Press Alt + R to read the document text or Alt + P to download or print.
This document contains no pages.
HomeMy WebLinkAbout26 00 00-6-0 - Roundabout Lighting_SKANSKA REVIEWED-NV5Skanska USA Building
221 Yale Avenue North
Suite 400
Seattle, Washington 98109
P: (206) 726-8000
F: (206) 328-9235
Project: 4222030 Amazon SWA2 - Sub Same Day
FC
1905 Raymond Ave. Renton, WA 98054-2621
Renton, Washington 98054
Submittal #26 00 00-6.0 - Roundabout Lighting
26 00 00 - Electrical and Lighting
Distribution Summary
Distributed by Peyton Yamamoto (Skanska USA Building Inc. (WA)) on Apr 24, 2023
To Paul Tosello (Skanska USA Building Inc. (WA)), Matthew Lyons (Skanska USA Building Inc. (WA)), Kory Amsbaugh (Skanska
USA Building Inc. (WA)), Bill Parsons (Ceccanti Inc.), Mark Wilhelm (Ceccanti Inc.), Jeremy Orr (Skanska USA Building Inc.
(WA))
Message Approved
Attachments
Name Response Attachments Comments
John Karnowski (NV5)Approved 26 00 00-6-0 - Roundabout
Lighting_SKANSKA
REVIEWED-NV5.pdf
Approved per Eric Cutshall, City of Renton 4-21-
2023
Revision 0 Submittal Manager Peyton Yamamoto (Skanska USA Building Inc.
(WA))
Status Approved Date Created Mar 29, 2023
Issue Date Mar 29, 2023 Spec Section 26 00 00 - Electrical and Lighting
Responsible
Contractor
Ceccanti Inc.Received From Bill Parsons (Ceccanti Inc.)
Received Date Submit By
Final Due Date Apr 18, 2023 Lead Time
Location Type
Approvers Peyton Yamamoto (Skanska USA Building Inc. (WA)), John Karnowski (NV5), Mark Marquez (NV5), James Miller (NV5), Shane
Walker (Amazon.com Services, Inc.), Greg Wegner (Amazon.com Services, Inc.), Brian Wiese (NV5)
Ball in Court
Distribution
Description Please see the attached submittal for the lighting at the 16th and Raymond roundabout.
ADDITIONAL SUBMITTAL DETAILS
Delivered Via Priority
LEED No Tracking Number
Track for Expediting No
Skanska USA Building Page 1 of 2 Printed On: Apr 24, 2023 07:14 AM PDT
Submittal Workflow
Name Sent Date Due Date Returned Date Response Attachments
General Information
Attachments
26 00 00-6-0 - Roundabout Lighting.pdf
Bill Parsons Apr 18, 2023 Mar 29, 2023 Submitted 26 00 00-6-0 - Roundabout Lighting.pdf
Peyton Yamamoto Mar 29, 2023 Apr 18, 2023 Mar 29, 2023 For Record Only 26 00 00-6-0 - Roundabout
Lighting_SKANSKA REVIEWED.pdf
John Karnowski Mar 29, 2023 Apr 18, 2023 Apr 24, 2023 Approved 26 00 00-6-0 - Roundabout
Lighting_SKANSKA REVIEWED-
NV5.pdf (Current)
Comment Approved per Eric Cutshall, City of Renton 4-21-2023
Mark Marquez Mar 29, 2023 Apr 18, 2023 Pending
James Miller Mar 29, 2023 Apr 18, 2023 Pending
Shane Walker Mar 29, 2023 Apr 18, 2023 Pending
Greg Wegner Mar 29, 2023 Apr 18, 2023 Pending
Brian Wiese Mar 29, 2023 Apr 18, 2023 Pending
Submittal #26 00 00-6.0 - Roundabout Lighting Project: 4222030 Amazon SWA2 - Sub Same Day FC
Skanska USA Building Page 2 of 2 Printed On: Apr 24, 2023 07:14 AM PDT
MATERIAL TRANSMITTAL
To: Skanska Transmittal No.: 019
Attn: Paul Tosello Date: 3-29-23
Project: SWA2 Amazon Project No.:
Owner: Amazon Location: Renton, WA
Previous Transmittal No. (if resubmitted)
Bid
Item
Spec.
Paragraph
Number Item Description and Use Manufacturer
Dwg.
No(s).
Approval
Status
(Engineer)
1 Lighting 16th and Raymond Roundabout Various
By this submittal, the Contractor represents that he has determined and verified all field measurements, field construction criteria,
materials, catalog numbers and similar data, or will do so, and that he has checked and coordinated each Shop Drawing with the
project requirements and the Contract Documents. Deviations from the Contract Documents are noted below.
