WATER PLAN GENERAL NOTES Standard Plan No. 300
1. ALL WORK AND MATERIALS SHALL BE IN ACCORDANCE WITH THE LATEST EDITION OF THE CITY OF RENTON PUBLIC WORKS
STANDARD SPECIFICATIONS AND SPECIAL PROVISIONS AND WSDOT / APWA STANDARD SPECIFICATIONS, LATEST EDITION AS
AMENDED BY THE CITY OF RENTON. A SET OF CITY APPROVED PLANS SHALL BE KEPT AT THE JOB SITE WHENEVER CONSTRUCTION
IS IN PROGRESS. A PRE -CONSTRUCTION CONFERENCE SHALL BE HELD PRIOR TO THE START OF CONSTRUCTION. THE CONTRACTOR
AND OR DEVELOPER SHALL BE RESPONSIBLE FOR SECURING ALL NECESSARY PERMITS PRIOR TO CONSTRUCTION.
2. ALL EXISTING UTILITIES SHALL REMAIN IN SERVICE DURING CONSTRUCTION UNLESS OTHERWISE NOTED. THE CONTRACTOR SHALL
CALL 1-800-424-5555 TO VERIFY UTILITY LOCATIONS BEFORE BEGINNING EXCAVATION.
3. ALL MATERIALS USED FOR THE CONSTRUCTION OF WATER SYSTEM IMPROVEMENTS SHALL BE NEW AND UNDAMAGED, AND
"CATALOG CUTS" FOR ALL MATERIALS SHALL BE APPROVED IN WRITING BY THE CITY OF RENTON PRIOR TO BRINGING ANY
MATERIALS ON -SITE.
4. ALL WATER MAIN PIPE MATERIALS SHALL BE CEMENT LINED DUCTILE IRON PIPE, THICKNESS CLASS 52 PER AWWA C 151 AND C
104. PIPE JOINTS SHALL BE PUSH -ON OR MECHANICAL JOINT. CAST IRON OR DUCTILE IRON PIPE FITTINGS SHALL BE CLASS 250 AS
PER ANSI/AWWA C110/A21.10-82. ALL DUCTILE IRON PIPE AND FITTINGS SHALL BE WRAPPED WITH 8-MIL BLACK, TUBE -TYPE,
POLYETHYLENE PLASTIC PER AWWA C105 STANDARDS.
5. MINIMUM COVER FROM TOP OF WATER MAINS TO FINISHED GRADE SHALL BE 36 INCHES FOR PIPE DIAMETER OF 10-INCH OR LESS
AND 48 INCHES FOR PIPE DIAMETER OF 12-INCH AND LARGER. MAXIMUM COVER FOR ALL WATER MAINS SHALL BE 60 INCHES.
ANY DEVIATIONS MUST BE APPROVED BY THE CITY OF RENTON PRIOR TO CONSTRUCTION. WHERE UTILITY CONFLICTS OCCUR,
THE PROFILE OF THE WATER MAIN SHALL BE ADJUSTED AS NECESSARY TO CLEAR CONFLICTS AND TO PROVIDE MINIMUM COVER.
PIPE DEFLECTION SHALL NOT EXCEED ONE-HALF OF PIPE MANUFACTURER'S SPECIFICATION FOR SIZE OF PIPE USED. ALL TRENCH
BACKFILL SHALL BE COMPACTED TO 95 PERCENT MAXIMUM DRY DENSITY AS DETERMINED BY THE MODIFIED PROCTOR TEST
METHOD (MDD) IN ROADWAYS, ROADWAY SHOULDERS, ROADWAY PRISM AND DRIVEWAYS, AND 85 PERCENT MDD IN UNPAVED
AREAS. ALL PIPE ZONE COMPACTION SHALL BE 95 MDD.
