HomeMy WebLinkAboutP_Construction-Drawings_T-Mobile_SE03411A_Shurgard-Mercer_LDC_v2_20230106TITLE SHEET T-1.0 APPROVED BY SIGNATURE CONSTRUCTION MANAGER PROJECT MANAGER DATE SITE ACQUISITION CONSTRUCTION MANAGER DOCUMENT REVIEW SIGN OFF PROJECT CONTACT LIST PROJECT INFORMATION ZONING CLASSIFICATION: CODE INFORMATION: CA (COMMERCIAL ARTERIAL) BUILDING CODE:IBC 2018 CONSTRUCTION TYPE:V-B OCCUPANCY:U-2 JURISDICTION:CITY OF RENTON, WA PROPOSED BUILDING USE:UNMANNED TELECOM LATITUDE: SITE LOCATION (NAD83): 47° 32' 01.60"N LONGITUDE:122° 11' 38.00"W TOP OF STRUCTURE:147.10'± AMSL BASE OF STRUCTURE:58.00'± AMSL N/A PROJECT LEASE AREA: 334330-1125 PARCEL NUMBER: 2.78 ACRES AREA OF PARCEL: 0 SF NEW IMPERVIOUS AREA: 1.PARKING REQUIREMENTS ARE UNCHANGED. 2.TRAFFIC IS UNAFFECTED. 3.SIGNAGE IS UNAFFECTED. GENERAL INFORMATION: ZONING 89.1' AGL 0.0' AGL PUBLIC STORAGE CONTACT: LORI KIND 701 WESTERN AVE GLENDALE, CA 91201 PROPERTY OWNER: (47.533778° N) (122.193889° W) REVIEWERS SHALL CLEARLY PLACE INITIALS ADJACENT TO EACH REDLINE NOTE AS DRAWINGS ARE BEING REVIEWED FROM T-MOBILE BOTHELL OFFICE: ·DEPART SOUTH ON N CREEK PKWY ·TURN RIGHT ONTO NE 195TH ST ·TAKE RAMP LEFT FOR I-405 S ·KEEP LEFT TO STAY ON I-405 S ·AT EXIT 7, TAKE RAMP RIGHT AND FOLLOW SIGNS FOR NE 44TH ST ·TURN LEFT ONTO NE 44TH ST ·TURN LEFT ONTO LAKE WASHINGTON BLVD NE ·TURN RIGHT ·TURN LEFT ·DESTINATION WILL BE ON THE RIGHT DRIVING DIRECTIONS VICINITY MAP NOT TO SCALE GENERAL LOCATION MAP NOT TO SCALE PROJECTPROJECT APPROVED BY DEVELOPMENT MANAGER RF ENGINEER DATE SIGNATURE REGULATORY OPERATIONS MANAGER APPLICANT: 1755 NE 48TH ST RENTON, WA 98056 SE03411A SHURGARD MERCER SOUTH SITE NUMBER: SITE NAME: SITE LOCATION: CROWN CASTLE BU #: 827896 47° 32' 01.60"N 122° 11' 38.00"W (47.533778° N) (122.193889° W) LAT: LONG: THE INFORMATION CONTAINED IN THIS SET OF CONSTRUCTION DOCUMENTS IS PROPRIETARY BY NATURE. ANY USE OR DISCLOSURE OTHER THAN THAT WHICH RELATES TO T-MOBILE USA, INC. SERVICES IS STRICTLY PROHIBITED. PROPRIETARY INFORMATION HILLMANS LK WN GARDEN OF EDEN #3 LOT 2 OF KC SHORT PLAT #485069 REC #8612231555 SD SP DAF - POR OF SW 1/4 OF SE 1/4 STR 29-24-05 BEG AT NW COR OF TR 182 SD HILLMANS ADD TH S 00-56-18 W 635.24 FT ALG W LN SD TR TH S 88-47-17 E 329.29 FT PLW N LN TH N 00-56-18 E 635.24 FT ALG E LN TO NE COR SD TR TH N88-47-17 W 329.29 FT TO POB PLat Block: Plat Lot: 182 LEGAL DESCRIPTION UTILITY COMPANIES PUGET SOUND ENERGY PHONE: (888) 225-5773 POWER: DO NOT SCALE DRAWINGS. CONTRACTOR MUST VERIFY ALL DIMENSIONS AND ADVISE CONSULTANTS OF ANY ERRORS AND OMISSIONS. ALL PREVIOUS ISSUES OF THIS DRAWINGS ARE SUPERSEDED BY THE LATEST REVISION. LDC TAKES NO RESPONSIBILITY FOR ADEQUACY OF TOWER MOUNTS FOR EXISTING OR PROPOSED LOADING. CONTRACTOR AND MOUNT MANUFACTURER TAKE FULL RESPONSIBILITY FOR MOUNTING PRODUCTS USED & THEIR ADEQUACY. MOUNTS SHOWN IN DRAWINGS ARE FOR ILLUSTRATIVE PURPOSES ONLY. DISCLAIMERS PROJECT DESCRIPTION T-MOBILE PROPOSES TO MODIFY AN EXISTING UNMANNED TELECOMMUNICATIONS FACILITY WITH THE ADDITION OF (1) 48kW DIESEL GENERATOR W/ TANK VENT & SPILL PREVENTION KIT ON CONCRETE PAD WITHIN EXISTING CMU COMPOUND. PROJECT CONSULTANT: LDC, INC. CONTACT: RICHARD B. HALL, AIA PHONE: (425) 806-1869 EMAIL: rhall@ldccorp.com PROJECT ARCHITECT: LDC, INC. 20210 142ND AVE NE WOODINVILLE, WA 98072 TBD FIBER: CROWN CASTLE USA, INC 1505 WESTLAKE AVE N, SUITE 800 SEATTLE, WA 98109 TOWER OWNER: PROJECT MANAGER: T-MOBILE USA, INC. CONTACT: MARK UNDERDOWN EMAIL: mark.underdown@t-mobile.com CONSTRUCTION MANAGER: LDC, INC. CONTACT: WALT DARBY PHONE: (425) 279-3533 EMAIL: wdarby@ldccorp.com LDC, INC. CONTACT: RICQUEL CARDOZA PHONE: (206) 713-1626 EMAIL: ricquelc@ldccorp.com SITE ACQUISITION: T-MOBILE USA, INC. 19807 NORTH CREEK PKWY N BOTHELL, WA 98011 PHONE: (425) 641-1140 DRAWING INDEX DWG. NO.DESCRIPTION T-1.0 TITLE SHEET G-1.0 GENERAL NOTES A-1.0 SITE PLAN A-2.0 EXISTING SITE PLAN A-2.1 PROPOSED SITE PLAN A-3.0 WEST ELEVATIONS A-4.0 CONSTRUCTION DETAILS A-4.1 CONSTRUCTION DETAILS S-1.0 STRUCTURAL NOTES & SPECIAL INSPECTIONS S-2.0 STRUCTURAL DETAILS M-1.0 DIESEL GENERATOR SPECIFICATIONS M-2.0 DIESEL GENERATOR SPECIFICATIONS M-3.0 DIESEL GENERATOR SPECIFICATIONS E-1.0 ELECTRICAL SITE PLAN E-2.0 SCHEMATIC GROUNDING PLAN E-3.0 GROUNDING DETAILS SHEET NUMBER SUBMITTALS DATE: DRAWN BY: CHECKED BY: SITE DESCRIPTION BYDATE SHEET TITLE REV SE03411A SHURGARD MERCER SOUTH 1755 NE 48TH ST RENTON, WA 98056 1-14-21 AAL RBH 1 1-14-21 PRELIMINARY ZONING AAL 2 3-12-21 RPZD: COMMENTS AAL 3 9-30-21 PRELIMINARY CONSTRUCTION PPK 4 10-18-21 FINAL CONSTRUCTION PPK 5 6-23-22 RFCD: UPDATED LAYOUT TNB 6 10-28-22 RFCD: UPDATED LAYOUT GA 7 1-6-23 RFCD: UPDATED LAYOUT TNB APPROVAL STAMP www.LDCcorp.com 20210 142nd Avenue NEWoodinville, WA 98072 F 425.482.2893T 425.806.1869 Surveying Engineering Planning Woodinville 1851 Central Pl S, #101Kent, WA 98030 Kent RICHARD B. HALLSTATE OF WASHINGTON 8828 REGISTERED ARCHITECT GENERAL NOTES G-1.0 1.THE PROPOSED INSTALLATION WILL BE UNMANNED AND DOES NOT REQUIRE POTABLE WATER OR SEWER SERVICE. 2.THE PROPOSED INSTALLATION IS UNMANNED AND IS NOT FOR HUMAN HABITATION (NO HANDICAP ACCESS IS REQUIRED) 3.OCCUPANCY IS LIMITED TO PERIODIC MAINTENANCE AND INSPECTION, APPROXIMATELY 2 TIMES PER MONTH, BY T-MOBILE TECHNICIANS. 4.NO NOISE, SMOKE, DUST OR ODOR WILL RESULT FROM THIS PROPOSAL. 5.OUTDOOR STORAGE AND SOLID WASTE CONTAINERS ARE NOT PROPOSED. 6.ALL REFERENCES TO SPECIFIC STANDARDS FOR THIS PROPOSAL ARE UNDERSTOOD TO BE THE LATEST VERSION. 7.THE TENDERED MUST UNDERGO A SITE VISIT TO CAREFULLY EXAMINE AND UNDERSTAND THE SCOPE OF THE WORK REQUIRED BEFORE BID SUBMISSION. NO COMPENSATION IN ANY FORM WILL BE PAID FOR EXPENSES RESULTING FROM FAILURE TO DO SO. 8.IF THE SPECIFIED EQUIPMENT CAN NOT BE INSTALLED AS SHOWN ON THESE DRAWINGS, THE CONTRACTOR SHALL PROPOSE AN ALTERNATIVE INSTALLATION FOR APPROVAL BY THE CONSTRUCTION MANAGER. 9.CONTRACTOR IS RESPONSIBLE FOR FIELD MEASUREMENTS TO CONFIRM LENGTHS OF CABLE TRAYS, ELECTRICAL LINES, AND ANTENNA CABLES. 