COMMENTS:
Contractor Ceccanti, Inc. Signature Brandon McDonald
(THIS SPACE FOR REVIEW ENGINEER)
To: Date:
Approval status as noted above is in accordance with the following legend:
A. No Exceptions Taken
B. Make Corrections Noted
C. Revise and Resubmit
D. Submit Specified Item By:
E. Rejected cc:
F. See attached Review Comment Sheet dated
A
John Karnowski
Approved per City of Renton
Request for Approval of Material
Contract Number
221110
FA Number SR
Date
Section / Title of Pr
Roundabout Lighting SW 16th ST and Raymond Ave SW
County
King
Contractor
Ceccanti
Subcontractor
West Coast Signal
This form shall be completed prior to submittal. If this form is not complete at time of submittal it may be returned for information that was omitted. For assistance in completing, see Instructions and Example
Project Engineer Distribution State Materials Engineer Distribution
Contractor Region Materials General File Signing Inspection
Region Operations Engineer
Fabrication Inspection
DOT Form 350-071 EF Revised 12/2012
State Materials Lab M/S 47365 Other
For WSDOT Use Only
RAM #
Bid
Item No.
Material or
Product/Type
Name and Location of Fabricator,
Manufacturer or Pit Number
Specification
Reference
PE/QPL
Code
Hdqtr./QPL
Code
2A Light Poles P&K Tubular Products – East Setauket
N.Y.
9-29.6(1)
2A Fixtures Cyclone – Terrebone Q.C. 9-29.10(1)A
2A Deco Arms Garmire – Marysville, WA 9-29.6(1)
2A Deco Bases Visco – Eugene, OR 9-29.6(1)
2A Anchor Bolts Portland Bolt – Portland, OR 9-06.6(4)
2A Service Cabinets Skyline MFG – Seattle, WA 9-29.24
2A Adaptor Plates Garmire – Marysville, WA 9-29.6(1)
Project Engineer Date State Materials Engineer Date
Acceptance Action Codes for use by Project Engineer and State Materials Laboratory
1. Acceptance Criteria: Acceptance based upon 'Satisfactory' Test Report for samples of materials to be incorporated into project.
2. Acceptance Criteria: Mfg. Cert. of Compliance for 'Acceptance' prior to use of material.
3. Acceptance Criteria: Catalog Cuts for 'Acceptance' prior to use of material. Catalog Cut Approved Yes No
4. Acceptance Criteria: Submit Shop Drawings for 'Approval' prior to fabrication of material.
5. Acceptance Criteria: Only 'Approved for Shipment', 'WSDOT Inspected' or 'Fabrication Approved Decal' material shall be used.
6. Acceptance Criteria: Submit Certificate of Materials Origin to Project Engineer Office.
7. Acceptance Criteria: Request Transmitted to State Materials Laboratory for Approval Action.
8. Source Approved: 9. Approval Withheld: Submit samples for preliminary evaluation.
10. Approval Withheld:
11. Miscellaneous Acceptance Criteria.
Remarks:
05/26/23
Submitted by The Lighting Group LLCMichelle Alexander
Job Name:
City of Renton - SW 19Th St/Lind Ave SW & SW
19Th St/Raymond Ave SW-Roundabout (aka Job
1332 Renton Amazon Signal and Lighting)
Architect: Pending Architect
Catalog Number:
RTA0X40AYBX-ALUM 40FT-RAL9005TX PRIMER-
PLUS TOP COAT-REF DWG # 18655.1
Notes:
Type:
LGNW23-96717
Submitted by The Lighting Group LLCMichelle Alexander
Job Name:
City of Renton - SW 19Th St/Lind Ave SW & SW
19Th St/Raymond Ave SW-Roundabout (aka Job
1332 Renton Amazon Signal and Lighting)
Architect: Pending Architect
Catalog Number:
CY55P1B-FGC-T3-P70-40K-240-
10KV-TBC-BK-TX-MG-CP3624
Notes:
Type:
100W
LGNW23-96717
04/26/23
Submitted by The Lighting Group LLCMichelle Alexander
Job Name:
City of Renton - SW 19Th St/Lind Ave SW & SW
19Th St/Raymond Ave SW-Roundabout (aka Job
1332 Renton Amazon Signal and Lighting)
Architect: Pending Architect
Catalog Number:
COR-PL-10-CA-A-BK70TX
Notes:
Type:
(*)
LGNW23-96717
Submitted by The Lighting Group LLCMichelle Alexander
Job Name:
City of Renton - SW 19Th St/Lind Ave SW & SW
19Th St/Raymond Ave SW-Roundabout (aka Job
1332 Renton Amazon Signal and Lighting)
Architect: Pending Architect
Catalog Number:
OCT10-CAST IRON SPLIT BASE-10-
1/8 ID" TOP ID-RAL9005TX
Notes:
Type:
LGNW23-96717
Submitted by The Lighting Group LLCMichelle Alexander
Job Name:
City of Renton - SW 19Th St/Lind Ave SW & SW
19Th St/Raymond Ave SW-Roundabout (aka Job
1332 Renton Amazon Signal and Lighting)
Architect: Pending Architect
Catalog Number:
(SET=4) 1-1/4 X 54 F1554 GR55-
GALV 14.5" BC
Notes:
Type:
SETS
LGNW23-96717
APPROVED BYAPPROVED BY DATEDATE
Bill of Material Bill of Material (Line 1)(Line 1)
QTY.QTY.SIZESIZE LEN.LEN.GRADE / DESCRIPTIONGRADE / DESCRIPTION
36 1-1/4 54 ASTM F1554 Grade 55 rod
216 1-1/4 ASTM A563 Grade DH heavy hex nut
216 1-1/4 ASTM F436 Type 1 hardened washer
NotesNotes
Meets the S1 requirement for weldability
Heavy hex nut dimensions meet ASME B18.2.2
Finish: Galvanized per ASTM F2329 and A153
Hardware is not provided assembled
Drawings are not to scale
xx
PROJECTPROJECT Renton Housing Authority
CUSTOMERCUSTOMER THE LIGHTING GROUP
Portland Bolt & Manufacturing Co.Portland Bolt & Manufacturing Co.
3441 NW Guam St.
Portland, OR 97210
[p] 800.547.6758
[f] 503.227.4634
[e] sales@portlandbolt .com
[w] www.portlandbolt.com© PORTLAND BOLT 2023© PORTLAND BOLT 2023 PAGEPAGE 1 of 4 ORDERORDER QUOTEQUOTE 173915 rev. 3 BYBY KT DATEDATE 3/28/2023
PROVIDED BY PORTLAND BOLT
Submitted by The Lighting Group LLCMichelle Alexander
Job Name:
City of Renton - SW 19Th St/Lind Ave SW & SW
19Th St/Raymond Ave SW-Roundabout (aka Job
1332 Renton Amazon Signal and Lighting)
Architect: Pending Architect
Catalog Number:
(SET=4) 1-1/4 X 54 F1554 GR55-
GALV 14.5" BC
Notes:
Type:
SETS
LGNW23-96717
APPROVED BYAPPROVED BY DATEDATE
Bill of Material Bill of Material (Line 2)(Line 2)
QTY.QTY.SIZESIZE LEN.LEN.GRADE / DESCRIPTIONGRADE / DESCRIPTION
18 1 ASTM A36 round plate
NotesNotes
Finish: Galvanized per ASTM F2329 and A153
Drawings are not to scale
xx
PROJECTPROJECT Renton Housing Authority
CUSTOMERCUSTOMER THE LIGHTING GROUP
Portland Bolt & Manufacturing Co.Portland Bolt & Manufacturing Co.
3441 NW Guam St.
Portland, OR 97210
[p] 800.547.6758
[f] 503.227.4634
[e] sales@portlandbolt .com
[w] www.portlandbolt.com© PORTLAND BOLT 2023© PORTLAND BOLT 2023 PAGEPAGE 2 of 4 ORDERORDER QUOTEQUOTE 173915 rev. 3 BYBY KT DATEDATE 3/28/2023
PROVIDED BY PORTLAND BOLT
SWA2 AMAZON
GRAYBAR for WEST COAST SIGNAL
SKYLINE ELECTRIC & MFG. CO.
SCALE DATE / DRAWN BY DRAWING NO.
N.T.S. 3-21-23 / C.S.T. 67987
1
2
3
4
5 6
FRONT SIDE
CITY OF RENTON
SKYLINE SERIES# 64380-5G
1 REQUIRED
SEE COMPONENT SCHEDULE AND CABINET SPECIFICATIONS
THE METER DOOR IS
REMOVABLE AND COMES
STANDARD HINGED ON THE LEFT.
HINGING ON THE RIGHT IS AVAILABLE AS
A NO-CHARGE OPTION
FOOTPRINT
DEADFRONT
SERVICE WIREWAY
WIRING SCHEMATIC
METER BASE
MAIN
CONTROL
LTG.
