GENERAL NOTES
1. PERFORM WORK IN ACCORDANCE WITH APPLICABLE
NATIONAL AND STATE CODES AS AMENDED LOCALLY
AND ENFORCED BY THE AHJ.
2. OBTAIN AND PAY FOR PERMITS REQUIRED FOR
INSTALLATION OF WORK. ARRANGE AND SCHEDULE
REQUIRED INSPECTIONS.
3. COORDINATE WITH UTILITY COMPANIES FURNISHING
SERVICES TO PROJECT. INSTALLATION OF UTILITY
SERVICES SHALL BE IN ACCORDANCE WITH UTILITY
REQUIREMENTS. VERIFY APPLICABLE INSTALLATION
STANDARDS AND REQUIREMENTS. PROVIDE AND
SUBMIT ELECTRICAL DRAWINGS TO UTILITY FOR
APPROVAL PRIOR TO ROUGH -IN AND PRIOR TO
ORDERING EQUIPMENT.
4. DEVICE LOCATIONS ARE APPROXIMATE. COORDINATE
DEVICE LOCATIONS AND ELEVATIONS WITH
APPROPRIATE DOCUMENTS INCLUDING CASEWORK
SHOP DRAWINGS AND ARCHITECT'S INTERIOR
ELEVATIONS PRIOR TO ROUGH -IN.
5. COORDINATE ELECTRICAL WORK WITH THAT OF
OTHER TRADES. REFER TO MECHANICAL,
ARCHITECTURAL, STRUCTURAL, CIVIL, AND
LANDSCAPE DRAWINGS AND SPECIFICATIONS.
COORDINATION SHALL OCCUR PRIOR TO
FABRICATION, PURCHASE, AND INSTALLATION OF
WORK.
6. COORDINATE LOCATION OF LIGHT FIXTURES AND
CEILING -MOUNTED DEVICES WITH ARCHITECTURAL
REFLECTED CEILING PLANS AND ELEVATIONS.
7. PROVIDE RATED ENCLOSURES AROUND ALL LIGHT
FIXTURES PENETRATING RATED CEILINGS.
COORDINATE WITH ARCHITECTURAL.
8. REFER TO ARCHITECTURAL AND STRUCTURAL
DRAWINGS FOR LOCATIONS OF EXPANSION/SEISMIC
JOINTS. PROVIDE RACEWAY EXPANSION/SEISMIC
JOINTS FOR RACEWAYS CROSSING BUILDING
EXPANSION/SEISMIC JOINTS.
9. DEMOLISH EXISTING SYSTEMS AS INDICATED ON
PLANS OR AS REQUIRED FOR INSTALLATION OF NEW
WORK. MATERIAL SHALL BE REMOVED FROM SITE
AND LEGALLY DISPOSED OF OFF SITE UNLESS
OTHERWISE DIRECTED. RETURN ITEMS TO OWNER IN
EXISTING CONDITION WHEN DIRECTED BY OWNER.
10. COMPLETION OF WORK SHALL BE EXECUTED IN
ACCORDANCE WITH THE PROJECT SCHEDULE.
SCHEDULE INSTALLATION WITH OTHER TRADES TO
ENSURE PROJECT MILESTONES ARE MET.
11. DRAWINGS ARE DIAGRAMMATIC AND DO NOT SHOW
ALL COMPONENTS REQUIRED FOR A COMPLETE
INSTALLATION. PROVIDE COMPONENTS REQUIRED
FOR COMPLETE AND OPERATIONAL SYSTEMS
INCLUDING RACEWAYS, CONDUCTORS, BOXES,
SUPPORTS AND SIMILAR ITEMS.
12. BRANCH CIRCUIT HOMERUNS ARE SHOWN TO
INDICATE CIRCUIT PROPERTIES AND CONFIGURATION.
