MATERIAL SUBMITTAL
AND
HYDRAULIC CALCULATIONS
FOR
LIMELITE SP – LOT 5
16214 114TH AVENUE SE
RENTON, WA 98055
BY
LIBERTY PLUMBING
26116 112TH STREET EAST
BUCKLEY, WA 98321
PR14000070
F19001679RECEIVED
04/02/2019 lwalker
BUILDING DIVISION
By: ccappelletti
Date: 04/08/2019
FIRE DEPARTMENT
For Construction Subject to
Corrections Noted in Red
APPROVED
LIMELITE LOT 5 RESIDENCE
TABLE OF CONTENTS
FIRE SPRINKLERS
RELIABLE MODEL RFC49 RESIDENTIAL CONCEALED SPRINKLER
RELIABLE MODEL G5‐56 CONCEALED SPRINKLER
FIRE SPRINKLER VALVES
AMES 200OB BACKFLOW PREVENTER
PIPE AND FITTINGS
HARVEL CPVC FIRE SPRINKLER PIPE
SPEARS FLAMEGUARD CPVC FITTINGS
HANGERS
TOLCO FIGURE 24 CPVC HANGER
TOLCO FIGURE 28 “STAND‐OFF” CPVC HANGER
TOLCO FIGURE 28M OFFSET CPVC HANGER
HYDRAULIC CALCULATIONS
BEDROOM – TWO SPRINKLER CALCULATION (RESIDENTIAL)
PR14000070
F19001679RECEIVED
04/02/2019 lwalker
BUILDING DIVISION
FIRE SPRINKLERS
PR14000070
F19001679RECEIVED
04/02/2019 lwalker
BUILDING DIVISION
Reliable Automatic Sprinkler Co., Inc., 103 Fairview Park Drive, Elmsford, New York 10523 Bulletin 006 Rev. IBulletin 006 Rev. I
Model RFC30 (SIN RA0611)
Model RFC43 (SIN RA0612)
Model RFC49 (SIN RA0616)
Residential Flat Concealed
Sprinklers
A Residential Flat Concealed
Sprinkler engineered for a minimum
design density of 0.05 gpm/ft2 with
low GPM requirements.
Features
1. Very low water flow requirements.
2.Cover plate attachment (Plain or Perforated)
with ½” (13mm) Total adjustment.
3. Thread-On/Thread-Off or Push-On/Thread
Off cover attachment option.
4. Smooth aesthetic ceiling profile.
5. Available in brass, chrome and black plated
or painted finishes.
Listings & Approval
1. Listed by Underwriters Laboratories, and
certified by UL for Canada (cULus)
UL Listing Categories
Residential Automatic Sprinklers
UL Guide Number
VKKW
Product Description
Model RFC30, RFC43 and RFC49 Concealed Residen-
tial Sprinklers are fast response residential fusible solder
link automatic sprinklers. Residential sprinklers differ
from standard sprinklers primarily in their response time
and water distribution patterns.
Model RFC30, RFC43 and RFC49 sprinklers discharge
water in a hemispherical pattern below the sprinkler de-
flector. Residential distribution patterns are higher and
generally contain a finer droplet size than standard sprin-
kler patterns.
The combination of speed of operation and high dis-
charge pattern required for residential sprinklers has
demonstrated, in fire testing, an ability for controlling
residential fires, and thereby providing significant evacu-
ation time for occupants.
The RFC30, RFC43 and RFC49 Sprinklers provide the
best form of fire protection by combining an attractive ap-
pearance and ½” (13mm) of cover adjustment for ease
of installation. The small diameter cover plate is easily
and positively attached and blends into the ceiling, con-
cealing the most dependable fire protection available, an
automatic sprinkler system.
The RFC30, RFC43 and RFC49 are UL Listed Residen-
tial Sprinklers to be installed in the residential portions
of any occupancy in accordance with NFPA 13, 13R, &
13D.
The RFC30, RFC43 and RFC49 can reduce the need
for precise cutting of drop nipples. The threaded cover
plate assembly can be adjusted without tools to fit ac-
curately against the ceiling. The fire protection system
need not be shut down to adjust or remove the cover
plate assembly.
Plain Cover Plate
Perforated Cover Plate
PR14000070
F19001679RECEIVED
04/02/2019 lwalker
BUILDING DIVISION
2.
Application and Installation
The RFC30, RFC43 and RFC49, for residential instal-
lations, use a 165°F (74°C) fusible solder link in a tun-
ing fork style sprinkler frame with a drop-down deflector.
This assembly is recessed into the ceiling and concealed
by a flat cover plate. The cover plate is attached to the
skirt, using 135°F (57°C) ordinary temperature classifica-
tion solder. When the ceiling temperature rises, the solder
holding the cover plate releases the cover allowing the
deflector to drop into position and exposing the sprinkler
inside to ceiling temperature. The subsequent operation
of the solder link opens the waterway and causes the de-
flector to drop into position to distribute the discharging
water in a hemispherical pattern below the sprinkler de-
flector. Any adjustment of thread engagement between
the cover plate and cup will assure that the drop-down
deflector is properly located below the ceiling. The resi-
dential distribution pattern contains a finer droplet size
than a standard sprinkler, and the pattern produces sig-
nificantly higher wall wetting.
After a 25/8 inch diameter hole is cut in the ceiling, the
sprinkler is to be installed with the Model FC Wrench.
When installing a sprinkler, the wrench is first positioned
into the sprinkler/cup assembly and around the hexago-
nal body of the sprinkler frame. The Wrench must bottom
out against the cup in order to ensure proper, safe instal-
lation. The sprinkler is then tightened into the pipe fitting.
When inserting or removing the wrench from the sprin-
kler/cup assembly, care should be taken to prevent dam-
age to the sprinkler. DO NOT WRENCH ON ANY OTHER
PART OF THE SPRINKLER/CUP ASSEMBLY. MODEL
RFC30, RFC43 AND RFC49 CONCEALED SPRINKLERS
MUST BE INSTALLED ONLY WITH 135°F RATED COV-
ERS.
Note: A leak tight ½” NPT (R1/2) sprinkler joint can be ob-
tained with a torque of 8-18 ft-lbs (10,8 - 24,4 N-m). Do not
tighten sprinklers over maximum recommended torque. It
may cause leakage or impairment of the sprinklers.
Cover assemblies provide up to 1/2” (13mm) of adjust-
ment. Turn the cover clockwise until the flange is in con-
tact with the ceiling. For the push-on/thread-off option,
the cover assembly is pushed onto the cup and final ad-
justment is made by turning the cover clockwise until the
skirt flange makes full contact with the ceiling. Cover re-
moval requires turning in the counter-clockwise direction.
In ceilings that have a plenum space above the
sprinkler, the plenum space may have neutral or neg-
ative pressurization but must not be positively pres-
surized. Inspect all sprinklers after installation to en-
sure that the gap between the cover plate and ceiling
and the 4 slots in the cup are all open and free from
any air fl ow impediment.
Model
(SIN)
Thread
Size
Inch (mm)
Nominal
Orifi ce
Inch (mm)
Sprinkler
Temp Rating
CCP Assembly
Temp. Rating
Max.
Ambient
Temp.
K
Factor
Max.
Pressure
psi (bar)°F °C °F °C °F °C
RFC 30
(RA0611)½” (15)21/64 (8,2) 165 74 135 57 100 38 3.0 (43.2) 175 (12)
RFC 43
(RA0612)½” (15)3/8 (10) 165 74 135 57 100 38 4.3 (62) 175 (12)
RFC 49
(RA0616)½” (15)7/16 (11) 165 74 135 57 100 38 4.9 (70.6) 175 (12)
Note: 1 bar = 100 Kpa
RFC 30
Max. Coverage
area
Ft x Ft (m x m)
Max. Spacing
Ft (m)
Ordinary Temp. Rating
(165°F/74°C)Top of Defl ector
to Ceiling
Inch (mm)
Installation
Type
Minimum
Spacing
Ft (m)Flow
GPM (L/min)
Pressure
PSI (bar)
12 x 12 (3,6 x 3,6) 12 (3,6) 9 (34,1) 9.0 (0,62) Smooth Ceilings ½ to 1 (13 to 25.4)
Beamed Ceilings per NFPA 13D, 13R or13 installed in beams ½ to 1 (13 to 25.4)Concealed 8 (2,4)
14 x 14 (4,3 x 4,3) 14 (4,3) 10 (37,8) 11.0 (0,76)
For Ceiling types refer to NFPA 13, 13R or 13D
PR14000070
F19001679RECEIVED
04/02/2019 lwalker
BUILDING DIVISION
3.
Maintenance
Model RFC30, RFC43 and RFC49 Concealed Sprin-
klers should be inspected and the sprinkler system
maintained in accordance with NFPA 25. Do not clean
sprinklers with soap and water, ammonia or any other
cleaning fluids. Remove dust by using a soft brush or
gentle vacuuming. Remove any sprinkler cover plate as-
sembly which has been painted (other than factory ap-
plied) or damaged in any way. A stock of spare sprin-
klers should be maintained to allow quick replacement
of damaged or operated sprinklers. Prior to installation,
sprinklers should be maintained in the original cartons
and packaging until used to minimize the potential for
damage to sprinklers that would cause improper opera-
tion or non-operation.
Model RFC30, RFC43 and RFC49 Residential
Concealed Sprinkler Specifi cation
Sprinklers shall be cULus Listed low flow residential con-
cealed sprinklers with drop-down deflector and adjust-
able flat cover plate engineered for a minimum design
density of 0.05 gpm/ft2. Sprinkler frame and deflector
shall be of bronze frame construction having a ½” NPT
thread. Thermal element shall consist of an approved
black-painted beryllium-nickel fusible solder link with
symmetric lever mechanism, maintaining a Teflon-coated
Belleville spring washer and machined brass cap water
seal assembly containing no plastic parts. Sprinkler K-
factor shall be nominal 3.0 (43.2), 4.3 (62), and 4.9 (70.6)
having a 5/16”, 3/8” and 7/16” orifice. Temperature rating
shall be Ordinary 165°F (74°C); cover plate temperature
rating to be 135°F (57°C). Cover plate assembly shall
consist of a brass cover plate and copper alloy retainer
flange allowing a ½” cover plate adjustment. Any secure
engagement between the cover plate and the cup will
assure that the drop-down deflector is properly located
below the ceiling. A plastic protective cap shall be
provided and factory installed inside the sprinkler cup
to protect the drop-down sprinkler deflector from dam-
age, which could occur during construction before the
cover plate is installed. Standard cover finish: [Chrome]
[White] [Specialty – specify]. Residential concealed
sprinklers shall be Reliable Model RFC30, SIN RA0611
(Bulletin 006), Model RFC43, SIN RA0612 (Bulletin 006)
or Model RFC49, SIN RA0616 (Bulletin 006).
