valves and four top mount ed, re sil ient seat ed test cocks. The as sem bly shall meet the re quire ments of ASSE Std. 1015 and AWWA Std. C510. Ap proved by the Foun da tion for Cross-Con nec tion Control and Hy drau lic Re search at the Uni ver si ty of South ern Cal i for nia. As sem bly shall be an Ames Company Series 2000B. Approvals Approved by the Foundation for Cross-Connection Control and Hy drau lic Research at the University of Southern California. LBV models not listed. Horizontal and vertical "flow up" approval on all sizes. ES-A-2000B 3⁄4" 2000B (20mm) 2" 2000B HC (50mm) Series 2000B Double Check Valve Assemblies Sizes: 1⁄2" – 2" (15 – 50mm) Job Name ________________________________________________Contractor ______________________________________________ Job Location ______________________________________________Approval _______________________________________________ Engineer _________________________________________________Contractor’s P.O. No. ______________________________________ Approval _________________________________________________Representative ___________________________________________ Ames product specifications in U.S. customary units and metric are ap prox i mate and are pro vid ed for ref er ence only. For precise mea sure ments, please contact Ames Technical Ser vice. Ames reserves the right to change or modify prod uct de sign, con struc tion, spec i fi ca tions, or ma te ri als with out prior notice and without in cur ring any ob li ga tion to make such chang es and mod i fi ca tions on Ames products previously or sub se quent ly sold.amesfirewater.com Features • Ease of maintenance with only one cover •Top entry •Replaceable seats and seat discs •Modular construction •Compact design •1⁄2" – 2" (15 – 50mm) Cast bronze body construction • Top mounted ball valve test cocks •Low pressure drop •No special tools required •1⁄2" – 1" (15 – 25 mm) have tee handles Available Models Suffix: B - Quarter turn ball valves LBV - less ball valves SH - stainless steel ball valve handles HC - 21⁄2" inlet/outlet fire hydrant fit ting (2" valve) Pressure — Temperature Temperature Range: 33°F – 140°F (0.5°C – 60°C) Maximum Working Pressure: 175psi (12.1 bar) Standards AWWA Std. C510, IAPMO PS31 1015 B64.5 3⁄4" - 2"(LBV Models Only) It is illegal to use this product in any plumbing system providing water for human consumption, such as drinking or dishwashing, in the United States. Before installing standard material prod-uct, consult your local water authority, building and plumbing codes. WARNING! PR14000070 F19001679RECEIVED 04/02/2019 lwalker BUILDING DIVISION Capacities As compiled from documented Foundation for Cross-Connection Control and Hydraulic Research at the University of Southern California lab tests. ∆Typical maximum system flow rate (7.5 feet/sec., 2.3 meters/sec.) kPa psi 83 12 69 10 55 8 41 6 28 4 14 2 0 0 ∆P 0 2 4 6 8 10 12 gpm0 7.6 15.2 22.8 30.4 38 45.6 lpm 5 7.5 10 fps 1.5 2.3 3.0 mps ∆ ∆P * ∆P ∆kPa psi 110 16 83 12 69 10 55 8 41 6 28 4 14 2 0 5 10 15 20 25 30 35 40 45 50 55 60 gpm0 19 38 57 76 95 114 133 152 171 190 209 228 lpm 5 7.5 10 15 fps 1.5 2.3 3.0 4.6 mps ∆P ∆kPa psi 96 14 83 12 69 10 55 8 41 6 28 4 14 2 0 0 0 10 20 30 40 50 60 70 80 90 100 110 120 gpm0 38 76 114 152 190 228 266 304 342 380 418 456 lpm 5 7.5 10 15 fps 1.5 2.3 3.0 4.6 mps kPa psi 83 12 69 10 55 8 41 6 28 4 14 2 0 0 ∆P0 10 20 30 40 50 60 70 80 90 100 110 120 gpm 0 38 76 114 152 190 228 266 304 342 380 418 456 lpm 5 7.5 10 15 fps 1.5 2.3 3.0 4.6 mps ∆ ∆P ∆kPa psi 83 12 69 10 55 8 41 6 28 4 14 2 0 0 0 25 50 75 100 125 150 175 200 gpm0 95 190 285 380 475 570 665 760 lpm 5 7.5 10 15 fps 1.5 2.3 3.0 4.6 mps 1⁄2" (15mm) 1" (25mm) 11⁄4" (32mm) 11⁄2" (40mm) 2" (50mm) kPa psi 152 22 124 18 96 14 69 10 41 6 14 2 3⁄4" (20mm) 0 5 10 15 20 25 30 35 40 45 50 gpm0 19 38 57 76 95 114 133 152 171 190 lpm7.5 15 fps 2.3 4.6 mps ∆ Dimensions – Weights Size (dn) diMenSiOnS WeigHt A B C F G H I in. mm in. mm in. mm in. mm in. mm in. mm in. mm in. mm lbs. kgs. 1⁄2 15 10 254 45⁄8 117 27⁄16 62 5 127 33⁄8 85 25⁄16 59 21⁄16 52 4.5 2 3⁄4 20 111⁄8 282 4 102 31⁄8 79 63⁄16 157 37⁄16 87 21⁄8 54 15⁄16 33 5 2.3 1 25 131⁄4 337 51⁄8 130 4 102 71⁄2 191 33⁄8 85 111⁄16 43 111⁄16 43 12 5.4 11⁄4 32 163⁄8 416 5 127 35⁄16 84 91⁄2 241 5 127 3 76 2 50 15 6.8 11⁄2 40 163⁄4 425 47⁄8 124 31⁄2 89 93⁄4 248 513⁄16 148 31⁄8 79 211⁄16 68 15.86 7.2 2 50 191⁄2 495 61⁄4 159 4 102 133⁄8 340 61⁄8 156 37⁄16 87 211⁄16 68 25.75 11.7 H g iSuffix HC — Fire Hydrant Fittings dimension "A" = 231⁄2" (594mm) C B F A Strainer sold separately Pressure LossPressure LossPressure LossPressure LossPressure LossPressure LossFlow Rate Flow Rate Flow Rate Flow Rate Flow Rate Flow Rate ES-A-2000B 1410 © 2014 Ames Fire & Waterworks USA: Backflow Tel: (978) 689-6066 • Fax: (978) 975-8350 • AmesFireWater.com USA: Control Valves Tel: (713) 943-0688 • Fax: (713) 944-9445 • AmesFireWater.com Canada: Tel: (905) 332-4090 • Fax: (905) 332-7068 • AmesFireWater.ca Latin America: Tel: (52) 81-1001-8600 • Fax: (52) 81-8000-7091 • AmesFireWater.com A Watts Water Technologies Company PR14000070 F19001679RECEIVED 04/02/2019 lwalker BUILDING DIVISION PIPE AND FITTINGS PR14000070 F19001679RECEIVED 04/02/2019 lwalker BUILDING DIVISION Harvel Plastics, Inc. • 300 Kuebler Rd., Easton, PA 18040-9290 Tel: 610.252.7355 • Fax: 610.253.4436 • www.harvel.com Product Specifications Harvel®Blazemaster®CPVC Fire Sprinkler Pipe Product SpecificationsHarvel®Blazemaster®Application: Corrosion resistant fire sprinkler pipe, IPS sizes 3/4" through 3", for use in wet automatic fire sprinkler systems. When installed in accordance with Harvel’s Installation Instructions, this pipe is Listed by Underwriters Laboratories (UL) for use in: Light Hazard Occupancies as defined in the Standard for Installation of Sprinkler systems (NFPA 13); Residential Occupancies up to and including four stories in height (NFPA 13R); and Residential Occupancies as defined in the Standard for Sprinkler Systems in One and Two Family Dwellings and Mobile Homes (NFPA 13D). Harvel BlazeMaster‚ pipe is UL Listed for use in Return Air Plenums (NFPA 90A), System Risers per NFPA 13 Light Hazard, 13R and 13D, Exposed installations, Garages per NFPA 13R, and for use as Underground Fire Service Mains (NFPA 24) when installed in accordance with Harvel CPVC Fire Sprinkler Pipe Installation Instructions. Scope: This specification outlines minimum manufacturing requirements for Chlorinated Polyvinyl