GROUND
FAULT RECEPT. NEUTRAL
GROUND
PHOTO CELL
TEST SWITCH
120/240V, SINGLE PHASE, 3 WIRE
CITY OF RENTON SERVICE CABINET
PER STANDARD PLANS 122.1, 122.2
SKYLINE SERIES# 64380-5G
COMPONENT SCHEDULE
1 METERBASE: 200 AMP, 4 JAW, MANUAL BYPASS, B-LINE U264
W/ 5TH JAW AT 9:00 POSITION
2 PANELBOARD: 120/240 VAC, 250 AMP COPPER BUS, 1 PHASE, 3 WIRE, 18 CKT, 65K AIC SERIES RATED
MAIN BREAKER: 200 AMP FRAME, 200 AMP TRIP, 2 POLE, EATON PDD22G0200TFFJ
BOLT-ON BRANCH BREAKERS, EATON TYPE BAB:
2 - 20/2 ILLUMINATION A, B
1 - 20/1 ITS
1 - 20/1 GROUND FAULT RECEPTACLE
1 - 40/1 SIGNAL
2 - 60/2 SMALL CELL BRANCH
1 - 15/1 CONTROL
3 - 20/1 SPARE
NO BREAKER SCHEDULE PROVIDED, PLEASE VERIFY PRIOR TO RELEASE
3 CONTACTOR: NEMA LIGHTING RATED, 30 AMP 4 POLE, 120 VAC COIL,
SQD 8910DPA34V02 – 1 REQUIRED
4 PHOTO ELECTRIC CELL: 1800 WATT, 120 VAC, TWIST LOCK, ALR #SST-IES-UL
MOUNTED INSIDE CABINET BEHIND WIREGLASS WINDOW
5 PHOTO-CELL BYPASS SWITCH:
SPDT, 15 AMP, RATED (UP TO) 277 VAC (FED THROUGH TERMINAL BLOCK)
6 GROUND FAULT RECEPTACLE: 20 AMP, 125 VAC, DUPLEX
CABINET:
CONSTRUCTION:
NEMA TYPE 3R, OUTDOOR PADMOUNT, 1/8” 5052-H32 ALUMINUM CONSTRUCTION, OPEN BOTTOM
FRAMED WITH 2” ANGLE, 2 SCREENED AND GASKETED VENTS, REMOVABLE EQUIPMENT
MOUNTING PAN, CABINET GROUND WITH MINIMUM BONDING WIRE TO NEUTRAL
DOORS: HEAVY-DUTY CONCEALED HINGES (LIFT-OFF TYPE),STAINLESS STEEL VAULT HANDLES WITH
ROLLER RODS THAT PROVIDE 3-POINT COMPRESSION ON CLOSED CELL NEOPRENE GASKET,
“BEST” LOCK ON LOWER DISTRIBUTION DOOR WITH CARD HOLDER,
PADLOCKABLE UPPER METER DOOR WITH POLISHED SAFETY GLASS WINDOW
DEADFRONT: HINGED AND SECURED WITH QUARTER-TURN FASTENERS
FINISH: MILL FINISH ALUMINUM
1 – REQUIRED
UL LISTED PER STANDARD #508A
“SUITABLE FOR USE AS SERVICE ENTRANCE”
SWA2 AMAZON
CITY OF RENTON
GRAYBAR P.O.# 4703630923
WEST COAST SIGNAL
3-21-23 C.S.T. S.O.# 67987
SKYLINE ELECTRIC & MFG. COMPANY
I N C O R P O R A T E D
Switchboards
Panelboards
Steel Cabinets
UL Registered
Metal Punching . . Forming . . Welding
Industrial Control Panels
3619 7TH AVENUE SOUTH
SEATTLE, WASHINGTON 98134
TELEPHONE (206) 682-4422 FAX (206) 682-0927
Garmire IronWorks, Inc.
5620-48th Drive N.E. • Marysville, WA 98270
(360) 651-1001 • Fax (360) 651-1002 • sales@garmireironworks.com
GABP1X15X15-15BCX1.25TO11.5BCX1-45DEG-HDG
TOP VIEW:
SIDE VIEW:
(NO SCALE)
8"DIAMETERCENTER HOLE
1"A36PLATE X 15" X 15" SQUARE
FIISH: HDG-HOT DIP GALVANIZED
(4) 1-1/2"BOLT HOLES AT 90-DEGREES
ON A 15" BOLT CIRCLE
(10.6" BOLT SQUARE)
(4) 1" X 8" ATR AT 90-DEGREES ON A 11-
1/2" BOLT CIRCLE