SINGLE -CIRCUIT HOMERUNS SERVED FROM THE
SAME PANELBOARD MAY BE COMBINED IN
ACCORDANCE WITH THE DIVISION 26 SPECIFICATIONS,
UNLESS INDICATED OTHERWISE. EXTEND AND
CONNECT BRANCH CIRCUIT RACEWAY AND WIRING
FROM HOMERUN TO DEVICES AND EQUIPMENT WITH
CIRCUIT NUMBERS INDICATED. CONDUCTOR
QUANTITIES AND SIZES ARE INDICATED AT
HOMERUNS ONLY. SHOW ACTUAL RACEWAY
ROUTING AND CIRCUITING ON RECORD DRAWINGS.
MINIMUM CONDUCTOR SIZE #12 AWG.
13. LIGHT FIXTURES MOUNTED IN CONTINUOUS ROWS
SHALL BE THROUGH -WIRED VIA FIXTURE INTERNAL
WIREWAYS. CIRCUITS AS INDICATED ON DRAWINGS.
FIXTURES NOT LISTED FOR THROUGH WIRING SHALL
BE WIRED VIA SEPARATE RACEWAY AND WIRING
SYSTEM EXTERNAL TO THE FIXTURES. PROVIDE
RACEWAYS, WIRING AND CONNECTIONS FOR A
COMPLETE AND OPERATIONAL SYSTEM.
14. LOCATIONS OF RACEWAY, PATHWAY AND SIMILAR
ITEMS ARE SHOWN SCHEMATICALLY. COORDINATE
INSTALLATION, INCLUDING BUT NOT LIMITED TO
CABLING, TELECOMMUNICATION PATHWAYS AND
SPACES, AND EXACT LOCATION OF HORIZONTAL AND
BACKBONE CABLING WITH LOCATIONS OF FIXED
CASEWORK AND BUILDING CONDITIONS AFFECTING
THE WORK OF THIS CONTRACT.
15. COORDINATE TELECOMMUNICATIONS WORK WITH
THAT OF OTHER TRADES. REFER TO ELECTRICAL,
MECHANICAL, ARCHITECTURAL, STRUCTURAL, CIVIL,
AND LANDSCAPE DRAWINGS AND SPECIFICATIONS.
COORDINATION SHALL OCCUR PRIOR TO
FABRICATION, PURCHASE, AND INSTALLATION OF
WORK.
16. NEW CABLING INSTALLATIONS SHALL BE CONCEALED
IN WALL, CEILINGS, AND BELOW RAISED FLOOR
SPACES UNLESS OTHERWISE NOTED ON THE
DRAWINGS. CABLING INACCESSIBLE CEILING
SPACES SHALL BE INSTALLED AS OPEN CABLING
NEAR STRUCTURES AND WALLS OR AS SPECIFICALLY
NOTED ON DRAWINGS. SEE SPECIFICATIONS FOR
SUPPORT REQUIREMENTS.
17. PROVIDE FIRESTOPPING SYSTEMS FOR CONDUIT AND
RACEWAY SYSTEMS AT PENETRATIONS, SLEEVES
AND SLOTS OF FIRE RATED CONSTRUCTION FOR
HORIZONTAL AND INTRABUILDING PATHWAYS AND
SPACES.
18. INTRABUILDING OPTICAL FIBER CABLING SHALL BE
CLEARLY AND VISIBLY IDENTIFIED IN PULLBOXES,
ENTRANCE POINTS, EACH RISER ROOM, AND 5'-0"
BEFORE ENTERING A FREE STANDING RACK UTILIZING
AN OPTICAL FIBER CABLE MARKER TAG SYSTEM.
19. CATEGORY 6/6A CABLING: MAINTAIN A MINIMUM
SPACING OF 12" FROM ELECTRICAL FEEDERS AND
BRANCH CIRCUIT WIRING AND 12" FROM AUXILIARY
SYSTEM CABLING.
20. MINIMUM SPACING FROM ELECTRICAL APPARATUS
SUCH AS MOTOR DRIVEN EQUIPMENT AND
TRANSFORMERS SHALL BE 6-0". SPACING
REQUIREMENTS SHALL APPLY TO OPEN CABLING
PATHWAYS WHERE EQUIPMENT IS LOCATED ON THE
SAME FLOOR, FLOOR ABOVE, FLOOR BELOW, OR IN
ROOMS ADJACENT TO SUCH EQUIPMENT AS THOUGH
WALLS AND FLOORS DID NOT EXIST. EXCEPTION:
BUILDING CONSTRUCTION THAT RESULTS IN
CONTINUOUS METALLIC BARRIER BETWEEN
ELECTRICAL APPARATUS AND CABLE PATHWAYS
SHALL BE CONSIDERED AS SUITABLE SEPARATION.