Chloride (CPVC) standard dimension ratio (SDR) 13.5 series iron pipe size (IPS) fire sprinkler pressure pipe. Pipe is intended for use in wet automatic fire sprinkler sys- tems when installed in accordance with Harvel Plastics, Inc. CPVC Fire Sprinkler Piping Products Installation Instructions. Harvel‚ BlazeMaster‚ pipe carries a maximum working pressure of 175 psi @ 150°F. Pipe meets or exceeds applicable industry standards and requirements as set forth by the American Society for Testing and Materials (ASTM), the National Sanitation Foundation (NSF), and Underwriters Laboratories (UL). Harvel‚ BlazeMaster‚ fire sprinkler pipe is approved by the Factory Mutual Corporation (FM) and the Loss Prevention Certification Board (LPCB). Refer to current approval guide and installation and design manual for installation limitations. CPVC Materials: The material used in the manufacture of the pipe shall be a rigid chlorinated polyvinyl chloride (CPVC) compound, Type IV Grade I, with a Cell Classification of 23447 as defined in ASTM D1784. The compound and the finished product shall be orange in color, and shall be approved by the National Sanitation Foundation (NSF) for use with potable water. Material used shall be domestically produced BlazeMaster‚ CPVC material as provided by Noveon, Inc. (formerly the BFGoodrich Company). System Design: The CPVC sprinkler system shall be hydraulically calculated using a Hazen-Williams C factor of 150, and shall be designed in strict accordance with the Standard for Installation of Sprinkler Systems, NFPA 13 Light Hazard, NFPA 13R, and NFPA 13D as applicable. Dimensions: Harvel BlazeMaster‚ CPVC fire sprinkler pipe shall be manufactured to Standard Dimension Ratio (SDR) 13.5 dimensions in strict accordance to the requirements of ASTM F442 for physical dimensions and tolerances. Each production run of pipe manufactured in compliance to this standard, shall also meet the test requirements for materials, workmanship, burst pressure, flattening, and extrusion quality defined in ASTM F442. Furthermore, this pipe shall consistently meet or exceed the physical performance test requirements of the appropriate approval/listing agency(s) follow-up procedures established for the product. Marking: Product marking shall meet the requirements of ASTM F 442 and the Listing agency. Marking shall include: the phrase Harvel® BlazeMaster® (or the manufacturers’ trademark when privately labeled); the nominal pipe size; the type of material and material designation code; the SDR series and pressure rating for water (SDR 13.5; 175 psi @ 150°F); the ASTM designation F 442; the logo of the Listing and Approval agencies (UL, FM, LPCB, etc.); the independent laboratory’s seal of approval for potable water usage (NSF-pw); the date and time of manufacture; and the UL assigned control number (2N95). Installation Procedures: All installation procedures such as storage and handling, solvent cement joining techniques, pipe support spacing, bracing, allowance for thermal expansion/contraction, component assembly techniques, and testing etc. shall be in strict accordance with Harvel Plastics, Inc. Installation Instructions and the UL Listing which includes installation limitations. System Components: Fittings used shall be UL Listed CPVC fittings and shall meet or exceed the requirements of ASTM F437 (Sch 80 threaded), ASTM F437 (Sch 80 socket), or ASTM F438 (Sch 40 socket) as applicable, such as those manufactured by Spears Manufacturing Co. or equivalent. Solvent cements used shall be those referenced in Harvel Plastics, Inc. Installation Instructions (such as Spears FS-5 or equivalent), which meet or exceed the requirements of ASTM F656 and ASTM F493, and shall be approved by the National Sanitation Foundation (NSF) for use with potable water. Socket type joints, sizes 3/4" - 3", shall be made up using the One-Step solvent cement joining method. The solvent cement joining method chosen shall be applied in strict accordance with the appropriate procedures as outlined in Harvel Plastics Installation Instructions. Maintenance: Maintenance shall be in accordance with the Standard for Inspection, Testing, and Maintenance of Water Based Sprinkler Systems as defined by NFPA 25. PR14000070 F19001679RECEIVED 04/02/2019 lwalker BUILDING DIVISION Harvel Plastics, Inc. • 300 Kuebler Rd., Easton, PA 18040-9290 Tel: 610.252.7355 • Fax: 610.253.4436 • www.harvel.com Product Specifications Harvel®Blazemaster®CPVC Fire Sprinkler Pipe Harvel®Blazemaster®Product Specifications Limitations: • CPVC systems are intended for use at a maximum working pressure of 175 psi and ambient temperature of 150°F. • CPVC systems shall employ sprinkler heads having a maximum temperature rating of 225°F or lower, regardless of type. • CPVC products shall be installed in wet pipe systems only. • Air or compressed gas shall never be used for pressure testing. • CPVC sprinkler systems shall be hydrostatically tested for 2 hours at 200 psi, or 50 psi in excess of the maximum working pressure when the maximum working pressure exceeds 150 psi. Lines shall be slowly filled with water and the air bled from the highest and farthest sprinkler heads before test pressure is applied. • Only Teflon® tape or a thread sealant specifically approved for use with Harvel® CPVC Fire Sprinkler Products shall be used in making threaded connections. • Where freeze protection is required, only glycerin based anti-freeze solutions shall be used and installed in accordance with NFPA 13. Do not use glycol base anti-freeze solutions or contaminated glycerin solutions. • CPVC is not approved for use in combustible concealed spaces where sprinklers are required to protect these areas as defined by NFPA 13, unless certain specific application sprinklers are installed per their listing. Refer to Harvel’s current Installation Instructions for additional information. • CPVC sprinkler piping may be installed in a plenum space adjacent to, but not over, openings in the ceiling such as open ventilation grills, and require the use of schedule 80 fittings for use on 11/2"and larger pipe sizes. Refer to Installation Instructions for additional detail. • Minimum protection when installed “concealed” shall consist of: 3/8" gypsum wallboard or drywall, suspended membrane ceiling panels weighing not less than .35 pounds per square foot, or 1/2" plywood soffits. Minimum protection for NFPA 13R and 13D systems may consist of 