RFC 43
Max. Coverage
area
Ft x Ft (m x m)
Max. Spacing
Ft (m)
Ordinary Temp. Rating
(165°F/74°C)Top of Defl ector
to Ceiling
Inch (mm)
Installation
Type
Minimum
Spacing
Ft (m)Flow
GPM (L/min)
Pressure
PSI (bar)
12 x 12 (3,6 x 3,6) 12 (3,6) 12 (4,5) 7.8 (0,54)
Smooth Ceilings ½ to 1 (13 to 25.4)
Beamed Ceilings per NFPA 13D, 13R or
13 installed in beams ½ to 1 (13 to 25.4)
Concealed 8 (2,4)
14 x 14 (4,3 x 4,3) 14 (4,3) 13 (49) 9.1 (0,63)
16 x 16 (4,9 x 4,9) 16 (4,9) 13 (49) 9.1 (0,63)
18 x 18 (5,5 x 5,5) 18 (5,5) 18 (68) 17.5 (1,21)
20 x 20 (6,1 x 6,1) 20 (6,1) 21 (79) 23.8 (1,64)
For Ceiling types refer to NFPA 13, 13R or 13D
RFC 49
Max. Coverage
area
Ft x Ft (m x m)
Max. Spacing
Ft (m)
Ordinary Temp. Rating
(165°F/74°C)Top of Defl ector
to Ceiling
Inch (mm)
Installation
Type
Minimum
Spacing
Ft (m)Flow
GPM (L/min)
Pressure
PSI (bar)
12 x 12 (3,6 x 3,6) 12 (3,6) 13 (49) 7.0 (0,48)
Smooth Ceilings ½ to 1 (13 to 25.4)Beamed Ceilings per NFPA 13D, 13R or
13 installed in beams ½ to 1 (13 to 25.4)
Concealed 8 (2,4)
14 x 14 (4,3 x 4,3) 14 (4,3) 13 (49) 7.0 (0,48)
16 x 16 (4,9 x 4,9) 16 (4,9) 13 (49) 7.0 (0,48)
18 x 18 (5,5 x 5,5) 18 (5,5) 17 (64,3) 12.0 (0,83)
20 x 20 (6,1 x 6,1) 20 (6,1) 20 (75,73) 16.7 (1,14)
For Ceiling types refer to NFPA 13, 13R or 13D
PR14000070
F19001679RECEIVED
04/02/2019 lwalker
BUILDING DIVISION
Reliable Automatic Sprinkler Co., Inc.
(800) 431-1588 Sales Offices(800) 848-6051 Sales Fax
(914) 829-2042 Corporate Offices
www.reliablesprinkler.com Internet Address
Manufactured by
Recycled
Paper
Revision lines indicate updated or new data.
EG. Printed in U.S.A. 11/14 P/N 9999970261
The equipment presented in this bulletin is to be installed in accordance with the latest published Standards of the National Fire Protection Association, Factory
Mutual Research Corporation, or other similar organizations and also with the provisions of governmental codes or ordinances whenever applicable.
Products manufactured and distributed by Reliable have been protecting life and property for over 90 years, and are installed and serviced by the most highly
qualified and reputable sprinkler contractors located throughout the United States, Canada and foreign countries.
Ordering Information
Specify:
1. Sprinkler Model
2. Cover Plate Finish
3. Thread-On or
Push-On Feature
Cover Plate Finishes(1)
Standard Finishes
Chrome
White Paint
Special Application
Finishes(2)
Bright Brass
Finished Bronze
Black Plating
Black Paint
Off White
Satin Chrome
(1)Other finishes and colors are
available on special order.
Consult factory for details.
Coverplate custom paint issemi-gloss, unless specified
otherwise.
(2)For the perforated style cover-
plate, consult factory for avail-
ability on these and other cus-tom finishes.
PR14000070
F19001679RECEIVED
04/02/2019 lwalker
BUILDING DIVISION
FIRE SPRINKLER VALVES
PR14000070
F19001679RECEIVED
04/02/2019 lwalker
BUILDING DIVISION
Series 2000B Double Check Valve Assemblies are designed to protect drinking water sup-plies for dangerous cross-connections in accordance with national plumbing codes and
water authority requirements for non-health-hazard non-potable service applications such as irrigation, fire line, or industrial processing.
These valves meet the requirements of ASSE Std. 1015 and AWWA Std. C510 and are approved by the Foun da tion for Cross-Con nec tion Control and Hy drau lic Re search at the University of South ern California.
Specifications
A Double Check Valve Assembly shall be installed at each not ed lo ca tion. The as sem bly shall con sist of two positive seat ing check mod ules with cap tured springs and rubber seat discs. The check module seats and seat discs shall be re place able. Ser vice of all internal com po nents shall be through a sin gle ac cess cover se cured with stainless steel bolts. The as sem bly shall also in clude two resilient seat ed iso la tion valves and four top mount ed, re sil ient seat ed test cocks. The as sem bly shall meet the re quire ments of ASSE Std. 1015 and AWWA Std. C510. Ap proved by the Foun da tion for Cross-Con nec tion Control and Hy drau lic Re search at the Uni ver si ty of South ern Cal i for nia. As sem bly shall be an Ames Company Series 2000B.
Approvals
Approved by the Foundation for Cross-Connection Control and Hy drau lic Research at
the University of Southern California.
LBV models not listed.
Horizontal and vertical "flow up" approval on all sizes.
ES-A-2000B
3⁄4" 2000B (20mm)
2" 2000B HC
(50mm)
Series 2000B
Double Check Valve Assemblies
Sizes: 1⁄2" – 2" (15 – 50mm)
Job Name ________________________________________________Contractor ______________________________________________
Job Location ______________________________________________Approval _______________________________________________
Engineer _________________________________________________Contractor’s P.O. No. ______________________________________
Approval _________________________________________________Representative ___________________________________________
Ames product specifications in U.S. customary units and metric are ap prox i mate and are pro vid ed for ref er ence only. For precise mea sure ments, please contact Ames Technical Ser vice. Ames reserves the right to change or modify prod uct de sign, con struc tion, spec i fi ca tions, or ma te ri als with out prior notice and without in cur ring any ob li ga tion to make such chang es and mod i fi ca tions on Ames products previously or sub se quent ly sold.amesfirewater.com
Features
• Ease of maintenance with only one
cover
•Top entry
•Replaceable seats and seat discs
•Modular construction
•Compact design
•1⁄2" – 2" (15 – 50mm) Cast bronze
body construction
• Top mounted ball valve test cocks
•Low pressure drop
•No special tools required
•1⁄2" – 1" (15 – 25 mm) have
tee handles
Available Models
Suffix:
B - Quarter turn ball valves
LBV - less ball valves
SH - stainless steel ball valve handles
HC - 21⁄2" inlet/outlet fire hydrant fit ting
(2" valve)
Pressure — Temperature
Temperature Range: 33°F – 140°F
(0.5°C – 60°C)
Maximum Working Pressure: 175psi (12.1 bar)
Standards
AWWA Std. C510, IAPMO PS31
1015 B64.5 3⁄4" - 2"(LBV Models Only)
It is illegal to use this product in any plumbing system providing water for human consumption, such as drinking or dishwashing, in the United States. Before installing standard material prod-uct, consult your local water authority, building and plumbing codes.
WARNING!
PR14000070
F19001679RECEIVED
04/02/2019 lwalker
BUILDING DIVISION
Capacities
As compiled from documented Foundation for Cross-Connection Control
and Hydraulic Research at the University of Southern California lab tests.
∆Typical maximum system flow rate (7.5 feet/sec., 2.3 meters/sec.)
kPa psi 83 12 69 10 55 8 41 6 28 4 14 2 0 0
∆P 0 2 4 6 8 10 12 gpm0 7.6 15.2 22.8 30.4 38 45.6 lpm
5 7.5 10 fps 1.5 2.3 3.0 mps
∆
∆P
*
∆P
∆kPa psi
110 16
83 12
69 10
55 8
41 6
28 4
14 2
0 5 10 15 20 25 30 35 40 45 50 55 60 gpm0 19 38 57 76 95 114 133 152 171 190 209 228 lpm
5 7.5 10 15 fps 1.5 2.3 3.0 4.6 mps
∆P
∆kPa psi
96 14
83 12
69 10
55 8
41 6
28 4
14 2
0 0
0 10 20 30 40 50 60 70 80 90 100 110 120 gpm0 38 76 114 152 190 228 266 304 342 380 418 456 lpm
5 7.5 10 15 fps 1.5 2.3 3.0 4.6 mps
kPa psi
83 12
69 10
55 8
41 6
28 4
14 2
0 0 ∆P0 10 20 30 40 50 60 70 80 90 100 110 120 gpm
0 38 76 114 152 190 228 266 304 342 380 418 456 lpm
5 7.5 10 15 fps 1.5 2.3 3.0 4.6 mps
∆
∆P
∆kPa psi
83 12
69 10
55 8
41 6
28 4
14 2
0 0 0 25 50 75 100 125 150 175 200 gpm0 95 190 285 380 475 570 665 760 lpm
5 7.5 10 15 fps 1.5 2.3 3.0 4.6 mps
1⁄2" (15mm)
1" (25mm)
11⁄4" (32mm)
11⁄2" (40mm)
2" (50mm)
kPa psi
152 22
124 18
96 14
69 10
41 6
14 2
3⁄4" (20mm)
0 5 10 15 20 25 30 35 40 45 50 gpm0 19 38 57 76 95 114 133 152 171 190 lpm7.5 15 fps 2.3 4.6 mps
∆
Dimensions – Weights
Size (dn) diMenSiOnS WeigHt
A B C F G H I
in. mm in. mm in. mm in. mm in. mm in. mm in. mm in. mm lbs. kgs.