10.ROUTING OF ALL CONDUITS, CABLES, CABLE TRAYS, ETC. IS INDICATED AT PROPOSED LOCATIONS ONLY. CONFIRM THE EXACT ROUTING WITH THE ON-SITE CONSTRUCTION MANAGER PRIOR TO THE START OF WORK. 11.ALL DAMAGE OR OPENING UP OF THE EXISTING STRUCTURE MUST BE MADE GOOD TO THE PRE-CONSTRUCTION CONDITION OR BETTER. 12.INSPECTION OF COMPLETED WORK IS REQUIRED BEFORE COVERING UP. PROVIDE A MINIMUM OF 72 HOURS NOTICE TO CONSULTANT. 13.REMOVE AND CLEAN UP ANY DEBRIS OR MATERIAL FROM THE SITE THROUGHOUT THE DURATION OF THE CONTRACT ON A DAILY BASIS AND UPON COMPLETION OF THE WORK AS DIRECTED BY THE CONSTRUCTION MANAGER. 14.OBTAIN AND PAY FOR ALL ELECTRICAL PERMITS AND INSPECTIONS REQUIRED FOR COMPLETION OF WORK AND ACCEPTANCE. PROVIDED CERTIFICATES TO THE CONSTRUCTION MANAGER VERIFYING THAT THE WORK CONFORMS TO THE REQUIREMENTS OF ALL CODES AND AUTHORITIES HAVING JURISDICTION. 15.PROVIDE T-MOBILE WITH A WRITTEN WARRANTY, EFFECTIVE FOR ONE YEAR AFTER DATE OF ACCEPTANCE. FOR THE COMPLETE INSTALLATION REPAIR OR REPLACE ANY DEFECTS ARISING DURING THIS PERIOD AT NO EXTRA COST TO T-MOBILE. 16.NO DEVIATIONS FROM DESIGN SHOWN ON THESE DRAWINGS IS ALLOWED WITHOUT WRITTEN APPROVAL FROM THE CONSULTANT. FAILURE TO OBSERVE THIS RULE MAY RESULT IN CONTRACTOR CORRECTING THE INSTALLATION AT THEIR EXPENSE. 17.THE CONTRACTOR SHALL COMPLY WITH ALL LOCAL AND NATIONAL CODES, REGULATIONS AND SAFETY REGULATIONS, ALL OSHA REGULATIONS, ALL PUBLIC AND MUNICIPAL AUTHORITIES, AND ANY UTILITY COMPANIES' REGULATIONS AND DIRECTIVES. 18.THE DRAWINGS AND SPECIFICATIONS ARE A GENERAL DIRECTIVE FOR THE SCOPE OF WORK. EXACT DIMENSIONS AND LOCATIONS MAY CHANGE IN THE FIELD. THE CONTRACTOR IS TO VERIFY THE DIMENSIONS AND LOCATIONS AND REPORT ANY AND ALL DISCREPANCIES TO REPRESENTATIVE. ANY MINOR ERRORS AND OMISSIONS IN THE DRAWINGS AND SPECIFICATIONS DO NOT EXCUSE THE CONTRACTOR FROM COMPLETING THE PROJECT AND IMPROVEMENTS IN ACCORDANCE WITH THE INTENT OF THESE DOCUMENTS. GENERAL NOTES:ABBREVIATIONS: AFF ABOVE FINISHED FLOOR AFG ABOVE FINISHED GRADE AFS ABOVE FINISHED SLAB ALUM ALUMINUM AB ANCHOR BOLT ∠ANGLE ARCH ARCHITECTURAL BTS BASE TRANSMISSION SYSTEM BLDG BUILDING BM BEAM BOT BOTTOM B.O.BOTTOM OF BOC BOTTOM OF CONCRETE BOS BOTTOM OF STEEL CJ CONTROL JOINT ℄CENTER LINE CLG CEILING CLR CLEAR CMU CONCRETE MASONRY UNIT COL COLUMN CONC CONCRETE CONST CONSTRUCTION CONT CONTINUOUS CTR CENTER DIA / Ø DIAMETER DTL DETAIL (E)EXISTING EA EACH EJ EXPANSION JOINT ELEC ELECTRIC/ELECTRICAL EL ELEVATION EQ EQUAL EW EACH WAY EXP EXPANSION EXT EXTERIOR FD FLOOR DRAIN FHFB FLEXI RRH 4-PIPE 1900 FIN FINISH FIN FLR FINISH FLOOR FLR FLOOR FSMF FLEXI MULTIRADIO SYSTEM MODULE FTG FOOTING GA GAUGE GALV GALVANIZED GYP GYPSUM GB GYPSUM BOARD HM HOLLOW METAL HOR HORIZONTAL HR HOUR HT HEIGHT HVAC HEATING VENTILATION AIR CONDITIONING INSUL INSULATION INT INTERIOR JT JOINT LAM LAMINATED LF LINEAL FOOT MANUF MANUFACTURER MAX MAXIMUM MECH MECHANICAL MH MANHOLE MM MILLIMETER MIN MINIMUM MISC MISCELLANEOUS MPH MILES PER HOUR MTL METAL NIC NOT IN CONTRACT NOM NOMINAL NTS NOT TO SCALE OC ON CENTER OD OUTSIDE DIAMETER OH OVERHEAD OPNG OPENING OPP OPPOSITE PCS PERSONAL COMMUNICATION SYSTEM ⅊PLATE PR PAIR PSI POUNDS PER SQUARE INCH PSF POUNDS PER SQUARE FOOT PT PRESSURE TREATED RAD RADIUS RD ROOF DRAIN REINF REINFORCED/REINFORCING REQ'D REQUIRED RM ROOM R/W RIGHT OF WAY SCHED SCHEDULE SECT SECTION SF SQUARE FOOT SIM SIMILAR SQ FT SQUARE FOOT SS STAINLESS STEEL STD STANDARD STL STEEL STRUC STRUCTURAL TEMP TEMPORARY THK THICK TMA TOWER MOUNTED ANTENNA T.O.TOP OF TOS TOP OF STEEL TOC TOP OF CONCRETE TYP TYPICAL UNO UNLESS NOTED OTHERWISE VERT VERTICAL W/WITH WWM WELDED WIRE MESH LEGEND AND SYMBOLS: CHAIN LINK FENCE CEDAR FENCE POWER UNDERGROUND POWER TELCO UNDERGROUND TELCO OVERHEAD POWER BOUNDARY CENTERLINE REVISION CLOUD REVISION BUG ELEVATION DETAIL NUMBER SHEET NUMBER SECTION CUT X X-X SHEET NUMBER SECTION NUMBER ELEVATION 0.0' AGL # SHEET NUMBER SUBMITTALS DATE: DRAWN BY: CHECKED BY: SITE DESCRIPTION BYDATE SHEET TITLE REV SE03411A SHURGARD MERCER SOUTH 1755 NE 48TH ST RENTON, WA 98056 1-14-21 AAL RBH 1 1-14-21 PRELIMINARY ZONING AAL 2 3-12-21 RPZD: COMMENTS AAL 3 9-30-21 PRELIMINARY CONSTRUCTION PPK 4 10-18-21 FINAL CONSTRUCTION PPK 5 6-23-22 RFCD: UPDATED LAYOUT TNB 6 10-28-22 RFCD: UPDATED LAYOUT GA 7 1-6-23 RFCD: UPDATED LAYOUT TNB APPROVAL STAMP www.LDCcorp.com 20210 142nd Avenue NEWoodinville, WA 98072 F 425.482.2893T 425.806.1869 Surveying Engineering Planning Woodinville 1851 Central Pl S, #101Kent, WA 98030 Kent RICHARD B. HALLSTATE OF WASHINGTON 8828 REGISTERED ARCHITECT PROPERTY LINES AND STRUCTURES HAVE BEEN DIGITIZED FROM PREVIOUS PLAN SETS OR FROM ASSESSORS MAPS. LDC HAS NOT COMPLETED A SITE SURVEY AND THEREFORE MAKES NO CLAIM AS TO THE ACCURACY OF INFORMATION DEPICTED ON THIS SHEET. 1SITE PLAN 22"x34" SCALE: 1" = 30'11"x17" SCALE: 1" = 60' SITE PLAN A-1.0 PROPOSED T-MOBILE 48KW DIESEL GENERATOR W/ TANK VENT ON EXISTING CONCRETE PAD WITHIN EXISTING CMU COMPOUND EXISTING T-MOBILE EQUIPMENT PAD WITHIN AN EXISTING CMU COMPOUND EXISTING 89.1' MONOPOLE ZONING: CA (COMMERCIAL ARTERIAL) ADJACENT ZONING: CA (COMMERCIAL ARTERIAL) ADJACENT ZONING: CA (COMMERCIAL ARTERIAL) ADJACENT ZONING: CA (COMMERCIAL ARTERIAL) ADJACENT ZONING: CA (COMMERCIAL ARTERIAL) EXISTING SITE ACCESS 1 A-2.1 9'-0" GENERATORSETBACK34'-0" GENERATOR SETBACK SHEET NUMBER SUBMITTALS DATE: DRAWN BY: CHECKED BY: SITE DESCRIPTION BYDATE SHEET TITLE REV SE03411A SHURGARD MERCER SOUTH 1755 NE 48TH ST RENTON, WA 98056 1-14-21 AAL RBH 1 1-14-21 PRELIMINARY ZONING AAL 2 3-12-21 RPZD: COMMENTS AAL 3 9-30-21 PRELIMINARY CONSTRUCTION PPK 4 10-18-21 FINAL CONSTRUCTION PPK 5 6-23-22 RFCD: UPDATED LAYOUT TNB 6 10-28-22 RFCD: UPDATED LAYOUT GA 7 1-6-23 RFCD: UPDATED LAYOUT TNB APPROVAL STAMP www.LDCcorp.com 20210 142nd Avenue NEWoodinville, WA 98072 F 425.482.2893T 425.806.1869 Surveying Engineering Planning Woodinville 1851 Central Pl S, #101Kent, WA 98030 Kent RICHARD B. HALLSTATE OF WASHINGTON 8828 REGISTERED ARCHITECT CONSTRUCTION PLAN KEYED NOTES EXISTING T-MOBILE 200A INTERSECT PANEL (ATS, GEN PLUG, DISCONNECT, DISTRIBUTION, TVSS - TO RECEIVE GENERATOR FEEDERS). EXISTING T-MOBILE ZAYO CABINET (TO REMAIN). EXISTING 6'-0" HIGH CMU WALL (TO REMAIN). EXISTING T-MOBILE ICE BRIDGE (TO BE REMOVED). EXISTING T-MOBILE J BOX (TO BE REMOVED). EXISTING T-MOBILE GPS ANTENNA (TO BE RELOCATED). EXISTING SECTION OF 6'-0" HIGH CMU WALL (TO BE REMOVED, GC SHALL GRIND MORTAR & GROUT FROM TOP OF SLAB ). EXISTING T-MOBILE HPL3 RADIO CABINET (TO BE RELOCATED). EXISTING T-MOBILE LB3 BATTERY CABINET (TO BE RELOCATED). EXISTING ACCESS GATE (TO REMAIN). EXISTING T-MOBILE EQUIPMENT CONCRETE PAD (TO REMAIN) EXISTING 89.1' MONOPOLE (TO REMAIN) EXISTING T-MOBILE UTILITY H-FRAME (TO REMAIN). 