6. CONCRETE BLOCKING FOR WATER MAINS SHALL BE DESIGNED, INSTALLED AND POURED IN PLACE IN ACCORDANCE WITH CITY OF
RENTON STANDARD DETAILS AND SPECIFICATIONS AND SHALL BE INSTALLED AT ALL VERTICAL AND HORIZONTAL BENDS, FITTINGS
AND BASE OF HYDRANTS. MEGA -LUGS (OR SIMILAR PRODUCT) MAYBE REQUIRED ON ALL MECHANICAL JOINTS IN ADDITION TO
CONCRETE BLOCKING.
7. ALL NEW WATER MAIN PIPES AND FITTINGS SHALL HAVE A FOAM PIPE PIG RUN THROUGH THEM PRIOR TO BEING FLUSHED,
DISINFECTED, AND TESTED. CLEANING, PRESSURE AND PURITY TESTING SHALL BE DONE IN THE PRESENCE OF AND UNDER THE
SUPERVISION OF A CITY OF RENTON UTILITY INSPECTOR. THE CONTRACTOR SHALL SUPPLY, INSTALL AND REMOVE PLUGS,
CORPORATION STOPS, BLOW -OFF ASSEMBLIES, AND THRUST RESTRAINT / BLOCKING FOR TESTING AND PURITY ACCEPTANCE. NO
CONNECTION SHALL BE MADE BETWEEN THE NEW MAIN OR BETWEEN THE NEW WET -TAP VALVE TO AN EXISTING MAIN UNTIL
THE NEW PIPING HAS BEEN FOAM -PIGGED, DISINFECTED, FLUSHED, AND PASSED BOTH PRESSURE AND PURITY TESTING.
B. NEW WATER MAINS INCLUDING SERVICE LATERALS SHALL BE TESTED AT A STATIC PRESSURE OF 150 PSI ABOVE WORKING
PRESSURE WITH A MINIMUM OF 225 PSI TEST PRESSURE FOR 120 MINUTES WITH A MAXIMUM OF 5 PSI PRESSURE DROP DURING
THE ENTIRE TEST PERIOD. UPON SATISFACTORY COMPLETION OF THE PRESSURE TEST, THE LINE SHALL BE DISINFECTED, FLUSHED,
AND THEN WATER SAMPLES SHALL BE TAKEN FOR PURITY TESTING BY THE PUBLIC WORKS INSPECTOR.
9. THE CONTRACTOR SHALL NOTIFY THE CITY OF RENTON WATER UTILITY AND MAINTENANCE DEPARTMENTS AT LEAST 10 WORKING
DAYS PRIOR TO MAKING CONNECTIONS TO THE EXISTING WATER SYSTEM. THE CONTRACTOR SHALL EXPOSE THE EXISTING WATER
MAIN AND FITTINGS AT THE CONNECTION POINT BEFORE ORDERING THE NECESSARY ADAPTORS AND FITTINGS REQUIRED FOR
THE FINAL CONNECTION. THE CONTRACTOR SHALL EXCAVATE, REMOVE ALL SURFACE MATERIALS, AND PROVIDE SHORING AND
ALL MATERIALS REQUIRED FOR THE CITY OF RENTON TO PERFORM THE CONNECTION TO THE EXISTING WATER SYSTEM. THE
CONTRACTOR SHALL PROVIDE AND INSTALL BACKFILL, CONCRETE BLOCKING, AND COMPLETE SURFACE RESTORATION.