1⁄2 15 10 254 45⁄8 117 27⁄16 62 5 127 33⁄8 85 25⁄16 59 21⁄16 52 4.5 2
3⁄4 20 111⁄8 282 4 102 31⁄8 79 63⁄16 157 37⁄16 87 21⁄8 54 15⁄16 33 5 2.3
1 25 131⁄4 337 51⁄8 130 4 102 71⁄2 191 33⁄8 85 111⁄16 43 111⁄16 43 12 5.4
11⁄4 32 163⁄8 416 5 127 35⁄16 84 91⁄2 241 5 127 3 76 2 50 15 6.8
11⁄2 40 163⁄4 425 47⁄8 124 31⁄2 89 93⁄4 248 513⁄16 148 31⁄8 79 211⁄16 68 15.86 7.2
2 50 191⁄2 495 61⁄4 159 4 102 133⁄8 340 61⁄8 156 37⁄16 87 211⁄16 68 25.75 11.7
H g iSuffix HC — Fire Hydrant Fittings dimension "A" = 231⁄2" (594mm)
C
B
F
A
Strainer sold separately
Pressure LossPressure LossPressure LossPressure LossPressure LossPressure LossFlow Rate
Flow Rate
Flow Rate
Flow Rate
Flow Rate
Flow Rate
ES-A-2000B 1410 © 2014 Ames Fire & Waterworks
USA: Backflow Tel: (978) 689-6066 • Fax: (978) 975-8350 • AmesFireWater.com
USA: Control Valves Tel: (713) 943-0688 • Fax: (713) 944-9445 • AmesFireWater.com
Canada: Tel: (905) 332-4090 • Fax: (905) 332-7068 • AmesFireWater.ca
Latin America: Tel: (52) 81-1001-8600 • Fax: (52) 81-8000-7091 • AmesFireWater.com
A Watts Water Technologies Company
PR14000070
F19001679RECEIVED
04/02/2019 lwalker
BUILDING DIVISION
PIPE AND FITTINGS
PR14000070
F19001679RECEIVED
04/02/2019 lwalker
BUILDING DIVISION
Harvel Plastics, Inc. • 300 Kuebler Rd., Easton, PA 18040-9290 Tel: 610.252.7355 • Fax: 610.253.4436 • www.harvel.com
Product Specifications
Harvel®Blazemaster®CPVC Fire Sprinkler Pipe
Product SpecificationsHarvel®Blazemaster®Application:
Corrosion resistant fire sprinkler pipe, IPS sizes 3/4" through 3",
for use in wet automatic fire sprinkler systems. When installed in
accordance with Harvel’s Installation Instructions, this pipe is
Listed by Underwriters Laboratories (UL) for use in: Light Hazard
Occupancies as defined in the Standard for Installation of
Sprinkler systems (NFPA 13); Residential Occupancies up to and
including four stories in height (NFPA 13R); and Residential
Occupancies as defined in the Standard for Sprinkler Systems in
One and Two Family Dwellings and Mobile Homes (NFPA 13D).
Harvel BlazeMaster‚ pipe is UL Listed for use in Return Air
Plenums (NFPA 90A), System Risers per NFPA 13 Light Hazard,
13R and 13D, Exposed installations, Garages per NFPA 13R, and
for use as Underground Fire Service Mains (NFPA 24) when
installed in accordance with Harvel CPVC Fire Sprinkler Pipe
Installation Instructions.
Scope:
This specification outlines minimum manufacturing requirements
for Chlorinated Polyvinyl Chloride (CPVC) standard dimension
ratio (SDR) 13.5 series iron pipe size (IPS) fire sprinkler pressure
pipe. Pipe is intended for use in wet automatic fire sprinkler sys-
tems when installed in accordance with Harvel Plastics, Inc.
CPVC Fire Sprinkler Piping Products Installation Instructions.
Harvel‚ BlazeMaster‚ pipe carries a maximum working pressure
of 175 psi @ 150°F. Pipe meets or exceeds applicable industry
standards and requirements as set forth by the American Society
for Testing and Materials (ASTM), the National Sanitation
Foundation (NSF), and Underwriters Laboratories (UL). Harvel‚
BlazeMaster‚ fire sprinkler pipe is approved by the Factory Mutual
Corporation (FM) and the Loss Prevention Certification Board
(LPCB). Refer to current approval guide and installation and
design manual for installation limitations.
CPVC Materials:
The material used in the manufacture of the pipe shall be a rigid
chlorinated polyvinyl chloride (CPVC) compound, Type IV Grade
I, with a Cell Classification of 23447 as defined in ASTM D1784.
The compound and the finished product shall be orange in color,
and shall be approved by the National Sanitation Foundation
(NSF) for use with potable water. Material used shall be
domestically produced BlazeMaster‚ CPVC material as provided
by Noveon, Inc. (formerly the BFGoodrich Company).
System Design:
The CPVC sprinkler system shall be hydraulically calculated using
a Hazen-Williams C factor of 150, and shall be designed in strict
accordance with the Standard for Installation of Sprinkler
Systems, NFPA 13 Light Hazard, NFPA 13R, and NFPA 13D
as applicable.
Dimensions:
Harvel BlazeMaster‚ CPVC fire sprinkler pipe shall be
manufactured to Standard Dimension Ratio (SDR) 13.5
dimensions in strict accordance to the requirements of ASTM
F442 for physical dimensions and tolerances. Each production
run of pipe manufactured in compliance to this standard, shall
also meet the test requirements for materials, workmanship,
burst pressure, flattening, and extrusion quality defined in
ASTM F442. Furthermore, this pipe shall consistently meet or
exceed the physical performance test requirements of the
appropriate approval/listing agency(s) follow-up procedures
established for the product.
Marking:
Product marking shall meet the requirements of ASTM F 442 and
the Listing agency. Marking shall include: the phrase Harvel®
BlazeMaster® (or the manufacturers’ trademark when privately
labeled); the nominal pipe size; the type of material and material
designation code; the SDR series and pressure rating for water
(SDR 13.5; 175 psi @ 150°F); the ASTM designation F 442; the
logo of the Listing and Approval agencies (UL, FM, LPCB, etc.);
the independent laboratory’s seal of approval for potable water
usage (NSF-pw); the date and time of manufacture; and the UL
assigned control number (2N95).
Installation Procedures:
All installation procedures such as storage and handling, solvent
cement joining techniques, pipe support spacing, bracing,
allowance for thermal expansion/contraction, component
assembly techniques, and testing etc. shall be in strict accordance
with Harvel Plastics, Inc. Installation Instructions and the UL
Listing which includes installation limitations.
System Components:
Fittings used shall be UL Listed CPVC fittings and shall meet or
exceed the requirements of ASTM F437 (Sch 80 threaded), ASTM
F437 (Sch 80 socket), or ASTM F438 (Sch 40 socket) as applicable,
such as those manufactured by Spears Manufacturing Co. or
equivalent. Solvent cements used shall be those referenced in
Harvel Plastics, Inc. Installation Instructions (such as Spears FS-5
or equivalent), which meet or exceed the requirements of ASTM
F656 and ASTM F493, and shall be approved by the National
Sanitation Foundation (NSF) for use with potable water. Socket
type joints, sizes 3/4" - 3", shall be made up using the One-Step
solvent cement joining method. The solvent cement joining
method chosen shall be applied in strict accordance with the
appropriate procedures as outlined in Harvel Plastics Installation
Instructions.
Maintenance:
Maintenance shall be in accordance with the Standard for
Inspection, Testing, and Maintenance of Water Based Sprinkler
Systems as defined by NFPA 25.
PR14000070
F19001679RECEIVED
04/02/2019 lwalker
BUILDING DIVISION
Harvel Plastics, Inc. • 300 Kuebler Rd., Easton, PA 18040-9290 Tel: 610.252.7355 • Fax: 610.253.4436 • www.harvel.com
Product Specifications
Harvel®Blazemaster®CPVC Fire Sprinkler Pipe
Harvel®Blazemaster®Product Specifications
Limitations:
• CPVC systems are intended for use at a maximum working
pressure of 175 psi and ambient temperature of 150°F.
• CPVC systems shall employ sprinkler heads having a maximum
temperature rating of 225°F or lower, regardless of type.
• CPVC products shall be installed in wet pipe systems only.
• Air or compressed gas shall never be used for pressure testing.
• CPVC sprinkler systems shall be hydrostatically tested for 2
hours at 200 psi, or 50 psi in excess of the maximum working
pressure when the maximum working pressure exceeds 150 psi.
Lines shall be slowly filled with water and the air bled from the
highest and farthest sprinkler heads before test pressure is
applied.
• Only Teflon® tape or a thread sealant specifically approved for
use with Harvel® CPVC Fire Sprinkler Products shall be used in
making threaded connections.
• Where freeze protection is required, only glycerin based
anti-freeze solutions shall be used and installed in accordance
with NFPA 13. Do not use glycol base anti-freeze solutions or
contaminated glycerin solutions.
• CPVC is not approved for use in combustible concealed spaces
where sprinklers are required to protect these areas as defined
by NFPA 13, unless certain specific application sprinklers are
installed per their listing. Refer to Harvel’s current Installation
Instructions for additional information.
• CPVC sprinkler piping may be installed in a plenum space
adjacent to, but not over, openings in the ceiling such as open
ventilation grills, and require the use of schedule 80 fittings for
use on 11/2"and larger pipe sizes. Refer to Installation
Instructions for additional detail.
• Minimum protection when installed “concealed” shall consist of:
3/8" gypsum wallboard or drywall, suspended membrane
ceiling panels weighing not less than .35 pounds per square foot,
or 1/2" plywood soffits. Minimum protection for NFPA 13R and
13D systems may consist of 1/2" plywood.
• Harvel‚ BlazeMaster‚ pipe is Listed for use in exposed
applications with certain limitations. When installed without
protection, “exposed” pipe is to be installed beneath smooth, flat,
horizontal ceiling construction. Exposed categories include:
standard coverage and residential pendent and sidewall
sprinkler applications, light hazard extended coverage and
residential sprinkler pendent and sidewall sprinkler
applications, use in unfinished basements with exposed solid
wood joists, light hazard upright quick response sprinklers,
and system risers (in 13R & 13D occupancies). Refer to Harvel’s
installation instructions for specific sprinkler head temperature
ratings and spacing requirements. The product must be installed
in strict accordance with NFPA 13, 13D, 13R and Harvel’s
current CPVC Fire Sprinkler Piping Products Installation
Instructions (HFS-3).
• Harvel CPVC Fire Sprinkler Products must be installed in
accordance with Harvel’s current installation instructions
(HFS-3).
Refer to this document for current listing limitations and
installation requirements.
ASTM STANDARD D1784 MATERIAL CLASSIFICATION
EQUIVALENTS:
Cell Classification 23447 = CPVC
Type IV Grade I = CPVC 4120
PIPE SIZES SHOWN ARE
MANUFACTURED IN STRICT
COMPLIANCE WITH ASTM F442
Sample Specification:
All CPVC fire sprinkler pipe shall be manufactured from a Type IV, Grade I Chlorinated Polyvinyl Chloride (CPVC) compound with a Cell
Classification of 23447 per ASTM D1784. Pipe shall be manufactured in strict compliance with ASTM F442 to SDR 13.5 dimensions, con-
sistently meeting the Quality Assurance test requirements of this standard with regard to material, workmanship, burst pressure, flatten-
ing, and extrusion quality. All CPVC fire sprinkler pipe shall be Listed by Underwriters Laboratories for wet pipe systems, and shall
carry a rated working pressure of 175 psi @ 150°F. All CPVC fire sprinkler pipe shall be installed in accordance with Harvel Plastics, Inc.
CPVC Fire Sprinkler Piping Products Installation Instructions. National Fire Protection Association (NFPA) Standards 13, 13D, and 13R
must be referenced for design and installation requirements in conjunction with the Installation Instructions. All CPVC fire sprinkler
pipe shall be manufactured in the USA by an ISO 9001 certified manufacturer and shall be FM and LPCB approved. All CPVC fire sprin-
kler pipe shall be packaged immediately after its manufacture to prevent damage and shall be stored indoors after production, at the
manufacturing site, until shipped from factory. This pipe shall bear the logo of the listing agencies, and shall carry the National
Sanitation Foundation (NSF) seal of approval for potable water applications. All CPVC fire sprinkler pipe shall be Harvel® BlazeMaster®
pipe as manufactured by HARVEL® PLASTICS, INC.
