HomeMy WebLinkAboutW-422905A PORTION OF THE NW 1/4 OF SECTION 19, TOWNSHIP 23 NORTH, RANGE 5 EAST, W.M., KING COUNTY, WASHINGTON
N
N
N
^^I
n
rr
1
.0
EXISTING AS -
WATER MAIN,
LOCATED 2024-C
SEE OVERALL I
FOR COORDII
ENLARGED DOUBLE DETECTOR CHECK VALVE
.` J SCALE: N.T.S.
KEY NOTES
1�
EXISTING 8" PUBLIC WATER MAIN
P�
HOT TAP, VALVE, AND METER PER
STD. PLAN 320.3/C5.4C
P�
8" VALVE BOX
4�
30" X 17" METER BOX
5�
±36" x 18" HOT BOX FOR RPBA
CONCRETE THRUST BLOCK AT 90°
BEND OF 6" FIRE SERVICE
DOMESTIC WATER
�'ATMCTION DETAILS.
GENERAL NOTES
1. SEE STD. PLAN 330.2/C5.3C FOR CONCRETE
THRUST BLOCKS.
2. SEE STD. PLAN 320.3/C5.4C FOR WATER METER
INSTALLATION.
3. SEE STD. PLAN 350.2/C5.4C FOR RPBA
INSTALLATION.
KEY NOTES
1� 6" DDCV ASSMBLY WITH STANDPIPE OUTSIDE CONNECTION PER STD.
PLAN 360.2/C5.3C
6" D.I. CLASS 52 SERVICE PIPING, LENGTH PER PLAN
3� 6" D.I. 90 DEGREE FITTING WITH CONCRETE THRUST BLOCK
8"X6" TAPPING TEE (MJxFL) WITH CONCRETE THRUST BLOCK
:� 6" GATE VALVE (FLxMJ)
4" x 2 Y2" FIRE DEPARTMENT DOUBLE CONNECTION
:� SUMP PUMP PER 520/C5.3C
8� INSTALL FIRE HYDRANT PER STD. PLAN 310.1/C5.4C
REMOVE EXISTING HYDRANT AND PIPE
GENERAL NOTES
1. SEE STD. PLAN 330.2/C5.3C FOR CONCRETE THRUST BLOCKS.
2. SEE STD. PLAN 360.2/C5.3C FOR ALL APPURTENANCES AND
DIMENSIONS ASSOCIATED WITH DDCV ASSEMBLY.
5
HORIZONTAL SCALE: 1"=5'
0 5 10
CAUTION VALVE BOX SHOULD NOT REST ON
?
PIPE. LATER COMPACTION IN AREA OF VALVE BOX
COULD CAUSE THE BREAKAGE OF THE SERVICE.
w
0 11 12 0
o:
a
En
PLUMBING
9" MIN.
9 SHALL CONNECT
X.
HERE
oo
rPRIVATE
M]
]
2" BRASS PLUG
CRUSHED ROCK BASE
(THREADED)
TO SUPPORT VAULT.BY
PASS NOT ALLOWED
FOR IRRIGATION METERS
13
MIPT x QUICK JOINT
1-1/2 AND 2 WATER SERVICE DETAIL
a
MATERIAL LIST FOR 2" SERVICE WITH METER LOCATED IN RIGHT-OF-WAY BEHIND SIDEWALK
1. 2" tapped tee on new water meter.
2. 4" long X 2" brass nipple with threaded ends (MIPT).
A -A
3. 2" resilient seat valve with threaded ends, square operating nut and valve nut extension if DRILL 2" HOLE
FOR
required (see standard detail 330.1). TOUCHREAD DEVICE
4. Two piece cast iron valve box. Standard B" top section with regular base section, length to
fit, "lug" type cover.
5. 2" brass bushing (MIPT x FIPT) 2 each 2" brass or bronze nipples 6" length, threaded ends 2
each 2"-90' brass or bronze elbows (FIPT x FIPT)
6. 2" (MIPT) x compression fitting, Ford C84-66 or equal.
