HomeMy WebLinkAboutR-422164REMOVE EX. WM AS REQ'D
DI CL. 52 SPOOL
LENGTH AS LENGTH AS x LF REQ'D
NEEDED NEEDED MJ SLEEVE
W/MEGA-LUGS
PROPOSED UTILITY (SEE NOTE BELOW)
EX. DI OR A/C WM - - - - - . - - - - - -- ---- EX. DI OR A/C WM
VERT. THRUST BLOCK
DI CL. 52 SPOOL x LF REQ'D
W/ REBAR STRAPS (TYP. OF 2)
(TYP. OF 2)
45" BEND (MJxMJ)
PROPOSED DI CL. 52 WM W/MEGA-LUGS
(TYP. OF 4)
ALL BELLS BETWEEN FITTINGS 12" MIN. VERT. CLEARANCE
SHALL HAVE FIELD-LOK GASKETS BETWEEN UTILITY & TOP OF WM
UNLESS OTHERWISE SHOWN ON
PROFILE, IF CROSSING GRAVITY SEWER
MIN. 18" VERT. CLEARANCE REQUIRED
(SEE NOTE 2 BELOW)
NOTES:
1. MEGA -LUGS SHALL NOT BE USED ON EXISTING WATER MAIN PIPE IF EXISTING PIPE IS
CLASS 50 D.I. OR A.C. PIPE. MJ SLEEVE TO BE INSTALLED ON CLASS 50 D.I. PIPE.
TRANSITION COUPLING TO BE INSTALLED ON A.C. PIPE. BLOCKING SHALL BE DETERMINED
IN FIELD BY DISTRICT FIELD REPRESENTATIVE.
2. SANITARY SEWER SHOULD BE LOCATED BELOW WATER MAINS IF POSSIBLE. GRAVITY
SEWERS MAY BE LOCATED ABOVE WATER MAINS AS LONG AS THERE IS 18" MIN.
SEPARATION AND THE WATER MAIN IS CASED FOR AT LEAST 10' EACH SIDE OF THE
CROSSING.
3. PRESSURE SEWER MAINS SHALL ONLY BE LOCATED BELOW WATER MAINS WITH 18"
MIN. SEPARATION. WATER MAIN SHALL ALSO BE CASED FOR 10' EACH SIDE OF
CROSSING.
NTS
SOOS CREEK STD W-92 TYPICAL UTILITY CROSSING
PLAN 4"-/2„
FINISH GRADE
ETAIL
3LOCKING
T BOX SHALL BE
NDARD WA TER
ER BOX PER
AIL W-17. INSTALL
ON VAUL T SIDE W1 TH
THE LEAST CONFLICTS.
8" MIN. ORGANIC TOPSOIL TOPSOIL
PER KCC 16.82.700
PIT RUN 3" MINUS
.3' MIN. 95% COMPACTON CRUSHED ROCK
5/8"-1 1 /2"
NA Tl - MA TERIAL IF
APPROVED BY PIT RUN 3" MINUS
DISTRICT AND 90% COMPACTION CRUSHED ROCK
PERMITTING AGENCY 5/8"-1 1/2"
12" MIN. 90% COMPACTION
SAND -SOIL ENGINEER APPROVAL
& COMPACTION TEST REQUIRED
PEA GRAVEL
5/8" MINUS CRUSHED
6" MIN.
2"-4" ROCK OR
SOILS ENGINEERING 90% COMPACTION OTHER MATERIAL
DETAIL NEEDED 1 LISTED ABOVE
NOTES:
BEDDING -IN RIGHT OF WAY, DRI VEWA Y
PAkKING L 0 TS, PAVED AREAS, AND NON
PAVED AREAS.
BEDDING FOR RIGID PIPE -NATIVE MATERIAL
UNLESS JUDGED UNSUITABLE BY THE
DISTRICT AND PERMITTING AGENCY.