Harvel CPVC Fire Sprinkler Pipe Dimensions
SDR 13.5 (ASTM F442)
Nominal Average Min. Average Nom.Wt.
Size (in.) O.D. Wall I.D. Lbs./Ft.
3/4 1.050 0.078 0.874 0.168
1 1.315 0.097 1.101 0.262
1-1/4 1.660 0.123 1.394 0.418
1-1/2 1.900 0.141 1.598 0.548
2 2.375 0.176 2.003 0.859
2-1/2 2.875 0.213 2.423 1.257
3 3.500 0.259 2.950 1.867
PR14000070
F19001679RECEIVED
04/02/2019 lwalker
BUILDING DIVISION
FlameGuard® CPVC FIRE SPRINKLER PIPING PRODUCTS
1 SPEARS® MANUFACTURING COMPANY
CPVC FIRE SPRINKLER PIPE SDR 13.5 (ASTM F 442)
Part Number Nominal Size Average O.D.Average I.D.Approx. Weight Lbs./Ft. Inches (mm) Inches (mm) Inches (mm)
CP-007 3/4 (19.1) 1.050 (26.7).874 (22.5).181
CP-010 1 (25.4) 1.315 (33.4)1.101 (28.2).280
CP-012 1-1/4 (31.8) 1.660 (42.2)1.394 (35.6).418
CP-015 1-1/2 (38.1) 1.900 (48.3)1.598 (40.7).550
CP-020 2 (50.8) 2.375 (60.3)2.003 (50.9).872
CP-025 2-1/2 (63.5) 2.875 (73.0)2.423 (61.5)1.260
CP-030 3 (76.2) 3.500 (88.9)2.950 (75.0)1.900
Dimension Reference
G = (LAYING LENGTH) Intersection of center lines to bottom of socket/thread; 90° elbows,
tees, crosses; ± 1/32 inch.
H = Intersection of center lines to face of fitting; 90° elbows tees, crosses; ± 1/32 inch.
J = Intersection of center lines to bottom of socket/thread; 45° elbows; ± 1/32 inch
L = Overall length of fittings; ± 1/16 inch.
M = Outside diameter of socket/thread hub; ± 1/16 inch.
N = Socket bottom to socket bottom; couplings; ± 1/16 inch.
Q = Width of flats; ±1/16 inch.
W = Height of cap; ± 1/16 inch.
The information contained in this publication is based on current information and Product design at the time of publication and is subject to change without
notification. Our ongoing commitment to product improvement may result in some variation. No representations, guarantees or warranties of any kind are made
as to its accuracy, suitability for particular applications or results to be obtained therefrom. For verification of technical data or additional information not contained
herein, please contact Spears® Technical Services Department [West Coast: (818) 364-1611—East Coast: (678) 985-1263].
General Information
RECOMMENDATIONS FOR INSTALLERS AND USERS:
Plastic piping systems should be ENGINEERED, INSTALLED and OPERATED in accordance with ESTABLISHED DESIGN AND ENGINEERING STANDARDS
AND PROCEDURES for plastic piping systems. Suitability for the intended service application should be determined by the installer and/or user prior to
installation of a plastic piping system. All Installation and maintenance personnel should be trained in the proper handling and installation requirements and
precautions of plastic piping systems. PRIOR TO ASSEMBLY, all piping system components should be inspected for damage or irregularities. Mating
components should be checked to assure that tolerances and engagements are compatible. Do not use any components that appear irregular or do
not fit properly. Contact the appropriate manufacturer of the component product in question to determine usability. Consult all applicable codes and
regulations for compliance prior to installation.
Installation must be made in accordance with Spears® Manufacturing Company
FlameGuard® CPVC Fire Sprinkler Piping Products Installation Instructions - FG-3
NOTE — Individual or group instruction in correct solvent welding procedures is available by contacting your local distributor or your servicing Spears® Regional
Distribution Center.
SOLVENT CEMENT CONNECTIONS — Spears® Manufacturing Company recommends the use of Spears® FS-5 One Step solvent cement for joining Spears®
products. Use of solvent cementing products not approved for CPVC fire sprinkler systems, or failure to follow installation instructions will automatically void
the warranty.
THREADED CONNECTION — Spears® Manufacturing Company recommends the use of Spears® BLUE 75™ Thread Sealant. This product has been tested
by Spears® and the sealant manufacturer for compatibility with the Spears® CPVC fire sprinkler products. Consult the sprinkler head manufacturer before using
this product. WARNING: OTHER PIPE JOINT COMPOUNDS OR PASTES MAY CONTAIN SUBSTANCES THAT COULD CAUSE STRESS CRACKING IN
THE CPVC OR OTHER FITTING COMPONENTS. Care must be taken to avoid over torquing - generally 1 to 2 turns beyond finger tight is all that is required
to make up a threaded connection. Factory testing has indicated 10-25 ft. lbs. of torque is adequate to obtain a leak free seal.
GASKET SEALED THREAD CONNECTIONS — This type of connection can only be made with Spears® TorqueSafe™ style Gasket Sealed Female Sprinkler
Adapters. DO NOT USE ANY TYPE OF THREAD SEALANT WHEN INSTALLING THIS TYPE OF ADAPTER. Tape or paste may impair proper sealing and
function. Testing has shown that hand tight until snug is all that is needed to seal this special connection.
PR14000070
F19001679RECEIVED
04/02/2019 lwalker
BUILDING DIVISION
FlameGuard® CPVC FIRE SPRINKLER PIPING PRODUCTS
MADE IN THE U.S.A. 2
TEE
Socket x Socket x Socket
G
H
L
M
Part Number Size G H L M Approx. Wt. (Lbs.)
4201-007 3/4 9/16 1-1/2 2-31/32 1-5/16 .11
4201-010 1 13/16 1-13/16 3-5/8 1-5/8 .20
4201-012 1-1/4 15/32 2-3/32 4-7/32 2 .29
4201-015 1-1/2 1-5/32 2-9/16 5-3/32 2-11/32 .54
4201-020 2 1-13/32 2-15/16 5-7/8 2-7/8 .86
4201-025 2-1/2 1-23/32 3-1/2 7 3-15/32 1.62
4201-030 3 2-1/16 3-15/16 7-7/8 4-3/16 3.02
REDUCING TEE
Socket x Socket x Socket
M
H1
H H2
G G2
L
G1
M2
M1
Part Number Size G G1 G2 H H1 H2 L M M1 M2
Approx. Wt.
(Lbs.)
4201-102 3/4x3/4x1 3/4 25/32 3/4 1-11/16 1-13/16 1-11/16 3-3/8 1-5/16 1-21/32 1-5/16 .13
4201-125 1x3/4x3/4 21/32 13/16 5/8 1-25/32 1-13/16 1-5/8 3-13/32 1-17/32 1-5/16 1-5/16 .15
4201-126 1x3/4x1 3/4 1-7/8 1-3/32 1-27/32 2-31/32 1-31/32 3-13/16 1-23/32 1-23/32 1-13/32 .26
4201-131 1x1x3/4 21/32 13/16 21/32 1-25/32 1-13/16 1-25/32 3-9/16 1-5/8 1-5/16 1-5/8 .16
4201-157 1-1/4x1x3/4 11/16 1-1/32 11/16 1-15/16 2-1/32 1-13/16 3-25/32 2-3/32 1-13/32 1-23/32 .32
4201-158 1-1/4x1x1 27/32 29/32 25/32 2-1/16 2-1/32 1-29/32 3-15/16 1-31/32 1-5/8 1-5/8 .24
4201-159 1-1/4x1x1-1/4 31/32 31/32 31/32 2-7/32 2-7/32 2-3/32 4-11/32 2-3/32 2-3/32 1-23/32 .35
4201-167 1-1/4x1-1/4x3/4 21/32 1 21/32 1-29/32 2 1-29/32 3-13/16 2 1-5/16 2 .22
4201-168 1-1/4x1-1/4x1 13/16 31/32 13/16 2-1/16 2-3/32 2-1/16 4-1/8 1-31/32 1-21/32 2 .24
4201-169 1-1/4x1-1/4x1-1/2 1-1/8 15/16 1-1/8 2-3/8 2-11/32 2-3/8 4-3/4 2-3/32 2-11/32 2-3/32 .51
4201-201 1-1/2x1-1/4x3/4 11/16 1 1/4 2-1/16 2 1-15/16 4 2-5/16 1-3/8 2-1/16 .41
4201-202 1-1/2x1-1/4x1 27/32 1-1/32 1 2-7/32 2-5/32 2-1/4 4-15/32 2-5/16 1-11/16 2-1/16 .42
4201-210 1-1/2x1-1/2x3/4 23/32 1-1/16 23/32 2-3/32 2-1/32 2-3/32 4-3/16 2-5/16 1-3/8 2-5/16 .37
4201-211 1-1/2x1-1/2x1 13/16 1-3/16 13/16 2-3/16 2-1/4 2-3/16 4-3/8 2-11/32 1-23/32 2-11/32 .41
4201-212 1-1/2x1-1/2x1-1/4 1 1-1/8 1 2-3/8 2-11/32 2-3/8 4-13/16 2-11/32 2-3/32 2-11/32 .48
4201-213 1-1/2x1-1/2x2 1-5/16 1-1/8 1-5/16 2-11/16 2-21/32 2-11/16 5-3/8 2-11/32 2-27/32 2-11/32 .72
PR14000070
F19001679RECEIVED
04/02/2019 lwalker
BUILDING DIVISION
FlameGuard® CPVC FIRE SPRINKLER PIPING PRODUCTS
3 SPEARS® MANUFACTURING COMPANY
REDUCING TEE
Socket x Socket x Socket
M
H1
H H2
G G2
L
G1
M2
M1
Part Number Size G G1 G2 H H1 H2 L M M1 M2 Approx. Wt.
(Lbs.)