STD. PLAN - 300.0
n * PUBLIC WORKS WATER PLAN GENERAL NOTES
DEPARTMENT MARCH 2O10
MARKER
� a
TWO LANE ROAD OFFSET
MARKER TO INDICATE
WHICH SIDE OF STREET
HYDRANT IS ON (4" FROM
DOTS OR PAINTED LINE)
MARKER
o
I o a
I
FOUR LANE ROAD OFFSET
MARKER TO INDICATE WHICH
SIDE OF STREET HYDRANT IS
ON (4" FROM DOTS OR
PAINTED LANE DIVIDER)
HYDRANT MARKERS
4„
RAISED PAVMENT MARKER TYPE 88 AB
STIMSONITE TWO-WAY (BLUE)
MARKER
a T
ON SIDE STREETS WHERE THE
HYDRANT IS WITHIN 20' OF A
MAIN TRAVELED STREET, THE
MARKER IS TO BE INSTALLED
ON THAT MAIN STREET
MARKER
o
FIVE LANE ROAD OFFSET
MARKER TO INDICATE WHICH
SIDE OF STREET HYDRANT IS
ON (4" FROM DOTS OR
PAINTED LANE DIVIDER)
TY ° STD. PLAN - 310.3
• PUBLIC WORKS
�'•` �` DEPARTMENT HYDRANT MARKER LAYOUT
ZN`f0
L
EXISTING WATER LINE
PLAN VIEW
TESTING DETAIL
n
±8 FT
- O NEW WATER LINE
�Lw
14
VERTICAL CROSS(MJxFL) FOR PDLYPIGGING
ONE BLIND FLANGE ❑N TOP WITH 2'TAP & 2'PLUG
ONE BLIND FLANGE ❑N BOTTOM
ONE (MJ) PLUG WITH 2' TAP & 2' TEMPORARY BLOW--:1
TEMPORARY BLOCK
CUT -IN (BY CITY FORCES)
TEE (FLxFU W/ CONC. BLOCK
3- GATE VALVES (FLxMJ)
2- SOLID SLEEVES (MJ) DR RO-MAC COUPLINGS
1- PLUG (MJ) W/2'TAP & TEMP. BLOW -OFF
TEMP. BLOCK
EXISTING WATER LINE
EXISTING WATER LINE
FINAL CONNECTION DETAIL
AFTER ALL TESTING, CLEANING BY PDLYPIG, AND DISINFECTION,
REMOVE TEMP BLOCK & BLOW-0FF & CONNECT
WITH SLEEVE (MJ) & D.I. SPOOLS
FINAL CONNECTION BY CITY FORCES
MT.M, UIPM LINE
PUBLIC WORKS CONNECTION TO WATER MAIN STD. PLAN - 300.4
DEPARTMENT CUT IN -LINE TEE & THREE VALVES
MARCH 2O10
CITY PRIVATE
PIPING PIPING
1-1/2" AND 2" WATER SERVICE DETAIL z z
F IN UNIMPROVED
CAUTION: VALVE BOX SHOULD NOT REST ON
12 w RIGHT-OF-WAY INSTALL METER w
BOX 10 AT PROPERTY LINE WITH
PIPE. LATER COMPACTION IN AREA OF VALVE BOX
a_ 0
12" LONG COPPER TAILPIECE
I
COULD CAUSE THE BREAKAGE OF THE SERVICE.
a a
12" MAX.
ZX
ZX
0 ¢,
4
LEAVE EXPOSED: - 0
MU 7 NM
N.0 12„
BY PASS NOT ALLOWED
FOR IRRIGATION METERS
1 2 3 6 (71
7 _
5
CRUSHED ROCK
a
BASE TO SUPPORT
A A
VAULT.
_
DRILL '2' CIA. HOLE FOR
TOUCHREAD DEVICE
QUICK -JOINT
COUPLING x MIPT CAST IRON OR DUCTILE IRON WATERMAIN
2-1/2" MIN. FROM NEAREST
NOTE:
AND FRONT EDGE OF PIT LID
THE CENTER OF THE HOLE MUST BE AT LEAST 1" FROM
UNDERNEATH RIBS UNLESS THE RIB SPACING ALLOWS
-�
THE NUT TO TIGHTEN AGAINST THE OPEN SIDE OF
MORE THAN ONE RIB.
TYPICAL RIB
MATERIAL LIST FOR 2" SERVICE: METER LOCATED IN PLANTING STRIP
MATERIAL LIST FOR 1-1/2" SERVICE: METER LOCATED IN PLANTING STRIP
BETWEEN CURB & SIDEWALK
BETWEEN CURB &SIDEWALK
A. 2" tapped tee on new water main.
1. 2" topped tee on new water main.
PP
4" I n X with threaded (MIPT).