1/2" plywood. • Harvel‚ BlazeMaster‚ pipe is Listed for use in exposed applications with certain limitations. When installed without protection, “exposed” pipe is to be installed beneath smooth, flat, horizontal ceiling construction. Exposed categories include: standard coverage and residential pendent and sidewall sprinkler applications, light hazard extended coverage and residential sprinkler pendent and sidewall sprinkler applications, use in unfinished basements with exposed solid wood joists, light hazard upright quick response sprinklers, and system risers (in 13R & 13D occupancies). Refer to Harvel’s installation instructions for specific sprinkler head temperature ratings and spacing requirements. The product must be installed in strict accordance with NFPA 13, 13D, 13R and Harvel’s current CPVC Fire Sprinkler Piping Products Installation Instructions (HFS-3). • Harvel CPVC Fire Sprinkler Products must be installed in accordance with Harvel’s current installation instructions (HFS-3). Refer to this document for current listing limitations and installation requirements. ASTM STANDARD D1784 MATERIAL CLASSIFICATION EQUIVALENTS: Cell Classification 23447 = CPVC Type IV Grade I = CPVC 4120 PIPE SIZES SHOWN ARE MANUFACTURED IN STRICT COMPLIANCE WITH ASTM F442 Sample Specification: All CPVC fire sprinkler pipe shall be manufactured from a Type IV, Grade I Chlorinated Polyvinyl Chloride (CPVC) compound with a Cell Classification of 23447 per ASTM D1784. Pipe shall be manufactured in strict compliance with ASTM F442 to SDR 13.5 dimensions, con- sistently meeting the Quality Assurance test requirements of this standard with regard to material, workmanship, burst pressure, flatten- ing, and extrusion quality. All CPVC fire sprinkler pipe shall be Listed by Underwriters Laboratories for wet pipe systems, and shall carry a rated working pressure of 175 psi @ 150°F. All CPVC fire sprinkler pipe shall be installed in accordance with Harvel Plastics, Inc. CPVC Fire Sprinkler Piping Products Installation Instructions. National Fire Protection Association (NFPA) Standards 13, 13D, and 13R must be referenced for design and installation requirements in conjunction with the Installation Instructions. All CPVC fire sprinkler pipe shall be manufactured in the USA by an ISO 9001 certified manufacturer and shall be FM and LPCB approved. All CPVC fire sprin- kler pipe shall be packaged immediately after its manufacture to prevent damage and shall be stored indoors after production, at the manufacturing site, until shipped from factory. This pipe shall bear the logo of the listing agencies, and shall carry the National Sanitation Foundation (NSF) seal of approval for potable water applications. All CPVC fire sprinkler pipe shall be Harvel® BlazeMaster® pipe as manufactured by HARVEL® PLASTICS, INC. Harvel CPVC Fire Sprinkler Pipe Dimensions SDR 13.5 (ASTM F442) Nominal Average Min. Average Nom.Wt. Size (in.) O.D. Wall I.D. Lbs./Ft. 3/4 1.050 0.078 0.874 0.168 1 1.315 0.097 1.101 0.262 1-1/4 1.660 0.123 1.394 0.418 1-1/2 1.900 0.141 1.598 0.548 2 2.375 0.176 2.003 0.859 2-1/2 2.875 0.213 2.423 1.257 3 3.500 0.259 2.950 1.867 PR14000070 F19001679RECEIVED 04/02/2019 lwalker BUILDING DIVISION FlameGuard® CPVC FIRE SPRINKLER PIPING PRODUCTS 1 SPEARS® MANUFACTURING COMPANY CPVC FIRE SPRINKLER PIPE SDR 13.5 (ASTM F 442) Part Number Nominal Size Average O.D.Average I.D.Approx. Weight Lbs./Ft. Inches (mm) Inches (mm) Inches (mm) CP-007 3/4 (19.1) 1.050 (26.7).874 (22.5).181 CP-010 1 (25.4) 1.315 (33.4)1.101 (28.2).280 CP-012 1-1/4 (31.8) 1.660 (42.2)1.394 (35.6).418 CP-015 1-1/2 (38.1) 1.900 (48.3)1.598 (40.7).550 CP-020 2 (50.8) 2.375 (60.3)2.003 (50.9).872 CP-025 2-1/2 (63.5) 2.875 (73.0)2.423 (61.5)1.260 CP-030 3 (76.2) 3.500 (88.9)2.950 (75.0)1.900 Dimension Reference G = (LAYING LENGTH) Intersection of center lines to bottom of socket/thread; 90° elbows, tees, crosses; ± 1/32 inch. H = Intersection of center lines to face of fitting; 90° elbows tees, crosses; ± 1/32 inch. J = Intersection of center lines to bottom of socket/thread; 45° elbows; ± 1/32 inch L = Overall length of fittings; ± 1/16 inch. M = Outside diameter of socket/thread hub; ± 1/16 inch. N = Socket bottom to socket bottom; couplings; ± 1/16 inch. Q = Width of flats; ±1/16 inch. W = Height of cap; ± 1/16 inch. The information contained in this publication is based on current information and Product design at the time of publication and is subject to change without notification. Our ongoing commitment to product improvement may result in some variation. No representations, guarantees or warranties of any kind are made as to its accuracy, suitability for particular applications or results to be obtained therefrom. For verification of technical data or additional information not contained herein, please contact Spears® Technical Services Department [West Coast: (818) 364-1611—East Coast: (678) 985-1263]. General Information RECOMMENDATIONS FOR INSTALLERS AND USERS: Plastic piping systems should be ENGINEERED, INSTALLED and OPERATED in accordance with ESTABLISHED DESIGN AND ENGINEERING STANDARDS AND PROCEDURES for plastic piping systems. Suitability for the intended service application should be determined by the installer and/or user prior to installation of a plastic piping system. All Installation and maintenance personnel should be trained in the proper handling and installation requirements and precautions of plastic piping systems. PRIOR TO ASSEMBLY, all piping system components should be inspected for damage or irregularities. Mating components should be checked to assure that tolerances and engagements are compatible. Do not use any components that appear irregular or do not fit properly. Contact the appropriate manufacturer of the component product in question to determine usability. Consult all applicable codes and regulations for compliance prior to installation. Installation must be made in accordance with Spears® Manufacturing Company FlameGuard® CPVC Fire Sprinkler Piping Products Installation Instructions - FG-3 NOTE — Individual or group instruction in correct solvent welding procedures is available by contacting your local distributor or your servicing Spears® Regional Distribution Center. SOLVENT CEMENT CONNECTIONS — Spears® Manufacturing Company recommends the use of Spears® FS-5 One Step solvent cement for joining Spears® products. Use of solvent cementing products not approved for CPVC fire sprinkler