1 2 3 4 5 6 7 8 9 12 14 18 22 1.PROPOSED IFC CHAPTER 50032.5 REQUIRED NFPA WARNING SIGN SHALL BE DISPLAYED PER DETAIL 2/M-1.0. 2.PROPOSED STATE TANK VENTS LOCATED AT UNCOVERED END OF GENERATOR TANK. 3.PROPOSED SPILL CONTAINMENT SYSTEM (ORDERED BY T-MOBILE PROCUREMENT AND PROVIDED BY MANUFACTURER). SITE NOTES EXISTING SITE PLAN A-2.01 EXISTING SITE PLAN 22"x34" SCALE: 1/2" = 1'-0"11"x17" SCALE: 1/4" = 1'-0" EXISTING BUILDING 16 8 (TO BE RELOCATED) (TO BE RELOCATED) EXISTING FIRE HYDRANT EXISTING BOLLARD 6 12 15 1 4 19'-7"1'-8"4'-0"6'-5"7'-7"2 2 22 18 5 (TO BE RELOCATED) (TO BE RELOCATED) 714 9 EXISTING OTHER CARRIER ICE-BRIDGE 15'-4" EXISTING MANHOLE 3 SHEET NUMBER SUBMITTALS DATE: DRAWN BY: CHECKED BY: SITE DESCRIPTION BYDATE SHEET TITLE REV SE03411A SHURGARD MERCER SOUTH 1755 NE 48TH ST RENTON, WA 98056 1-14-21 AAL RBH 1 1-14-21 PRELIMINARY ZONING AAL 2 3-12-21 RPZD: COMMENTS AAL 3 9-30-21 PRELIMINARY CONSTRUCTION PPK 4 10-18-21 FINAL CONSTRUCTION PPK 5 6-23-22 RFCD: UPDATED LAYOUT TNB 6 10-28-22 RFCD: UPDATED LAYOUT GA 7 1-6-23 RFCD: UPDATED LAYOUT TNB APPROVAL STAMP www.LDCcorp.com 20210 142nd Avenue NEWoodinville, WA 98072 F 425.482.2893T 425.806.1869 Surveying Engineering Planning Woodinville 1851 Central Pl S, #101Kent, WA 98030 Kent RICHARD B. HALLSTATE OF WASHINGTON 8828 REGISTERED ARCHITECT PROPOSED SITE PLAN A-2.11 PROPOSED SITE PLAN 22"x34" SCALE: 1/2" = 1'-0"11"x17" SCALE: 1/4" = 1'-0" CONSTRUCTION PLAN KEYED NOTES PROPOSED T-MOBILE 1'-3" WIDE CHAIN LINK FENCE SECTION WITH WHITE PRIVACY SLATS. PROPOSED T-MOBILE 24"x24" RAISED GALV. GRIP STRUT CONDUIT STEP-OVER BRIDGE (SUPPORTED ON (4) 1-5/8"x1-5/8" UNISTRUT POSTS W/ BASE PLATE ANCHORED TO CONCRETE SLAB W/ 3/8"Ø CONCRETE ANCHORS W/ 3" EMBEDMENT. EXISTING T-MOBILE 200A INTERSECT PANEL (ATS, GEN PLUG, DISCONNECT, DISTRIBUTION, TVSS - TO RECEIVE GENERATOR FEEDERS). PROPOSED T-MOBILE 48kW DIESEL GENERATOR W/ TANK VENT & 5 GALLON SPILL CONTAINMENT KIT ON EXISTING CONCRETE PAD. EXISTING T-MOBILE ZAYO CABINET (TO REMAIN). EXISTING T-MOBILE HCS 2.0 JUNCTION BOX (TYP. OF 3-TO BE RELOCATED TO WALL MOUNTED 1-5/8"x1-5/8" GALV. UNISTRUT W/ SAFETY END RUBBER CAPS ANCHORED DIRECT TO EXISTING CMU WALL W/ 1/2"Ø CONCRETE ANCHORS IN EPOXY TUBE). EXISTING 6'-0" HIGH CMU WALL (TO REMAIN). PROPOSED T-MOBILE (2) 1"Ø & (1) 2"Ø SCHED 40 PVC CONDUITS FOR POWER & ALARM CONTROL FROM PROPOSED GENERATOR TO PROPOSED ATS. PROPOSED T-MOBILE ICE BRIDGE (TO REPLACE EXISTING). EXISTING T-MOBILE GPS ANTENNA (TO BE RELOCATED). PROPOSED T-MOBILE 3'-0" WIDE REMOVABLE CHAIN LINK FENCE SECTION WITH PRIVACY SLATS (TYP OF 2). EXISTING T-MOBILE HPL3 RADIO CABINET (TO BE RELOCATED). EXISTING T-MOBILE LB3 BATTERY CABINET (TO BE RELOCATED). EXISTING ACCESS GATE (TO REMAIN). EXISTING T-MOBILE EQUIPMENT CONCRETE PAD (TO REMAIN) EXISTING 89.1' MONOPOLE (TO REMAIN) PROPOSED T-MOBILE LED LIGHT W/ TIME SWITCH AND AC RECEPTACLE. EXISTING T-MOBILE UTILITY H-FRAME (TO REMAIN). 1 2 3 4 5 7 8 9 10 11 13 14 16 17 18 19 21 23 1.PROPOSED IFC CHAPTER 50032.5 REQUIRED NFPA WARNING SIGN SHALL BE DISPLAYED PER DETAIL 2/M-1.0. 2.PROPOSED STATE TANK VENTS LOCATED AT UNCOVERED END OF GENERATOR TANK. 3.PROPOSED SPILL CONTAINMENT SYSTEM (ORDERED BY T-MOBILE PROCUREMENT AND PROVIDED BY MANUFACTURER). SITE NOTES 4 A-4.1 ALL M-1.0 TO ALL M-3.0 1-2 A-4.0 4-5 S-2.0 ALL E-1.0 EXISTING BUILDING 1 810 1'-4"2'-7" 15'-4"19'-7"3'-0"(RELOCATED) 2 EXISTING FIRE HYDRANT EXISTING BOLLARD EXISTING MANHOLE 18 (RELOCATED) 13 3'-0"2'-6"2'-6"17 11 21 8" 8" 8" 5 (RELOCATED)1'-3"0'-4" 714 4 4'-3"2'-11"4'-3"4"3'-0"6"4'-3"19 (RELOCATED) 9 29'-0"EXISTING OTHER CARRIER ICE-BRIDGE 16 23 4'-8"4"1'-3"4"3'-0"3 2'-0"SHEET NUMBER SUBMITTALS DATE: DRAWN BY: CHECKED BY: SITE DESCRIPTION BYDATE SHEET TITLE REV SE03411A SHURGARD MERCER SOUTH 1755 NE 48TH ST RENTON, WA 98056 1-14-21 AAL RBH 1 1-14-21 PRELIMINARY ZONING AAL 2 3-12-21 RPZD: COMMENTS AAL 3 9-30-21 PRELIMINARY CONSTRUCTION PPK 4 10-18-21 FINAL CONSTRUCTION PPK 5 6-23-22 RFCD: UPDATED LAYOUT TNB 6 10-28-22 RFCD: UPDATED LAYOUT GA 7 1-6-23 RFCD: UPDATED LAYOUT TNB APPROVAL STAMP www.LDCcorp.com 20210 142nd Avenue NEWoodinville, WA 98072 F 425.482.2893T 425.806.1869 Surveying Engineering Planning Woodinville 1851 Central Pl S, #101Kent, WA 98030 Kent RICHARD B. HALLSTATE OF WASHINGTON 8828 REGISTERED ARCHITECT WEST ELEVATIONS A-3.02 122"x34" SCALE: 3/8" = 1'-0"11"x17" SCALE: 3/16" = 1'-0" PROPOSED WEST ELEVATION (LOOKING EAST) EXISTING WEST ELEVATION (LOOKING EAST ) CONSTRUCTION PLAN KEYED NOTES PROPOSED T-MOBILE 1'-3" WIDE CHAIN LINK FENCE SECTION WITH WHITE PRIVACY SLATS. PROPOSED T-MOBILE 48kW DIESEL GENERATOR W/ TANK VENT & 5 GALLON SPILL CONTAINMENT KIT ON EXISTING CONCRETE PAD. EXISTING T-MOBILE HCS 2.0 JUNCTION BOX (TYP. OF 3-TO BE RELOCATED TO WALL MOUNTED 1-5/8"x1-5/8" GALV. UNISTRUT W/ SAFETY END RUBBER CAPS ANCHORED DIRECT TO EXISTING CMU WALL W/ 1/2"Ø CONCRETE ANCHORS IN EPOXY TUBE). EXISTING 6'-0" HIGH CMU WALL (TO REMAIN). EXISTING T-MOBILE ICE BRIDGE (TO BE REMOVED). PROPOSED T-MOBILE ICE BRIDGE (TO REPLACE EXISTING). EXISTING T-MOBILE GPS ANTENNA (TO BE RELOCATED). EXISTING SECTION OF 6'-0" HIGH CMU WALL (TO BE REMOVED, GC SHALL GRIND MORTAR & GROUT FROM TOP OF SLAB ). PROPOSED T-MOBILE 3'-0" WIDE REMOVABLE CHAIN LINK FENCE SECTION WITH PRIVACY SLATS (TYP OF 2). EXISTING ACCESS GATE (TO REMAIN). EXISTING 89.1' MONOPOLE (TO REMAIN)1 2 3 6 8 10 11 16 19 22 23 1.PROPOSED IFC CHAPTER 50032.5 REQUIRED NFPA WARNING SIGN SHALL BE DISPLAYED PER DETAIL 2/M-1.0. 