HomeMy WebLinkAboutR-422951A PORTION OF THE NW 1/4 OF SECTION 19, TOWNSHIP 23 NORTH, RANGE 5 EAST, W.M., KING COUNTY, WASHINGTON
rn
N
N
I
O
w
z
J
U-
4 3
34
18 10 9
19 33
� 4 �_4
I
12
8
15 7
8
TYP.) 1s
HATCH IN
OPEN POSITION
VALVE VAULT
PLAN VIEW
VALVE VAULT
PROFILE VIEW
PROVIDE 25 MIL A. d a
COAL TAR EPDXY a d
EXTERIOR COATING ° a a .a "
A• 19 21
15
36 ; a 10
17
3
FORCEMAIN
PER PLAN r,
HATCH IN
OPEN
POSITION
SLOPE POURED CONCRLIL
FLOOR 2% MIN.
a
d• d 40 d d
C : d ` d
d
STAINLESS STEEL PIPE SUPPORTS, BOLT TO SLAB, TYP.
PUMP STATION DATA
PUMP STATION SCHEDULE P-1 AND P-2
SPECIFICATIONS
MAKE =
FLYGT
MODEL =
NP 3085 SH
Q =
270 GPM
STATIC HEAD =11.8
FEET
PUMP DISCHARGE SIZE =
3—INCH TO 4—INCH
PUMP MOTOR =
N3085.070 05-07-4AL—W 2.2HP, 3 PHASE, 460 V,
60 HZ
MOTOR SPEED =
VARIABLE SPEED (MAX:1670 RPM)
PUMP IMPELLER =133mm
DIAMETER
6" DIA. SDR35 PVC VENT ELEVATION =
21.14
12" DIP OVERFLOW ELEVATION =
20.64
HIGH LEVEL ALARM ELEVATION =
20.64
LEAD PUMP ON MAX POWER ELEVATION =15.32
LEAD PUMP ON MIN POWER FLOW ELEVATION =13.82
LAG PUMP ON MIN POWER FLOW ELEVATION =16.42
PUMP OFF ELEVATION =
9.82
LOW LEVEL ALARM ELEVATION =
7.44
WET WELL FLOOR ELEVATION =
6.08
WET WELL 4—INCH FORCEMAIN ELEVATION =
20.21
PUMP STATION NOTES
1. IN THE EVENT THAT SUMP LEVEL EXCEEDS ELEVATION 18.90, OR DROPS BELOW
ELEVATION 6.81, ACTIVATE LOCAL ALARM. ALARM STYLE TO BE DETERMINED BY OWNER
PREFERENCE.
2. FORCEMAIN PIPING SHALL BE INSTALLED WITH A MINIMUM OF 2' COVER OUTSIDE OF
VAULTS AND ADJACENT PAVED SURFACES.
3. SEE ELECTRICAL PLANS FOR PUMP POWER AND CONTROL PANEL
4. CONTROL PANEL SHALL HAVE LOCAL HAND —OFF —AUTO SWITCHES FOR EACH PUMP TO
OVERRIDE COMMANDED POSITION IN AN EMERGENCY.
5. LIFT STATION CONTROL PANEL SHALL BE EQUIPPED WITH PUMP STATUS LIGHTS.
6. LIFT STATION SHALL BE EQUIPPED WITH INTERNAL LIGHTS FOR SERVICING AND
MAINTENANCE OF THE PUMPS, PIPING, AND VALVES. LIGHT SWITCHES SHALL BE
LOCATED ON PUMP PANEL.
7. FLOAT ELEVATIONS TO BE ADJUSTED BASED ON FIELD PERFORMANCE TO PREVENT
FLOODING OF THE PUMP STATION AND TO MATCH DESIGN FLOWS.
8. PUMPS SHOULD BE INSTALLED SO AS TO SLOWLY RAMP UP OR DOWN TO DESIGN FLOWS
OVER A PERIOD OF 30 SECONDS.
AS A CONDITION OF APPROVAL:
9. VERIFY PUMPS DISCHARGE AT DESIGN FLOW RATES.
THE FINAL TAB REPORT SHALL BE
PROVIDED TO THE CITY'S
DEVELOPMENT ENGINEERING PROJECT
MANAGER TO VALIDATE THE DESIGN
FLOWS HAVE BEEN ACHIEVED.
6" DIA. SDR 35 PVC VENT,
COORDINATE OUTLET WITH
OWNER. RIM TO IE=3'—O"
26 MOUNT FLOAT TREE WITH
STAINLESS STEEL BOLTS IN
LOCATION ACCESSIBLE FROM
LADDER. ROUTE CONTROLS
(TY
P.)
AND POWER TO PUMP PANEL.
4
(TYP.) 4
22
n (TYP.)
(TYP.) (TYP.) �J
(TYP.)
14 (TYP.)