7. 2" soft copper type K or brass nipples, length to fit.
TYPICAL RIB�
8. 2" threaded brass 90' ell.
9. 2" Customsetter with by-pass Ford VBH 86-128-11-77 (17-3/16") or McDonald brass
2-1/2" MIN. FROM NEAREST
3OB715WDFF775, with flanged angle ball valve and padlock wings on inlet, and angle check valve
AND FRONT EDGE OF PIT LID
outlet, ball valve on bypass with padlock wings. Customsetter shall have vertical inlet and outlet.
10. Rigid meter spreader to be supplied and installed in meter setter by contractor.
11. Water meter shall be supplied and installed by City of Renton upon payment of all related water
meter fee and satisfactory pressure and purity tests.
12. 17"x3O" equal to Mid -States Plastics, Inc. BCF Series MSBCF 1730-18 with 2" thick Ductile iron
damond plate cover 18"x31" equal to Mid -States Plastics, Inc. MSCBC-1730-R with 2" drilled hole
for touchread pit lid, and meter read lid.
13. 2" coupling (compression x FIPT) with 2" plug (MIPT), Ford C-14-66 or equal. The property
owner is responsible for any necessary adaptation or extension of water service.
MATERIAL LIST FOR 1-1/2" SERVICE WITH METER LOCATED IN RIGHT -Of -WAY BEHIND SIDEWALK
1. 2" tapped tee on new water main
2. 4" long X 2" brass nipple with threaded ends (MIPT).
3. 2" resilient seat valve with threaded ends, square operating nut and valve nut extension if required
(see standard detail 330.1).
4. Two piece cast iron valve box. Standard 8" top section with regular base section, length to fit,
"lug" type cover.
5. 2" X 1-1/2" hex brass bushing (MIPT x FIPT), 2 each 1-1/2" brass or bronze nipples 6" length
(threaded ends), 2 each 1-1/2"- 90' brass or bronze elbows (FIPT x FIPT)
6. 1-1/2" (MIPT) x compression fitting, Ford C84-66 or equal.
7. 1-1/2" soft copper type K or brass nipples, length to fit.
8. 1-1/2" pack -joint 90' ell, for Ford L44-77 or equal.
9. 1-1/2" Customsetter with by-pass Ford VBH 66-12B x 13-3/16" or McDonald brass, with flanged
angle ball volve and padlock wings on inlet, and angle check valve outlet, ball valve on bypass with
padlock wings. Customsetter shall have vertical inlet and outlet.
10. Rigid meter spreader to be supplied and installed in meter setter by contractor.
11. Water meter shall be supplied and installed by City of Renton upon payment of all related water
meter fee and satisfactory pressure and purity tests.
12. 17%30" equal to Mid -States Plastics, Inc. BCF Series MSBCF 1730-18 with 2" thick Ductile iron
damond plate cover 18"x31" equal to Mid -States Plastics, Inc. MSCBC-1730-R with 2" drilled hole
for touchread pit lid and meter read lid.
13. 1-1/2" coupling (compression x FIPT) with 1-1/2" plug (MIPT), Ford C-14-56 or equal. The
property owner is responsible for any necessary adaptation or extension of water service.
NOTE:
ALL METER BOXES INSTALLED IN CONCRETE OR PAVED
DRIVEWAYS SHALL BE CAST-IRON EQUAL TO OLYMPIC
FOUNDARY.
EXPANSION JOINTS MUST BE INSTALLED 12" MINIMUM ON BOTH
SIDES OF METER BOX.