systems, or failure to follow installation instructions will automatically void the warranty. THREADED CONNECTION — Spears® Manufacturing Company recommends the use of Spears® BLUE 75™ Thread Sealant. This product has been tested by Spears® and the sealant manufacturer for compatibility with the Spears® CPVC fire sprinkler products. Consult the sprinkler head manufacturer before using this product. WARNING: OTHER PIPE JOINT COMPOUNDS OR PASTES MAY CONTAIN SUBSTANCES THAT COULD CAUSE STRESS CRACKING IN THE CPVC OR OTHER FITTING COMPONENTS. Care must be taken to avoid over torquing - generally 1 to 2 turns beyond finger tight is all that is required to make up a threaded connection. Factory testing has indicated 10-25 ft. lbs. of torque is adequate to obtain a leak free seal. GASKET SEALED THREAD CONNECTIONS — This type of connection can only be made with Spears® TorqueSafe™ style Gasket Sealed Female Sprinkler Adapters. DO NOT USE ANY TYPE OF THREAD SEALANT WHEN INSTALLING THIS TYPE OF ADAPTER. Tape or paste may impair proper sealing and function. Testing has shown that hand tight until snug is all that is needed to seal this special connection. PR14000070 F19001679RECEIVED 04/02/2019 lwalker BUILDING DIVISION FlameGuard® CPVC FIRE SPRINKLER PIPING PRODUCTS MADE IN THE U.S.A. 2 TEE Socket x Socket x Socket G H L M Part Number Size G H L M Approx. Wt. (Lbs.) 4201-007 3/4 9/16 1-1/2 2-31/32 1-5/16 .11 4201-010 1 13/16 1-13/16 3-5/8 1-5/8 .20 4201-012 1-1/4 15/32 2-3/32 4-7/32 2 .29 4201-015 1-1/2 1-5/32 2-9/16 5-3/32 2-11/32 .54 4201-020 2 1-13/32 2-15/16 5-7/8 2-7/8 .86 4201-025 2-1/2 1-23/32 3-1/2 7 3-15/32 1.62 4201-030 3 2-1/16 3-15/16 7-7/8 4-3/16 3.02 REDUCING TEE Socket x Socket x Socket M H1 H H2 G G2 L G1 M2 M1 Part Number Size G G1 G2 H H1 H2 L M M1 M2 Approx. Wt. (Lbs.) 4201-102 3/4x3/4x1 3/4 25/32 3/4 1-11/16 1-13/16 1-11/16 3-3/8 1-5/16 1-21/32 1-5/16 .13 4201-125 1x3/4x3/4 21/32 13/16 5/8 1-25/32 1-13/16 1-5/8 3-13/32 1-17/32 1-5/16 1-5/16 .15 4201-126 1x3/4x1 3/4 1-7/8 1-3/32 1-27/32 2-31/32 1-31/32 3-13/16 1-23/32 1-23/32 1-13/32 .26 4201-131 1x1x3/4 21/32 13/16 21/32 1-25/32 1-13/16 1-25/32 3-9/16 1-5/8 1-5/16 1-5/8 .16 4201-157 1-1/4x1x3/4 11/16 1-1/32 11/16 1-15/16 2-1/32 1-13/16 3-25/32 2-3/32 1-13/32 1-23/32 .32 4201-158 1-1/4x1x1 27/32 29/32 25/32 2-1/16 2-1/32 1-29/32 3-15/16 1-31/32 1-5/8 1-5/8 .24 4201-159 1-1/4x1x1-1/4 31/32 31/32 31/32 2-7/32 2-7/32 2-3/32 4-11/32 2-3/32 2-3/32 1-23/32 .35 4201-167 1-1/4x1-1/4x3/4 21/32 1 21/32 1-29/32 2 1-29/32 3-13/16 2 1-5/16 2 .22 4201-168 1-1/4x1-1/4x1 13/16 31/32 13/16 2-1/16 2-3/32 2-1/16 4-1/8 1-31/32 1-21/32 2 .24 4201-169 1-1/4x1-1/4x1-1/2 1-1/8 15/16 1-1/8 2-3/8 2-11/32 2-3/8 4-3/4 2-3/32 2-11/32 2-3/32 .51 4201-201 1-1/2x1-1/4x3/4 11/16 1 1/4 2-1/16 2 1-15/16 4 2-5/16 1-3/8 2-1/16 .41 4201-202 1-1/2x1-1/4x1 27/32 1-1/32 1 2-7/32 2-5/32 2-1/4 4-15/32 2-5/16 1-11/16 2-1/16 .42 4201-210 1-1/2x1-1/2x3/4 23/32 1-1/16 23/32 2-3/32 2-1/32 2-3/32 4-3/16 2-5/16 1-3/8 2-5/16 .37 4201-211 1-1/2x1-1/2x1 13/16 1-3/16 13/16 2-3/16 2-1/4 2-3/16 4-3/8 2-11/32 1-23/32 2-11/32 .41 4201-212 1-1/2x1-1/2x1-1/4 1 1-1/8 1 2-3/8 2-11/32 2-3/8 4-13/16 2-11/32 2-3/32 2-11/32 .48 4201-213 1-1/2x1-1/2x2 1-5/16 1-1/8 1-5/16 2-11/16 2-21/32 2-11/16 5-3/8 2-11/32 2-27/32 2-11/32 .72 PR14000070 F19001679RECEIVED 04/02/2019 lwalker BUILDING DIVISION FlameGuard® CPVC FIRE SPRINKLER PIPING PRODUCTS 3 SPEARS® MANUFACTURING COMPANY REDUCING TEE Socket x Socket x Socket M H1 H H2 G G2 L G1 M2 M1 Part Number Size G G1 G2 H H1 H2 L M M1 M2 Approx. Wt. (Lbs.) 4201-248 2x2x3/4 11/16 1-13/32 11/16 2-7/32 2-7/16 2-7/32 4-7/16 2-27/32 1-3/8 2-27/32 .52 4201-249 2x2x1 27/32 1-7/16 27/32 2-11/32 2-9/16 2-11/32 4-23/32 2-7/8 1-3/4 2-7/8 .57 4201-250 2x2x1-1/4 1 1-11/32 1 2-17/32 2-19/32 2-17/32 5-3/32 2-27/32 2-3/32 2-27/32 .63 4201-251 2x2x1-1/2 1-7/32 1-13/32 1-7/32 2-11/16 2-25/32 2-11/16 5-3/8 2-27/32 2-11/32 2-27/32 .85 4201-289 2-1/2x2-1/2x1 29/32 25/32 29/32 2-21/32 1-29/32 2-21/32 5-5/16 3-1/2 1-23/32 3-1/2 1.03 4201-290 2-1/2x2-1/2x1-1/4 1-3/32 1-23/32 1-3/32 2-27/32 2-31/32 2-27/32 5-21/32 3-17/32 2-3/32 3-17/32 1.13 4201-291 2-1/2x2-1/2x1-1/2 1-3/16 1/2 1-3/16 2-15/16 1-7/8 2-15/16 5-7/8 3-15/32 2-11/32 3-15/32 1.26 4201-292 2-1/2x2-1/2x2 1-13/32 1-5/8 1-13/32 3-3/16 3-1/8 3-3/16 6-11/32 3-1/2 3-7/8 3-1/2 1.34 4201-335 3x3x1 7/8 1-15/16 7/8 2-3/4 3-1/16 2-3/4 5-15/32 4-3/16 1-23/32 4-3/16 1.26 4201-336* 3x3x1-1/4 1-3/8 1-3/4 1-3/8 3-5/16 3-1/2 3-5/16 6-5/8 4-1/8 2-7/8 4-1/8 1.94 4201-337 3x3x1-1/2 1-5/32 2-1/16 1-5/32 3-1/32 3-7/16 3-1/32 6-3/32 4-3/16 2-3/8 4-3/16 1.46 4201-338 3x3x2 1-7/16 1-13/16 1-7/16 3-5/16 3-5/16 3-5/16 6-19/32 4-3/16 2-7/8 4-3/16 1.69 4201-339 3x3x2-1/2 1-3/4 1-31/32 1-3/4 3-5/8 3-23/32 3-5/8 7-1/4 4-3/16 3-17/32 4-3/16 2.11 * Branch Outlet Sized with Bushing CONTINUED SPRINKLER HEAD TEE Gasket Sealed Brass Thread Insert Style Socket x Socket x Gasket FIPT With Elastomer Seal - Use NO Thread Sealant Part Number Size G G1 G2 H H1 H2 L M M1 M2 Approx. Wt. (Lbs.) 4202-101 G 3/4x3/4x1/2 7/16 1-3/16 7/16 1-7/16 1-7/16 1-17/32 2-29/32 1-3/8 1-3/8 1-3/8 .22 4202-124 G 1x3/4x1/2 7/16 1-11/32 9/16 1-9/16 1-11/16 1-9/16 3-1/8 1-11/16 1-3/8 1-3/8 .26 4202-130 G 1x1x1/2 7/16 1-11/32 7/16 1-9/16 1-11/16 1-9/16 3-1/8 1-23/32 1-3/8 1-23/32 .28 4202-166 G 1-1/4x1-1/4x1/2 7/16 1-5/8 7/16 1-11/16 1-15/16 1-11/16 3-3/8 2-1/16 1-3/8 2-1/16 .34 4202-209 G 1-1/2x1-1/2x1/2 1/2 1-13/16 1/2 1-7/8 2-3/32 1-7/8 3-3/4 2-11/32 1-3/8 2-11/32 .41 4202-247 G 2x2x1/2 1/2 2-1/16 1/2 2 2-11/32 2 4-1/32 2-27/32 1-3/8 2-27/32 .54 Not intended to convey or dispense water for human consumption through drinking or cooking H M G1 H1 M1 H2 G2G M2 L PR14000070 F19001679RECEIVED 04/02/2019 lwalker BUILDING DIVISION FlameGuard® CPVC FIRE SPRINKLER PIPING PRODUCTS MADE IN THE U.S.A. 4 SPRINKLER HEAD TEE Special Reinforced Plastic Thread Style Socket x Socket x SR Fipt L H M G1 H1 M1 H2 G2G M2 Part Number Size G G1 G2 H H1 H2 L M M1 M2 Approx. Wt. (Lbs.) 4202-101SR 3/4x3/4x1/2 19/32 3/4 19/32 1-19/32 1-7/16 1-19/32 3-7/32 1-13/32 1-3/16 1-13/32 .16 4202-124SR 1x3/4x1/2 7/16 29/32 9/16 1-19/32 1-5/8 1-9/16 3-5/32 1-23/32 1-3/16 1-17/32 .19 4202-130SR 1x1x1/2 7/16 29/32 7/16 1-9/16 1-5/8 1-9/16 3-1/8 1-23/32 1-3/16 1-23/32 .20 4202-010SR 1x1x1 21/32 3/4 21/32 1-25/32 1-5/8 1-25/32 3-19/32 1-23/32 1-11/16 1-23/32 .26 4202-156SR 1-1/4x1x1/2 15/32 1-5/32 19/32 1-23/32 1-7/8 1-23/32 3-13/32 2-3/32 1-3/16 1-23/32 .26 4202-166SR 1-1/4x1-1/4x1/2 7/16 1-1/8 