TRENCH BACKFILL, BEDDING AND MATERIAL
TO CONFORM TO PERMITTING AGENCY
SPECIFICATIONS AND DISTRICT STANDARDS.
TRENCH WIDTHS
NOMINAL
PIPE
DIAMETER
MINIMUM
EARTH
MINIMUM
ROCK
MAXIMUM
2
18
24
36
3
18
24
36
4
18
24
36
6
21
24
36
8
24
24
36
12
28
28
40
(IN INCHES)
NTS
SOOS CREEK STD W-34 TYPICAL TRENCH DETAIL (OUTSIDE ROADWAY)
METER SIZE
VAULT SIZES
CATALOG#
VAULT#
COVER#
BASE#
3"
575-LA
575-BL
57TL-S-332P
575-BL
4"
575-LA
575-BL
57TL-S-332P
575-BL
6"
675-LA
675-ML
675-TL-30C
675-BL
GENERAL NOTES:
1. PAINT ALL INTERIOR METAL INCLUDING PIPE, VALVES, AND FITTINGS WITH TWO COATS OF EPDXY AS APPROVED BY
THE ENGINEER. USE TNEMEC SERIES 135 CHEMBUILD MODIFIED POLYAMIDOAMINE EPDXY. APPLY PER MANUFACTURERS
INSTRUCTIONS.
2. THE ABOVE VAULT SIZES WERE SUPPLIED BY UTILTY VAULT CO. AS A REFERENCE FOR REQUIRED VAULT DIMENSIONS.
SHOP DRAWINGS SHALL BE SUBMITTED FOR APPROVAL.
3. ALL ACCESS COVERS MUST BE MARKED "WATER", AND BE LOCKING, & TRAFFIC BEARING. AS REQUIRED BY DIST.
WITH THREE (3) TAPPED 5/8" HOLES (SEE DWG. 26C). SQUARE HATCH MAY BE USED, SUBJECT TO APPROVAL
BY DISTRICT.
4. CLASS 52 D.I.PIPE IS REQUIRED.
5. ALTERNATE METHODS OF RESTRAINT SHALL BE APPROVED BY THE DISTRICT.
MATERIAL LIST
2
2
WATERTIGHT
1O
HATCH --------eASTIRON OR ALUMINUM MANHOLE GRATE AND COVER (30"x 6") SEE #3 ABOVE
SEALED
Y4" 90' PVC
\,-,Y4"
2
O
LADDER RUNGS BAST IN PLACE 3 4" GALV. BAR AT 12" O.C. OR FABRICATED ALUMINUM LADDER SECURED
5BEND
ELECTRICAL
AT TOP AND BOTT M.
V
PVC CONDUIT
3
CONCRETE VAULT SUBMIT DETAILS FOR APPROVAL. (SEE TABLE ABOVE)
4 6
1
4O
METER COMPOUND WATER METER FLG. x FLG. SUPPLIED BY DISTRICT.
a
SO
MAIN VALVE TWO EACH, AWWA, FL x MJ W/RESTRAINTS GATE VALVES WITH HANDWHEEL. MUST BE LOCATED INSIDE
t�0
OF VAULT.
O
6O
COUPLING ADAPTER -9NE EACH, CAST IRON, (FLANGE BY MECHANICAL JOINT) COUPLING ADAPTER.
O O
7D
FLOOR DRAIN 4' PVC, SLOPED TO STORM SEWER OR DAYLIGHT TO DRAINAGE DITCH.
16
12" MIN ;r\-
ALTERNATE: WATERPROOF VAULT W/ XYPEX. ALTERNATE MUST BE APPROVED BY THE DISTRICT
CONC.SEE
PIPE
AND WILL BE ALLOWED ONLY IF DAYLIGHT DRAIN IS EXTENDED OVER 300 FEET.
BLOCKING . '°
.
SLEEVE DETAIL
SPOOL SPOOL PLANE -END x FLANGED D.I.P. (CL52)
ADJUSTABLE PIPE
�►
9O
1-1/2" VALVE ENO EA. BRASS GATE VALVES FOR BY-PASS.
