INSTALL DECAL NUMBERS/LETTERS VERTICALLY
DECAL NUMBERS/LETTERS, SEE NUMBERING
EXAMPLE, THIS SHEET. SHALL BE INSTALLED IN
DRY WEATHER. 50' F OR ABOVE
3
E?
4
C
5
i
6
C0
z
7
0
NUI�EItlNO E7iANltb �
Tn
NOUNiMO118WOl7AL
1-3/4- TO 2'
�- PEDESTRIAN SCALE
CURB DECAL
TRAFFIC
Fl_Dw
OVAL 01MAYION
FOR POU3 $11MM ON SM PLAN 1111.1
PEDESTRIAN SCALE
DECAL
Ci-PEDESTRIAN SCALE
CURB DECAL GCURB
1RAIDC TRAFFIC
~FLOWW
DWALOIICRAlION
PORIO1N!lI "ONlfOR M1O2
TRAFFIC
Flow
DECAL ORIENTATION
FOR POLES SHOIM ON STD PLAN 117.1 A 117AA
NOAONA7�CAIJIOlCAL P®Ei1gANNCAl,E061
DECAL NOTES:
1, DECALS SHALL BE REFLECTORIZED, GOTHIC FONT, GOLD OR WHITE LEGEND ON
BLACK BACKGROUND
LUMINAIRE STANDARD DECAL
PUBLIC WORKS NUMBERING SYSTEM
i� DEPARTMENT APPROVED: 7/27/2022 1
Pa P ! Mardn stucha
N S DATE
SCALE
CALE
STD. PLAN - 121
Envelope ID: 9D9BODA8-03854664-AE66-57BFF1561D7F NOTES
1. WHERE FOUNDATION PAD IS LOCATED WITHIN A SIDEWALK. CONSTRUCT
PAD TOP FLUSH WITH SIDEWALK GRADE, OMITTING CHAMFER WHERE
TOP AND SIDEWALK ABUT. MOUNT TOP SHALL BE FINISHED BY A
CONCRETE CONTRACTOR AND SHALL MEET THE REQUIREMENTS OF
SECTION B-14,3 IN THE WSDOT STANDARD SPEaFTCATIONS.
2. PAD MOUNT DESIGN IS TYPICAL
3. PLACE A SILICONE SEAL BETWEEN THE FOUNDATION AND CABINET.
4. ANCHOR BOLTS AND THEIR SPACING TO BE SUPPLIED BY CABINET
MANUFACTURER AND SUBMITTED TO THE ENGINEER FOR APPROVAL
5. CONDUIT SIZES/OUANTITIES FOR CONTROLLER CABINETS SHALL BE
INSTALLED PER THE CONTRACT PLANS. PLUS ONE 2' SPARE CAPPED
OUT PAST THE FOUNDATION.
6- CONCRETE CLASS PER STD PLAN 135.
ELECTRICAL SERV7CE/BBS CARNET --, 7 2' CONDUIT SHALL BE PLACED FROM THE ELECTRICAL SERVICE/HBS
CONTROLLER CABINET
SHIM TO PLUMB
SHIM TO PLUMB
SEE NOTE 3 SEE NOTE 3
4 HOOPS
CABINET TO THE CONTROLLER CABINET.
S. EACH CABINET SHALL HAVE A )V DIAMETER PLASTIC DRAIN PIPE.
9. LOCATE CONDUITS CENTRALLY WITHIN THE CABINETS.
10. WHEN ALL THREE CABINETS ARE TO BE INSTALLED AND SPACE
ALLOWS, A COMBINED FOUNDATION SHALL BE USED.
11. WOODEN SHIMS SHALL NOT BE USED
12. GROUNDING SHALL BE PER WSDOT STANDARD PLAN J-60.05, SHEET 3
11 CONDUIT SIZES/QUANTITIES FOR ELECTRICAL SERVICE CABINETS SHALL
BE INSTALLED PER THE CONTRACT PLANS, PLUS ONE 2- SPARE
CAPPED OUT PAST THE FOUNDATION.