7/16 1-11/16 1-27/32 1-11/16 3-3/8 2-3/32 1-3/16 2-3/32 .26 4202-168SR 1-1/4x1-1/4x1 27/32 1-1/32 27/32 2-3/32 1-29/32 2-3/32 4-7/32 2-3/32 1-11/16 2-3/32 .34 4202-199SR 1-1/2x1-1/4x1/2 9/16 1-9/32 17/32 1-15/16 2 1-25/32 3-23/32 2-11/32 1-3/16 2-3/32 .33 4202-209SR 1-1/2x1-1/2x1/2 1/2 1-1/4 1/2 1-7/8 1-31/32 1-7/8 3-3/4 2-11/32 1-3/16 2-11/32 .35 4202-211SR 1-1/2x1-1/2x1 27/32 1-7/32 27/32 2-7/32 2-1/8 2-7/32 4-15/32 2-11/32 1-23/32 2-11/32 .44 4202-237SR 2x1-1/2x1/2 23/32 1-9/16 3/8 2-7/32 2-9/32 1-3/4 3-31/32 2-7/8 1-3/16 2-11/32 .45 4202-247SR 2x2x1/2 1/2 31/32 1/2 2 1-11/16 19/32 4 2-7/8 1-3/16 2-7/8 .48 4202-287SR 2-1/2x2-1/2x1/2 17/32 1-3/4 17/32 2-9/32 2-1/2 2-9/32 4-19/32 3-1/2 1-7/32 3-1/2 .78 SPRINKLER HEAD TEE Brass Thread Insert Style Socket x Socket x Fipt Part Number Size G G1 G2 H H1 H2 L M M1 M2 Approx. Wt. (Lbs.) 4202-101 3/4x3/4x1/2 7/16 1-5/32 7/16 1-7/16 1-17/32 1-7/16 2-29/32 1-3/8 1-7/32 1-3/8 .27 4202-124 1x3/4x1/2 7/16 1-11/32 9/16 1-9/16 1-11/16 1-9/16 3-1/8 1-11/16 1-3/8 1-3/8 .26 4202-130 1x1x1/2 7/16 1-7/32 7/16 1-9/16 1-25/32 1-9/16 3-1/8 1-3/4 1-3/16 1-3/4 .26 4202-010 1x1x1 11/16 1-3/32 11/16 1-13/16 1-29/32 1-13/16 3-19/32 1-23/32 1-23/32 1-23/32 .37 4202-156 1-1/4x1x1/2 7/16 1-15/32 9/16 1-11/16 2-1/32 1-11/16 3-3/8 2-3/32 1-7/32 1-3/4 .30 4202-166 1-1/4x1-1/4x1/2 7/16 1-1/2 7/16 1-11/16 2-1/16 1-11/16 3-13/32 2-3/32 1-3/16 2-3/32 .32 4202-199 1-1/2x1-1/4x1/2 1/2 1-5/8 9/16 1-7/8 2-3/16 1-13/16 3-11/16 2-5/16 1-7/32 2-1/16 .37 4202-209 1-1/2x1-1/2x1/2 1/2 1-23/32 1/2 1-7/8 2-3/32 1-7/8 3-3/4 2-5/16 1-17/32 2-5/16 .45 4202-237 2x1-1/2x1/2 1/2 1-7/8 17/32 2 2-7/16 1-29/32 3-15/16 2-27/32 1-7/32 2-5/16 .48 4202-247 2x2x1/2 1/2 1-31/32 1/2 2 2-3/8 2 4-1/32 2-27/32 1-17/32 2-27/32 .58 Not intended to convey or dispense water for human consumption through drinking or cooking H M G1 H1 M1 H2 G2G M2 L PR14000070 F19001679RECEIVED 04/02/2019 lwalker BUILDING DIVISION FlameGuard® CPVC FIRE SPRINKLER PIPING PRODUCTS 5 SPEARS® MANUFACTURING COMPANY SPRINKLER HEAD TEE Special Reinforced Plastic Thread Style Socket x SR Fipt x Socket L G H G1 H1 M1 M H2 G2 M2 Part Number Size G G1 G2 H H1 H2 L M M1 M2 Approx. Wt. (Lbs.) 4203-122SR 1x1/2x1 27/32 23/32 1-3/32 1-23/32 1-5/8 1-25/32 3-13/32 1-3/4 1-3/4 1-3/16 .21 SPRINKLER HEAD TEE Brass Thread Insert Style Socket x Fipt x Socket H2 L G H G1 H1 M1 M G2 M2 Part Number Size G G1 G2 H H1 H2 L M M1 M2 Approx. Wt. (Lbs.) 4203-122 1x1/2x1 23/32 3/4 1-1/4 1-5/8 1-5/8 1-15/16 3-1/2 1-23/32 1-23/32 1-3/16 .25 Not intended to convey or dispense water for human consumption through drinking or cooking TORQUESAFE™ SPRINKLER HEAD TEE Gasket Sealed Brass Thread Insert Style Socket x Gasket FIPT x Socket With Elastomer Seal - Use NO Thread Sealant H2L G H G1 H1 M1 M G2 M2 Part Number Size G G1 G2 H H1 H2 L M M1 M2 Approx. Wt. (Lbs.) 4203-122 G 1x1/2x1 19/32 13/16 1-13/32 1-19/32 1-27/32 1-3/4 3-11/32 1-5/8 1-5/8 1-3/8 .25 Not intended to convey or dispense water for human consumption through drinking or cooking PR14000070 F19001679RECEIVED 04/02/2019 lwalker BUILDING DIVISION FlameGuard® CPVC FIRE SPRINKLER PIPING PRODUCTS MADE IN THE U.S.A. 6 SIDE OUTLET ELBOW Socket x Socket x Socket Part Number Size G H M Approx. Wt. (Lbs.) 4213-007 3/4 27/32 1-19/32 1-5/16 .09 4213-010 1 13/16 1-7/8 1-5/8 .18 H G M 90° ELBOW Socket x Socket Part Number Size G H M Approx. Wt. (Lbs.) 4206-007 3/4 9/16 1-1/2 1-5/16 .07 4206-010 1 3/4 1-5/8 1-5/8 .11 4206-012 1-1/4 7/8 2-5/32 2 .21 4206-015 1-1/2 1-5/32 2-17/32 2-3/8 .41 4206-020 2 1-13/32 2-29/32 2-7/8 .45 4206-025 2-1/2 1-5/8 3-7/16 3-7/16 1.17 4206-030 3 1-29/32 3-23/32 4-3/16 1.80 H M G STREET TEE Spigot x Socket x Socket Part Number Size G G1 G2 H H1 H2 L M1 M2 Approx. Wt. (Lbs.) 4244-007 3/4 13/16 27/32 27/32 1-13/16 1-7/8 1-7/8 3-5/8 1-13/32 1-13/32 .16 4244-010 1 1-5/32 1-1/32 1-1/32 2-1/8 1-29/32 1-29/32 4-3/16 1-3/4 1-3/4 .27 4244-012 1-1/4 1-1/4 1 1 2-7/16 2-9/32 2-9/32 4-27/32 2-3/32 2-3/32 .42 4244-015 1-1/2 1-13/16 1-1/8 1-1/8 2-7/8 2-9/16 2-9/16 5-11/32 2-11/32 2-11/32 .56 4244-020 2 1-23/32 1-7/16 1-13/32 3-1/4 2-15/16 2-15/16 6-5/32 2-7/8 2-7/8 .84 M1 PIPEO.D. H H1 L H2 M2 G1 G G2 PR14000070 F19001679RECEIVED 04/02/2019 lwalker BUILDING DIVISION FlameGuard® CPVC FIRE SPRINKLER PIPING PRODUCTS 7 SPEARS® MANUFACTURING COMPANY 90° SPRINKLER HEAD ELBOW Gasket Sealed Brass Thread Insert Style Socket x Gasket FIPT With Elastomer Seal - Use NO Thread Sealant G H M1 H1 M G1 Part Number Size G G1 H H1 M M1 Approx. Wt. (Lbs.) 4207-101 G 3/4x1/2 9/16 1-7/32 1-13/32 1-17/32 1-13/32 1-3/8 .19 4207-130 G 1x1/2 15/32 1-13/32 1-9/16 1-11/16 1-23/32 1-3/8 .23 4207-166 G 1-1/4x1/2 15/32 1-19/32 1-15/16 1-11/16 2-3/32 1-3/8 .25 Not intended to convey or dispense water for human consumption through drinking or cooking REDUCING 90° ELBOW Socket x Socket Part Number Size G G1 H H1 M M1 Approx. Wt. (Lbs.) 4206-131 1x3/4 25/32 11/16 1-25/32 1-25/32 1-19/32 1-5/16 .11 H1 G1 M1 H G M SPRINKLER HEAD 90° ELBOW Brass Thread Insert Style Socket x Fipt Part Number Size G G1 H H1 M M1 Approx. Wt. (Lbs.) 4207-101 3/4x1/2 7/16 1-5/32 1-23/32 1-17/32 1-13/32 1-17/32 .25 4207-130 1x1/2 15/32 1-5/8 1-9/16 1-11/16 1-23/32 1-17/32 .28 4207-131 1x3/4 17/32 1-1/4 1-21/32 2 1-23/32 1-3/8 .25 4207-166 1-1/4x1/2 15/32 1-17/32 1-11/16 1-15/16 2-3/32 1-17/32 .33 Not intended to convey or dispense water for human consumption through drinking or cooking G H M1 G1 H1 M PR14000070 F19001679RECEIVED 04/02/2019 lwalker BUILDING DIVISION FlameGuard® CPVC FIRE SPRINKLER PIPING PRODUCTS MADE IN THE U.S.A. 8 90° STREET ELBOW Spigot x Socket PIPE O.D. H1 G1 G H M1 Part Number Size G G1 H H1 M1 Approx. Wt. (Lbs.) 4209-007 3/4 29/32 19/32 1-15/16 1-11/16 1-13/32 .12 4209-010 1 1-9/32 23/32 2-13/32 1-27/32 1-3/4 .21 4209-012 1-1/4 1-9/16 27/32 2-13/16 2-3/32 2-3/32 .32 4209-015 1-1/2 1-15/32 1-3/16 2-27/32 2-9/16 2-11/32 .42 4209-020 2 1-23/32 1-3/8 3-7/32 2-15/16 2-27/32 .65 SPRINKLER HEAD 90° ELBOW Special Reinforced Plastic Thread Style Socket x SR Fipt G H M M1 G1 H1 Part Number Size G G1 H H1 M M1 Approx. Wt. (Lbs.) 4207-101SR 3/4x1/2 11/32 13/16 1-15/32 1-1/2 1-13/32 1-3/16 .14 4207-130SR 1x1/2 7/16 7/8 1-9/16 1-5/8 1-23/32 1-3/8 .20 4207-131SR 1x3/4 1/2 7/8 1-5/8 1-9/16 1-23/32 1-3/8 .16 4207-166SR 1-1/4x1/2 13/32 1-1/32 1-21/32 1-23/32 2-3/32 1-7/32 .19 PR14000070 F19001679RECEIVED 04/02/2019 lwalker BUILDING DIVISION FlameGuard® CPVC FIRE SPRINKLER PIPING PRODUCTS 9 SPEARS® MANUFACTURING COMPANY 