2.PROPOSED STATE TANK VENTS LOCATED AT UNCOVERED END OF GENERATOR TANK. 3.PROPOSED SPILL CONTAINMENT SYSTEM (ORDERED BY T-MOBILE PROCUREMENT AND PROVIDED BY MANUFACTURER). SITE NOTES 4 A-4.1 ALL M-1.0 TO ALL M-3.0 1-2 A-4.0 4-5 S-2.0 22"x34" SCALE: 3/8" = 1'-0"11"x17" SCALE: 3/16" = 1'-0" EXISTING STORAGE BUILDING (TO REMAIN) 1 6 3 11 12'-0" MAX FROM CONCRETE PADTO TOP OF TANK VENTSPROPOSED (1) 2" TANK VENT PIPE (BEYOND) & (2) 3" EMERGENCY VENT PIPES SHEET NUMBER SUBMITTALS DATE: DRAWN BY: CHECKED BY: SITE DESCRIPTION BYDATE SHEET TITLE REV SE03411A SHURGARD MERCER SOUTH 1755 NE 48TH ST RENTON, WA 98056 1-14-21 AAL RBH 1 1-14-21 PRELIMINARY ZONING AAL 2 3-12-21 RPZD: COMMENTS AAL 3 9-30-21 PRELIMINARY CONSTRUCTION PPK 4 10-18-21 FINAL CONSTRUCTION PPK 5 6-23-22 RFCD: UPDATED LAYOUT TNB 6 10-28-22 RFCD: UPDATED LAYOUT GA 7 1-6-23 RFCD: UPDATED LAYOUT TNB APPROVAL STAMP www.LDCcorp.com 20210 142nd Avenue NEWoodinville, WA 98072 F 425.482.2893T 425.806.1869 Surveying Engineering Planning Woodinville 1851 Central Pl S, #101Kent, WA 98030 Kent RICHARD B. HALLSTATE OF WASHINGTON 8828 REGISTERED ARCHITECT 8 8 (TO BE RELOCATED) (RELOCATED) EXISTING STORAGE BUILDING (TO REMAIN) 19 PROPOSED 3" EMERGENCY VENT PIPES (2 TOTAL) EXISTING OTHER CARRIER ICE-BRIDGE 22 1 3 2 10 23 EXISTING OTHER CARRIER ICE-BRIDGE 2 8"x8"x3/8" ICE BRIDGE SUPPORT BASE SHOE, SEE PLATE DETAIL FOR ANCHORS. TRAPEZE COAX CABLE SUPPORTS @ 4'-0" o/c. 8'-0" CLEAR BENEATH LOWEST CABLE SUPPORT 12" WIDE HOT DIP GALVANIZED GRIP STRUT ICE-BRIDGE KIT (SITE PRO PART # IB12B-Z) 3-1/2" GALV STD PIPE FOR ICE BRIDGE SUPPORT WITH END CAP. MIN (2) PER GRIP STRUT CHANNEL MOUNTING BRACKET ASSEMBLY 10'-0" MIN BELOW ICE BRIDGE (TYP)8'-0" (MAX) NOTE 1.#2 SOLID TINNED GROUND WIRE TO BE CADWELDED FROM EACH SUPPORT COLUMN TO GROUND RING 2.STAGGER ICE-BRIDGE POST AT 8'-0" O.C. (SEE ENLARGED SITE PLAN)8"8" GUSSET TO BASE PLATE PLATE DETAIL 22"X34" SCALE: 1 1/2" = 1'-0" PIPE TO BASE PLATE 1 1/2" TYP 3/8" GALV BASE PLATE 3 1/2" O.D. GALV STD STEEL PIPE 1 1/2" SQ.X3/8" GUSSET PLATE (4)-SIDES 1 1/2" TYP 1/4 (4)5/8"Ø A193 GRADE B6 ANCHOR RODS & SIMPSON STRONG-TIE SET-XP ADHESIVE W/ 5"MIN. EMBEDMENT 1/4 CONSTRUCTION DETAILS A-4.0 SHEET NUMBER SUBMITTALS DATE: DRAWN BY: CHECKED BY: SITE DESCRIPTION BYDATE SHEET TITLE REV SE03411A SHURGARD MERCER SOUTH 1755 NE 48TH ST RENTON, WA 98056 1-14-21 AAL RBH 1 1-14-21 PRELIMINARY ZONING AAL 2 3-12-21 RPZD: COMMENTS AAL 3 9-30-21 PRELIMINARY CONSTRUCTION PPK 4 10-18-21 FINAL CONSTRUCTION PPK 5 6-23-22 RFCD: UPDATED LAYOUT TNB 6 10-28-22 RFCD: UPDATED LAYOUT GA 7 1-6-23 RFCD: UPDATED LAYOUT TNB APPROVAL STAMP www.LDCcorp.com 20210 142nd Avenue NEWoodinville, WA 98072 F 425.482.2893T 425.806.1869 Surveying Engineering Planning Woodinville 1851 Central Pl S, #101Kent, WA 98030 Kent RICHARD B. HALLSTATE OF WASHINGTON 8828 REGISTERED ARCHITECT NOT USED 522"x34" SCALE: N.T.S.11"x17" SCALE: N.T.S.4FILL SPILL CONTAINMENT SPECIFICATIONS 1ICE BRIDGE DETAIL ON CONCRETE PAD 22"x34" SCALE: 1:16_XREF 11"x17" SCALE: 3/8" = 1'-0" NOT USED 32ICE BRDGE SUPPORT PLATE DETAIL 22"x34" SCALE: 1 1/2" = 1'-0"11"x17" SCALE: 3/4" = 1'-0" 1.ALL ITEMS TO CONFORM TO ASTM F1083 FOR FENCING, ASTM F900 FOR GATES, ASTM A392-89 FOR FENCE FABRIC AND ASTM A121-86 FOR BARBED WIRE. 2.ALL PIPE TO BE SCHEDULE 40 UNLESS NOTED OTHERWISE. 3.ALL ITEMS TO BE GALVANIZED PER ASTM F1083. 4.HOG RINGS AND WIRE FASTENERS TO BE SPACED NO MORE THAN 20" OC HORIZONTALLY AT 12" OC VERTICALLY. 5.BOTTOM TENSION WIRE TO BE NO MORE THAN 4" ABOVE GRADE. 6.PROVIDE STRETCHER BAR AND TENSION BANDS AT ALL GATES, GATE POSTS AND CORNER POSTS. 7.PROVIDE 1.75" INSIDE DIAMETER, 17 GAGE GALVANIZED TUBE FOR TOP RAIL SPLICE WHERE REQUIRED. 8.PROVIDE TURNBUCKLE OR TIGHTENER AT ALL TRUSS RODS AND TENSION WIRES. 9.A FROST FREE GATE LATCH WITH CHAIN AND PADLOCK MAY BE USED INSTEAD OF A DROP ROD UPON APPROVAL FROM THE C.M. CORNER POSTS:2.875" OD GATE POSTS:2.875" OD LINE POSTS:2.875" OD GATE FRAME:1.66" OD DROP ROD:1.375" OD BRACE RAIL:1.66" OD TOP RAIL:1.66" OD TRUSS ROD:3/8" DIA TENSION WIRE:7 GAUGE WIRE FASTENERS:11 GAUGE HOG RINGS:9 GAUGE CHAIN LINK FABRIC:9 GAUGE, 2" MESH BARBED SUPPORT:1/4" BAR OR 12 GAUGE FOLD PAINT NOTE:6'-0"HOG RINGS TENSION WIRE CHAIN LINK FABRIC EXTENDED DOWN TO CRUSHED ROCK BASE TENSION BAR CORNER POST TOP RAIL GATE POST GATE FRAME LOCKING PIN WIRE FASTENERS HORIZONTAL BRACE RAIL TRUSS ROD LINE POST CHAIN LINK FENCE FABRIC & METAL PRIVACY SLATS SHALL BE POWDER COATED & PAINTED WHITE. CHAIN LINK W/ WHITE VINYL COATING & WHITE PRIVACY SLATS EXISTING CONCRETE PAD CONSTRUCTION DETAILS A-4.1 SHEET NUMBER SUBMITTALS DATE: DRAWN BY: CHECKED BY: SITE DESCRIPTION BYDATE SHEET TITLE REV SE03411A SHURGARD MERCER SOUTH 1755 NE 48TH ST RENTON, WA 98056 1-14-21 AAL RBH 1 1-14-21 PRELIMINARY ZONING AAL 2 3-12-21 RPZD: COMMENTS AAL 3 9-30-21 PRELIMINARY CONSTRUCTION PPK 4 10-18-21 FINAL CONSTRUCTION PPK 5 6-23-22 RFCD: UPDATED LAYOUT TNB 6 10-28-22 RFCD: UPDATED LAYOUT GA 7 1-6-23 RFCD: UPDATED LAYOUT TNB APPROVAL STAMP www.LDCcorp.com 20210 142nd Avenue NEWoodinville, WA 98072 F 425.482.2893T 425.806.1869 Surveying Engineering Planning Woodinville 1851 Central Pl S, #101Kent, WA 98030 Kent RICHARD B. HALLSTATE OF WASHINGTON 8828 REGISTERED ARCHITECT NOT USED 1 NOT USED 3NOT USED 2 22"x34" SCALE: N.T.S.11"x17" SCALE: N.T.S.4FILL SPILL CONTAINMENT SPECIFICATIONS PROPOSED GENERATOR ANCHORAGE NOTES & SPECIAL INSPECTIONS (APPLICABLE FOR ANCHORAGE TO PROPOSED SLABS) 1.GENERAL 1.1.ALL CONSTRUCTION SHALL CONFORM TO THE 2018 INTERNATIONAL BUILDING CODE. REFERENCE TO OTHER STANDARDS OR CODES SHALL MEAN THE LATEST STANDARD OR CODE ADOPTED & PUBLISHED. 1.2.DRAWINGS SHOW TYPICAL & CERTAIN SPECIFIC CONDITIONS ONLY. FOR DETAILS NOT SPECIFICALLY SHOWN, PROVIDE DETAILS SIMILAR TO THOSE SHOWN. 1.3.EXISTING STRUCTURES & UNDERGROUND UTILITIES/STRUCTURES ARE ON DRAWINGS FOR CLARITY ONLY. VERIFY ALL EXISTING CONDITIONS, DIMENSIONS & ELEVATIONS BEFORE STARTING WORK. NOTIFY STRUCTURAL ENGINEER IN WRITING OF ANY INTERFERENCE AND/OR DISCREPANCIES THAT MIGHT EXIST. 1.4.THE DESIGN, ADEQUACY, AND SAFETY OF ERECTION BRACING, SHORING TEMPORARY SUPPORTS, ETC., IS THE SOLE RESPONSIBILITY OF THE CONTRACTOR. 