SHIM TO PLUMB
(EQUAL SPACES)
SEE NOTE 3
.401
III
2-
1r
111 -_1J
11
6• MIN
Jr
Ld Li I'
TO 2' J
FRONT VIEW
3 - jV REINFORCING BAR (EQUAL SPACES) -,
W
�j--
3/8- DIAMETER PLASTIC
DRNN (ONE PER CABINET)
SEE NOTE 5
/
SEE NOTE 7
3/8' DIAMETER PLASTIC DRAIN
SEE NOTE 13
iC
E
,
Do=
m; _=
-�O: -=
31
I�
1'-0-
NQRIZQNTAL_
COMBINED FOUNDATION
A
REINF. BAR DIAGRAM
6 PIECES
k�
REINFORCING BAR
I
(EQUAL SPACES)
Icr
PLAN VIEW
COMBINED CONTROLLER/ELECTRICAL SERVIQE/BBS FOUNDATION
` CABINET FOUNDATION STD. PLAN - 126.2
PUBLIC WORKS DETAILS APPROVED:
DEPARTMENT M Pastucha 7/27/2022
" DATE
M
a
M
Z
LABEL THE STREET FACING SIDE OF THE CABINET
WITH ADDRESS NUMBER (W/O STREET NAME) USING
AN ENGRAVED PHENOLIC NAMEPLATE WITH 2" HIGH
BLACK LETTERING ON WHITE BACKGROUND. ATTACH
NAMEPLATE WITH ADHESIVE
BASE
MAIN
CONTROL
LTG
GROUND
FAULT
RECEPT
THE METER DOOR SHALL BE REMOVABLE.
UNLESS SPECIFIED IN THE PLANS, THE
METER DOOR HINGE SHALL BE LOCATED
ON LEFT SIDE OF THE CABINET
WIRING SCHEMATIC
PHOTO
CELL
TEST SERV
SWITCH VVIREV
120/24OV, SINGLE PHASE, 3 WIRE
DIAMETER = 7/8"
4- 7/8"
ILL UMINA TION PLAN
OF
C YPR US LANE SHORT PLAT
A PORTION OF SECTION 11, TOWNSHIP 23 N., RANGE 05 E., W.M.
CITY OF RENTON, KING COUNTY, WASHINGTON
ELEVATION
L 32"
I
O
40"
SECTION
72"
O
FOOTPRINT
O NOTES PER STANDARD PLAN 122-2
LOAD LINE 1/4"
FUSE
I
CUTTING RINGS
FUSE KIT
VV I C 3r LII.0
SPLICE KIT FUSE KIT & SPLICE KIT DETAILS
ADOPTED
CITY OF RENTON
._
STANDARD PLANS
LST DATE:04/04
nwr. NAMF, .11111 CP PA(:
REVISION
DocuSign Envelope ID. F09FD439-BD22.4654-ABD3-E560AA1F5959
l'l)'V1NU�E� 1 M HEDULE
O METERBASE: 200 AMP, 4 JAW, MANUAL BYPASS, B-LINE U264
W/ 51' JAW AT 9:00 POSITION
O PANELBOARD: 120/240 VAC, 125 AMP COPPER BUS, I PHASE, 3 WIRE, 18 CKT, I OK AIC
MAIN BREAKER: 200 AMP FRAME, 200 AMP TRIP, 2 POLE, EATON ED2200
BOLT -ON BRANCH BREAKERS, EATON TYPE BAB:
2 - 20/2 ILLUMINATION A. B
1 - 20/1 ITS
1 - 20/1 GROUND FAULT RECEPTACLE
1 -40/1 SIGNAL (IF PRESENT)
I - 40/1 AUXILLIARY SIGNAL (IF PRESENT)
2 - 60/2 SMALL CELL BRANCH
I - 1511 CONTROL
3 - 20/1 SPARE
3O CONTACTOR: NEMA LIGHTING RATED, 30 AMP 4 POLE, 120 VAC COIL,
SQD 891ODPA34VO2 -1 REQUIRED
4O PHOTO ELECTRIC CELL: 1800 WATT, 120 VAC, TWIST LOCK, ALR #SST-TES-UL
MOUNTED INSIDE CABINET BEHIND WIREGLASS WINDOW