�. o g 2" brass nipple t t Boded ends ( )
2. 4" Ion X 2" brass nipple with threaded ends (MIPT).
g pp ( )
3. 2" resilient seat gate valve with threaded ends, square operating nut,
3. 2" resilient seat gate valve with threaded ends, square operating nut, and
and valve nut extension if required (see standard detail 330.1).
valve nut extension if required (see standard detail 330.1).
4. Two piece cast iron valve box. Standard 8" top section with regular
1, Two piece cast iron valve box. Standard 8" top section with regular base
base section, length to fit, "lug" type cover. 2" brass bushing (MIPT x
section, length to fit, "lug" type cover.
FIPT).;'
2" X 1-1/2" hex brass bushing (MIPT x FIPT). 2 each 1-1/2" brass or
5. 2 each 2" brass or bronze nipples 6" length, threaded ends. 2 sachi
bronze nipples 6" length, threaded ends. 2 each 1-1/2"-90' brass or
2"-90' brass or bronze elbows (FIPT x FIPT).
bronze elbows (FIPT x FIPT).
6. 2" (MIPT) x compression fitting, Ford C84-66 or equal.
6. 1-1/2" (MIPT) x compression fitting, Ford C84-66 or equal.
7. 2" soft copper tubing type K or brass nipples (MIPT x MIPT), length to
7. 1-1/2" soft copper tubing type K or brass nipples (MIPT x MIPT), length
fit.
to fit.
8. 2" threaded brass 90' ell.
8. 1-1/2" threaded brass 90' ell, for Ford L44-77 or equal.
9. 2" Customsetter with by-pass Ford: VBH 86-12B-11-77 (x 17-3/16"
9. 1-1/2" Customsetter with by-pass Ford: VBH 86-12B-11-66 (x
), McDonald Bross: 308715WDFF775 or Mueller B-1427-2", with flanged
13-3/16"), McDonald Bross: 308612WDFF665 or Mueller B-1427-1 1/2",
angle ball valve and padlock wings on inlet, and angle check valve
with flanged angle ball valve and padlock wings on inlet, and angle check
outlet, ball valve on bypass with padlock wings. Customsetter shall
valve outlet, ball valve on bypass with padlock wings. Customsetter shall
have vertical inlet cod outlet.
have vertical inlet and outlet.
10. Rigid meter spreader to be supplied and installed in meter setter by!(?.
Rigid meter spreader to be supplied and installed in meter setter by
contractor.
contractor.
119. Water meter shall be supplied and installed by City of Renton upon
T11,. Water meter shall be supplied and installed by City of Renton upon
payment of all related water meter fee and satisfactory pressure and
payment of all related water meter fee and satisfactory pressure and
purity tests.
purity tests.
I12. 17%30" Plastic meter box equal to Mid -States Plastics, Inc. 8CF Series
12. 17"x30' Plastic meter box equal to Mid -States Plastics, Inc. BCF Series
MSBCF 1730-18 with 2" thick Ductile iron diamond plate cover 18"x31"
MSBCF 1730-18 with 2" thick Ductile iron diamond plate co er 18"x31"
equal to Mid -States Plastics, Inc. MSCBC-1730-R with 2" drilled hole
equal to Mid -States Plastics, Inc. MSCBC-1730-R with 2"drilled hole for
for touchread pit lid, and meter read lid.
touchread pit lid.
13. 2" coupling (compression x FIPT) with 2" plug (MIPT), Ford C-14-66
13. 1-1/2" coupling (compression x FIPT) with 1-1/2" plug (MIPT), Ford
or equal. The property owner is responsible for any necessary adaptation or
C-14-66 or equal. The property owner is responsible for cry necessary
extension of water service.
adaptation or extension of water service.
NOTE:
ALL METER BOXES INSTALLED IN CONCRETE OR PAVED
DRIVEWAYS SHALL BE CAST-IRON EQUAL TO OLYMPIC
FOUNDARY.
EXPANSION JOINTS MUST BE INSTALLED 12" MINIMUM ON BOTH
SIDES OF METER.. BOX.