SADDLE SUPPORT
(GRINNELL #264
10
BEND TWO EA. 1-1/2 INCH 90' BRASS BENDS.
OR EQUIV.)
ELEVATION
11
UNION ENE EA. 1-1/2 INCH TWO-PART UNION BRASS.
12
BY-PASS PIPE ---t-1/2 INCH BRASS PIPE AS NEEDED.
PIPE SLEEVE
LEAD & OAKUM OR
13
SADDLE ENO EA. 1-1/2 INCH SMITH BLAIR TYPE 313 OR EQUAL.
"• EPDXY SEALANT
PIPE
14
TEE 1/2"x 1-1/2" BRASS TEE.
15
BUSHING 1 1/2"x 3/4" BUSHING WITH 3/4" PLUG.
4 CEMENT DRY PACK
16
WATER MAIN CLASS 52 DUCTILE IRON PIPE WITH MEGALUG RESTRAINED JOINTS.
PIPE SLEEVE DETAIL
17
WALL FLANGE TWO EACH
NTS
�
NTS
SOOS CREEK STDW-26A 4"
WATER METER
SOOS CREEK STDW-26A 4" WATER METER 5
MATERIALS (Revised 05-1 6-1 1)
2.
3
4.
5.
DUCTILE IRON PIPE
ALL DUCTILE IRON PIPE SHALL CONFORM TO SECTION 9-30.1(1) OF THE STANDARD
SPECIFICATIONS. PIPE SHALL BE CLASS 52 CONFORMING TO LAYING CONDITION TYPE 2,
SHALL BE LINED WITH CEMENT MORTAR PER ANSI/AWWA C104/A21.4-95, AND SHALL BE
SEAL COATED. JOINTS SHALL BE PUSH -ON TYPES WITH RUBBER GASKETS, WHICH FIT INTO
ANNULAR GROOVES. JOINTS AT VALVES OR FITTINGS MAY BE MECHANICAL JOINT OR FLANGED
DEPENDING ON SPECIFICATION AND DRAWING REQUIREMENT. DUCTILE IRON PIPE
MANUFACTURED AND DISTRIBUTED BY PACIFIC STATES CAST IRON PIPE COMPANY SHALL BE
MANUFACTURED AFTER 1988. RESTRAINED JOINTS FOR -DUCTILE IRON PIPE SHALL BE U.S.
PIPE FIELD LOCK GASKET SYSTEM OR APPROVED EQUAL.
FITTINGS
FITTINGS FOR DUCTILE IRON PIPE SHALL CONFORM TO SECTION 9-30.2(1) OF THE STANDARD
SPECIFICATIONS AND MAY BE FLANGED, MECHANICAL OR PUSH -ON AS REQUIRED. FLANGED
FITTINGS SHALL CONFORM TO A CLASS 125 PRESSURE RATING. MECHANICAL JOINT FITTINGS
SHALL BE RESTRAINED WITH MEGA -LUG RESTRAINING DEVICES OR APPROVED EQUAL.
RESTRAINING DEVICES SHALL BE MANUFACTURED OF HIGH STRENGTH DUCTILE IRON, ASTM
A536, GRADE 65-45-12. BOLTS AND CONNECTING HARDWARE SHALL BE OF HIGH STRENGTH
LOW ALLOY MATERIAL IN ACCORDANCE WITH ANSI/AWWA C111/A21.11. ALL RESTRAINING
DEVICES SHALL HAVE A WATER WORKING PRESSURE RATING EQUIVALENT TO THE FULL RATED
PRESSURE OF THE PIPE ON WHICH THEY ARE INSTALLED, WITH A MINIMUM 2:1 SAFETY
FACTOR IN ANY NOMINAL PIPE SIZE. NOTARIZED CERTIFICATION FROM THE MANUFACTURER OF
THE RESTRAINT DEVICE SHALL BE PROVIDED WITH SUBMITTALS.