SO PHOTO -CELL BYPASS SWITCH:
SPDT, 15 AMP, RATED (UP TO) 277 VAC (FED THROUGH TERMINAL BLOCK)
6O GROUND FAULT RECEPTACLE: 20 AMP, 125 VAC. DUPLEX
CABINET:
CONSTRUCTION:
NEMA TYPE 3R, OUTDOOR PADMOUNT, 1 /8" 5052-H32 ALUMINUM CONSTRUCTION, OPEN BOTTOM
FRAMED WITH 2" ANGLE, 2 SCREENED AND GASKETED VENTS, REMOVABLE EQUIPMENT
MOUNTING PAN, CABINET GROUND WITH MINIMUM BONDING WIRE TO NEUTRAL
DOORS: HEAVY-DUTY CONCEALED HINGES (LIFT-OFF TYPE),STAINLESS STEEL VAULT HANDLES WITH
ROLLER RODS THAT PROVIDE 3-POINT COMPRESSION ON CLOSED CELL NEOPRENE GASKET,
"BEST" LOCK ON LOWER DISTRIBUTION DOOR WITH CARD HOLDER,
PADLOCKABLE UPPER METER DOOR WITH POLISHED SAFETY GLASS WINDOW
DEADFRONT: FANGED AND SECURED WITH QUARTER -TURN FASTENERS
FINISH: MILL FINISH ALUMINUM
I - REQUIRED
UL LISTED PER STANDARD #508A
"SUITABLE FOR USE AS SERVICE ENTRANCE"
NOTE:
1. SIGNAL BREAKER(S) SHALL BE ADDED WHEN APPLICABLE
\ SERVICE CABINET NOTES PLAN - 122.2
PUBLIC WORKS APP OV D:
BStUCK4/2021 1DEPARTMENT 4
NT madinDATE
GENERAL NOTES:
1. ALL EXISTING TRANSPORTATION INFRASTRUCTURE FEATURES SHALL BE MAINTAINED ON LEVEL
GRADE IF THE SURFACE LEVEL FROM CONSTRUCTION IS CHANGED (I. E. JUNCTION BOXES,
LUMINAIRE POLES, TRAFFIC SIGNAL POLES, SIGN POSTS).
2. ALL TRANSPORTATION INFRASTRUCTURE SHALL BE PROVIDED ON LEVEL GRADE ONCE
CONSTRUCTION IS COMPLETE.
3. ALL EXISTING OR PROPOSED TRANSPORTATION INFRASTRUCTURE FEATURES WITHIN THE PROJECT
CONSTRUCTION LIMITS SHALL MEET CURRENT ADA STANDARDS (I.E. JUNCTION BOXES SHALL
HAVE NON-SKID LIDS).
4. ALL NEW TRAFFIC SIGNALS SHALL BE CONSTRUCTED WITH FIBER COMMUNICATION CONNECTION
TO CITY OF RENTON TRANSPORTATION FIBER OPTIC NETWORK.
5. ALL TRANSPORTATION INFRASTRUCTURE FEATURES THAT ARE TO BE REMOVED AND REINSTALLED
AT A LATER DATE SHALL BE RE -INSTALLED TO CURRENT STANDARDS.
6. ALL CONDUIT SHALL BE PVC SCHEDULE 80.
7. SIGNAL POLE, LUMINAIRE, AND CABINET FOUNDATIONS SHALL BE CLASS 4000P CONCRETE.
8. ALL PROPOSED SIGNAL POLE FOUNDATIONS AND EXISTING MODIFIED SIGNAL POLE FOUNDATIONS
SHALL INCLUDE A CONCRETE PAD AROUND THE FOUNDATION. PROPOSED OR EXISTING SIDEWALK
SHALL BE CONSIDERED PART OF THE FOUNDATION PAD. FOUNDATION PAD SHALL BE AT LEAST
2 FEET OFFSET FROM THE SIGNAL POLE FOUNDATION, AS SPACE ALLOWS OR UNLESS
OTHERWISE APPROVED.