4201-248 2x2x3/4 11/16 1-13/32 11/16 2-7/32 2-7/16 2-7/32 4-7/16 2-27/32 1-3/8 2-27/32 .52
4201-249 2x2x1 27/32 1-7/16 27/32 2-11/32 2-9/16 2-11/32 4-23/32 2-7/8 1-3/4 2-7/8 .57
4201-250 2x2x1-1/4 1 1-11/32 1 2-17/32 2-19/32 2-17/32 5-3/32 2-27/32 2-3/32 2-27/32 .63
4201-251 2x2x1-1/2 1-7/32 1-13/32 1-7/32 2-11/16 2-25/32 2-11/16 5-3/8 2-27/32 2-11/32 2-27/32 .85
4201-289 2-1/2x2-1/2x1 29/32 25/32 29/32 2-21/32 1-29/32 2-21/32 5-5/16 3-1/2 1-23/32 3-1/2 1.03
4201-290 2-1/2x2-1/2x1-1/4 1-3/32 1-23/32 1-3/32 2-27/32 2-31/32 2-27/32 5-21/32 3-17/32 2-3/32 3-17/32 1.13
4201-291 2-1/2x2-1/2x1-1/2 1-3/16 1/2 1-3/16 2-15/16 1-7/8 2-15/16 5-7/8 3-15/32 2-11/32 3-15/32 1.26
4201-292 2-1/2x2-1/2x2 1-13/32 1-5/8 1-13/32 3-3/16 3-1/8 3-3/16 6-11/32 3-1/2 3-7/8 3-1/2 1.34
4201-335 3x3x1 7/8 1-15/16 7/8 2-3/4 3-1/16 2-3/4 5-15/32 4-3/16 1-23/32 4-3/16 1.26
4201-336* 3x3x1-1/4 1-3/8 1-3/4 1-3/8 3-5/16 3-1/2 3-5/16 6-5/8 4-1/8 2-7/8 4-1/8 1.94
4201-337 3x3x1-1/2 1-5/32 2-1/16 1-5/32 3-1/32 3-7/16 3-1/32 6-3/32 4-3/16 2-3/8 4-3/16 1.46
4201-338 3x3x2 1-7/16 1-13/16 1-7/16 3-5/16 3-5/16 3-5/16 6-19/32 4-3/16 2-7/8 4-3/16 1.69
4201-339 3x3x2-1/2 1-3/4 1-31/32 1-3/4 3-5/8 3-23/32 3-5/8 7-1/4 4-3/16 3-17/32 4-3/16 2.11
* Branch Outlet Sized with Bushing
CONTINUED
SPRINKLER HEAD TEE
Gasket Sealed Brass
Thread Insert Style
Socket x Socket x Gasket FIPT
With Elastomer Seal - Use NO Thread Sealant
Part Number Size G G1 G2 H H1 H2 L M M1 M2 Approx. Wt. (Lbs.)
4202-101 G 3/4x3/4x1/2 7/16 1-3/16 7/16 1-7/16 1-7/16 1-17/32 2-29/32 1-3/8 1-3/8 1-3/8 .22
4202-124 G 1x3/4x1/2 7/16 1-11/32 9/16 1-9/16 1-11/16 1-9/16 3-1/8 1-11/16 1-3/8 1-3/8 .26
4202-130 G 1x1x1/2 7/16 1-11/32 7/16 1-9/16 1-11/16 1-9/16 3-1/8 1-23/32 1-3/8 1-23/32 .28
4202-166 G 1-1/4x1-1/4x1/2 7/16 1-5/8 7/16 1-11/16 1-15/16 1-11/16 3-3/8 2-1/16 1-3/8 2-1/16 .34
4202-209 G 1-1/2x1-1/2x1/2 1/2 1-13/16 1/2 1-7/8 2-3/32 1-7/8 3-3/4 2-11/32 1-3/8 2-11/32 .41
4202-247 G 2x2x1/2 1/2 2-1/16 1/2 2 2-11/32 2 4-1/32 2-27/32 1-3/8 2-27/32 .54
Not intended to convey or dispense water for human consumption through drinking or cooking
H
M
G1
H1
M1
H2
G2G
M2
L
PR14000070
F19001679RECEIVED
04/02/2019 lwalker
BUILDING DIVISION
FlameGuard® CPVC FIRE SPRINKLER PIPING PRODUCTS
MADE IN THE U.S.A. 4
SPRINKLER HEAD TEE
Special Reinforced Plastic Thread Style
Socket x Socket x SR Fipt
L
H
M
G1
H1
M1
H2
G2G
M2
Part Number Size G G1 G2 H H1 H2 L M M1 M2 Approx. Wt. (Lbs.)
4202-101SR 3/4x3/4x1/2 19/32 3/4 19/32 1-19/32 1-7/16 1-19/32 3-7/32 1-13/32 1-3/16 1-13/32 .16
4202-124SR 1x3/4x1/2 7/16 29/32 9/16 1-19/32 1-5/8 1-9/16 3-5/32 1-23/32 1-3/16 1-17/32 .19
4202-130SR 1x1x1/2 7/16 29/32 7/16 1-9/16 1-5/8 1-9/16 3-1/8 1-23/32 1-3/16 1-23/32 .20
4202-010SR 1x1x1 21/32 3/4 21/32 1-25/32 1-5/8 1-25/32 3-19/32 1-23/32 1-11/16 1-23/32 .26
4202-156SR 1-1/4x1x1/2 15/32 1-5/32 19/32 1-23/32 1-7/8 1-23/32 3-13/32 2-3/32 1-3/16 1-23/32 .26
4202-166SR 1-1/4x1-1/4x1/2 7/16 1-1/8 7/16 1-11/16 1-27/32 1-11/16 3-3/8 2-3/32 1-3/16 2-3/32 .26
4202-168SR 1-1/4x1-1/4x1 27/32 1-1/32 27/32 2-3/32 1-29/32 2-3/32 4-7/32 2-3/32 1-11/16 2-3/32 .34
4202-199SR 1-1/2x1-1/4x1/2 9/16 1-9/32 17/32 1-15/16 2 1-25/32 3-23/32 2-11/32 1-3/16 2-3/32 .33
4202-209SR 1-1/2x1-1/2x1/2 1/2 1-1/4 1/2 1-7/8 1-31/32 1-7/8 3-3/4 2-11/32 1-3/16 2-11/32 .35
4202-211SR 1-1/2x1-1/2x1 27/32 1-7/32 27/32 2-7/32 2-1/8 2-7/32 4-15/32 2-11/32 1-23/32 2-11/32 .44
4202-237SR 2x1-1/2x1/2 23/32 1-9/16 3/8 2-7/32 2-9/32 1-3/4 3-31/32 2-7/8 1-3/16 2-11/32 .45
4202-247SR 2x2x1/2 1/2 31/32 1/2 2 1-11/16 19/32 4 2-7/8 1-3/16 2-7/8 .48
4202-287SR 2-1/2x2-1/2x1/2 17/32 1-3/4 17/32 2-9/32 2-1/2 2-9/32 4-19/32 3-1/2 1-7/32 3-1/2 .78
SPRINKLER HEAD TEE
Brass Thread Insert Style
Socket x Socket x Fipt
Part Number Size G G1 G2 H H1 H2 L M M1 M2 Approx. Wt. (Lbs.)
4202-101 3/4x3/4x1/2 7/16 1-5/32 7/16 1-7/16 1-17/32 1-7/16 2-29/32 1-3/8 1-7/32 1-3/8 .27
4202-124 1x3/4x1/2 7/16 1-11/32 9/16 1-9/16 1-11/16 1-9/16 3-1/8 1-11/16 1-3/8 1-3/8 .26
4202-130 1x1x1/2 7/16 1-7/32 7/16 1-9/16 1-25/32 1-9/16 3-1/8 1-3/4 1-3/16 1-3/4 .26
4202-010 1x1x1 11/16 1-3/32 11/16 1-13/16 1-29/32 1-13/16 3-19/32 1-23/32 1-23/32 1-23/32 .37
4202-156 1-1/4x1x1/2 7/16 1-15/32 9/16 1-11/16 2-1/32 1-11/16 3-3/8 2-3/32 1-7/32 1-3/4 .30
4202-166 1-1/4x1-1/4x1/2 7/16 1-1/2 7/16 1-11/16 2-1/16 1-11/16 3-13/32 2-3/32 1-3/16 2-3/32 .32
4202-199 1-1/2x1-1/4x1/2 1/2 1-5/8 9/16 1-7/8 2-3/16 1-13/16 3-11/16 2-5/16 1-7/32 2-1/16 .37
4202-209 1-1/2x1-1/2x1/2 1/2 1-23/32 1/2 1-7/8 2-3/32 1-7/8 3-3/4 2-5/16 1-17/32 2-5/16 .45
4202-237 2x1-1/2x1/2 1/2 1-7/8 17/32 2 2-7/16 1-29/32 3-15/16 2-27/32 1-7/32 2-5/16 .48
4202-247 2x2x1/2 1/2 1-31/32 1/2 2 2-3/8 2 4-1/32 2-27/32 1-17/32 2-27/32 .58
Not intended to convey or dispense water for human consumption through drinking or cooking
H
M
G1
H1
M1
H2
G2G
M2
L
PR14000070
F19001679RECEIVED
04/02/2019 lwalker
BUILDING DIVISION
FlameGuard® CPVC FIRE SPRINKLER PIPING PRODUCTS
5 SPEARS® MANUFACTURING COMPANY
SPRINKLER HEAD TEE
Special Reinforced Plastic Thread Style
Socket x SR Fipt x Socket
L
G H
G1 H1
M1
M
H2 G2
M2
Part Number Size G G1 G2 H H1 H2 L M M1 M2 Approx. Wt. (Lbs.)
4203-122SR 1x1/2x1 27/32 23/32 1-3/32 1-23/32 1-5/8 1-25/32 3-13/32 1-3/4 1-3/4 1-3/16 .21
SPRINKLER HEAD TEE
Brass Thread Insert Style
Socket x Fipt x Socket
H2
L
G
H
G1
H1
M1
M
G2
M2
Part Number Size G G1 G2 H H1 H2 L M M1 M2 Approx. Wt. (Lbs.)
4203-122 1x1/2x1 23/32 3/4 1-1/4 1-5/8 1-5/8 1-15/16 3-1/2 1-23/32 1-23/32 1-3/16 .25
Not intended to convey or dispense water for human consumption through drinking or cooking
TORQUESAFE™ SPRINKLER HEAD TEE
Gasket Sealed Brass Thread Insert Style
Socket x Gasket FIPT x Socket With Elastomer Seal -
Use NO Thread Sealant
H2L
G
H
G1
H1
M1
M
G2
M2
Part Number Size G G1 G2 H H1 H2 L M M1 M2 Approx. Wt. (Lbs.)
4203-122 G 1x1/2x1 19/32 13/16 1-13/32 1-19/32 1-27/32 1-3/4 3-11/32 1-5/8 1-5/8 1-3/8 .25
Not intended to convey or dispense water for human consumption through drinking or cooking
PR14000070
F19001679RECEIVED
04/02/2019 lwalker
BUILDING DIVISION
FlameGuard® CPVC FIRE SPRINKLER PIPING PRODUCTS
MADE IN THE U.S.A. 6
SIDE OUTLET ELBOW
Socket x Socket x Socket
Part Number Size G H M Approx. Wt. (Lbs.)
4213-007 3/4 27/32 1-19/32 1-5/16 .09
4213-010 1 13/16 1-7/8 1-5/8 .18
H
G
M
90° ELBOW
Socket x Socket
Part Number Size G H M Approx. Wt. (Lbs.)