THE EXTERIOR OF ALL DUCTILE IRON FITTINGS SHALL BE COATED WITH BITUMINOUS PAINT.
FIRE HYDRANTS
HYDRANTS SHALL CONFORM TO AWWA C-502, EXCEPT AS HEREIN MODIFIED. HYDRANTS
SHALL HAVE A MINIMUM OF 5-1/4-INCH MAIN VALVE OPENING WITH TWO 2-1/2-INCH HOSE
CONNECTIONS AND ONE 4-1/2-INCH PUMPER CONNECTION. ALL PORTS SHALL BE
FURNISHED WITH NATIONAL STANDARD HOSE THREAD AND 1-1/4-INCH OPERATING NUTS THAT
TURN COUNTERCLOCKWISE TO OPEN.
THE PUMPER CONNECTION SHALL BE EQUIPPED WITH A 5-INCH STORZ ADAPTER MEETING OR
EXCEEDING THE FOLLOWING SPECIFICATIONS.
A. STORZ ADAPTER AND CAP SHALL BE FORGED AND/OR EXTRUDED 6061-T6 ALUMINUM
ALLOY, HARD COAT ANODIZED.
:��:I:1�_117�:�1:1:i�[:l��l:>•:/1�/�l�i�L:�.`l��.Yy:���i�E.`iE:�:3i_1J_1:�/_1�11��[:>•l�leL`>A
1:1 icy_ 81=1:1.:l1411111XINF.AlMTNIIImmilk [:xe-A 1:1mWEt:]ATi9W_lI:II
D. STORZ CAP TO HAVE SYNTHETIC MOLDED RUBBER GASKET AND SHALL BE ATTACHED TO
HYDRANT ADAPTER WITH 1/8-INCH COATED STAINLESS STEEL AIRCRAFT CABLE.
E. CAP TO BE CONNECTED AND DISCONNECTED WITH STORZ WRENCHES ONLY. TORQUE TO
BE SUFFICIENT SO CAP CANNOT BE REMOVED BY HAND.
HYDRANTS SHALL BE FURNISHED WITH A 6-INCH MECHANICAL JOINT OUTLET, TWO 3/4-INCH
DIAMETER TIE RODS, OR MEGA -LUGS, A 6-INCH AUXILIARY GATE VALVE WITH VALVE BOX, AND
A RISER TO SUIT TRENCH DEPTH AT EACH INSTALLATION. THE GATE VALVE SHALL BE
FLANGED TO THE MAIN TEE. HYDRANT SHALL BE FURNISHED WITH A BREAK -OFF FLANGE ON
THE BARREL AND A BREAK -OFF COUPLING FOR THE STEM. HYDRANTS SHALL CONFORM TO
DISTRICT STANDARDS.
ALL FIRE HYDRANTS SHALL BE M & H STYLE 929 RELIANT, MUELLER CENTURION MODEL
A-423, CLOW MEDALLION OR WATEROUS PACER NO. WB-67.
NOZZLES SHALL BE FITTED WITH RENEWABLE BRONZE NIPPLE LOCKED IN PLACE. MAINTAIN 3
FEET CLEARANCE BETWEEN HYDRANT AND PROPERTY OR EASEMENT LINE.
TYPE 1 BLUE REFLECTIVE MARKERS AS DESCRIBED IN SECTION 9-21.1 OF THE STANDARD
SPECIFICATIONS SHALL BE INSTALLED AS REQUIRED BY THE GOVERNING ROAD AGENCY.
FIRE HYDRANTS SHALL BE EQUIPPED WITH STEAMER AND HOSE PORT THREADS IN
ACCORDANCE WITH THE REQUIREMENTS OF THE LOCAL FIRE PROTECTION DISTRICT.