STD. PLAN - 320.2
PUBLIC WORKS
1 12" AND 2" WATER
SERVICE LOCATED
* ''•` .` DEPARTMENT
IN PLANTING
STRIP
��N Sow
MARCH 2O10
design PLLC
A CIVIL ENGINEERING COMPANY
219 First Avenue S., Suite 401
Seattle WA 98104
206 402 4644
FINISHED GRADE ELEVATION
3 FT MIN. COVER (10-INCH DIAMETER AND UNDER)
4 FT MIN. COVER (12-INCH DIAMETER AND OVER)
\ NEW WATER MAIN POLYPIG rj
1>
VERTICAL CROSS FOR POLYPIGGING STATION
TEMPORARY 2" GALVANIZED PIPE
AND 2" GATE VALVE
INSTALL 2" PLUG
ON
TOP BLIND
FLANGN
AFTER REMOVAL
OF
POLYPIG
SIZE OF VERTICAL CROSS SHALL BE THE SAME AS SIZE OF MAIN LINE
VERTICAL CROSS (MJ X FL)
ONE BLIND FLANGE ON TOP OF CROSS WITH 2" TAP & 2" TEMPORARY BLOW -OFF ASSEMBLY
(REMOVE BLOW -OFF ASSEMBLY AND INSTALL 2" PLUG AFTER REMOVAL OF CLEANING "POLY -PIG")
ONE BLIND FLANGE ON BOTTOM OF CROSS
ONE PLUG (MJ) ON END OF CROSS
CONCRETE BLOCKING
ALL DEBRIS AND POLYPIGS SHALL BE REMOVED FROM SUMP OF VERTICAL CROSS BEFORE
DISINFECTION OF NEW WATER MAIN
° n l PUBLIC WORK; POLY PIG STATION FOR CLEANING OF STD. PLAN - 300.6
'`•` ` DEPARTMENT WATER MAINS
r�N'CO, MARCH 2O10
A q
PLAN VIEW
WATER
VALVE BOX LID WITH
EARS IN DIRECTION OF
2" SQUARE
WATER MAIN AND WORD
"WATER"
i OPERATING NUT
12" MIN.
CAST INTO IT
-
L0." MAX
4" CONCRETE COLLAR FOR
VALVES IN PAVED AREAS
4-1/4" DIA.
12„
`�-
1/8' MIN. THICKNESS
51 E' I7LtAfL
2 PIECE" 'CAST IRON'VALVE
BOX, RICH-SEATTLE TYPE
OR OLYMPIC FOUNDRY
LENGTH LENGTH AS REQUIRED
1 /8" MIN. THICKNESS
2-1/4" INSIDE MEASUREMENT
2-1/4" DEPTH
SECTION A -A
VALVE OPERATING NUT
EXTENSION
VALVE OPERATION NUT EXTENSION NOTE:
EXTENSIONS ARE REQUIRED WHEN VALVE NUT
IS MORE THAN THREE (3) FEET BELOW
FINISHED GRADE. EXTENSIONS ARE TO BE A
MINIMUM OF ONE (1) FOOT LONG. ONLY ONE
EXTENSION TO BE USED PER VALVE.
NOTE: ALL EXTENSIONS ARE TO BE MADE
OF STEEL, SIZED AS NOTED, AND PAINTED
WITH TWO COATS OF METAL PAINT.
VALVE MARKER NOTES:
VALVE MARKERS SHALL BE EQUAL
TO CARSONITE UTILITY MARKER
VALVE MARKER POST TO BE USED FOR ALL
MAIN LINE VALVES OUTSIDE PAVED AREAS
3
�3
T -'
3"
38" MIN.