1.5.COORDINATE STRUCTURAL CONTRACT DOCUMENTS WITH ARCHITECTURAL, MECHANICAL, ELECTRICAL, PLUMBING & CIVIL. NOTIFY STRUCTURAL ENGINEER OF ANY CONFLICT AND/OR OMISSION. 1.6.COORDINATE & VERIFY FLOOR, ROOF AND WALL OPENING SIZES & LOCATIONS WITH ARCHITECTURAL, MECHANICAL, PLUMBING & ELECTRICAL DRAWINGS. FOR ADDITIONAL OPENINGS NOT SHOWN ON THE STRUCTURAL DRAWINGS, SEE ARCHITECTURAL & MECHANICAL DRAWINGS. 1.7.FOR DIMENSIONS NOT SHOWN, SEE ARCHITECTURAL DRAWINGS. 1.8.REVIEW OF SUBMITTALS AND/OR SHOP DRAWINGS BY THE STRUCTURAL ENGINEER DOES NOT RELIEVE THE CONTRACTOR OF THE RESPONSIBILITY TO REVIEW & CHECK SHOP DRAWINGS BEFORE SUBMITTAL TO THE STRUCTURAL ENGINEER. THE CONTRACTOR REMAINS SOLELY RESPONSIBLE FOR ERRORS & OMISSIONS ASSOCIATED WITH THE PREPARATION OF SHOP DRAWINGS AS THEY PERTAIN TO MEMBER SIZES, DETAILS, & DIMENSIONS SPECIFIED IN THE CONTRACT DOCUMENTS. CONTRACTOR IS ALSO RESPONSIBLE FOR MEANS, METHODS, TECHNIQUES, SEQUENCES, AND PROCEDURES OF CONSTRUCTION. 1.9.STRUCTURAL DESIGN DRAWINGS SHALL NOT BE REPRODUCED AS SHOP DRAWINGS. CONTRACTOR & THEIR SUBCONTRACTORS SHALL PREPARE ORIGINAL SHOP DRAWINGS. 1.10.CONTRACTOR SHALL REVIEW & STAMP ALL SHOP DRAWINGS BEFORE SUBMITTAL FOR REVIEW. PROPOSED FABRICATION CHANGES FROM DESIGN DRAWINGS SHALL BE NOTED IN SHOP DRAWINGS. ANY DISCREPANCIES BETWEEN ARCHITECTURAL & STRUCTURAL DRAWINGS SHALL BE NOTED TO BE VERIFIED ON SHOP DRAWINGS. 1.11.COMPLETE SHOP DRAWINGS FOR CONSTRUCTION OF ALL APPLICABLE SPECIALTY ITEMS INCLUDING CURTAIN WALL GLAZING SYSTEMS, LIGHT GAUGE STEEL FRAMING, ORNAMENTAL GUARDRAILS, SKYLIGHTS, METAL GRATING & STAIRS SHALL BE SEALED & SIGNED BY A PROFESSIONAL ENGINEER LICENSED IN THE STATE OF WASHINGTON & SHALL BE AVAILABLE AT THE JOB SITE DURING THE TIMES OF INSPECTION. 1.12.FOR SITE-SPECIFIC LOAD PARAMETERS, SEE THE GENERATOR ANCHORAGE REPORT. 2.FOUNDATIONS & SLAB ON GRADE 2.1.WHERE FOOTING STEPS ARE NECESSARY, THEY SHALL BE NO STEEPER THAN ONE VERTICAL TO TWO HORIZONTAL. 2.2.COMPACT ALL FILL USED UNDER SLAB TO 95% OF STANDARD PROCTOR DENSITY AT OPTIMUM MOISTURE CONTENT. 2.3.ESTABLISH BENCH MARKS ON SURROUNDING STRUCTURES & PAVEMENTS PRIOR TO EXCAVATION, MONITOR VERTICAL & HORIZONTAL REGULARLY DURING EXCAVATION & CONSTRUCTION & SUBMIT WRITTEN REPORTS TO ARCHITECT & STRUCTURAL ENGINEER FOR REVIEW. 2.4.CONTRACTOR SHALL BE RESPONSIBLE FOR MAINTAINING SAFETY IN CONNECTION WITH EARTH SLOPES CAUSED BY TRENCHING, EXCAVATION AND/OR FILL DURING CONSTRUCTION. 2.5.BOTTOM OF ALL FOUNDATIONS SHALL EXTEND A MINIMUM OF 12 INCHES BELOW THE TOP OF FINISH GRADE. 3.REINFORCED CONCRETE 3.1.ALL CONCRETE WORK SHALL CONFORM TO ACI 301, SPECIFICATIONS FOR STRUCTURAL CONCRETE FOR BUILDINGS. DESIGN IS BASED ON ACI 318-14, BUILDING CODE REQUIREMENTS FOR REINFORCED CONCRETE 3.2.UNLESS NOTED OTHERWISE, ALL CONCRETE SHALL BE NORMAL WEIGHT & SHALL HAVE MINIMUM 28 DAY STRENGTHS AS FOLLOWS: 3.3.THE PROPOSED MATERIALS & MIX DESIGN SHALL BE FULLY DOCUMENTED & REVIEWED BY THE OWNER'S TESTING LABORATORY. RESPONSIBILITY FOR OBTAINING THE REQUIRED DESIGN STRENGTH IS THE CONTRACTOR'S. 3.4.USE OF CALCIUM CHLORIDE, CHLORIDE IONS, OR OTHER SALTS IN CONCRETE IS NOT PERMITTED. 3.5.HORIZONTAL CONSTRUCTION JOINTS ARE PERMITTED ONLY WHERE INDICATED. THE LOCATIONS OF VERTICAL CONSTRUCTION JOINTS SHALL BE APPROVED BY THE STRUCTURAL ENGINEER. CONSTRUCTION JOINTS SHALL BE THOROUGHLY ROUGHENED BY MECHANICAL MEANS & CLEANED. 3.6.UNLESS NOTED OTHERWISE, CHAMFER OR ROUND ALL EXPOSED CORNERS MINIMUM 3/4". SEE ARCHITECTURAL DRAWINGS FOR CHAMFER OR REVEAL REQUIREMENTS FOR ARCHITECTURAL CONCRETE. 3.7.DETAIL CONCRETE REINFORCEMENT & ACCESSORIES IN ACCORDANCE WITH THE LATEST EDITION OF ACI 315 & ACI DETAILING MANUAL (LATEST EDITION). SUBMIT SHOP DRAWINGS FOR REVIEW SHOWING ALL FABRICATION DIMENSIONS & LOCATIONS FOR PLACING REINFORCING STEEL & ACCESSORIES. DO NOT BEGIN FABRICATION UNTIL SHOP DRAWINGS ARE COMPLETED & REVIEWED. 3.8.DETAIL ALL CONCRETE WALLS & BEAMS ON THE SHOP DRAWINGS IN ELEVATION UNLESS SPECIFICALLY APPROVED OTHERWISE. 3.9.REINFORCING STEEL SHALL CONFORM TO ASTM A615, GRADE 60 UNLESS NOTED OTHERWISE. 3.10.WELDED WIRE FABRIC (MESH) SHALL CONFORM TO ASTM A185. 3.11.TIE ALL REINFORCING STEEL & EMBEDMENTS SECURELY IN PLACE PRIOR TO PLACING CONCRETE. PROVIDE SUFFICIENT SUPPORTS TO MAINTAIN THE POSITION OF REINFORCEMENT WITHIN SPECIFIED TOLERANCES DURING ALL CONSTRUCTION ACTIVITIES. 3.12.PROVIDE CONTINUOUS REINFORCEMENT WHEREVER POSSIBLE; SPLICE ONLY AS SHOWN OR APPROVED; STAGGER SPLICES WHERE POSSIBLE; USE FULL TENSION SPLICE UNLESS NOTED OTHERWISE. 3.13.REINFORCING STEEL SHALL HAVE THE FOLLOWING CONCRETE COVER UNLESS NOTED OTHERWISE: CONCRETE AGAINST EARTH (NOT FORMED)3" FORMED CONCRETE EXPOSED TO EARTH OR WEATHER #6 THROUGH #18 BARS 2" #5 BARS & SMALLER 1-1/2" CONCRETE NOT EXPOSED TO EARTH OR WEATHER SLABS & WALLS 1" BEAMS (STIRRUPS) & COLUMNS (TIES)1-1/2" 3.14.DO NOT WELD OR TACK WELD REINFORCING STEEL UNLESS APPROVED OR DIRECTED BY THE STRUCTURAL ENGINEER. 3.15.STEEL REINFORCEMENT TO BE WELDED SHALL CONFORM TO THE REQUIREMENTS OF ASTM A706 & THAT WELDING SHALL BE IN ACCORDANCE WITH AWS D1.4, STRUCTURAL WELDING CODE - REINFORCING STEEL BY AMERICAN WELDING SOCIETY FOR COMPLIANCE WITH ACI 318-14 SECTION 3.2.5. 3.16.SEE CIVIL & ARCHITECTURAL DRAWINGS FOR EXTERIOR SLAB WORK & JOINTING. 3.17.INCLUDE AIR ENTRAINING ADMIXTURE IN ALL CONCRETE THAT WILL BE EXPOSED TO WEATHER EXCEPT IN FOOTINGS. 3.18.INCLUDE WATER REDUCING ADMIXTURE IN ALL CONCRETE MIXES. 3.19.THE PROPOSED MATERIALS & MIX DESIGN SHALL BE FULLY DOCUMENTED & REVIEWED BY THE OWNER'S TESTING LABORATORY. RESPONSIBILITY FOR OBTAINING THE REQUIRED DESIGN STRENGTH IS THE CONTRACTOR'S. RESULTS OF COMPRESSIVE STRENGTH TESTS SHALL BE AVAILABLE ON SITE FOR INSPECTOR'S REVIEW. 3.20.BARS, OTHER THAN GRADE 40, SHALL BE MILL MARKED SO THAT TYPE, GRADE & YIELD STRENGTH ARE VISIBLY IDENTIFIABLE. 3.21.PROVIDE CORNER BARS AS PER TYPICAL DETAIL AT CORNERS & INTERSECTIONS OF ALL GRADE BEAMS & WALLS. 