THE HYDRANT SHALL BE CLEANSED AND PRIME COATED WITH A HEAVY-DUTY BRUSH TYPE
PRIMER OR APPROVED EQUAL. ALL HYDRANTS SHALL BE PAINTED YELLOW WITH TWO
TOPCOATS OF OIL RESISTANT ENAMEL, BRUSH TYPE OR APPROVED EQUAL. THE DISTANCE
FROM THE HYDRANT TO THE 6-INCH GATE VALVE SHALL BE STENCILED ON THE HYDRANT
WITH 2-INCH LETTERS.
DURING THE CHLORINATING PROCESS FOR THE NEWLY LAID PIPE, ALL VALVES ASSOCIATED
WITH THE FIRE HYDRANTS SHALL BE OPERATED WHILE THE PIPELINE IS FILLED WITH THE
CHLORINATING AGENT AND UNDER NORMAL OPERATING PRESSURE.
aIN=:17:11`011Weill-Al 11hl:>•IeL91M
GUARD POSTS SHALL NOT BE INSTALLED WITH FIRE HYDRANT ASSEMBLIES UNLESS REQUIRED
BY DISTRICT. IF GUARD POSTS ARE REQUIRED BY DISTRICT, THEY SHALL BE MADE OF
REINFORCED CONCRETE, 8 INCHES IN DIAMETER, 6 FEET LONG AND BURIED TO A MINIMUM
DEPTH OF 3 FEET. GUARD POSTS SHALL BE SET WITH THEIR TOPS AT THE SAME ELEVATION
AS THE BONNET FLANGE OF THE HYDRANT. THE EXPOSED PORTION OF THE GUARD POSTS
SHALL BE PAINTED WITH 2 COATS OF EXTERIOR CONCRETE PAINT, COLOR AS DESIGNATED BY
THE DISTRICT.
GATE VALVES
GATE VALVES SHALL BE OF THE SIZE AND TYPE INDICATED ON THE DRAWINGS WITH
BRONZE -MOUNTED RESILIENT SEAT WEDGING DEVICES CONFORMING TO AWWA C509 OR AWWA
C515. VALVES SHALL BE COATED PER AWWA C550 WITH NON -RISING STEMS, OPEN
COUNTERCLOCKWISE, AND BE EQUIPPED WITH AN 0-RING STUFFING BOX. VALVE END
CONNECTIONS MAY BE FLANGED, MECHANICAL JOINT OR PUSH -ON AS REQUIRED. ALL FLANGE
FACES SHALL BE MACHINED AND DRILLED TO STRADDLE THE VERTICAL CENTERLINE. VALVE
STEM EXTENSIONS WITH PLATE WELDED TO OPERATING NUT WILL BE REQUIRED WHERE
OPERATING NUT IS MORE THAN 4 FEET BELOW SURFACE. THE VALVE STEM EXTENSION TOP
SHALL BE INSTALLED WITHIN 18 INCHES TO 24 INCHES BELOW FINISH GRADE AND SHALL
HAVE A 2-INCH SQUARE OPERATING NUT AND SELF -CENTERING ROCK PLATE SUPPORT. LOCK
DOWN SET SCREWS SHALL NOT BE USED ON VALVE OPERATING NUT EXTENSIONS.
MANUFACTURER SHALL PROVIDE CATALOG DATA, NET WEIGHT, AND ASSEMBLY DRAWINGS OF
ALL VALVES TO BE PURCHASED AND INSTALLED AS WELL AS AN AFFIDAVIT OF COMPLIANCE.
ALL VALVES SHALL HAVE A WATER WORKING PRESSURE RATING EQUIVALENT TO THE FULL
RATED PRESSURE OF THE PIPE ON WHICH THEY ARE INSTALLED, WITH A MINIMUM 2:1 SAFETY
FACTOR IN ANY NOMINAL PIPE SIZE.
6. VALVE BOX
VALVE BOX
SHALL BE CAST
IRON SERIES 940B AS
MANUFACTURED BY OLYMPIC FOUNDRY OR
APPROVED
EQUAL WITH LID
MARKED "WATER". ALL
BOXES SHALL BE ADJUSTED TO MATCH
THE FINISH
GRADE AT THE
VALVE LOCATION. ALL
VALVE BOX COVERS SHALL BE PAINTED
BLUE. ORIENT
THE VALVE
BOXES SO THE "EARS" ARE SET THE SAME AS THE PIPE DIRECTION.