STD' PLAN - 320.3
PUBLIC WORKS
2 AND 1 %z' WATER SERVICE LOCATED
DEPARTMENT
O
IN RIGHT OF WAY BEHIND SIDEWALK
FEBRUARY 2010
TESTING DETAIL
00-A "
TAPPING TEE (MJxFL)
TAPPING GATE VALVE (FL XMJ)
TEMPORARY PLUG (MJ) WITH 2-INCH TAP
AND 2-INCH BLOW -OFF ASSEMBLY
CONCRETE BLOCKING
VERTICAL CROSS(MJxFL) FOR POLYPIGGING
1-BLIND FLANGE ON TOP WITH 2" TAP AND 2" PLUG
1-BLIND FLANGE ON BOTTOM
1-PLUG(MJ) WITH 2"TAP & 2" BLOW -OFF
TEMPORARY BLOCK
FINAL CONNECTION DETAIL
' O NEW D.I. WATER LINE
(IFTER ALL CLEANING BY POLYP G, PRESSURE TESTIN
G
AND DISINFECTION, REMOVE TEMPORAY BLOCK & BLOW -OFF
AND CONNECT TO VALVE WITH D.I. SLEEVE (MJ) & D.I. SPOOLS
FINAL CONNECTION BY CITY FORCES
NOTES:
1. TAPPING TEES SHALL BE MADE OF CAST IRON, DUCTILE IRON OR
EPDXY -COATED STEEL. BOLTS AND NUTS SHAL BE COR-TEN. ALL TEES
AND VALVES SHALL BE WATER TESTED BEFORE TAP
2. NO SIZE ON S1ZE TAPS ON CAST-IRON WATER LINES. TAP SHALL BE AT
LEAST 2" SMALLER DIAMETER THAN THE EXISTING MAIN.
3. NO WET TAP ON ASBESTOS CEMENT LINE OR STEEL LINE
4. WET -TAPPING OF EXISTING CITY OF RENTON WATER MAINS WILL BE DONE BY
SPEER TAP OR SUPERIOR TAPPING INC.
5. CONTRACTOR SHALL POTHOLE AND VERIFY THE HORIZONTAL AND VERTICAL
ALIGNMENT OF EXISTING LINE OR STUB AND SHALL START LAYING THE NEW
LINE AT THE SAME HORIZONTAL AND VERTICAL ALIGNMENT OF THE EXISTING
STUB.
6. CITY FORCES WILL PERFORM THE FINAL CONNECTION FROM THE WATER LINE
TO THE TAPPING VALVE WITH D.I. SLEEVE AND D.I. SPOOL.
PUBLIC WORKS CONNECTION TO WATER MAIN WITH STD. PLAN - 300.1
i DEPARTMENT TAPPING TEE & VALVE MARCH 2O10
F
FIRE HYDRANT SHALL BE COREY-TYPE EQUAL TO IOWA F-5110 OR
COMPRESSION TYPE SUCH AS CLOW MEDALLION; M & H 929, MUELLER
SUPER CENTURION 200, AND WATEROUS PACER WITH 6" MECHANICAL
JOINT INLET WITH LUGS. 5-1/4" MAIN VALVE OPENING. TWO 2-1/2"
HOSE CONNECTIONS NATIONAL STANDARD THREADS. 4" PUMPER
CONNECTION CITY OF SEATTLE THREADS WITH A STORZ ADAPTOR,
4.875" SEATTLE THREAD X 5" STORZ, ATTACHED WITH 1/8" STAINLESS
STEEL CABLE. 1-1/4" PENTAGON OPERATING NUT. FIRE HYDRANT TO
BE PAINTED WITH TWO COATS OF PAINT. KELLY-MOORE/PRESERVATIVE
PAINT No. 5780-563 DTM ACRYLIC GLOSS, SAFETY YELLOW OR
APPROVED EQUAL. PUMPER CONNECTION TO FACE ROADWAY OR AS
DIRECTED BY RENTON FIRE DEPARTMENT. FIRE HYDRANT EXTENSION TO
BE USED IF REQUIRED.