21. PRIOR TO STARTING TELECOMMUNICATIONS
INSTALLATION, CAREFULLY INSPECT INSTALLED
WORK OF OTHER TRADES AND VERIFY THAT SUCH
WORK IS COMPLETE TO THE POINT WHERE WORK
MAY PROPERLY COMMENCE. NOTIFY THE ARCHITECT
AND ENGINEER IN WRITING OF CONDITIONS
DETRIMENTAL TO THE PROPER AND TIMELY
COMPLETION OF THE WORK.
22. DO NOT BEGIN TELECOMMUNICATIONS INSTALLATION
UNTIL ALL UNSATISFACTORY CONDITIONS ARE
RESOLVED. BEGINNING WORK CONSTITUTES
ACCEPTANCE OF CONDITIONS AS SATISFACTORY.
23. ROUTE CATEGORY 6/6A CABLES TO THEIR ASSIGNED
CROSS -CONNECT PER THE IDENTIFICATION LABEL AT
EACH TELECOMMUNICATIONS WORKSTATION DEVICE.
TERMINATE ALL CABLES ON 48-PORT PATCH PANELS
ON RACKS UNLESS OTHERWISE NOTED.
24. THE ELECTRICAL CONTRACTOR SHALL PROVIDE ALL
CONDUIT, OUTLET BOXES, JUNCTION BOXES,
RACEWAY SYSTEMS, ETC. FOR A COMPLETE AND
OPERATIONAL PATHWAY SYSTEM FOR ALL
TELECOMMUNICATIONS SYSTEMS PER THE SCOPE OF
WORK INDICATED ON THE CONSTRUCTION DRAWINGS
AND BID SPECIFICATIONS.
25. CABLE TRAY PATHWAYS ABOVE ACCESSIBLE
CEILINGS SHALL BE PROVIDED BY THE ELECTRICAL
CONTRACTOR. CABLE TRAY PATHWAYS BELOW
RAISED FLOOR SPACES SHALL BE PROVIDED BY THE
TELECOMMUNICATIONS CONTRACTOR.
/7PERMIT RESUBMITTAL
6 CIVIL PERMIT RESPONSE
NO. REVISION
ABBREVIATIONS
A
AMPERE
AIR CONDITIONING; ALTERNATING CURRENT;
AC
ABOVE COUNTER
AF
AMP FUSE; AMP FRAME
AFC
AVAILABLE FAULT CURRENT
AFF
ABOVE FINISHED FLOOR
AG
ABOVE GRADE
AHJ
AUTHORITIES HAVING JURISDICTION
AHU
AIR HANDLING UNIT
AIC
AMPERE INTERRUPTING CURRENT
AL
ALUMINUM
ANSI
AMERICAN NATIONAL STANDARDS INSTITUTE
AS
AMP SWITCH
AT
AMP TRIP
ATM
ASYNCHRONOUS TRANSFER MODE
ATS
AUTOMATIC TRANSFER SWITCH
AV
AUDIO VISUAL
AWG
AMERICAN WIRE GAUGE
C0
O
O
SMFC
SURFACE -MOUNTED OPTICAL FIBER CABINET
0
O
IBC
INTERNATIONAL BUILDING CODE
SMR
SURFACE METAL RACEWAY
IC
INTERMEDIATE CROSS CONNECT
SONET
SYNCHRONOUS OPTICAL NETWORK
N
N
IDF
INTERMEDIATE DISTRIBUTION FRAME
SP
SERVICE PROVIDER
Q
IEEE
INSTITUTE OF ELECTRICAL AND ELECTRONIC
SPD
SURGE PROTECTIVE DEVICE
ENGINEERS
SPEC
SPECIFICATIONS
J
IG
ISOLATED GROUND
SPST
SINGLE POLE SINGLE THROW
IMC