PROVIDE 4-INCH
THICK BY
2-FOOT WIDE ASPHALT
OR CONCRETE COLLAR AROUND VALVE BOX
COVERS IN
UNIMPROVED AREAS, LANDSCAPE AREAS
AND EASEMENTS.
7. VALVE MARKER
POSTS
VALVE MARKER POSTS SHALL BE FURNISHED AND INSTALLED WITH EACH VALVE UNLESS THE
VALVE IS LOCATED IN THE PAVEMENT OR IN A VAULT. MARKER POSTS SHALL BE CONCRETE
WITH 4-INCH MINIMUM SQUARE SECTION, 42-INCH LENGTH, AND SHALL BE REINFORCED WITH
ONE 3/8" X 39" BAR OF REINFORCING STEEL. MARKERS SHALL BE PLACED AT THE EDGE
OF THE RIGHT-OF-WAY OPPOSITE THE VALVE OR AS DIRECTED BY THE DISTRICT WITH 18
INCHES OF THE POST EXPOSED ABOVE GRADE. THE EXPOSED PORTION SHALL BE PAINTED
WITH TWO COATS OF WHITE EXTERIOR CONCRETE PAINT WITH THE SIZE OF THE VALVE AND
THE DISTANCE IN FEET AND INCHES TO THE VALVE STENCILED WITH BLACK PAINT ON THE
FACE OF THE POST USING A STENCIL THAT WILL PRODUCE LETTERS TWO INCHES HIGH.
8. WET TAPS
TAPPING SLEEVE SHALL BE JCM 432 OR ROMAC "SST" STAINLESS STEEL SLEEVES WITH FULL
COVERAGE RUBBER GASKET, OR EPDXY COATED LONG PATTERN SLEEVE, OR APPROVED EQUAL.
VALVE SHALL BE A RESILIENT SEATED VALVE MADE FOR TAPPING, U.S. PIPE METROSEAL 250
OR APPROVED EQUAL. REFER TO THE GATE VALVE DESCRIPTION FOR ADDITIONAL DETAILS.
SUBMITTALS REQUIRED FOR ALL WET TAP MATERIALS.
9. WATER SERVICES AND METERS
NEW SERVICE LINES SHALL BE CLASS 200, HI-MOL OR APPROVED EQUAL AND SHALL
CONFORM TO THE STANDARD DETAILS AND SECTIONS 9-30.6 AND 9-30.6(3)B OF THE
STANDARD SPECIFICATIONS. INSTALL PLASTIC -COATED 16-GAUGE COPPER TRACER WIRE
ALONG TOP OF ALL PLASTIC SERVICE PIPES. ATTACH BARE WIRE TO ANGLE AND
CORPORATION STOPS.
CONNECTIONS FROM PIPE TO ANGLE AND CORPORATION STOPS SHALL BE WITH COMPRESSION
PACK JOINTS. METER BOXES SHALL BE AS CALLED OUT ON THE STANDARD DETAILS. METER
BOXES AND LIDS LOCATED IN DRIVEWAYS OR SIDEWALKS SHALL BE TRAFFIC BEARING AS
APPROVED BY THE DISTRICT.
WATER SERVICES SHALL BE LOCATED BY MUTUAL AGREEMENT BETWEEN DEVELOPER, DISTRICT,
AND OTHER UTILITY COMPANIES. PAINT SERVICE LOCATIONS ON CURB WITH BLUE PAINT.
METER BOXES SHALL BE FURNISHED AND INSTALLED BY DEVELOPER/CONTRACTOR. WATER
SERVICE SHALL BE LOCATED NO CLOSER THAN 5 FEET FROM POWER VAULTS, HAND HOLES
AND LIGHT STANDARDS.
