FIELD REPORT
Date Project Name Project No. Report No.
11/30/2022 Renton Elementary School 16 20180398E003 073
Location Municipality AESI Project Manager AESI Field Rep
1075 Duvall Ave NE Renton Bruce Guenzler, L.E.G. Roberto Piemontese
Permit No. Client/Owner Attn Requested By
B21004604 Renton School District No. 403 Ed Thomson Contractor
Engineer/Architect General Contractor Grading Contractor Weather
CPL / Hutteball + Oremus Cornerstone/Kyle Continental Dirt Contractors/ Jerry Jr. Cloudy, 30s
THE FOLLOWING WAS NOTED:
AESI arrived on site at 10:30am at the request of the contractor to perform compaction tests on the electrical trench backfill.
When we arrived on site, we met Jason for the trench backfill.
Electrical Trench Backfill:
Upon arrival, the contractor was working on some patches along the electrical trench that needed to be backfilled. They
informed us that the trench will be mostly below a sidewalk. We performed 10 compaction tests. 8 compaction tests met
the specification requirement of at least 95% compaction and 2 compaction tests did not meet the specification
requirement. The two failing tests were on the southern access road. The contractor informed us that later in the day they
compact again the area identified. The results and locations are shown in Table 1 and Figure 1.
Test
No. Location Depth (ft) Material Proctor
DD (pcf) / Opt. W (%) DD (pcf) W (%) Compaction (%) Pass/Fail
1 See Fig1 0 Import 121.7 / 5.4 122.5 15.8 99+ Pass
2 See Fig1 0 Import 121.7 / 5.4 116.7 16.7 96 Pass
3 See Fig1 0 Import 121.7 / 5.4 115.9 16.4 95 Pass
4 See Fig1 0 Import 121.7 / 5.4 119.1 14.5 98 Pass
5 See Fig1 0 Import 121.7 / 5.4 116.9 11.0 96 Pass
6 See Fig1 0 Import 121.7 / 5.4 121.7 10.1 99+ Pass
7 See Fig1 0 Import 121.7 / 5.4 123.5 13.7 99+ Pass
8 See Fig1 0 Import 121.7 / 5.4 110.7 12.1 91 Fail
9 See Fig1 0 Import 121.7 / 5.4 112.5 11.9 92 Fail
10 See Fig1 0 Import 121.7 / 5.4 121.3 11.7 99 Pass
Table 1: Compaction test results. Electrical trench backfill. Final elevation as a reference elevation.
Figure 1: Approximate backfill for the electrical trench in yellow. Tests in red.
1 2 3 4 5 6 7 8 9 10
16
Date Project Name Project No. Report No.
11/30/2022 Renton ES 16 20180398E003 073
Page 2 of 2
FIELD REPORT
Photo 1: Electrical trench backfill progress. Patch to be backfilled. Facing North.
Photo 2: Electrical trench backfill. Facing North.