22-1/2° STREET ELBOW Spigot x Socket PIPE O.D. M1 H H1 J J1 Part Number Size H H1 J J1 M1 Approx. Wt. (Lbs.) 4242-007 3/4 1-1/4 1-1/2 1/4 1/2 1-3/8 .08 4242-010 1 1-7/16 1-11/32 5/16 7/32 1-23/32 .14 4242-012 1-1/4 1-9/16 1-25/32 17/32 11/16 2-1/16 .21 4242-015 1-1/2 1-13/32 1-23/32 1/2 11/32 2-11/32 .28 4242-020 2 1-29/32 2-1/8 7/32 5/8 2-7/8 .42 4242-025 2-1/2 2-1/8 2-1/4 13/32 1/2 3-1/2 .68 4242-030 3 2-13/32 2-13/32 9/16 17/32 4-5/32 .99 22-1/2° ELBOW Socket x Socket M H J Part Number Size H J M Approx. Wt. (Lbs.) 4216-007 3/4 1-3/16 7/32 1-13/32 .09 4216-010 1 1-3/8 9/32 1-25/32 .14 4216-012 1-1/4 1-1/2 5/16 2-3/32 .20 4216-015 1-1/2 1-7/16 13/32 1-3/8 .19 4216-020 2 1-7/8 3/8 2-27/32 .43 4216-030 3 2-3/8 1/2 4-5/32 1.00 PR14000070 F19001679RECEIVED 04/02/2019 lwalker BUILDING DIVISION FlameGuard® CPVC FIRE SPRINKLER PIPING PRODUCTS MADE IN THE U.S.A. 10 45° STREET ELBOW Spigot x Socket J1 H1 M1 JH PIPE O.D. Part Number Size H H1 J J1 M1 Approx. Wt. (Lbs.) 4227-010 1 1-1/2 1-5/16 1/2 1/4 1-5/8 .10 4227-012 1-1/4 1-25/32 1-9/16 9/16 11/32 1-31/32 .15 4227-015 1-1/2 2-1/32 2-1/8 19/32 25/32 2-11/32 .29 4227-020 2 2-5/16 1-15/16 25/32 13/32 2-7/8 .44 45° ELBOW Socket x Socket J H M Part Number Size H J M Approx. Wt. (Lbs.) 4217-007 3/4 1-5/16 5/16 1-5/16 .07 4217-010 1 1-13/32 3/8 1-5/8 .11 4217-012 1-1/4 1-5/8 3/8 2-5/32 .21 4217-015 1-1/2 1-27/32 15/32 2-11/32 .32 4217-020 2 2-1/8 21/32 2-7/8 .48 4217-025 2-1/2 2-17/32 3/4 3-1/2 .88 4217-030 3 2-29/32 29/32 4-5/32 1.17 PR14000070 F19001679RECEIVED 04/02/2019 lwalker BUILDING DIVISION FlameGuard® CPVC FIRE SPRINKLER PIPING PRODUCTS 11 SPEARS® MANUFACTURING COMPANY REDUCING CROSS Socket x Socket x Socket x Socket M L G H G1 H1 L1 M1 Part Number Size G G1 H H1 L L1 M M1 Approx. Wt. (Lbs.) 4220-131 1x3/4 23/32 5/8 1-5/8 1-5/8 3-1/4 3-1/4 1-7/8 1-1/2 .31 4220-167 1-1/4x3/4 1-1/16 23/32 2-1/16 1-31/32 4-3/32 3-31/32 2-1/16 1-13/32 .35 4220-210 1-1/2x3/4 11/16 1-5/32 2-3/32 2-3/16 4-3/16 4-11/32 2-3/8 1-13/32 .42 4220-248 2x3/4 11/16 1-7/16 2-7/32 2-7/16 4-13/32 4-7/8 2-29/32 1-13/32 .56 4220-289 2-1/2x1 29/32 1-3/4 2-11/16 2-7/8 5-11/32 5-3/4 3-1/2 1-3/4 .98 CROSS Socket x Socket x Socket x Socket L1 L H G H1 G1 M Part Number Size G G1 H H1 L L1 M Approx. Wt. (Lbs.) 4220-007 3/4 5/8 5/8 1-21/32 1-21/32 3-5/16 3-5/16 1-13/32 .22 4220-010 1 3/4 3/4 1-5/8 1-5/8 3-1/4 3-1/4 1-23/32 .20 4220-012 1-1/4 1-1/8 1-1/8 2-3/8 2-3/8 4-3/4 4-3/4 2-3/32 .63 4220-015 1-1/2 1-7/32 1-7/32 2-5/8 2-5/8 5-7/32 5-7/32 2-3/8 .80 4220-020 2 1-1/2 1-1/2 3 3 6 6 3 1.43 4220-025 2-1/2 1-11/16 1-11/16 3-7/16 3-7/16 6-7/8 6-7/8 3-17/32 2.16 4220-030 3 2-3/32 2-3/32 3-31/32 3-31/32 7-15/16 7-15/16 4-7/16 3.37 PR14000070 F19001679RECEIVED 04/02/2019 lwalker BUILDING DIVISION FlameGuard® CPVC FIRE SPRINKLER PIPING PRODUCTS MADE IN THE U.S.A. 12 REDUCER COUPLING Socket x Socket N L M1M Part Number Size L M M1 N Approx. Wt. (Lbs.) 4229-131 1x3/4 2-3/8 1-23/32 1-13/32 7/32 .10 4229-167 1-1/4x3/4 2-19/32 2-3/32 1-5/8 11/32 .17 4229-168 1-1/4x1 2-11/16 2-3/32 1-23/32 5/16 .18 4229-210 1-1/2x3/4 2-13/16 2-11/32 1-13/32 15/32 .19 4229-211 1-1/2x1 2-7/8 2-11/32 1-15/16 3/8 .24 4229-212 1-1/2x1-1/4 2-13/16 2-13/32 2-1/8 5/32 .23 4229-248 2x3/4 3-3/16 2-7/8 1-7/16 23/32 .32 4229-249 2x1 3-1/8 2-7/8 1-23/32 1/2 .31 4229-250 2x1-1/4 3-3/16 2-7/8 2-1/8 17/32 .33 4229-251 2x1-1/2 3-3/16 2-27/32 2-11/32 9/32 .31 4229-291 2-1/2x1-1/2 3-23/32 3-15/32 2-11/32 21/32 .51 4229-292 2-1/2x2 3-21/32 3-1/2 2-7/8 13/32 .52 COUPLING Socket x Socket N L M Part Number Size L M N Approx. Wt. (Lbs.) 4229-007 3/4 2-1/8 1-5/16 3/16 .05 4229-010 1 2-3/16 1-5/8 3/32 .08 4229-012 1-1/4 2-19/32 2 3/32 .13 4229-015 1-1/2 2-7/8 2-11/32 3/32 .22 4229-020 2 3-1/8 2-7/8 1/8 .33 4229-025 2-1/2 3-11/16 3-15/32 3/16 .48 4229-030 3 4 4-3/16 1/4 .89 PR14000070 F19001679RECEIVED 04/02/2019 lwalker BUILDING DIVISION FlameGuard® CPVC FIRE SPRINKLER PIPING PRODUCTS 13 SPEARS® MANUFACTURING COMPANY FEMALE ADAPTER Brass Thread Insert Style Socket x Fipt N L M M1 Part Number Size L M M1 N Approx. Wt. (Lbs.) 4235-007 3/4 2 1-13/32 1-3/8 5/16 .23 4235-010 1 2-3/16 1-3/4 1-11/16 11/32 .25 4235-012 1-1/4 2-3/8 2-3/32 2-1/16 11/32 .36 4235-015 1-1/2 2-9/16 2-3/8 2-7/16 11/32 .47 4235-020 2 2-25/32 2-27/32 3-3/16 7/16 1.05 Not intended to convey or dispense water for human consumption through drinking or cooking GROOVED COUPLING ADAPTER Groove x Socket N L PIPEO.D.M1 Part Number Size L M1 N Approx. Wt. (Lbs.) 4233-012 1-1/4 3-5/8 2-3/32 2-11/32 .72 4233-015 1-1/2 3-3/4 2-11/32 2-11/32 .83 4233-020 2 3-27/32 2-27/32 2-11/32 1.27 4233-025 2-1/2 4-3/16 3-15/32 2-7/16 2.02 4233-030 3 4-5/16 4-1/8 1-7/16 2.76 PR14000070 F19001679RECEIVED 04/02/2019 lwalker BUILDING DIVISION HANGERS AND SEISMIC BRACING PR14000070 F19001679RECEIVED 04/02/2019 lwalker BUILDING DIVISION Pipe ClampsAll dimensions in charts and on drawings are in inches. Dimensions shown in parentheses are in millimeters unless otherwise specified. Pipe Clamps 34 Fig. 24 - Hanger for CPVC Plastic Pipe & IPS Steel Pipe** Double Fastener Strap Side Mounted (Cooper B-Line B3183) Size Range:3/4" (20mm)thru 2" (50mm)CPVC pipe Material:Pre-Galvanized Steel Function:Intended to perform as a hanger to support CPVC piping used in automatic fire sprinkler systems. Can be installed on the top or on the bottom of a beam. Approvals:Underwriters Laboratories Listed in the USA (UL)and Canada (cUL)to support fire sprinkler piping. May be installed in wood using fasteners supplied with product, or into minimum 20 gauge (0.912mm)steel using (2) 1/4" x 1" tek type screws. Meets and exceeds the requirements of NFPA 13, 13R and 13D. Features:Fig. 24 incorporates features which protect the pipe and ease installation. The flared edge design protects the CPVC pipe from any rough surface. Easily attaches to the building structure using the two UL Listed hex head self threading screws* furnished with the product. It is recommended that rechargeable electric drills fitted with a hex socket attachment be used as installation tools. No impact tools (such as a hammer) are allowed. Damage has been known to result from installations using impact type tools. No pre-drilling of a pilot hole in wood is required. Finish:Pre-Galvanized Order By:Figure number and pipe size *Hardened hex head self threading screw is furnished with the product and is the minimum fastener size acceptable. ** With reduced spacing, consult factory. C A B B CPVC Max. Hanger Fastener Hex Approx. Pipe Size