3.22.PROVIDE #3 @ 12" DOWELS FROM ALL ADJACENT CONCRETE GRADE BEAMS & WALLS TO INTERIOR SLABS-ON-GROUND, U.N.O. 3.23.ALL REINFORCING LAP SPLICES, UNLESS OTHERWISE SHOWN, SHALL SATISFY THE FOLLOWING SCHEDULE: ALL BAR DEVELOPMENT LENGTHS, UNLESS OTHERWISE SHOWN, SHALL SATISFY THE FOLLOWING SCHEDULE: * TOP BAR SHALL BE DEFINED AS ANY HORIZONTAL BARS PLACED SUCH THAT MORE THAN 12" OF FRESH CONCRETE IS CAST IN THE MEMBER BELOW THE BAR, IN ANY SINGLE CONCRETE PLACEMENT. HORIZONTAL WALL BARS ARE CONSIDERED TOP BARS. 4.POST-INSTALLED REBAR & ANCHORS 4.1.SPECIFIC PRODUCT, DIAMETER, AND EMBEDMENT SHALL BE SHOWN IN THE DETAILS. INSTALL PRODUCTS IN ACCORDANCE WITH MANUFACTURER' PRINTED INSTALLATION INSTRUCTIONS (MPII). CONTRACTOR SHALL CONTACT MANUFACTURER'S REPRESENTATIVE FOR PRODUCT INSTALLATION TRAINING AND SHALL SUBMIT LETTER TO THE ENGINEER-OF-RECORD (EOR) INDICATING TRAINING HAS TAKEN PLACE. REFER TO THE PROJECT BUILDING CODE AND/OR EVALUATION REPORT FOR SPECIAL INSPECTIONS AND PROOF LOAD REQUIREMENTS. SUBSTITUTION REQUESTS FOR PRODUCTS OTHER THAN THOSE LISTSED BELOW MAY BE SUBMITTED BY THE CONTRACTOR TO THE EOR FOR REVIEW. SUBSTITUTIONS WILL ONLY BE CONSIDERED FOR PRODUCTS HAVING A RESEARCH REPORT RECOGNIZING THE PRODUCT FOR THE APPROPRIATE APPLICATION UNDER THE PROJECT BUILDING CODE. SUBSTITUTION REQUEST SHALL INCLUDE CALCULATIONS THAT DEMONSTRATE THE SUBSTITUTED PRODUCT IS CAPABLE OF ACHIEVING THE EQUIVALENT PERFORMANCE VALUES OF THE DESIGN BASIS PRODUCT. 4.2.FOR ANCHORING INTO CONCRETE: 4.2.a.MECHANICAL ANCHORS SHALL HAVE BEEN TESTED IN ACCORDANCE WITH ACI 355.2 AND ICC-ES AC193 FOR CRACKED CONCRETE AND SEISMIC APPLICATIONS. 4.2.b.ADHESIVE FOR REBAR AND ANCHORS SHALL HAVE BEEN TESTED IN ACCORDANCE WITH ACI355.4 AND ICC-ES AC308 FOR CRACKED CONCRETE AND SEISMIC APPLICATIONS. DESIGN ADHESIVE BOND STRENGTH HAS BEEN BASED ON ACI 355.4 TEMPERATURE CATEGORY B WITH INSTALLATIONS INTO DRY HOLES DRILLED USING A CARBIDE DRILL BIT INTO CRACKED CONCRETE THAT HAS CURED FOR AT LEAST 21 DAYS. ADHESIVE ANCHORS REQUIRING CERTIFIED INSTALLATIONS SHALL BE INSTALLED BY A CERTIFIED ADHESIVE ANCHOR INSTALLER PER ACI 318-14 17.8.2.2. INSTALLATIONS REQUIRING CERTIFIED INSTALLERS SHALL BE INSPECTED PER ACI 318-14 17.8.2.4. 5.SPECIAL INSPECTIONS 5.1.STRUCTURAL TESTS AND INSPECTIONS SHALL COMPLY WITH THE REQUIREMENTS OF THE INTERNATIONAL BUILDING CODE. 5.1.a.THE INSPECTOR SHALL BE HIRED AND PAID FOR BY THE OWNER. 5.1.b.THE INSPECTOR SHALL BE RESPONSIBLE FOR COMPLIANCE WITH THE APPROVED STRUCTURAL PLANS AND SHALL SUBMIT PROGRESS REPORTS AND INSPECTION REPORTS TO THE BUILDING OFFICIAL AND TO THE STRUCTURAL ENGINEER OF RECORD. 5.2.SATISFY MINIMUM INSPECTION AND QUALITY CONTROL REQUIREMENTS OF THE INTERNATIONAL BUILDING CODE. CONCRETE DURABILITY REQUIREMENTS PER ACI-318 FOUNDATIONS 28-DAY COMPRESSIVE STRENGTH (f'c) FREEZING/THAWING CLASS SULFATE CLASS PERMEABILITY CLASS CORROSION CLASS MAX AGGREGATE(IN) MAX W/CM RATIO TARGET AIR CONTENT(%) PROJECT SCHEDULE OF SPECIAL INSPECTIONS MATERIAL/ACTIVITY SERVICE APPLICABLE TO THIS PROJECT Y/N EXTENT AGENT DATE COMPLETED 1705.3 CONCRETE CONSTRUCTION 1. INSPECTION OF REINFORCING STEEL INSTALLATION (SEE 1705.2.2 FOR WELDING)SHOP (3) AND FIELD INSPECTION Y PERIODIC 3. INSPECTION OF ANCHORS CAST IN CONCRETE WHERE ALLOWABLE LOADS HAVE BEEN INCREASED PER SECTION 1908.5 OR WHERE STRENGTH DESIGN IS USED SHOP (3) AND FIELD INSPECTION Y PERIODIC 4. INSPECTION OF ANCHORS AND REINFORCING STEEL POST-INSTALLED IN HARDENED CONCRETE PER RESEARCH REPORTS INCLUDING VERIFICATION OF ANCHOR TYPE, ANCHOR DIMENSIONS, HOLE DIMENSIONS, HOLE CLEANING PROCEDURES, ANCHOR SPACING, EDGE DISTANCE, CONCRETE MINIMUM THICKNESS, ANCHOR EMBEDMENT, AND TIGHTENING TORQUE FIELD INSPECTION Y PERIODIC OR AS REQUIRED BY THE RESEARCH REPORT ISSUED BY AN APPROVED SOURCE 5. VERIFY USE OF APPROVED DESIGN MIX SHOP (3) AND FIELD INSPECTION Y PERIODIC 6. FRESH CONCRETE SAMPLING, PERFORM SLUMP AND AIR CONTENT TESTS AND DETERMINE TEMPERATURE OF CONCRETE SHOP (3) AND FIELD INSPECTION Y CONTINUOUS 7. INSPECTION OF CONCRETE AND SHOTCRETE PLACEMENT FOR PROPER APPLICATION TECHNIQUES SHOP (3) AND FIELD INSPECTION Y CONTINUOUS 8. INSPECTION FOR MAINTENANCE OF SPECIFIED CURING TEMPERATURE AND TECHNIQUES SHOP (3) AND FIELD INSPECTION Y PERIODIC 1705.12.1 STRUCTURAL STEEL SPECIAL INSPECTIONS FOR SEISMIC RESISTANCE 1. INSPECTION OF STRUCTURAL STEEL IN ACCORDANCE WITH AISC 341 SHOP (3) AND FIELD INSPECTION Y IN ACCORDANCE WITH AISC 341 1705 POST-INSTALLED ANCHORS 1. PREPARE A REPORT INCLUDING THE FOLLOWING DETAILS: A. ANCHOR DESCRIPTION, INCLUDING THE ANCHOR PRODUCT NAME, BOLT DIAMETER, AND ANCHOR LENGTH FIELD INSPECTION Y CONTINUOUS B. HOLE DESCRIPTION INCLUDING VERIFICATION OF DRILL BIT COMPLIANCE WITH ANSI B212.15-1994. RECORD INSTALLATION DESCRIPTION, INCLUDING VERIFICATION OF MASONRY/CONCRETE COMPRESSIVE STRENGTH, AND ANCHOR INSTALLATION AND LOCATION (SPACING AND EDGE DISTANCE) IN ACCORDANCE WITH MANUFACTURER'S PUBLISHED INSTALLATION INSTRUCTIONS FIELD INSPECTION Y CONTINUOUS CONCRETE REINFORCEMENT LAP SPLICE LENGTH (in) GRADE 60 BAR SIZE #3 #4 #5 #6 #7 #8 #9 #10 #11 TOP BAR *23 31 38 46 67 76 86 96 107 OTHER 18 24 30 35 51 59 66 74 82 CONCRETE REINFORCEMENT DEVELOPMENT LENGTH (in) GRADE 60 BAR SIZE #3 #4 #5 #6 #7 #8 #9 #10 #11 TOP BAR *18 24 30 35 51 59 66 74 82 OTHER 14 18 23 27 40 45 51 57 64 STRUCTURAL NOTES & SPECIAL INSPECTIONS S-1.022"x34" SCALE: N.T.S.11"x17" SCALE: N.T.S.1 SHEET NUMBER SUBMITTALS DATE: DRAWN BY: CHECKED BY: SITE DESCRIPTION BYDATE SHEET TITLE REV SE03411A SHURGARD MERCER SOUTH 1755 NE 48TH ST RENTON, WA 98056 1-14-21 AAL RBH 1 1-14-21 PRELIMINARY ZONING AAL 2 3-12-21 RPZD: COMMENTS AAL 3 9-30-21 PRELIMINARY CONSTRUCTION PPK 4 10-18-21 FINAL CONSTRUCTION PPK 5 6-23-22 RFCD: UPDATED LAYOUT TNB 6 10-28-22 RFCD: UPDATED LAYOUT GA APPROVAL STAMP www.LDCcorp.com 20210 142nd Avenue NEWoodinville, WA 98072 F 425.482.2893T 425.806.1869 Surveying Engineering Planning Woodinville 1851 Central Pl S, #101Kent, WA 98030 Kent RICHARD B. HALLSTATE OF WASHINGTON 8828 REGISTERED ARCHITECT 21-0304-065.1 11-17-22 GENERATOR W/ MANUFACTURER'S RECOMMENDED ANCHOR LAYOUT, MIN. (6) 5/8"Ø SS SIMPSON STRONG-TIE STRONG-BOLT 2 EXPANSION ANCHORS W/ 3-5/8" EMBEDMENT SEE ARCHITECTURAL7'-7 3/4" MAX0'-6" MINCONTRACTOR NOTE: SEE ARCHITECTURAL DRAWINGS FOR PLACEMENT. 