4206-007 3/4 9/16 1-1/2 1-5/16 .07
4206-010 1 3/4 1-5/8 1-5/8 .11
4206-012 1-1/4 7/8 2-5/32 2 .21
4206-015 1-1/2 1-5/32 2-17/32 2-3/8 .41
4206-020 2 1-13/32 2-29/32 2-7/8 .45
4206-025 2-1/2 1-5/8 3-7/16 3-7/16 1.17
4206-030 3 1-29/32 3-23/32 4-3/16 1.80
H
M
G
STREET TEE
Spigot x Socket x Socket
Part Number Size G G1 G2 H H1 H2 L M1 M2 Approx. Wt. (Lbs.)
4244-007 3/4 13/16 27/32 27/32 1-13/16 1-7/8 1-7/8 3-5/8 1-13/32 1-13/32 .16
4244-010 1 1-5/32 1-1/32 1-1/32 2-1/8 1-29/32 1-29/32 4-3/16 1-3/4 1-3/4 .27
4244-012 1-1/4 1-1/4 1 1 2-7/16 2-9/32 2-9/32 4-27/32 2-3/32 2-3/32 .42
4244-015 1-1/2 1-13/16 1-1/8 1-1/8 2-7/8 2-9/16 2-9/16 5-11/32 2-11/32 2-11/32 .56
4244-020 2 1-23/32 1-7/16 1-13/32 3-1/4 2-15/16 2-15/16 6-5/32 2-7/8 2-7/8 .84
M1
PIPEO.D.
H
H1
L H2
M2
G1
G G2
PR14000070
F19001679RECEIVED
04/02/2019 lwalker
BUILDING DIVISION
FlameGuard® CPVC FIRE SPRINKLER PIPING PRODUCTS
7 SPEARS® MANUFACTURING COMPANY
90° SPRINKLER HEAD ELBOW
Gasket Sealed Brass Thread Insert Style
Socket x Gasket FIPT With Elastomer Seal -
Use NO Thread Sealant
G
H
M1
H1
M
G1
Part Number Size G G1 H H1 M M1 Approx. Wt. (Lbs.)
4207-101 G 3/4x1/2 9/16 1-7/32 1-13/32 1-17/32 1-13/32 1-3/8 .19
4207-130 G 1x1/2 15/32 1-13/32 1-9/16 1-11/16 1-23/32 1-3/8 .23
4207-166 G 1-1/4x1/2 15/32 1-19/32 1-15/16 1-11/16 2-3/32 1-3/8 .25
Not intended to convey or dispense water for human consumption through drinking or cooking
REDUCING 90° ELBOW
Socket x Socket
Part Number Size G G1 H H1 M M1 Approx. Wt. (Lbs.)
4206-131 1x3/4 25/32 11/16 1-25/32 1-25/32 1-19/32 1-5/16 .11
H1
G1
M1
H
G
M
SPRINKLER HEAD 90° ELBOW
Brass Thread Insert Style
Socket x Fipt
Part Number Size G G1 H H1 M M1 Approx. Wt. (Lbs.)
4207-101 3/4x1/2 7/16 1-5/32 1-23/32 1-17/32 1-13/32 1-17/32 .25
4207-130 1x1/2 15/32 1-5/8 1-9/16 1-11/16 1-23/32 1-17/32 .28
4207-131 1x3/4 17/32 1-1/4 1-21/32 2 1-23/32 1-3/8 .25
4207-166 1-1/4x1/2 15/32 1-17/32 1-11/16 1-15/16 2-3/32 1-17/32 .33
Not intended to convey or dispense water for human consumption through drinking or cooking
G
H
M1
G1
H1
M
PR14000070
F19001679RECEIVED
04/02/2019 lwalker
BUILDING DIVISION
FlameGuard® CPVC FIRE SPRINKLER PIPING PRODUCTS
MADE IN THE U.S.A. 8
90° STREET ELBOW
Spigot x Socket
PIPE O.D.
H1
G1
G
H
M1
Part Number Size G G1 H H1 M1 Approx. Wt. (Lbs.)
4209-007 3/4 29/32 19/32 1-15/16 1-11/16 1-13/32 .12
4209-010 1 1-9/32 23/32 2-13/32 1-27/32 1-3/4 .21
4209-012 1-1/4 1-9/16 27/32 2-13/16 2-3/32 2-3/32 .32
4209-015 1-1/2 1-15/32 1-3/16 2-27/32 2-9/16 2-11/32 .42
4209-020 2 1-23/32 1-3/8 3-7/32 2-15/16 2-27/32 .65
SPRINKLER HEAD 90° ELBOW
Special Reinforced Plastic Thread Style
Socket x SR Fipt
G
H
M
M1
G1
H1
Part Number Size G G1 H H1 M M1 Approx. Wt. (Lbs.)
4207-101SR 3/4x1/2 11/32 13/16 1-15/32 1-1/2 1-13/32 1-3/16 .14
4207-130SR 1x1/2 7/16 7/8 1-9/16 1-5/8 1-23/32 1-3/8 .20
4207-131SR 1x3/4 1/2 7/8 1-5/8 1-9/16 1-23/32 1-3/8 .16
4207-166SR 1-1/4x1/2 13/32 1-1/32 1-21/32 1-23/32 2-3/32 1-7/32 .19
PR14000070
F19001679RECEIVED
04/02/2019 lwalker
BUILDING DIVISION
FlameGuard® CPVC FIRE SPRINKLER PIPING PRODUCTS
9 SPEARS® MANUFACTURING COMPANY
22-1/2° STREET ELBOW
Spigot x Socket
PIPE O.D.
M1
H
H1
J
J1
Part Number Size H H1 J J1 M1 Approx. Wt. (Lbs.)
4242-007 3/4 1-1/4 1-1/2 1/4 1/2 1-3/8 .08
4242-010 1 1-7/16 1-11/32 5/16 7/32 1-23/32 .14
4242-012 1-1/4 1-9/16 1-25/32 17/32 11/16 2-1/16 .21
4242-015 1-1/2 1-13/32 1-23/32 1/2 11/32 2-11/32 .28
4242-020 2 1-29/32 2-1/8 7/32 5/8 2-7/8 .42
4242-025 2-1/2 2-1/8 2-1/4 13/32 1/2 3-1/2 .68
4242-030 3 2-13/32 2-13/32 9/16 17/32 4-5/32 .99
22-1/2° ELBOW
Socket x Socket
M
H
J
Part Number Size H J M Approx. Wt. (Lbs.)
4216-007 3/4 1-3/16 7/32 1-13/32 .09
4216-010 1 1-3/8 9/32 1-25/32 .14
4216-012 1-1/4 1-1/2 5/16 2-3/32 .20
4216-015 1-1/2 1-7/16 13/32 1-3/8 .19
4216-020 2 1-7/8 3/8 2-27/32 .43
4216-030 3 2-3/8 1/2 4-5/32 1.00
PR14000070
F19001679RECEIVED
04/02/2019 lwalker
BUILDING DIVISION
FlameGuard® CPVC FIRE SPRINKLER PIPING PRODUCTS
MADE IN THE U.S.A. 10
45° STREET ELBOW
Spigot x Socket
J1
H1
M1
JH
PIPE O.D.
Part Number Size H H1 J J1 M1 Approx. Wt. (Lbs.)
4227-010 1 1-1/2 1-5/16 1/2 1/4 1-5/8 .10
4227-012 1-1/4 1-25/32 1-9/16 9/16 11/32 1-31/32 .15
4227-015 1-1/2 2-1/32 2-1/8 19/32 25/32 2-11/32 .29
4227-020 2 2-5/16 1-15/16 25/32 13/32 2-7/8 .44
45° ELBOW
Socket x Socket
J
H
M
Part Number Size H J M Approx. Wt. (Lbs.)
4217-007 3/4 1-5/16 5/16 1-5/16 .07
4217-010 1 1-13/32 3/8 1-5/8 .11
4217-012 1-1/4 1-5/8 3/8 2-5/32 .21
4217-015 1-1/2 1-27/32 15/32 2-11/32 .32
4217-020 2 2-1/8 21/32 2-7/8 .48
4217-025 2-1/2 2-17/32 3/4 3-1/2 .88
4217-030 3 2-29/32 29/32 4-5/32 1.17
PR14000070
F19001679RECEIVED
04/02/2019 lwalker
BUILDING DIVISION
FlameGuard® CPVC FIRE SPRINKLER PIPING PRODUCTS
11 SPEARS® MANUFACTURING COMPANY
REDUCING CROSS
Socket x Socket x Socket x Socket
M
L
G
H
G1
H1
L1
M1
Part Number Size G G1 H H1 L L1 M M1 Approx. Wt. (Lbs.)
4220-131 1x3/4 23/32 5/8 1-5/8 1-5/8 3-1/4 3-1/4 1-7/8 1-1/2 .31
4220-167 1-1/4x3/4 1-1/16 23/32 2-1/16 1-31/32 4-3/32 3-31/32 2-1/16 1-13/32 .35
4220-210 1-1/2x3/4 11/16 1-5/32 2-3/32 2-3/16 4-3/16 4-11/32 2-3/8 1-13/32 .42
4220-248 2x3/4 11/16 1-7/16 2-7/32 2-7/16 4-13/32 4-7/8 2-29/32 1-13/32 .56
4220-289 2-1/2x1 29/32 1-3/4 2-11/16 2-7/8 5-11/32 5-3/4 3-1/2 1-3/4 .98
CROSS
Socket x Socket x Socket x Socket
L1
L
H
G
H1
G1
M
Part Number Size G G1 H H1 L L1 M Approx. Wt. (Lbs.)
4220-007 3/4 5/8 5/8 1-21/32 1-21/32 3-5/16 3-5/16 1-13/32 .22
4220-010 1 3/4 3/4 1-5/8 1-5/8 3-1/4 3-1/4 1-23/32 .20
4220-012 1-1/4 1-1/8 1-1/8 2-3/8 2-3/8 4-3/4 4-3/4 2-3/32 .63
4220-015 1-1/2 1-7/32 1-7/32 2-5/8 2-5/8 5-7/32 5-7/32 2-3/8 .80
4220-020 2 1-1/2 1-1/2 3 3 6 6 3 1.43
4220-025 2-1/2 1-11/16 1-11/16 3-7/16 3-7/16 6-7/8 6-7/8 3-17/32 2.16
4220-030 3 2-3/32 2-3/32 3-31/32 3-31/32 7-15/16 7-15/16 4-7/16 3.37
PR14000070
F19001679RECEIVED
04/02/2019 lwalker
BUILDING DIVISION
FlameGuard® CPVC FIRE SPRINKLER PIPING PRODUCTS
MADE IN THE U.S.A. 12
REDUCER COUPLING
Socket x Socket
N
L
M1M
Part Number Size L M M1 N Approx. Wt. (Lbs.)