WIDTH
WHITE PC
_I =1 62„
IIIIIIIIIITI IIII
I -III_ ! i l lil
=1 I
24"
VALVE MARKER POST
STD. PLAN - 330.1
O PUBLIC WORKS VALVE BOX, MARKER & OPERATING
DEPARTMENT NUT EXTENSION
2 BID ADDENDUM # 1 8 18 2017 SURVEYED_
3 BID ADDENDUM # 2 08 29 2017 DESIGNED:
5 CONSTRUCTION ASI-1 11 15 2017 TTG
DRAWN:
TTG
CHECKED:
WE
N0. REVISION BY DATE APPR APPROVED
SCALE:
1 " = 10,
ONE INCH
AT FULL SCALE
IF NOT ONE INCH
SCALE ACCORDINGLY
VERTICAL: NAVD 1988
HORIZONTAL: NAD 1983/1991
DATU M
FIRE HYDRANT SHALL BE COREY-TYPE EQUAL TO IOWA F-5110 OR
COMPRESSION TYPE SUCH AS CLOW MEDALLION; M & H 929, MUELLER
SUPER CENTURION 200, AND WATEROUS PACER WITH 6" MECHANICAL
JOINT INLET WITH LUGS. 5-1/4" MAIN VALVE OPENING. TWO 2-1/2"
HOSE CONNECTIONS NATIONAL STANDARD THREADS. 4" PUMPER
CONNECTION CITY OF SEATTLE THREADS WITH A STORZ ADAPTOR,
4.875" SEATTLE THREAD X 5" STORZ, ATTACHED WITH 1/8" STAINLESS
STEEL CABLE. 1-1/4" PENTAGON OPERATING NUT. FIRE HYDRANT TO
BE PAINTED WITH TWO COATS OF PAINT. KELLY-MOORE/PRESERVATIVE
PAINT No. 5780-563 DTM ACRYLIC GLOSS, SAFETY YELLOW OR
APPROVED EQUAL. PUMPER CONNECTION TO FACE ROADWAY OR AS
DIRECTED BY RENTON FIRE DEPARTMENT. FIRE HYDRANT EXTENSION TO
BE USED IF REQUIRED.
MIN. 18" TO 20" BEHIND BACK OF
CURB OR 12" BEHIND BACK OF
3'
SIDEWALK THAT IS ADJACENT TO
CURB
4.875" x 5" STORZ TWO-PIECE CAST IRON VALVE BOX WITH LUG
5'x5'x6" THICK CONCRETE PAD AROUND TYPE COVER. EQUAL TO OLYMPIC FOUNDRY CO.
HYDRANT. FINISH TO MATCH SIDEWALK. STANDARD 8" TOP SECTION WITH REGULAR BASE
rye
EXPANSION JOINT AT SECTION LENGTH TO FIT. VALVE NUT EXTENSION
Oo
BACK OF SIDEWALK AS REQUIRED.
2„�
�CONCRETE SIDEWALK RAISED PAVEMENT MARKER TYPE 88-A
OR PLANTING STRIP STIMSONITE TWO-WAY BLUE REFLECTIVE
36" MIN
COVER K-y -CONCRETE BLOCKING
CONCRETE -�
THRUST BLOCK MAIN LINE TEE. WITH 6" FLANGE SIDE OUTLET.
6" GATE VALVE (FL X MJ) AWWA C-509, RESILIENT SEAT
6" DUCTILE IRON PIPE, CLASS 52 CEMENT LINED, LENGTH TO FIT
2-3/4" COR-TEN STEEL TIE RODS.
16" x 8" x 4" MININUM 1/2 YARD OF 1-1/4" WASHED DRAIN ROCK
CONCRETE BEARING 1' ABOVE BOOT FLANGE. PLACE 8 MIL
BLOCK UNDER HYDRANT POLYETHYLENE. .FILM ARCLIND TOP AND. .SIDES OF
GRAVEL.