INTERMEDIATE METALLIC CONDUIT
ST
SHUNT TRIP
ISDN
INTEGRATED SERVICES DIGITAL NETWORK
STP
SHIELDED TWISTED PAIR
SVGA
SUPER VIDEO GRAPHICS ARRAY
J
JUNCTION
SW
SWITCH
SWBD
SWITCHBOARD
K KIRK KEY
KCMIL THOUSAND CIRCULAR MILS
kVA KILOVOLT AMPERE
KVAR KILOVOLT AMPERE REACTIVE
kW KILOWATT
LAN
LOCAL AREA NETWORK
BAS
BUILDING AUTOMATION SYSTEM
LCP
LIGHTING CONTROL PANEL
BATT
BATTERIES
LEC
LOCAL EXCHANGE CARRIER
BIL
BASIC IMPULSE INSULATION LEVEL
LT
LIGHT
BKBD
BACKBOARD
LTG
LIGHTING
BKR
BREAKER
BLDG
BUILDING
M
METER
MAN
METROPOLITAN AREA NETWORK
C
CONDUIT; DEGREES CELSIUS
M
METER
CAB
CABINET
MAN
METROPOLITAN AREA NETWORK
CAT
CATEGORY
MAX
MAXIMUM
CATV
COMMUNITY ANTENNA TELEVISION
MC
MAIN CROSS CONNECT; METAL CLAD (CABLE)
CB
CIRCUIT BREAKER
MCB
MAIN CIRCUIT BREAKER
CCTV
CLOSED CIRCUIT TELEVISION
MCC
MOTOR CONTROL CENTER
CLG
CEILING
MDF
MAIN DISTRIBUTION FRAME
CM
CEILING -MOUNTED
MDP
MAIN DISTRIBUTION PANEL
CO
CONDUIT ONLY
MFR
MANUFACTURER
COW
COMPUTER ON WHEELS
MH
MANHOLE
CR
CONTROLLED RECEPTACLE
MIN
MINIMUM
CT
CURRENT TRANSFORMER
MLO
MAIN LUGS ONLY
CU
COPPER
MM
MULTIMODE
MPOE
MAIN POINT OF ENTRY
D
DEDICATED
MPOP
MAIN POINT OF PRESENCE
DDC
DIRECT DIGITAL CONTROL
MTD
MOUNTED
DEMARC
DEMARCATION POINT
MTS
MANUAL TRANSFER SWITCH
DISC
DISCONNECT
DIST
DISTRIBUTION
(N)
NEW
DSL
DIGITAL SUBSCRIBER LINE
N
NEUTRAL
DWG
DRAWING
NAC
NOTIFICATION APPLIANCE CIRCUIT
NEC
NATIONAL ELECTRICAL CODE
(E)
EXISTING
NEMA
NATIONAL ELECTRICAL MANUFACTURERS
EA
EACH
ASSOCIATION
EF
EXHAUST FAN
NF
NON -FUSED
EIA
ELECTRONIC INDUSTRIES ASSOCIATION
NIC
NOT IN CONTRACT
ELEV
ELEVATION
NL
NIGHT LIGHT
EM
EMERGENCY
EMT
ELECTRICAL METALLIC TUBING
OFC
OPTICAL FIBER CABLE
ENCL
ENCLOSURE
OHL
OVERHEAD LINE
EPM
ELECTRONIC POWER METER
OL
OVERLOAD
EPO
EMERGENCY POWER OFF
OS
OCCUPANCY SENSOR
EQUIP
EQUIPMENT
OSP
OUTSIDE PLANT
ETR
EXISTING TO REMAIN
EWC
ELECTRIC WATER COOLER
P
POLE
PBX
PRIVATE BRANCH EXCHANGE
F
FUSE; DEGREES FAHRENHEIT
PF
POWER FACTOR
FA
FIRE ALARM
PH
PHASE
FAAP
FIRE ALARM ANNUNCIATOR PANEL
PIR
PASSIVE INFRARED
FACP
FIRE ALARM CONTROL PANEL
PIV
POST INDICATING VALVE
FBO
FURNISHED BY OWNER