A B C Spacing Head Size Wt./100 Part No.in. (mm) in. (mm) in. (mm) in. (mm) Ft. (m) in. (mm) Lbs. (kg) 24-3/4 3/4"(20)25/16"(58.7)15/32"(27.8)13/16"(30.2)51/2 (1.67)5/16"(7.9)9 (4.1) 24-1 1"(25)25/8"(66.7)15/16"(33.3)13/16"(30.2)6 (1.83)5/16"(7.9)9 (4.1) 24-11/4 11/4"(32)3"(76.2)11/2"(38.1)13/16"(30.2)61/2 (1.98)5/16"(7.9)11 (5.0) 24-11/2 11/2"(40)31/4"(82.5)15/8"(42.3)13/16"(30.2)7 (2.13)5/16"(7.9)12 (5.4) 24-2 2"(50)311/16"(93.7)127/32"(43.6)13/16"(30.2)8 (2.44)5/16"(7.9)15 (6.8) Fig. 25 - Surge Restrainer Size Range:— One size fits 3/4"(20mm)thru 2"(40mm)pipe. Material:— Pre-Galvanized Steel Function:— Designed to be used in conjunction with Fig. 200 band hangers to restrict the upward movement of piping as it occurs during sprinkler head activation or earthquake type activity. The surge restrainer is easily and efficiently installed by snapping into a locking position on the band hanger. This product is intended to satisfy the requirements as indicated in the National Fire Protection Association NFPA 13, 2010 edition, 9.2.3.4.4.1 and 9.2.3.4.4.4 Can be used to restrain either steel pipe or CPVC plastic Pipe. Approvals:— Underwriters Laboratories Listed only when used with band hanger Fig. 200, in the USA (UL)and Canada (cUL). Finish:Pre-Galvanized Order By:Figure number and band hanger, size from 3/4"(20mm)thru 2"(40mm). Patent #5,344,108 PR14000070 F19001679RECEIVED 04/02/2019 lwalker BUILDING DIVISION Pipe ClampsAll dimensions in charts and on drawings are in inches. Dimensions shown in parentheses are in millimeters unless otherwise specified. Pipe Clamps Fig. 28 - “Stand-Off” Hanger & Restrainer for CPVC Plastic Pipe & IPS Steel Pipe ** Size Range:— 3/4"(20mm)through 2"(50mm) Material:— Steel, Pre-Galvanized Function:— Designed to be used as a hanger and restrainer for CPVC piping where the "stand-off" design will ease installation by eliminating the need for wood blocking. Features: • Flared edge design protects CPVC pipe from any rough or abrasive surfaces. • Unique twist and lock design holds pipe firmly in place and allows retrofit type of installation. • The "Stand-Off" design eliminates the need for wood block extension. • Can be installed on horizontal or vertical piping regardless of mounting surface orientation. • Attaches easily to wood structure with two hex head self-threading screws furnished with product. • Installs easily using rechargeable electrical driver with 5/16"(7.9mm)extension socket eliminating impact tool damage to pipe. • Attaches easily to steel, minimum 18 gauge (1.024mm)with (2) 1/4" x 1" tek type self drilling tapping screws. • UL Listed as a hanger and a restrainer for fire sprinkler piping. Approvals:— Underwriters Laboratory Listed in the USA (UL)and Canada (cUL)to support automatic fire sprinkler systems. May be installed into wood using fasteners supplied with product, or into minimum 18 gauge steel using (2) 1/4" x 1" tek type screws. Meets and exceeds the requirements of NFPA 13, 13R and 13D. Fig. 28 satisfies the UL vertical restraint requirement where needed. UL Listed as a hanger and vertical restraint when installed on 3/8"(9.5mm)composite wood material. Use two Fig. 27B Speed Nuts when used as a hanger and restraint. Use one Fig. 27B Speed Nut on the upper installed screw when used as a hanger only. Order by:— Figure number and pipe size. Pat. # 7,455,268, Pat. # 7,832,248 ** With reduced spacing, consult factory. C A B Pipe Size A B C Max Hanger Approx. Spacing Wt./100 Part No.in. (mm) in. (mm) in. (mm) in. (mm) Ft. (m) lbs. (kg) 28-3/4 3/4"(20)31/32"(77.0)2"(50.8)31/2"(88.9)51/2 (1.67)18 (8.1) 28-1 1"(25)35/16"(84.1)23/16"(55.6)31/2"(88.9)6 (1.83)21 (9.5) 28-11/4 11/4"(32)35/8"(92.1)23/8"(60.3)31/2"(88.9)61/2 (1.98)23 (10.4) 28-11/2 11/2"(40)4"(101.6)21/2"(63.5)31/2"(88.9)7 (2.13)31 (14.0) 28-2 2"(50)41/2"(114.3)211/16"(68.3)35/8"(92.1)8 (2.44)34 (15.4) Hanger Application Hanger and Restraint Application Fig. 27B (2)RequiredFig. 27B (1)Required High Side of Hanger Application 36 PR14000070 F19001679RECEIVED 04/02/2019 lwalker BUILDING DIVISION Pipe ClampsPipe Clamps All dimensions in charts and on drawings are in inches. Dimensions shown in parentheses are in millimeters unless otherwise specified. Fig. 28M - Offset Hanger & Restrainer for CPVC Plastic Pipe and IPS Steel Pipe ** Size Range:3/4"(20mm)thru 2"(32mm) Material:Steel, Pre-Galvanized Function:Designed to be used as a hanger and restrainer for CPVC piping or steel piping where the “stand-off” design will ease installation by eliminating the need for wood blocking. Features: • Flared edge design protects CPVC pipe from any rough or abrasive surfaces •Unique snap-on design holds pipe firmly in place and allows retrofit type of installation •The “Stand-Off” design eliminates the need for wood block extension •Can be installed on horizontal or vertical piping regardless of mounting surface orientation •Attaches easily to wood structure with two hex head self-threading screws furnished with product •Installs easily using rechargeable electrical driver with 5/16”(7.9mm)extension socket eliminating impact tool damage to pipe •Attaches easily to steel, minimum 18 gauge (1.024mm)with (2) 1/4” x 1” tek type self drilling tapping screws •cULus Listed as a hanger and a restrainer for fire sprinkler piping Installation Note:When installed in wood structural members and threads from the #10 x 1" screws are exposed, use Fig. 27B speed nut to secure Approvals:Underwriters Laboratory Listed in the USA (UL)and Canada (cUL) to support automatic fire sprinkler systems. May be installed into wood using fasteners screws. Meets and exceeds the requirements of NFPA 13, 13R and 13D. Fig. 28M satisfies the UL vertical restraint requirements where needed. Order By:Figure number and pipe size Patent #7,744,042 ** With reduced spacing, consult factory. C A B Pipe Size A Hole Dia. B C Max Spacing* Approx. Wt./100 Part No.in. (mm) in. (mm) in. (mm) in. (mm) in. (mm) lbs. (kg) 28M-3/4 3/4"(20)2"(50.8)3/16"(4.8)35/16"(84.1)5’-6”(1676)9 (4.1) 28M-1 1"(25)21/8"(54.0)3/16"(4.8)31/2"(88.9)6’-0”(1829)12 (5.4) 28M-11/4 11/4"(32)25/16"(58.7)3/16"(4.8)31/2"(88.9)6’-6”(1981)13 (5.9) 28M-11/2 11/2"(49)27/16"(61.9)3/16"(4.8)37/8"(98.4)7’-0”(2133)14 (6.3) 28M-2 2"(50)25/8"(66.7)3/16"(4.8)47/16"(112.7)8’-0”(2438)15 (6.8) * Required per NFPA 13 for CPVC plastic pipe Hanger and Restraint Application Restraint Restraint Detail A Hanger Application Fig. 27B (2)Required Fig. 27B (1)Required High