FIRS HYDRANT ASSEMBLY
LEVEL ALL GROUND
LEVEL ALL GRDUN➢ MIN 3' RADIUS
MIN 3' RADIUS
1 6 ONE MAN ROCK
�1 1
1 -
6
.,
6" CONCRETE PAD 6 CONCRETE PAD,,
CU T FILL
HYDRANT LOCATION IN CUT OR FILL
TY
�► °� PUBLIC WORKS FIRE HYDRANT ASSEMBLY STD. PLAN - 310.1
DEPARTMENT
�F.N,Vp MARCH .2010
4�
4:_
11-1/4` BEND 22-1/2` BEND 45' BEND
CAP
GEE 90, BEND
'THIROSY BLOCK BEAOIOG AREA II S00ABE"FEET (SEE NOTES) 1Ftlt�''NttRlZDia^FA'L "1k`NEi lFibitfd^IYDI�U VFfiTiCA't- BL'iV115'„
SOIL
FIRM SILT OR
SISAND FIRM LTY
COMPACT SAND
COMPACT SAND & GRAVEL
90,
45' BEND
11 1/4'
90'
45' BEND
11 1/4'
90'
45' BEND
11 1/4'
FITTING
BEND
TEE
CAP OR PLUG
& 22 1/2'
BEND
TEE
CAP OR PLUG
& 22 1/2"
BEND
TEE
CAP OR PLUG
& 22 1/2'
BEND
BEND
BEND
4"
7.0
4.2
1 4.2
1.7
2.9
2.1
2.1
1.0
2.2
1.6
1.6
1.0
C
13.3
9.4
9.4
3.8
6.7
4.7
4.7
1.9
5.0
3.5
3.5
1.4
8"
23.3
16.7
1 16.7
6.7
11.7
8.4
8.4
3.4
8.8
6.3
6.3
2.5
12"
53.0
37.51
37.5
15.0
26.5
18.8
18.8
7.5
20.0
14.0
14.0
5.6
AREAS CALCULATED ON 300 PSI TEST PRESSURE, 3'-0" MIN, COVER FOR WATERMAIN LESS THAN 12",
4'-0" MIN. COVER FOR WATERMAIN 12" OR GREATER.
MAX. HEIGHT OF THRUST BLOCK (FT) - 0.5 x DEPTH OF TRENCH
MIN. HEIGHT OF THRUST BLOCK (FT) = O.D. PIPE + 1.0'
THRUST BLOCK BEARING
AREA REFERS TO THE
FACE OF BLOCK MEASURED
IN SQUARE FEET
NOTES:
1. LOCATION AND SIZE OF BLOCKING FOR PIPE LARGER THAN 12"DIAMETER AND. FOR SOIL TYPES
DIFFERENT THAN SHOWN SHALL BE DETERMINED BY THE ENGINEER.,
2. ALL BLOCKING SHALL BE POURED IN PLACE AGAINST UNDISTURBED NATIVE GROUND.
3. ALL POURED THRUST BLOCKS SHALL BE BACKFILLED AFTER MIN. 1 DAY. PRESSURE TESTING
SHALL OCCUR AFTER CONCRETE HAS REACHED NOMINAL COMPRESSIVE STRENGTH.
4. ALL BLOCKING SHALL BE CONCRETE CL 5 (1-1/2"),
5. BLOCKING AGAINST FITTINGS SHALL BEAR AGAINST THE GREATEST FITTING SURFACE AREA
POSSIBLE, BUT SHALL NOT COVER OR ENCLOSE BELL ENDS, JOINT BOLTS OR GLANDS
REASONABLE ACCESS TO BOLTS AND GLANDS SHALL BE PROVIDED.
CONCRETE BLOCKING FOR STD. PLAN - 330.2
• PUBLIC WORKS
+ + HORIZONTAL AND DOWNWARD
DEPARTMENT VERTICAL BENDS
MARCH 2O10
CALL 48 HOURS
BEFORE YOU DIG!
811
Aowu %R1
CITY OF
17 RENTON
Planning/Building/Public Works Dept.
W - 395504
T
J
W
17)
IN COMPLIANCE WITH CITY OF RENTON STANDARDS 0
RENTON COMMONS LLC
215 WHITWORTH AVE S, RENTON, WA 98057
COR STD DETAILS
m
Cn
Z
O
75
2
O
DATE: U
11/15/2017 Z
FIELDBOOK: O
PAGE: I _
DRAWING NO:
C7.4 ,z
SHEET: 1 3 OF: 15 Ir