ALL SERVICE LINES SHALL BE ONE -INCH MINIMUM, AND SHALL BE CONTINUOUS AND
UNSPLICED FROM CORPORATION STOP TO METER AND SHALL HAVE 6 INCHES OF SAND
BEDDING SURROUNDING THE SERVICE LINE. EXPANSION LOOPS ARE TO BE HELD AS FLAT AS
POSSIBLE WITH NO REVERSE GRADE. WATER MAIN SERVICE SADDLE AND CORPORATION STOP
WITH COMPRESSION ADAPTER SHALL BE LOCATED AT APPROXIMATELY 10° ABOVE SPRING LINE
PER THE STANDARD DETAIL.
THE DEVELOPER/CONTRACTOR SHALL NOT BACKFILL ANY SERVICE LINES UNTIL ALL BRASS
FITTINGS ASSOCIATED WITH THAT SERVICE LINE HAVE BEEN INSPECTED AND ACCEPTED BY THE
DISTRICT.
EXISTING WATER SERVICES, WHICH NEED TO BE ABANDONED, SHALL BE DISCONNECTED AT THE
WATER MAIN CORPORATION STOP. THE DEVELOPER/CONTRACTOR SHALL COORDINATE WITH THE
DISTRICT'S FIELD REPRESENTATIVE AS REQUIRED.
10. IMPORTED GRAVEL MATERIAL
PIPE BEDDING SHALL CONFORM TO SECTION 9-03.12(3) OF THE STANDARD SPECIFICATIONS.
FOUNDATION GRAVEL SHALL CONFORM TO SECTION 9-03.17 OF THE STANDARD
SPECIFICATIONS. BANKRUN GRAVEL FOR TRENCH BACKFILL SHALL CONFORM TO SECTION
9-03.19 OF THE STANDARD SPECIFICATIONS, EXCEPT AT TRANSVERSE CUTS TO THE ROAD
ALIGNMENT OR AT UTILITY CROSSINGS, WHICH SHALL BE BACKFILLED WITH CRUSHED GRAVEL
SURFACING OR AS REQUIRED BY THE GOVERNING AGENCY. DEVELOPER/CONTRACTOR SHALL
BE RESPONSIBLE FOR REMOVING AND DISPOSING OF ANY EXCESS EXCAVATED SOIL MATERIAL
AT AN APPROVED DISPOSAL SITE.
11. CRUSHED GRAVEL SURFACING
CRUSHED GRAVEL SURFACING SHALL CONFORM TO THE REQUIREMENTS OF SECTION 9-03.9(3)
OF THE STANDARD SPECIFICATIONS.
12. ASPHALT CONCRETE PATCH AND OVERLAY
ASPHALT CONCRETE SURFACING FOR PATCHING AND OVERLAY SHALL CONFORM TO SECTION
5-04.2 AND 5-04.3 OF THE STANDARD SPECIFICATIONS. ASPHALT CONCRETE SURFACING
SHALL MEET CLASS 1/2-INCH, P.G. 58-22 GRADING REQUIREMENTS, OR AS REQUIRED BY
THE GOVERNING ROAD AGENCY.
FOR REFERENCE
ONLY
w
0
m
O
z
z
a
2i
w
J
>
�>
z
ww
0
z
w�
Z�
3
0
aQ
o
oQ
o
Y
m
E
0
0
1
o
J
w
00
N Q1 ['V M
�
L
Ew
O ^
LL N N
-6
Q
�6
N O p
OMl � N N
1 cn cn a
3
U
Y
_
Q
m
0
N
W
w N
J - F-
V) 2 >
0
N �
z z z
0 w U\
z _
Q /
O 06
w U)
X J w
W 00
z = z
Q U Z
� � Q
_ _j
Lu V 0-
Q = z
w
m ry
w
o �
z Q
R-422164
BASE MAP
SHEET 3
DRAWING
OF 3
SHEET 64 of 64