Side of Hanger 37 PR14000070 F19001679RECEIVED 04/02/2019 lwalker BUILDING DIVISION HYDRAULIC CALCULATIONS PR14000070 F19001679RECEIVED 04/02/2019 lwalker BUILDING DIVISION Hydraulic Overview Job Number: LIB2019-01 Report Description: Residential Node Flow(gpm)Hose Flow(gpm)Static(psi)Residual(psi)Name 100 500.00 50.000 20.000Water Supply Identifier Pressure(psi)K-Factor(K)Flow(gpm) Job System Supplies Check Point Gauges LIB2019-01 Justin Lees Limelite SP Lot 5 16214 114th Avenue SE Renton, WA 98055 253-677-0563 Limelite SP Lot 5 City of Renton Bedroom Job Name: Address 1 Address 2 Design Engineer Phone FAX State Certification/License Number AHJ Job Site/Building Most Demanding Sprinkler Data Coverage Per Sprinkler Total Demand Area of Application Hose Streams Number Of Sprinklers Calculated Pressure Result Job Number 26.47 @ 40.625 Water Supply at Node 100 (500.00, 0.00, 50.000, 20.000) 0.050gpm/ft² 4.9 K-Factor 12.96 at 7.000 256.00ft² 163.00ft² (Actual 163.85ft²) 0.00 2 Density +9.244 (18.5%) Address 3 System Pressure Demand System Flow Demand 40.625 26.47 © M.E.P.CAD, Inc.Page 1 PR14000070 F19001679RECEIVED 04/02/2019 lwalker BUILDING DIVISION Hydraulic Summary Report Description: Residential Job Number: LIB2019-01 Node Flow(gpm) Total Hose Streams 0.00 Safety MarginRequiredAvailable Node Hose Flow Static Residual Flow Total Demand (gpm) (psi)(psi) (gpm) (psi)(gpm)(psi)(psi)@@Name 100 49.869 40.625 9.244500.0020.00050.000 26.47Water Supply Design EngineerJob Number Total Water Required (Including Hose Allowance) 26.47 Maximum Pressure Unbalance In Loops 0.000 Additional Hose Supplies 0.00 Hose Allowance At Source Supplies 24.20gal Residential 0.050gpm/ft² 256.00ft² 163.00ft² (Actual 163.85ft²) 2 Occupancy Area of Application Coverage Per SprinklerNumber Of Sprinklers Calculated Density Job Suffix Volume capacity of Dry PipesVolume capacity of Wet Pipes 4.93 between nodes 100 and 99 Maximum Velocity Under Ground 8.92 between nodes 99 and 103 Maximum Velocity Above Ground 4.9 K-Factor 12.96 at 7.000 Most Demanding Sprinkler Data System BedroomRenton, WA 98055 Job Site/Building City of Renton16214 114th Avenue SE AHJ Limelite SP Lot 5 Job State Certification/License NumberJob Name: Justin LeesLIB2019-01 Contractor Contractor NumberLIBPLUMB Name of Contractor: Liberty Plumbing Address 1 26116 112th Street East Address 2 Buckley, WA 98321 Contact Name Contact Title ExtensionPhone 253-677-0563 FAX E-mail justin@libplumb.com Web-Site Justin Lees Address 3 Address 1 Address 2 Drawing Name Limelite SP Lot 5 System Flow Demand 26.47 Remote Area(s) Address 3 © M.E.P.CAD, Inc.Page 2AutoSPRINK® 12 v12.0.61.0 PR14000070 F19001679RECEIVED 04/02/2019 lwalker BUILDING DIVISION Device (gpm) Actual Flow Minimum Flow (gpm)(K) K-Factor (psi) Pressure Summary Of Outflowing Devices Report Description: Residential Job Number: LIB2019-01 Sprinkler 101 12.96 12.80 4.9 7.000 Sprinkler 102 13.51 12.80 4.9 7.597 Most Demanding Sprinkler Data © M.E.P.CAD, Inc.Page 3AutoSPRINK® 12 v12.0.61.0 PR14000070 F19001679RECEIVED 04/02/2019 lwalker BUILDING DIVISION FittingsNodeElevation(Foot)Pressure(psi) Discharge(gpm) Node Analysis Report Description: Residential Job Number: LIB2019-01 100 -3'-0 S 40.625 26.47 101 19'-6 Spr(-7.000)7.000 12.96 102 19'-6 Spr(-7.597)7.597 13.51 99 3'-0 BFP(-5.717)30.763 © M.E.P.CAD, Inc.Page 4AutoSPRINK® 12 v12.0.61.0 PR14000070 F19001679RECEIVED 04/02/2019 lwalker BUILDING DIVISION Pipe Type Diameter Flow Velocity Friction Loss Length Pressure Downstream Elevation Discharge K-Factor Pt Pn Fittings Eq. Length Summary Upstream Total Length HWC Hydraulic Analysis Job Number: LIB2019-01 Report Description: Residential • • • • • Route 1 • • • • • Pf Pe Pv BL 1.1010 12.96 4.37 0.030510 10'-6 0.778 101 19'-6 12.96 4.9 7.000 15'-0 -0.217 103 20'-0 7.561 25'-6 150 Sprinkler, 2E(7'-0), Tr(1'-0) Pf Pe Pv BL 1.1010 26.47 8.92 0.114276 48'-6 15.832 103 20'-0 13.51 7.561 40'-0 7.370 99 3'-0 30.763 88'-6 150 Flow (q) from Route 2 2T(5'-0), 2Tr(1'-0), 4E(7'-0), BFP(-5.717) Pf Pe Pv UG 1.4810 26.47 4.93 0.026969 81'-0¼7.252 99 3'-0 30.763 2'-6 2.610 100 -3'-0 40.625 83'-6¼ 150 E(2'-6), WMV(-5.000), S 26.47 0.00 Hose Allowance At Source 100 • • • • • Route 2 • • • • • Pf Pe Pv BL 1.1010 13.51 4.55 0.032910 0'-6 0.181 102 19'-6 13.51 4.9 7.597 5'-0 -0.217 103 20'-0 7.561 5'-6 150 Sprinkler, T(5'-0) 1.51 4.87 )(150 1.33 140 1.16 130 0.713 100 Equivalent Pipe Lengths of Valves and Fittings (C=120 only) Actual Inside Diameter Schedule 40 Steel Pipe Inside Diameter = Factor C Value Multiplier Value Of C Multiplying Factor © M.E.P.CAD, Inc.Page 5AutoSPRINK® 12 v12.0.61.0 PR14000070 F19001679RECEIVED 04/02/2019 lwalker BUILDING DIVISION Pipe Type Diameter Flow Velocity Friction Loss Length Pressure Downstream Elevation Discharge K-Factor Pt Pn Fittings Eq. Length Summary Upstream Total Length HWC Hydraulic Analysis Job Number: LIB2019-01 Report Description: Residential Pipe Type Legend AO Arm-Over BL Branch Line CM Cross Main DN Drain DR Drop DY Dynamic FM Feed Main FR Feed Riser MS Miscellaneous OR Outrigger RN Riser Nipple SP Sprig ST Stand Pipe UG Underground Units Legend Diameter Inch Elevation Foot Flow gpm Discharge gpm Velocity fps Pressure psi Length Foot Friction Loss psi/Foot HWC Hazen-Williams Constant Pt Total pressure at a point in a pipe Pn Normal pressure at a point in a pipe Pf Pressure loss due to friction between points Pe Pressure due to elevation difference between indicated points Pv Velocity pressure at a point in a pipe Fittings Legend ALV Alarm Valve AngV Angle Valve b Bushing BalV Ball Valve BFP Backflow Preventer BV Butterfly Valve C Cross Flow Turn 90° cplg Coupling Cr Cross Run CV Check Valve DelV Deluge Valve DPV Dry Pipe Valve E 90° Elbow EE 45° Elbow Ee1 11¼° Elbow Ee2 22½° Elbow f Flow Device fd Flex Drop FDC Fire Department Connection fE 90° FireLock(TM) Elbow fEE 45° FireLock(TM) Elbow flg Flange FN Floating Node fT FireLock(TM) Tee g Gauge GloV Globe Valve GV Gate Valve Ho Hose Hose Hose HV Hose Valve Hyd Hydrant LtE Long Turn Elbow mecT Mechanical Tee Noz Nozzle P1 Pump In P2 Pump Out PIV Post Indicating Valve PO Pipe Outlet PRV Pressure Reducing Valve PrV Pressure Relief Valve red Reducer/Adapter S Supply sCV Swing Check Valve Spr Sprinkler St Strainer T Tee Flow Turn 90° Tr Tee Run U Union WirF Wirsbo WMV Water Meter Valve Z Cap © M.E.P.CAD, Inc.Page 6AutoSPRINK® 12 v12.0.61.0 PR14000070 F19001679RECEIVED 04/02/2019 lwalker BUILDING DIVISION