9. WHEN THE TRAFFIC SIGNAL IS OPERATIONAL, VEHICLE DETECTION SHALL BE MAINTAINED AND
REMAIN FUNCTIONAL. NEW PERMANENT/TEMPORARY VIDEO DETECTION SHALL BE INSTALLED
AND OPERATIONAL PRIOR TO DESTROYING ANY EXISTING VEHICLE DETECTION.
10. ALL TRAFFIC SIGNAL SYSTEMS, ILLUMINATION SYSTEMS, OR OTHER ELECTRICAL TRANSPORTATION
SYSTEMS ARE SUBJECT TO INSPECTION BY CITY OF RENTON PUBLIC WORKS/TRANSPORTATION
PRIOR TO FINAL ACCEPTANCE. CONTRACTOR TO COORDINATE INSPECTION WITH THE
TRANSPORTATION OPERATIONS MAINTENANCE MANAGER OR OTHER TRANSPORTATION OPERATIONS
MAINTENANCE REPRESENTATIVE.
.-
I� PUBLIC WORKS
DEPARTMENT
NS
TRANSPORTATION NOTES
STD. PLAN - 135
APPROVED: 7/27/2022 I
Martln Pastucha
UA IE
SURVEYED: QD'A/
DESIGNED: /
UOI f//ITD/l?
DRAWN: 914LIZAS
CHECKED: TDO
BY DATE AP P R APPROVED: CTB
SCALE:
ONE INCH
AT FULL SCALE
IF NOT ONE INCH
SCALE ACCORDINGLY
DocuSign Envelope ID. 9D9BODA8-0385-4664-AE66-578FF1561D7F
CONDUIT ENTRANCE AREA, SEE NOTE 13, STD PLAN 126.2
o•o
SEE STD PLAN 126.2 FOR ADDITIONAL NOTES
d d
PLAN VIEW
SIZE TO FIT SIZE TO FIT
CABINETCABINET
-GRADE LEVEL
N • ,• • d
FRONT VIEW SIDE VIEW
ELECTRICAL SERVICE CABINET FOUNDATION
SEE STD PLAN 126.2 FOR ADDITIONAL NOTES
El
SHIM TO PLUMB
SEE NOTE 3
T
0
4 HOOPS
I
4 BAR EACV CORNER
MIN
- - - Nq
-
`
1 TO 2"
3/8" DIAMETER PLASTIC DRAIN
SIDE VIEW
CABINET DEPTH
V-6" + 2
V-6"
4
- - -
- -
#4 BAR EACH
i
#4
CORNER
z
CD
_ _ _
P�
-N�
_HOOPS
PLAN VIEW
CONDUIT ENTRANCE AREA,
SEE NOTE 5, STD PLAN 126.2
CONTROLLER CABINET FOUNDATION
` CABINET FOUNDATION STD. PLAN - 126.1
y� PUBLIC WORKS DETAILS APPROVED:
DEPARTMENT Martin Pastucha 7/27/2022
N -
DATE
TENW PROJECT NO. 2022-135
9TENW
Transportation Engineering NorthWest
Transportation Planning I Design I Traffic Impact & Operations
11400 SE 8th St, Suite 200, Bellevue, WA 98004 1 Office (425) 889-6747
Project Contact: Trevin Roletto, P.E.
Phone: 425-250-0583
VERTICAL: NAVD 1988
HORIZONTAL: NAD 1983/1991 CITY OF
RENTON
DATU M vftov
Planning/Building/Public Works Dept.
T-423006 � 044-2023
IN COMPLIANCE WITH CITY OF RENTON STANDARDS
alb
DEVELOPMENT ENGINEERING TRANSPORTATION OPERATION
Wanders 06/07/2023 5 ~
CBarnes 06/12/2023 J
I-
W
Z
DATE:
0411412022 rJn
CY P R U S LANE PLAT FIELDBOOK:
PAGE:
TUSCANY CONSTRUCTION LLC DRAWING NO:
PO BOX 2170 I L-04
RENTON, WASHINGTON 98056 SHEET: 37 0F: 37 CU