PNL
PANEL
FC
FOOT-CANDLE
PP
PATCH PANEL
FURNISHED BY OWNER INSTALLED BY
PT
POTENTIAL TRANSFORMER
FDIC
CONTRACTOR
PVC
POLYVINYL CHLORIDE
FOIO
FURNISHED BY OWNER INSTALLED BY OWNER
FSD
FIRE SMOKE DAMPER
RC
ROOM CONTROLLER
RCP
REFLECTED CEILING PLAN
G
GROUND
REC
RECEPTACLE
GB
GROUND FAULT CIRCUIT BREAKER
REF
REFER TO
GF
GROUND FAULT CIRCUIT INTERRUPTER
REV
REVISION
GFP
GROUND FAULT PROTECTION
RM
ROOM
GND
GROUND
RTRC
REINFORCED THERMORESETTING RESIN
GRS
GALVANIZED RIGID STEEL
CONDUIT
RU
RACK UNIT
HC
HORIZONTAL CROSS CONNECT
HID
HIGH INTENSITY DISCHARGE
SB
STANDBY
HP
HORSEPOWER
SHT
SHEET
HTR
HEATER
SLC
SIGNALING LINE CIRCUIT
Hz
HERTZ
SM
SINGLEMODE s.��
SURVEYED:
DESIGNED:
KSR
12/12/22 DRAWN: KSR
10/26/22 j CHECKED:
TSV
BY DATE AP P R APPROVED:
SCALE:
NONE
ONE INCH
AT FULL SCALE
IF NOT ONE INCH
SCALE ACCORDINGLY
VERTICAL: NAVD 1988
HORIZONTAL: NAD 1983/1991
DATUM
uCITY OF
RENTON
Planning/Building/Public Works Dept.
TBB
TELECOMMUNICATIONS BONDING BACKBONE
TEL
TELEPHONE
TELCO
TELEPHONE COMPANY
TGB
TELECOMMUNICATIONS GROUNDING BUSBAR
00
TIA
TELECOMMUNICATIONS INDUSTRY ASSOCIATION
M
TMGB
TELECOMMUNICATIONS MAIN GROUNDING
C)
BUSBAR
0
TP
TAMPERPROOF
0
TR
TELECOMMUNICATIONS ROOM
CV
TTB
TELEPHONE TERMINAL BOARD
(V
TV
TELEVISION��'
TVSS
TRANSIENT VOLTAGE SURGE SUPPRESSION
TYP
TYPICAL
UG
UNDERGROUND
UL
UNDERWRITERS LABORATORIES
UON
UNLESS OTHERWISE NOTED
UPS
UNINTERRUPTIBLE POWER SUPPLY
USB
UNIVERSAL SERIAL BUS
UTP
UNSHIELDED TWISTED PAIR
UV
UNIT VENTILATOR
(C)
V
VOLTS
Ln
00
VA
VOLT AMPERES
N
VFD
VARIABLE FREQUENCY DRIVE
0
O
W
WATT; WIRE
N
N
W/
WITH
U
W/O
WITHOUT
WA
WORKSTATION AREA
WAN
WIDE AREA NETWORK
WG
WIRE GUARD
WH
WATT HOUR METER
WP
WEATHERPROOF
XMFR TRANSFORMER I
Y WYE I
Z
IMPEDANCE
T-422110
R-422156
IN COMPLIANCE WITH CITY OF RENTON STANDARDS
CURRENT PLANNINGDEVELOPMENT ENGINEERING r �'
oJ
J
Alex MC
[1/27/2023]Michael Sippo 01/27/2023 Q
6L m
DATE:co
LINDBERGH HIGH SCHOOL MODERNIZATION 12 DEC 2022 /W
16426128TH AVE SE FIELDBOOK: 1„L
PAGE:
RENTON, WA 98058 DRAWING NO:
ELECTRICAL ABBREVIATIONS AND GENERAL NOTES C EO.02 a:
SHEET: OF: W
56 64 CL