MIN. 18" TO 20" BEHIND BACK OF
CURB OR 12" BEHIND BACK OF
3'
SIDEWALK THAT IS ADJACENT TO
CURB
x x 5" STORZ
5'x5'x5x6" THICK CONCRETE PAD AROUND
HYDRANT. FINISH TO MATCH SIDEWALK
O
2
EXPANSION JOINT AT
BACK OF SIDEWALK
�fCRETE SIDEWALK
ORNPLANTING STRIP
36" MIN
COVER
TWO-PIECE CAST IRON VALVE BOX WITH LUG
TYPE COVER. EQUAL TO OLYMPIC FOUNDRY CO.
STANDARD 8" TOP SECTION WITH REGULAR BASE
SECTION LENGTH TO FIT. VALVE NUT EXTENSION
AS REQUIRED.
RAISED PAVEMENT MARKER TYPE 88-A
STIMSONITE TWO-WAY BLUE REFLECTIVE
CONCRETE BLOCKING
CONCRETE � `�i�
THRUST BLOCK
MAIN LINE TEE. WITH 6" FLANGE SIDE OUTLET.
i
GATE VALVE (FL X MJ) AWWA C-509, RESILIENT SEAT
i
6" DUCTILE IRON PIPE, CLASS 52 CEMENT LINED, LENGTH TO FIT
2-3/4" COR-TEN STEEL TIE RODS.
16" x 8" x 4" MININUM 1/2 YARD OF 1-1/4" WASHED DRAIN ROCK
CONCRETE BEARING 1' ABOVE BOOT FLANGE. PLACE 8 MIL
BLOCK UNDER HYDRANT POLYETHYLENE FILM AROUND TOP AND SIDES OF
GRAVEL.
FIRE HYDRANT ASSEMBLY
LEVEL ALL GROUND LEVEL ALL GROUND
MIN 3' RADIUS
MIN 3' RADIUS
1 ONE MAN ROCK
s
6" CONCRETE PAD 16" CONCRETE PAD
CUT FILL
HYDRANT LOCATION IN CUT OR FILL
PUBLIC WORKS FIRE HYDRANT ASSEMBLY STD. PLAN - 310.1
' ''•` ,' DEPARTMENT
V o, MARCH 2O10
HORIZONTAL SCALE: 1"=5'
5 0 5 10
SURVEYED: SCALE: e
DESIGNED: AS NOTED
DKM/RJJ
• CaLdays 2 AS -BUILT WATER MAIN ADJUSTMENTS S&H 03.21.24 DCD DRAWN: /
KLK DKM ONE INCH
• 0 two bu1 RFI 010 FIRE RISER RELOCATION S&H 08.22.23 DCD CHECKED: AT FULL SCALE
DCD before APPROVED: IF NOT ONE INCH
N0. REVISION BY DATE APPR SCALE ACCORDINGLY
DCD
VERTICAL: NAVD 1988
HORIZONTAL: NAD 1983/1991
DATUM
L] 120 VOLT ELECTRICAL OUTLET FOR
z HEAT TAPE. INSTALL HEAT TAPE
r FOR FREEZE PROTECTION
3 CENTER BACKFLOW
I PREVENTER IN
O o REDUCED PRESSURE ENCLOSURE
BACKFLOW ASSEMBLY
(RPBA) 3" MIN.
� O I
3" MIN. INSULATED ENCLOSURE
3" MIN. "HOT BOX" OR EQUAL
3/8" X 4" ANCHOR
BOLTS PER
MANUFACTURER O
�- 3" MIN.
CONCRETE SLAB z UNION Z: FINISHED
N GRADE
FINISHED
GRAD
OODRAIN
z SEE NOTE 4
6" MINIMUM SLEEVE
FREE DRAINING (TYP.)