2'-9 1/2" MIN 1'-1/2" MIN, TYP ASSUMPTIONS TO BE VERIFIED IN FIELD: 1.2,500 PSI MIN CONCRETE STRENGTH (f'c) 2.60,000 PSI MIN REBAR STRENGTH (fy) 3.0.18% MIN STEEL REINFORCEMENT MIN WITHIN SLAB 4.0'-6" MIN SLAB THICKNESS (E) CONCRETE SLAB GENERATOR W/ STATE TANK (MAX 4626#) STRUCTURAL DETAILS S-2.0 1GENERATOR ATTACHMENT DETAIL 22"x34" SCALE: 3/4" = 1'-0"11"x17" SCALE: 3/8" = 1'-0" NOT USED 4 NOT USED 3NOT USED 2 NOT USED 5 NOT USED 6 SHEET NUMBER SUBMITTALS DATE: DRAWN BY: CHECKED BY: SITE DESCRIPTION BYDATE SHEET TITLE REV SE03411A SHURGARD MERCER SOUTH 1755 NE 48TH ST RENTON, WA 98056 1-14-21 AAL RBH 1 1-14-21 PRELIMINARY ZONING AAL 2 3-12-21 RPZD: COMMENTS AAL 3 9-30-21 PRELIMINARY CONSTRUCTION PPK 4 10-18-21 FINAL CONSTRUCTION PPK 5 6-23-22 RFCD: UPDATED LAYOUT TNB 6 10-28-22 RFCD: UPDATED LAYOUT GA APPROVAL STAMP www.LDCcorp.com 20210 142nd Avenue NEWoodinville, WA 98072 F 425.482.2893T 425.806.1869 Surveying Engineering Planning Woodinville 1851 Central Pl S, #101Kent, WA 98030 Kent RICHARD B. HALLSTATE OF WASHINGTON 8828 REGISTERED ARCHITECT 21-0304-065.1 11-17-22 DIESEL GENERATOR SPECIFICATIONS M-1.022"x34" SCALE: N.T.S.11"x17" SCALE: N.T.S.1GENERATOR SPECIFICATIONS 22"x34" SCALE: N.T.S.11"x17" SCALE: N.T.S.2TANK SIGNAGE SHEET NUMBER SUBMITTALS DATE: DRAWN BY: CHECKED BY: SITE DESCRIPTION BYDATE SHEET TITLE REV SE03411A SHURGARD MERCER SOUTH 1755 NE 48TH ST RENTON, WA 98056 1-14-21 AAL RBH 1 1-14-21 PRELIMINARY ZONING AAL 2 3-12-21 RPZD: COMMENTS AAL 3 9-30-21 PRELIMINARY CONSTRUCTION PPK 4 10-18-21 FINAL CONSTRUCTION PPK 5 6-23-22 RFCD: UPDATED LAYOUT TNB 6 10-28-22 RFCD: UPDATED LAYOUT GA 7 1-6-23 RFCD: UPDATED LAYOUT TNB APPROVAL STAMP www.LDCcorp.com 20210 142nd Avenue NEWoodinville, WA 98072 F 425.482.2893T 425.806.1869 Surveying Engineering Planning Woodinville 1851 Central Pl S, #101Kent, WA 98030 Kent RICHARD B. HALLSTATE OF WASHINGTON 8828 REGISTERED ARCHITECT 1.PLACE AT DOOR OR TANK. 2.SIGNS MUST BE OF DURABLE MATERIAL WITH RED LETTERING (OR OTHERWISE SHOWN IN GRAPHICS) ON A WHITE BACKGROUND. 3.LETTERS SHALL NOT BE LESS THAN 3 INCHES (76.2 MM) IN HEIGHT AND 1/2 INCH (12.7 MM) IN STROKE. 4.SIGNS SHALL NOT BE OBSCURED OR REMOVED AND SHALL BE IN ENGLISH AS PRIMARY LANGUAGE 5.COMBUSTIBLE SIGN MAY ALSO BE WHITE LETTERS ON RED BACKGROUND. HAZARD RANGE: NINE O'CLOCK:HEALTH TWELVE O'CLOCK:FLAMMABILITY THREE O'CLOCK:INSTABILITY SIX O'CLOCK:SPECIAL REFERENCES:NFPA 704 WFC 7901.9 IFC 2703.5 NOTES 22"x34" SCALE: N.T.S.11"x17" SCALE: N.T.S.2TANK SIGNAGE 229 GALLON DIESEL PRODUCT IDENTIFICATION COMBUSTIBLE FLAMMABLE NO SMOKING NO SMOKING 012 DANGER NO OPEN FLAMES DIESEL FUEL DIESEL GENERATOR SPECIFICATIONS M-2.022"x34" SCALE: N.T.S.11"x17" SCALE: N.T.S.1GENERATOR SPECIFICATIONS SHEET NUMBER SUBMITTALS DATE: DRAWN BY: CHECKED BY: SITE DESCRIPTION BYDATE SHEET TITLE REV SE03411A SHURGARD MERCER SOUTH 1755 NE 48TH ST RENTON, WA 98056 1-14-21 AAL RBH 1 1-14-21 PRELIMINARY ZONING AAL 2 3-12-21 RPZD: COMMENTS AAL 3 9-30-21 PRELIMINARY CONSTRUCTION PPK 4 10-18-21 FINAL CONSTRUCTION PPK 5 6-23-22 RFCD: UPDATED LAYOUT TNB 6 10-28-22 RFCD: UPDATED LAYOUT GA 7 1-6-23 RFCD: UPDATED LAYOUT TNB APPROVAL STAMP www.LDCcorp.com 20210 142nd Avenue NEWoodinville, WA 98072 F 425.482.2893T 425.806.1869 Surveying Engineering Planning Woodinville 1851 Central Pl S, #101Kent, WA 98030 Kent RICHARD B. HALLSTATE OF WASHINGTON 8828 REGISTERED ARCHITECT DIESEL GENERATOR SPECIFICATIONS M-3.022"x34" SCALE: N.T.S.11"x17" SCALE: N.T.S.1GENERATOR TANK SPECIFICATIONS SHEET NUMBER SUBMITTALS DATE: DRAWN BY: CHECKED BY: SITE DESCRIPTION BYDATE SHEET TITLE REV SE03411A SHURGARD MERCER SOUTH 1755 NE 48TH ST RENTON, WA 98056 1-14-21 AAL RBH 1 1-14-21 PRELIMINARY ZONING AAL 2 3-12-21 RPZD: COMMENTS AAL 3 9-30-21 PRELIMINARY CONSTRUCTION PPK 4 10-18-21 FINAL CONSTRUCTION PPK 5 6-23-22 RFCD: UPDATED LAYOUT TNB 6 10-28-22 RFCD: UPDATED LAYOUT GA 7 1-6-23 RFCD: UPDATED LAYOUT TNB APPROVAL STAMP www.LDCcorp.com 20210 142nd Avenue NEWoodinville, WA 98072 F 425.482.2893T 425.806.1869 Surveying Engineering Planning Woodinville 1851 Central Pl S, #101Kent, WA 98030 Kent RICHARD B. HALLSTATE OF WASHINGTON 8828 REGISTERED ARCHITECT C EXISTING PANEL C M FROM EXISTING METER & DISCONNECT PROVIDE CONTROLS CONNECTION, TYP CONNECTIONS IN ATS & GENERATOR EXISTING ATS FROM EXISTING ATS TO EXISTING T-MOBILE DISTRIBUTION PANEL PROPOSED (1) 1"Ø SCHD PVC CONDUITS FOR POWER TO BLOCK HEATER AND BATTERY CHARGER PROPOSED (1) 1"Ø SCHD PVC CONDUIT FOR ALARM CONTROLS PROPOSED OUTPUT BREAKER PROPOSED GENERATOR, CONNECT COMPLETE PROPOSED (1) 2"Ø SCHD PVC CONDUITS FOR POWER FROM GENERATOR TO EXISTING ATS EXISTING POWER CABINET W/ EXISTING ATS ELECTRICAL SITE PLAN E-1.0122"x34" SCALE: 1/2" = 1'-0"11"x17" SCALE: 1/4" = 1'-0" ELECTRICAL SITE PLAN 22"x34" SCALE: N.T.S.11"x17" SCALE: N.T.S.3ONE-LINE DIAGRAM 22"x34" SCALE: N.T.S.11"x17" SCALE: N.T.S.2ELECTRICAL TRENCH NOTES: 1.CONTRACTOR SHALL CALL FOR LOCATES PRIOR TO TRENCHING. 2.THE LOCATION OF UTILITY CONDUIT ROUTING SHOWN ARE APPROXIMATE. 3.COORDINATE EXACT CONDUIT ROUTING & STUB-UP LOCATIONS W/ UTILITIES & CONSTRUCTION MANAGER PRIOR TO ROUGH-IN. PROPOSED T-MOBILE 48kW DIESEL W/ TANK VENT ON EXISTING CONCRETE PAD PROPOSED (1) 2"Ø SCHD 40 PVC CONDUITS FOR POWER FROM GENERATOR TO EXISTING ATS PROPOSED (2) 1"Ø SCHD 40 PVC CONDUITS FOR ALARM CONTROLS, BATTERY CHARGER, & BLOCK HEATER FROM GENERATOR TO EXISTING 200A INTERSECT PANEL (4 PAIR, #18 AWG INDIVIDUALLY SHIELDED PAIRS) SHEET NUMBER SUBMITTALS DATE: DRAWN BY: CHECKED BY: SITE DESCRIPTION BYDATE SHEET TITLE REV SE03411A SHURGARD MERCER SOUTH 1755 NE 48TH ST RENTON, WA 98056 1-14-21 AAL RBH 1 1-14-21 PRELIMINARY ZONING AAL 2 3-12-21 RPZD: COMMENTS AAL 3 9-30-21 PRELIMINARY CONSTRUCTION PPK 4 10-18-21 FINAL CONSTRUCTION PPK 5 6-23-22 RFCD: UPDATED LAYOUT TNB 6 10-28-22 RFCD: UPDATED LAYOUT GA 7 1-6-23 RFCD: UPDATED LAYOUT TNB APPROVAL STAMP www.LDCcorp.com 20210 142nd Avenue NEWoodinville, WA 98072 F 425.482.2893T 425.806.1869 Surveying Engineering Planning Woodinville 1851 Central Pl S, #101Kent, WA 98030 Kent RICHARD B. HALLSTATE OF WASHINGTON 8828 REGISTERED ARCHITECT CONTRACTOR SHALL CALL FOR LOCATES PRIOR TO TRENCHING 2'-0" UNEXCAVATED AREA COMPACTED FILL PER UTILITY COMPANY REQUIREMENTS EXCAVATION/MAGNETIC WARNING TAPE SAND FILL (2) 1" ELECTRICAL CONDUITS MATCH EXISTING SURFACE NOTE: JURISDICTION MAY REQUIRE DIRECTIONAL BORING OF TRENCH FOR CONDUITS - CONSULT WITH JURISDICTION. (1) 2" CONDUIT1'-2"8"4"1'-6"COVEREDDEPTHEXISTING H-FRAME MOUNTED 200A INTERSECT PANEL SCHEMATIC GROUNDING PLAN E-2.0122"x34" SCALE: 1/2" = 1'-0"11"x17" SCALE: 1/4" = 1'-0" CONSTRUCTION PLAN KEYED NOTES CONNECT PROPOSED GENERATOR W/ #2 BTCW TO GROUND BAR (TYPICAL AT 2 PLACES). EXISTING GROUND BAR. EXISTING GROUND BAR TO TIE TO EXISTING EQUIPMENT GROUND RING.1 3 4 1.ALL DETAILS ARE SHOWN IN GENERAL TERMS. ACTUAL INSTALLATION AND CONSTRUCTION MAY VARY DUE TO SITE SPECIFIC CONDITIONS. 