4229-131 1x3/4 2-3/8 1-23/32 1-13/32 7/32 .10
4229-167 1-1/4x3/4 2-19/32 2-3/32 1-5/8 11/32 .17
4229-168 1-1/4x1 2-11/16 2-3/32 1-23/32 5/16 .18
4229-210 1-1/2x3/4 2-13/16 2-11/32 1-13/32 15/32 .19
4229-211 1-1/2x1 2-7/8 2-11/32 1-15/16 3/8 .24
4229-212 1-1/2x1-1/4 2-13/16 2-13/32 2-1/8 5/32 .23
4229-248 2x3/4 3-3/16 2-7/8 1-7/16 23/32 .32
4229-249 2x1 3-1/8 2-7/8 1-23/32 1/2 .31
4229-250 2x1-1/4 3-3/16 2-7/8 2-1/8 17/32 .33
4229-251 2x1-1/2 3-3/16 2-27/32 2-11/32 9/32 .31
4229-291 2-1/2x1-1/2 3-23/32 3-15/32 2-11/32 21/32 .51
4229-292 2-1/2x2 3-21/32 3-1/2 2-7/8 13/32 .52
COUPLING
Socket x Socket
N
L
M
Part Number Size L M N Approx. Wt. (Lbs.)
4229-007 3/4 2-1/8 1-5/16 3/16 .05
4229-010 1 2-3/16 1-5/8 3/32 .08
4229-012 1-1/4 2-19/32 2 3/32 .13
4229-015 1-1/2 2-7/8 2-11/32 3/32 .22
4229-020 2 3-1/8 2-7/8 1/8 .33
4229-025 2-1/2 3-11/16 3-15/32 3/16 .48
4229-030 3 4 4-3/16 1/4 .89
PR14000070
F19001679RECEIVED
04/02/2019 lwalker
BUILDING DIVISION
FlameGuard® CPVC FIRE SPRINKLER PIPING PRODUCTS
13 SPEARS® MANUFACTURING COMPANY
FEMALE ADAPTER
Brass Thread Insert Style
Socket x Fipt
N
L
M M1
Part Number Size L M M1 N Approx. Wt. (Lbs.)
4235-007 3/4 2 1-13/32 1-3/8 5/16 .23
4235-010 1 2-3/16 1-3/4 1-11/16 11/32 .25
4235-012 1-1/4 2-3/8 2-3/32 2-1/16 11/32 .36
4235-015 1-1/2 2-9/16 2-3/8 2-7/16 11/32 .47
4235-020 2 2-25/32 2-27/32 3-3/16 7/16 1.05
Not intended to convey or dispense water for human consumption through drinking or cooking
GROOVED COUPLING ADAPTER
Groove x Socket
N
L
PIPEO.D.M1
Part Number Size L M1 N Approx. Wt. (Lbs.)
4233-012 1-1/4 3-5/8 2-3/32 2-11/32 .72
4233-015 1-1/2 3-3/4 2-11/32 2-11/32 .83
4233-020 2 3-27/32 2-27/32 2-11/32 1.27
4233-025 2-1/2 4-3/16 3-15/32 2-7/16 2.02
4233-030 3 4-5/16 4-1/8 1-7/16 2.76
PR14000070
F19001679RECEIVED
04/02/2019 lwalker
BUILDING DIVISION
HANGERS AND SEISMIC BRACING
PR14000070
F19001679RECEIVED
04/02/2019 lwalker
BUILDING DIVISION
Pipe ClampsAll dimensions in charts and on drawings are in inches. Dimensions shown in parentheses are in millimeters unless otherwise specified.
Pipe Clamps
34
Fig. 24 - Hanger for CPVC Plastic Pipe & IPS Steel Pipe**
Double Fastener Strap Side Mounted (Cooper B-Line B3183)
Size Range:3/4" (20mm)thru 2" (50mm)CPVC pipe
Material:Pre-Galvanized Steel
Function:Intended to perform as a hanger to support CPVC piping used in
automatic fire sprinkler systems. Can be installed on the top or on the bottom
of a beam.
Approvals:Underwriters Laboratories Listed in the USA (UL)and
Canada (cUL)to support fire sprinkler piping. May be installed in wood using
fasteners supplied with product, or into minimum 20 gauge (0.912mm)steel
using (2) 1/4" x 1" tek type screws. Meets and exceeds the requirements of
NFPA 13, 13R and 13D.
Features:Fig. 24 incorporates features which protect the pipe and
ease installation. The flared edge design protects the CPVC pipe from
any rough surface. Easily attaches to the building structure using the
two UL Listed hex head self threading screws* furnished with the
product. It is recommended that rechargeable electric drills fitted with
a hex socket attachment be used as installation tools. No impact
tools (such as a hammer) are allowed. Damage has been known to
result from installations using impact type tools. No pre-drilling of a
pilot hole in wood is required.
Finish:Pre-Galvanized
Order By:Figure number and pipe size
*Hardened hex head self threading screw is furnished with the
product and is the minimum fastener size acceptable.
** With reduced spacing, consult factory.
C
A
B
B
CPVC Max. Hanger Fastener Hex Approx.
Pipe Size A B C Spacing Head Size Wt./100
Part No.in. (mm) in. (mm) in. (mm) in. (mm) Ft. (m) in. (mm) Lbs. (kg)
24-3/4 3/4"(20)25/16"(58.7)15/32"(27.8)13/16"(30.2)51/2 (1.67)5/16"(7.9)9 (4.1)
24-1 1"(25)25/8"(66.7)15/16"(33.3)13/16"(30.2)6 (1.83)5/16"(7.9)9 (4.1)
24-11/4 11/4"(32)3"(76.2)11/2"(38.1)13/16"(30.2)61/2 (1.98)5/16"(7.9)11 (5.0)
24-11/2 11/2"(40)31/4"(82.5)15/8"(42.3)13/16"(30.2)7 (2.13)5/16"(7.9)12 (5.4)
24-2 2"(50)311/16"(93.7)127/32"(43.6)13/16"(30.2)8 (2.44)5/16"(7.9)15 (6.8)
Fig. 25 - Surge Restrainer
Size Range:— One size fits 3/4"(20mm)thru 2"(40mm)pipe.
Material:— Pre-Galvanized Steel
Function:— Designed to be used in conjunction with Fig. 200 band
hangers
to restrict the upward movement of piping as it occurs during sprinkler
head activation or earthquake type activity. The surge restrainer is
easily and efficiently installed by snapping into a locking position on
the band hanger. This product is intended to satisfy the requirements
as indicated in the National Fire Protection Association NFPA 13, 2010
edition, 9.2.3.4.4.1 and 9.2.3.4.4.4 Can be used to restrain either steel
pipe or CPVC plastic Pipe.
Approvals:— Underwriters Laboratories Listed only when used with
band hanger Fig. 200, in the USA (UL)and Canada (cUL).
Finish:Pre-Galvanized
Order By:Figure number and band hanger, size from
3/4"(20mm)thru 2"(40mm).
Patent #5,344,108
PR14000070
F19001679RECEIVED
04/02/2019 lwalker
BUILDING DIVISION
Pipe ClampsAll dimensions in charts and on drawings are in inches. Dimensions shown in parentheses are in millimeters unless otherwise specified.
Pipe Clamps
Fig. 28 - “Stand-Off” Hanger & Restrainer for CPVC Plastic Pipe & IPS Steel Pipe **
Size Range:— 3/4"(20mm)through 2"(50mm)
Material:— Steel, Pre-Galvanized
Function:— Designed to be used as a hanger and restrainer for CPVC piping where
the "stand-off" design will ease installation by eliminating the need for wood blocking.
Features:
• Flared edge design protects CPVC pipe from any rough or abrasive surfaces.
• Unique twist and lock design holds pipe firmly in place and allows retrofit type of installation.
• The "Stand-Off" design eliminates the need for wood block extension.
• Can be installed on horizontal or vertical piping regardless of mounting surface orientation.
• Attaches easily to wood structure with two hex head self-threading screws furnished with
product.
• Installs easily using rechargeable electrical driver with
5/16"(7.9mm)extension socket
eliminating impact tool damage to pipe.
• Attaches easily to steel, minimum 18 gauge (1.024mm)with (2) 1/4" x 1" tek type self drilling
tapping screws.
• UL Listed as a hanger and a restrainer for fire sprinkler piping.
Approvals:— Underwriters Laboratory Listed in the USA (UL)and Canada (cUL)to
support automatic fire sprinkler systems. May be installed into wood using fasteners
supplied with product, or into minimum 18 gauge steel using (2) 1/4" x 1" tek type
screws. Meets and exceeds the requirements of NFPA 13, 13R and 13D. Fig. 28 satisfies
the UL vertical restraint requirement where needed. UL Listed as a hanger and vertical
restraint when installed on 3/8"(9.5mm)composite wood material. Use two Fig. 27B Speed
Nuts when used as a hanger and restraint. Use one Fig. 27B Speed Nut on the upper
installed screw when used as a hanger only.
Order by:— Figure number and pipe size.
Pat. # 7,455,268, Pat. # 7,832,248
** With reduced spacing, consult factory.
C
A
B
Pipe Size A B C Max Hanger Approx.
Spacing Wt./100
Part No.in. (mm) in. (mm) in. (mm) in. (mm) Ft. (m) lbs. (kg)
28-3/4 3/4"(20)31/32"(77.0)2"(50.8)31/2"(88.9)51/2 (1.67)18 (8.1)
28-1 1"(25)35/16"(84.1)23/16"(55.6)31/2"(88.9)6 (1.83)21 (9.5)
28-11/4 11/4"(32)35/8"(92.1)23/8"(60.3)31/2"(88.9)61/2 (1.98)23 (10.4)
28-11/2 11/2"(40)4"(101.6)21/2"(63.5)31/2"(88.9)7 (2.13)31 (14.0)
28-2 2"(50)41/2"(114.3)211/16"(68.3)35/8"(92.1)8 (2.44)34 (15.4)
Hanger Application Hanger and Restraint
Application
Fig. 27B
(2)RequiredFig. 27B
(1)Required High
Side of Hanger
Application
36
PR14000070
F19001679RECEIVED
04/02/2019 lwalker
BUILDING DIVISION
Pipe ClampsPipe Clamps
All dimensions in charts and on drawings are in inches. Dimensions shown in parentheses are in millimeters unless otherwise specified.
Fig. 28M - Offset Hanger & Restrainer for CPVC Plastic Pipe and IPS Steel Pipe **
Size Range:3/4"(20mm)thru 2"(32mm)
Material:Steel, Pre-Galvanized
Function:Designed to be used as a hanger and restrainer for CPVC piping or steel piping
where the “stand-off” design will ease installation by eliminating the need for wood blocking.
Features:
• Flared edge design protects CPVC pipe from any rough or abrasive surfaces
•Unique snap-on design holds pipe firmly in place and allows retrofit type of installation
•The “Stand-Off” design eliminates the need for wood block extension
•Can be installed on horizontal or vertical piping regardless of mounting surface orientation
•Attaches easily to wood structure with two hex head self-threading screws furnished with
product
•Installs easily using rechargeable electrical driver with 5/16”(7.9mm)extension socket
eliminating impact tool damage to pipe
•Attaches easily to steel, minimum 18 gauge (1.024mm)with (2) 1/4” x 1” tek type self
drilling
tapping screws
•cULus Listed as a hanger and a restrainer for fire sprinkler piping
Installation Note:When installed in wood structural members and threads from the
#10 x 1" screws are exposed, use Fig. 27B speed nut to secure
Approvals:Underwriters Laboratory Listed in the USA (UL)and Canada (cUL)
to support automatic fire sprinkler systems.