GRAVEL z
CONNECT TO N
WATER METER
IMMEDIATELY
ADJACENT TO
RPBA
FLOW
INSTALLED W/ APP'D. TO OWNERS ELECTRICAL PANEL. FRONT VIEW
MATERIAL PER UPC DIRECT BURIAL OR IN RIGID METER SIDE
(SIZE AS REQ.) CONDUIT PER ELECTRICAL
SIDE VIEW PERMIT REQUIREMENTS.
NOTES:
1. ALL REDUCED PRESSURE BACKFLOW ASSEMBLIES (RPBA's) MUST BE LISTED ON LATEST LIST OF "BACKFLOW
PREVENTION ASSEMBLIES APPROVED FOR INSTALLATION IN WASHINGTON STATE", PUBLISHED BY STATE OF
WASHINGTON DEPARTMENT OF HEALTH.
2. THE OWNER/APPLICANT MUST OBTAIN A SEPARATE CITY OF RENTON PLUMBING PERMIT FOR THE INSPECTION
OF THE INSTALLATION OF THE RPBA AND PIPING. THE OWNER SHALL FURNISH, INSTALL AND MAINTAIN THE
RPBA AND ALL PIPING AND APPURTENANCES SHOWN ON THIS PLAN.
3. THE RPBA MUST BE TESTED BY A STATE CERTIFIED BACKFLOW ASSEMBLY TESTER AFTER ITS INITIAL
INSTALLATION, AFTER REPAIRS AND ANNUALLY THEREAFTER AT OWNER'S EXPENSE. A COPY OF THE TEST
REPORT SHALL BE SENT OR FAXED TO CITY OF RENTON WATER UTILITY ENGINEERING DEPT., ATTN: WATER
UTILITY CROSS -CONNECTION CONTROL SPECIALSIT, FAX NO. 425-430-7241.
4. DRAIN SHALL BE SIZED IN ACCORDANCE WITH AWWA CROSS CONNECTION CONTROL MANUAL STANDARDS
3" DRAIN FOR 1" OR SMALLER RPBA's, 4" DRAIN FOR 1.5" TO 2" RPBA's, 6" FOR 3" RPBA'S.
5. RPBA AND ENCLOSURE SHALL BE LOCATED ON PRIVATE PROPERTY AND AS NEAR AS POSSIBLE TO THE
WATER METER.
2Y STD. PLAN - 350.2
�u PUBLIC WORKS REDUCED PRESSURE BACKFLOW
DEPARTMENT ASSEMBLY IN HOT BOX
'�'f� • MARCH 2O10
CONSTRUCTION
RECORD DRAWING
PROJECT WAS COMPLETED IN SUBSTANTIAL
CONFORMANCE WITH THE APPROVED
PLANS. ELEVATION DEVIATIONS, WHERE
APPLICABLE, ARE DENOTED WITH PLAN
CALLOUT UPDATES, AND A STRIKEOUT
THROUGH THE ORIGINAL ELEVATION.
UTILITY AS -BUILT INFORMATION OBTAINED
BY MCKEE ENTERPRISES AND VERIFIED BY
SITTS & HILL ENGINEERS, INC.
It. I C TY OF
7R RENTON
vassiv
Planning/Building/Public Works Dept.
D C.
sitts&hill
�d9 I
�4s
tt CIVIL I STRUCTURAL I SURVEY
4815 CENTER STREET I TACOMA, WA. 98409
PHONE: (253) 474-9449 I FAX: (253) 474-0153
http://www.sittshill.com/
'�o G 49 1%� Project No.: 19480 Project Mgr.: DCD
SjOyAL �`vG Proj. Engineer: DKM/RJJ Proj. Drafter: KLK/DKM
W-422905
IN COMPLIANCE WITH CITY OF RENTON STANDARDS
BROTHERTON CADILLAC - RENTON
WASTEWATER AND WATER UTILITIES DETAILS
(PRIVATE AND PUBLIC)
DATE:
FIELDBOOK:
PAGE:
DRAWING NO:
C5.4C
SHEET: OF:
31 39