2.ANY METAL OBJECTS WITHIN 6 FEET OF THE EXTERNAL GROUND RING SHALL BE GROUNDED. 3.ALL GROUND CONNECTIONS SHALL BE CADWELD AND CLEANED THOROUGHLY THEN COVERED WITH TWO (2) COATS OF SHERWIN WILLIAMS GALVANTE PAINT B350W3 OR EQUAL. SEE 3/E-3.0 FOR TYPICAL CONNECTIONS. 4.ALL WIRES SHALL BE COPPER THHN/THWN. ALL GROUND WIRE SHALL BE GREEN INSULATED WIRE ABOVE GROUND. 3.ALL ELECTRICAL CADWELD AND MECHANICAL CONNECTIONS SHALL HAVE NON-OXIDATION COMPOUND APPLIED TO CONNECTION. 4.ALL MATERIALS AND CADWELD MOLDS, SHOTS, ETC. SHALL BE FURNISHED AND INSTALLED BY CONTRACTOR UNLESS OTHERWISE NOTED. 5.REFER TO DIVISION 16 GENERAL ELECTRIC; GENERAL ELECTRICAL PROVISION AND COMPLY WITH ALL REQUIREMENTS OF GROUNDING STANDARDS. 6.NOTIFY CONSTRUCTION MANAGER IF THERE ARE ANY DIFFICULTIES INSTALLING GROUNDING SYSTEM DUE TO SITE SOIL CONDITIONS. 7.USE PANI SCHEME FOR LOADING GROUNDS ON MGB AS DISCUSSED IN NSTD 119, 33 & 36. GENERAL GROUNDING NOTES SCHEMATIC GROUNDING PLAN GROUND BAR GROUND INSPECTION WELL COPPER GROUND ROD COMPRESSION LUG CADWELD CONNECTION SIDE SPLICE CADWELD FIELD VERIFY & TIE INTO EXISTING GROUNDING SYSTEM GENERAL LEGEND 1 3 4 SHEET NUMBER SUBMITTALS DATE: DRAWN BY: CHECKED BY: SITE DESCRIPTION BYDATE SHEET TITLE REV SE03411A SHURGARD MERCER SOUTH 1755 NE 48TH ST RENTON, WA 98056 1-14-21 AAL RBH 1 1-14-21 PRELIMINARY ZONING AAL 2 3-12-21 RPZD: COMMENTS AAL 3 9-30-21 PRELIMINARY CONSTRUCTION PPK 4 10-18-21 FINAL CONSTRUCTION PPK 5 6-23-22 RFCD: UPDATED LAYOUT TNB 6 10-28-22 RFCD: UPDATED LAYOUT GA 7 1-6-23 RFCD: UPDATED LAYOUT TNB APPROVAL STAMP www.LDCcorp.com 20210 142nd Avenue NEWoodinville, WA 98072 F 425.482.2893T 425.806.1869 Surveying Engineering Planning Woodinville 1851 Central Pl S, #101Kent, WA 98030 Kent RICHARD B. HALLSTATE OF WASHINGTON 8828 REGISTERED ARCHITECT TOP OF GRADE 30" MIM(OR FROST DEPTH)COVER 5/8" GROUND ROD METAL FRAME WITH SOLID LID ENGRAVED WITH "GROUND" ON LID OF COVER WITH 1"Ø LIFT HOLE AT CENTER OF COVER PERIMETER GROUND RING #2 BARE TINNED COPPER LOOPED IN TEST WELL GROUND WELL 12"Ø X 24" LONG CONC PIPE WITH COVER (SEE BELOW) NEW COAXIAL GROUND KITS W/LONG BARREL COMPRESSION DOUBLE LUGS, ATTACH TO GROUND BAR & INSTALL BY ANTENNA CONTRACTOR (CADWELD TYPE-GL) NEW 4"x20"x1/4 THK COPPER GROUND BAR INSTALLED BY GENERAL CONTRACTORGROUND ISOLATOR (TYP AT EACH GROUND BAR) #2 SOLID BARE TINNED COPPER WIRE CADWELD (TYPE-GL) 20" MGB OR 10" ANTENNA AGB FIELD VERIFY 4"NOTE: COAT ALL MECHANICAL CONNECTIONS W/ "NOOX" OR APPROVED EQUAL. AGGREGATE SURFACE FINISHED GRADE CONTINUOUS WARNING TAPE CONTINUOUS GROUND RING. SIZED PER GROUNDING DETAIL COMPACTED EARTH BACKFILL 6" MIN.30" OR 6"BELOW FROST DEPTHWHICHEVER IS GREATER12"6"TYPE GTTYPE VV TYPE GY TYPE VS TYPE TA TYPE VN TYPE GL TYPE PT TYPE GR TYPE VB TYPE NC TYPE SS P A N I PANI SCHEME SPECIFICATIONS: PRODUCER (P) CONNECTS TO WIRELESS EQUIPMENT CABINETS, CABLE ENTRANCE GROUND BAR (CEGB), MAIN DISTRIBUTION FRAME GROUND BAR (MDFB), AND STANDBY ENGINE GENERATOR SET FRAME AND OTHER NOISE PRODUCING EQUIPMENT. ABSORBER (A) CONNECTS TO THE EARTH ELECTRODE SYSTEM INCLUDING CENTRAL OFFICE GROUND GRID, BUILDING STRUCTURAL GROUND, METALLIC WATER PIPE SYSTEM, ANTENNA SUPPORTING STRUCTURE GROUND SYSTEM, AND ELECTRICAL SERVICE ENTRANCE GROUND. NON-ISOLATED (N) CONNECTS TO EQUIPMENT NOT IN AN ISOLATED GROUND ZONE (IGZ) SUCH AS CBN EQUIPMENT FRAME GROUNDS AND DC GROUND CONDUCTORS FOR DC POWER SYSTEMS THAT SERVE CBN OR BOTH CBN AND IBN EQUIPMENT ISOLATED (I) CONNECTS TO THE SINGLE POINT CONNECTION BAR (SPCB) FOR IBN EQUIPMENT *TWO HOLE LUG, TO BE USED W/ #2 AWG SOLID TINNED BARE CU WIRE OR STRANDED CU WIRE W/ GREEN, 600V, THHN/THWN INSULATION TO ANTENNA STRUCTURE, BUILDING RING GROUND, OR MGB COPPER GROUND BAR ON WALL, ICE BRIDGE, FLOOR OR ON ANTENNA TOWER TWO HOLE LUG, BOLTED TO GROUND BAR USING 3/8"-16X1/4" STAINLESS STEEL HEX HEAD BOLTS & HARDWARE STRANDED CU WIRE W/ GREEN, 600V, THHN/THWN INSULATION. SIZE AS SPECIFIED NOTE: *GROUND BARS AT BOTTOM OF WATER TANK SHALL USE EXOTHERMIC CONNECTION.8'-0"GROUND ROD GROUNDING ELECTRODE CONDUCTOR GROUND ROD CAD WELD FINISHED GRADE 36"GROUNDING DETAILS E-3.06GROUND WELL DETAIL 22"x34" SCALE: 1" = 1'-0"11"x17" SCALE: 1/2" = 1'-0" 1GROUND BAR DETAIL 22"x34" SCALE: 3/16" = 1'-0"11"x17" SCALE: 1/8" = 1'-0" 4GROUND RING TRENCH DETAIL 22"x34" SCALE: 2" = 1'-0"11"x17" SCALE: 1" = 1'-0" 22"x34" SCALE: N.T.S.11"x17" SCALE: N.T.S.3TYPICAL CADWELD CONNECTIONS DETAIL 5GROUND ROD DETAIL 22"x34" SCALE: 3/8" = 1'-0"11"x17" SCALE: 1/8" = 1'-0" 2GROUND BAR CONNECTION DETAIL 22"x34" SCALE: 1" = 1'-0"11"x17" SCALE: 1/2" = 1'-0" SHEET NUMBER SUBMITTALS DATE: DRAWN BY: CHECKED BY: SITE DESCRIPTION BYDATE SHEET TITLE REV SE03411A SHURGARD MERCER SOUTH 1755 NE 48TH ST RENTON, WA 98056 1-14-21 AAL RBH 1 1-14-21 PRELIMINARY ZONING AAL 2 3-12-21 RPZD: COMMENTS AAL 3 9-30-21 PRELIMINARY CONSTRUCTION PPK 4 10-18-21 FINAL CONSTRUCTION PPK 5 6-23-22 RFCD: UPDATED LAYOUT TNB 6 10-28-22 RFCD: UPDATED LAYOUT GA 7 1-6-23 RFCD: UPDATED LAYOUT TNB APPROVAL STAMP www.LDCcorp.com 20210 142nd Avenue NEWoodinville, WA 98072 F 425.482.2893T 425.806.1869 Surveying Engineering Planning Woodinville 1851 Central Pl S, #101Kent, WA 98030 Kent RICHARD B. HALLSTATE OF WASHINGTON 8828 REGISTERED ARCHITECT