SLOPE POURED FLOOR
TO DRAIN (TYP.)
6" DIA. SDR 35 PVC VENT,
COORDINATE OUTLET WITH
OWNER. RIM TO IE=1'-6"
ATTACH UPPER STAINLESS
STEEL SLIDE RAIL SUPPORT _
TO PUMP VAULT LID WITH
STAINLESS STEEL BOLTS
FORCEMAIN FORCEMAIN
• d
PER PLAN n PER PLAN
IV
PROVIDE o4" VAULT
DRAIN BETWEEN WET
WELL AND VALVE VAULT. C25
31
30
30
.d
4.
a_
STAINLESS
STAINLESS STEEL
LIFT CHAIN
:a
d
29
SLOPE LIP AT 45°.
CLEAR PUMPS AND
COUPLINGS
• Call 811
• ® two business days
before you dig No.
n
a
10
1
HATCH IN
OPEN POSITION
DUPLEX SUBMERSIBLE
PUMPS P-1 & P-2
HATCH IN
OPEN POSITION
PUMP STATION
PLAN VIEW
LO) PUMP CONTROL FLOAT SWITCHES. SHOWN
37 AT THIS LOCATION FOR CLARITY, FLOAT
TREE SHALL BE MOUNTED BEHIND LADDER
FOR EASE OF ACCESS/MAINTENANCE
PUMP STATION
a PROFILE VIEW
REVISION
Ell
J
27
ELEV PER STATION TABLE
PROVIDE 25 MIL COAL TAR
EPDXY EXTERIOR COATING
LAG PUMP ON MIN.
ELEV PER STATION TABLE
ONE PUMP ON MAX.
FLOW ELEV PER STATION TABLE
d
ONE PUMP ON MIN.
a.
a
FLOW ELEV PER STATION TABLE
INLET PIPE PER
PLAN
PUMP OFF ELEV
PER STATION TABLE
LOW LEVEL ALARM
ELEV PER STATION TABLE
DUPLEX SUBMERSIBLE
PUMPS P-1 & P-2
PUMP INLET ELEV PER
PER STATION TABLE
VAULT BOTTOM ELEV PER
PLAN
SURVEYED:
DESIGNED:
DKM/RJJ
DRAWN:
KLK/DKM
CHECKED:
DCD
BY DATE APPR APPROVED:
DCD
SCALE:
AS NOTED
ONE INCH
AT FULL SCALE
IF NOT ONE INCH
SCALE ACCORDINGLY
MATERIALS LIST
MATERIALS LIST
SIZE
TYPE
1
PUMP BASE
3" DIA
2
FL X MJ ADAPTER WITH MEGALUG
3" DIA
DIP
3
FL X MJ ADAPTER WITH MEGALUG
4" DIA
DIP
4
PUMP DISCHARGE PIPELINE
4" DIA
DIP
5
IMJ 90 DEGREE ELL WITH 2 MEGALUGS
4" DIA
DIP
6
IROMAC 501 TRANSITION COUPLING
4" DIA
DIP
7
ROMAC 501FAC (FLANGED COUPLING ADAPTER)
4" DIA
DIP
8
FLANGED DIP TEE
4"X1 "X4"
DIP
9
MUELLER A-2602-6-0261 RUBBER DISC FACE
4" DIA
DIP
10
FL RESILIENT SEAT WEDGE GATE VALVE NON RISING STEM WITH 2" OPERATIONAL NUT. GATE VALVE NORMALLY
4" DIA
DIP
OPEN
11
MJ WYE WITH MEGALUGS
6"X6"X6"
DIP
12
FL X MJ 45 DEGREE ELL WITH MEGALUG
4" DIA
DIP
13
PROVIDE H-20 RATED LOCKING FRAME AND COVER, OLYMPIC FOUNDRY M1025 OR EQUAL. CAST INTO THE
4" DIA
DIP
VAULT TOP.
14
ISHACKLED CLAMP OR MEGALUG
4" DIA
DIP
15
SEWAGE COMBINATION AIR/VAC VALVE. APCO SERIES 440 SCAV, MODEL 443 1". PROVIDE INLET AND OUTLET
1
BACKFLUSHING NIPPLES AND SHUT OFF GATE VALVES. GATE VALVES NORMALLY CLOSED.
16
LINK SEAL. SIZE TO FIT ANNULAR SPACE BETWEEN PIPELINE OUTSIDE DIAMETER AND CONCRETE VAULT WALL
CORE DRILL.
PROVIDE 3" DIAMETER DIP BLIND FLANGE, DRILLED AND TAPPED FOR 1" NPT, (2) 1" DIAMETER S.S. NIPPLES
17
AND (1) INLET S.S. GATE VALVE. GATE VALVE NORMALLY OPEN.