May be installed into wood using fasteners screws.
Meets and exceeds the requirements of NFPA 13,
13R and 13D. Fig. 28M satisfies the UL vertical
restraint requirements where needed.
Order By:Figure number and pipe size
Patent #7,744,042
** With reduced spacing, consult factory.
C
A
B
Pipe Size A Hole Dia. B C Max Spacing* Approx. Wt./100
Part No.in. (mm) in. (mm) in. (mm) in. (mm) in. (mm) lbs. (kg)
28M-3/4 3/4"(20)2"(50.8)3/16"(4.8)35/16"(84.1)5’-6”(1676)9 (4.1)
28M-1 1"(25)21/8"(54.0)3/16"(4.8)31/2"(88.9)6’-0”(1829)12 (5.4)
28M-11/4 11/4"(32)25/16"(58.7)3/16"(4.8)31/2"(88.9)6’-6”(1981)13 (5.9)
28M-11/2 11/2"(49)27/16"(61.9)3/16"(4.8)37/8"(98.4)7’-0”(2133)14 (6.3)
28M-2 2"(50)25/8"(66.7)3/16"(4.8)47/16"(112.7)8’-0”(2438)15 (6.8)
* Required per NFPA 13 for CPVC plastic pipe
Hanger and Restraint
Application
Restraint
Restraint
Detail A
Hanger Application
Fig. 27B
(2)Required
Fig. 27B
(1)Required
High Side of Hanger
37
PR14000070
F19001679RECEIVED
04/02/2019 lwalker
BUILDING DIVISION
HYDRAULIC CALCULATIONS
PR14000070
F19001679RECEIVED
04/02/2019 lwalker
BUILDING DIVISION
Hydraulic Overview Job Number: LIB2019-01
Report Description: Residential
Node Flow(gpm)Hose Flow(gpm)Static(psi)Residual(psi)Name
100 500.00 50.000 20.000Water Supply
Identifier Pressure(psi)K-Factor(K)Flow(gpm)
Job
System
Supplies Check Point Gauges
LIB2019-01 Justin Lees
Limelite SP Lot 5
16214 114th Avenue SE
Renton, WA 98055
253-677-0563
Limelite SP Lot 5
City of Renton
Bedroom
Job Name:
Address 1
Address 2
Design Engineer
Phone FAX
State Certification/License Number
AHJ
Job Site/Building
Most Demanding Sprinkler Data
Coverage Per Sprinkler
Total Demand
Area of Application
Hose Streams
Number Of Sprinklers Calculated
Pressure Result
Job Number
26.47 @ 40.625
Water Supply at Node 100 (500.00, 0.00, 50.000, 20.000)
0.050gpm/ft²
4.9 K-Factor 12.96 at 7.000
256.00ft²
163.00ft² (Actual 163.85ft²)
0.00
2
Density
+9.244 (18.5%)
Address 3
System Pressure Demand System Flow Demand
40.625 26.47
© M.E.P.CAD, Inc.Page 1
PR14000070
F19001679RECEIVED
04/02/2019 lwalker
BUILDING DIVISION
Hydraulic Summary Report Description: Residential
Job Number: LIB2019-01
Node Flow(gpm)
Total Hose Streams
0.00
Safety MarginRequiredAvailable
Node
Hose Flow Static Residual Flow Total Demand
(gpm) (psi)(psi) (gpm) (psi)(gpm)(psi)(psi)@@Name
100 49.869 40.625 9.244500.0020.00050.000 26.47Water Supply
Design EngineerJob Number
Total Water Required (Including Hose Allowance)
26.47
Maximum Pressure Unbalance In Loops
0.000
Additional Hose Supplies
0.00
Hose Allowance At Source
Supplies
24.20gal
Residential
0.050gpm/ft²
256.00ft²
163.00ft² (Actual 163.85ft²)
2
Occupancy
Area of Application
Coverage Per SprinklerNumber Of Sprinklers Calculated
Density
Job Suffix
Volume capacity of Dry PipesVolume capacity of Wet Pipes
4.93 between nodes 100 and 99
Maximum Velocity Under Ground
8.92 between nodes 99 and 103
Maximum Velocity Above Ground
4.9 K-Factor 12.96 at 7.000
Most Demanding Sprinkler Data
System
BedroomRenton, WA 98055
Job Site/Building
City of Renton16214 114th Avenue SE
AHJ
Limelite SP Lot 5
Job
State Certification/License NumberJob Name:
Justin LeesLIB2019-01
Contractor
Contractor NumberLIBPLUMB
Name of Contractor:
Liberty Plumbing
Address 1
26116 112th Street East
Address 2
Buckley, WA 98321
Contact Name Contact Title
ExtensionPhone
253-677-0563
FAX
E-mail
justin@libplumb.com
Web-Site
Justin Lees
Address 3
Address 1
Address 2
Drawing Name
Limelite SP Lot 5
System Flow Demand
26.47
Remote Area(s)
Address 3
© M.E.P.CAD, Inc.Page 2AutoSPRINK® 12 v12.0.61.0
PR14000070
F19001679RECEIVED
04/02/2019 lwalker
BUILDING DIVISION
Device (gpm)
Actual Flow Minimum Flow
(gpm)(K)
K-Factor
(psi)
Pressure
Summary Of Outflowing Devices Report Description: Residential
Job Number: LIB2019-01
Sprinkler 101 12.96 12.80 4.9 7.000
Sprinkler 102 13.51 12.80 4.9 7.597
Most Demanding Sprinkler Data
© M.E.P.CAD, Inc.Page 3AutoSPRINK® 12 v12.0.61.0
PR14000070
F19001679RECEIVED
04/02/2019 lwalker
BUILDING DIVISION
FittingsNodeElevation(Foot)Pressure(psi) Discharge(gpm)
Node Analysis
Report Description: Residential
Job Number: LIB2019-01
100 -3'-0 S 40.625 26.47
101 19'-6 Spr(-7.000)7.000 12.96
102 19'-6 Spr(-7.597)7.597 13.51
99 3'-0 BFP(-5.717)30.763
© M.E.P.CAD, Inc.Page 4AutoSPRINK® 12 v12.0.61.0
PR14000070
F19001679RECEIVED
04/02/2019 lwalker
BUILDING DIVISION
Pipe Type Diameter Flow Velocity Friction Loss Length Pressure
Downstream Elevation Discharge K-Factor Pt Pn Fittings Eq. Length Summary
Upstream Total Length
HWC
Hydraulic Analysis Job Number: LIB2019-01
Report Description: Residential
• • • • • Route 1 • • • • •
Pf
Pe
Pv
BL 1.1010 12.96 4.37 0.030510 10'-6 0.778
101 19'-6 12.96 4.9 7.000 15'-0 -0.217
103 20'-0 7.561 25'-6
150 Sprinkler,
2E(7'-0), Tr(1'-0)
Pf
Pe
Pv
BL 1.1010 26.47 8.92 0.114276 48'-6 15.832
103 20'-0 13.51 7.561 40'-0 7.370
99 3'-0 30.763 88'-6
150
Flow (q) from Route 2
2T(5'-0), 2Tr(1'-0), 4E(7'-0),
BFP(-5.717)
Pf
Pe
Pv
UG 1.4810 26.47 4.93 0.026969 81'-0¼7.252
99 3'-0 30.763 2'-6 2.610
100 -3'-0 40.625 83'-6¼
150
E(2'-6), WMV(-5.000), S
26.47
0.00 Hose Allowance At Source
100
• • • • • Route 2 • • • • •
Pf
Pe
Pv
BL 1.1010 13.51 4.55 0.032910 0'-6 0.181
102 19'-6 13.51 4.9 7.597 5'-0 -0.217
103 20'-0 7.561 5'-6
150 Sprinkler,
T(5'-0)
1.51
4.87 )(150
1.33
140
1.16
130
0.713
100
Equivalent Pipe Lengths of Valves and Fittings (C=120 only)
Actual Inside Diameter
Schedule 40 Steel Pipe Inside Diameter = Factor
C Value Multiplier
Value Of C
Multiplying Factor
© M.E.P.CAD, Inc.Page 5AutoSPRINK® 12 v12.0.61.0
PR14000070
F19001679RECEIVED
04/02/2019 lwalker
BUILDING DIVISION
Pipe Type Diameter Flow Velocity Friction Loss Length Pressure
Downstream Elevation Discharge K-Factor Pt Pn Fittings Eq. Length Summary
Upstream Total Length
HWC
Hydraulic Analysis Job Number: LIB2019-01
Report Description: Residential
Pipe Type Legend
AO Arm-Over
BL Branch Line
CM Cross Main
DN Drain
DR Drop
DY Dynamic
FM Feed Main
FR Feed Riser
MS Miscellaneous
OR Outrigger
RN Riser Nipple
SP Sprig
ST Stand Pipe
UG Underground
Units Legend
Diameter Inch
Elevation Foot
Flow gpm
Discharge gpm
Velocity fps
Pressure psi
Length Foot
Friction Loss psi/Foot
HWC Hazen-Williams Constant
Pt Total pressure at a point in a pipe
Pn Normal pressure at a point in a pipe
Pf Pressure loss due to friction between points
Pe Pressure due to elevation difference between indicated points
Pv Velocity pressure at a point in a pipe
Fittings Legend
ALV Alarm Valve
AngV Angle Valve
b Bushing
BalV Ball Valve
BFP Backflow Preventer
BV Butterfly Valve
C Cross Flow Turn 90°
cplg Coupling
Cr Cross Run
CV Check Valve
DelV Deluge Valve
DPV Dry Pipe Valve
E 90° Elbow
EE 45° Elbow
Ee1 11¼° Elbow
Ee2 22½° Elbow
f Flow Device
fd Flex Drop
FDC Fire Department Connection
fE 90° FireLock(TM) Elbow
fEE 45° FireLock(TM) Elbow
flg Flange
FN Floating Node
fT FireLock(TM) Tee
g Gauge
GloV Globe Valve
GV Gate Valve
Ho Hose
Hose Hose
HV Hose Valve
Hyd Hydrant
LtE Long Turn Elbow
mecT Mechanical Tee
Noz Nozzle
P1 Pump In
P2 Pump Out
PIV Post Indicating Valve
PO Pipe Outlet
PRV Pressure Reducing Valve
PrV Pressure Relief Valve
red Reducer/Adapter
S Supply
sCV Swing Check Valve
Spr Sprinkler
St Strainer
T Tee Flow Turn 90°
Tr Tee Run
U Union
WirF Wirsbo
WMV Water Meter Valve
Z Cap
© M.E.P.CAD, Inc.Page 6AutoSPRINK® 12 v12.0.61.0
PR14000070
F19001679RECEIVED
04/02/2019 lwalker
BUILDING DIVISION