PROVIDE 24" DIAMETER DIP FRAME AND COVER PER WSDOT STANDARD PLAN B-30.70-04, H2O RATED, BOLT
18
DOWN/WATERTIGHT TYPE 2, STANDARD "STORM." CAST INTO VAULT TOP.
PROVIDE POLYPROPOLENE LADDER WITH RETRACTABLE CENTER SAFETY RAIL, LANE POLYPROPOLENE VAULT
19
LADDER COMPLYING WITH ASTM D4101 AND C497 REQUIREMENTS. SECURE IN ACCORDANCE WITH
MANUFACTURER REQUIREMENTS.
ACCESS HATCH, LW HATCH HD-3C, 36" X 54" DOUBLE LEAF DOOR WITH SAFETY GRATING, ALUMINUM
20
DIAMOND PLATE HATCH COVER, S.S. HARDWARE, SPRING LOADED WITH LOCKING MECHANISM, DRAINAGE
CHANNEL AND HOLD OPEN ARM. CAST INTO VAULT TOP.
PROVIDE 2" SQUARE VALVE EXTENSION, FIELD DETERMINE LENGTH. PROVIDE 10" DIAMETER X Y4" RING AT TOP
21
OF EXTENSION AND WELD TO EXTENSION. PROVIDE 3' TALL TEE HANDLE EXTENSION FOR ABOVE GRADE VALVE
OPERATION. STORE THE TEE HANDLE INSIDE OF THE VAULT ON HANGARS LOCATED NEAR THE LADDER.
PROVIDE BLACK POWDER COATING ON THE VALVE EXTENSION AND THE TEE HANDLE.
22
4" DIAMETER GPK SAND COLLAR
23
4" DIAMETER SDR 35 PVC PIPE
24
PROVIDE PIPE BELL OR GASKETED STOP COUPLING
25
PROVIDE 4" DIAMETER PVC SOLVENT WELD BACKWATER CHECK
26
6" DIAMETER GPK SAND COLLAR
27
72" DIAMETER TYPE 3 CONCRETE PUMP STATION PER WSDOT STANDARD PLAN B-15.60-02 ABD B-30.90-02
28
MJ ENLARGEMENT WITH MEGALUGS
3"x4"
DIP
29
CLASS 3000 COMMERCIAL CONCRETE PER WSDOT STANDARD SPECIFICATION 6.02
30
PROVIDE PUMP GUIDE RAIL SYSTEM, GUIDE RAIL SUPPORT AND HARDWARE. ALL COMPONENTS SHALL BE
STAINLESS STEEL.
31
PROVIDE PUMP DISCHARGE PIPE SUPPORT, SHACKLE CLAMPS, ALL THREAD AND WALL ANCHORS AT MINIMUM'
O.C. ALL COMPONENTS SHALL BE S.S. OR DUCTILE IRON.
PROVIDE 1-12—SE (30"X60") ALUMINUM DIAMOND PLATE DOOR WITH SAFETY GRATING, H-20 HATCH, S.S.
32
HARDWARE, SPRING LOADED WITH LOCKING MECHANISM, DRAINAGE CHANNEL AND HOLD OPEN ARM CAST INTO
TOP.
33
MJ ENLARGEMENT WITH MEGALUGS
4%6"
DIP
34
PUMP DISCHARGE PIPELINE
6" DIA
DIP
35
ROMAC 501 TRANSITION COPUPLING
6" DIA
DIP
36
SHACKLED CLAMP OR MEGALUG
6" DIA
DIP
37
OVERFLOW PIPE
12" DIA
DIP
1,D C. sitts&hill
O� of w�'9�
4 C rJ1 CIVIL I STRUCTURAL I SURVEY
4815 CENTER STREET I TACOMA, WA. 98409
V PHONE: (253) 474-9449 1 FAX: (253) 474-0153
http://www.sittshill.com/
Project No.: 19480 Project Mgr.: DCD
46449 4
Proj. Engineer: DKM/RJJ Proj. Drafter: KLK/DKM
SIpNpL >��
4M. R-422951
IN COMPLIANCE WITH CITY OF RENTON STANDARDS
DEVELOPMENT ENGINEERING
- Wanders 05/08/2023
HORIZONTAL SCALE: 1 "=2'
4 0 2 4
2 VERTICAL SCALE: 1"=2' 4 NORTH
DATE:
VERTICAL: NAVD
1988
HORIZONTAL: NAD 1983/1991 CITY OF • BROTHERTON CADILLAC - RENTON
3/1
[;R
FIELDBOOK:
RENTON PAGE:
• DRAWING NO:
DATUM Planning/Building/Public Works Dept. LIFT STATION AND VALVE VAULT NOTES AND DETAILS C3.1 OC
(PRIVATE AND PUBLIC) SHEET: nC OF:2A
Ln
N
T
O
O
I
N
Q
J
LO
O
co
N
N
WE