AMERISTAR® PERIMETER SECURITY USA INC.
Montage Commercial® – Commercial Steel Ornamental Fence System – Fusion Welded and Rackable
CONSTRUCTION SPECIFICATION - SECTION 32 31 19
PART 1 - GENERAL
1.01 WORK INCLUDED
The contractor shall provide all labor, materials and appurtenances necessary for installation of the welded ornamental steel fence
system defined herein at (specify project site).
1.02 RELATED WORK
Section __ __ __ - Earthwork
Section __ __ __ - Concrete
1.03 SYSTEM DESCRIPTION
The manufacturer shall supply a total fence system of (specify Montage Commercial® standard picket space or Montage Commercial®
Pool, Pet & Play® 3” air space) Welded and Rackable (ATF – All Terrain Flexibility) Ornamental Steel (for standard picket space, specify
Classic™, Majestic™, Genesis™, or Invincible™; for 3” air space, specify Classic™, Majestic™, or Genesis™) design. The ornamental fence
system shall be (specify 7’ height or 8’height) from grade. The system shall include all components (i.e., panels, posts, gates and
hardware) required.
1.04 QUALITY ASSURANCE
The contractor shall provide laborers and supervisors who are thoroughly familiar with the type of construction involved and
materials and techniques specified.
1.05 REFERENCES
ASTM A653/A653M - Standard Specification for Steel Sheet, Zinc-Coated (Galvanized) or Zinc-Iron Alloy Coated (Galvannealed)
by the Hot-Dip Process.
ASTM B117 - Practice for Operating Salt-Spray (Fog) Apparatus.
ASTM D523 - Test Method for Specular Gloss. 0020
ASTM D714 - Test Method for Evaluating Degree of Blistering in Paint.
ASTM D822 - Practice for Conducting Tests on Paint and Related Coatings and Materials using Filtered Open-Flame Carbon-Arc
Light and Water Exposure Apparatus.
ASTM D1654 - Test Method for Evaluation of Painted or Coated Specimens Subjected to Corrosive Environments.
ASTM D2244 - Test Method for Calculation of Color Differences from Instrumentally Measured Color Coordinates.
ASTM D2794 - Test Method for Resistance of Organic Coatings to the Effects of Rapid Deformation (Impact).
ASTM D3359 - Test Method for Measuring Adhesion by Tape Test.
ASTM F2408 – Ornamental Fences Employing Galvanized Steel Tubular Pickets.
1.06 SUBMITTAL
The manufacturer’s literature shall be submitted prior to installation.
1.07 PRODUCT HANDLING AND STORAGE
Upon receipt at the job site, all materials shall be checked to ensure that no damage occurred during shipping or handling. Materials
shall be stored in such a manner to ensure proper ventilation and drainage, and to protect against damage, weather, vandalism and
theft.
1.08 PRODUCT WARRANTY
A. All structural fence components (i.e. rails, pickets, and posts) shall be warranted within specified limitations, by the manufacturer
for a period of 20 years from date of original purchase. Warranty shall cover any defects in material finish, including cracking,
peeling, chipping, blistering or corroding.
B. Reimbursement for labor necessary to restore or replace components that have been found to be defective under the terms of
manufactures warranty shall be guaranteed for five (5) years from date of original purchase.
Montage Commercial Specification Ameristar Perimeter Security USA Inc. Rev. 12/08/2022
PART 2 - MATERIALS
2.01 MANUFACTURER
The fence system shall conform to (specify Montage Commercial standard picket space or Montage Commercial Pool, Pet & Play 3”
air space) Welded and Rackable (ATF – All Terrain Flexibility) Ornamental Steel, (for standard picket space, specify Classic, Majestic,
Genesis, or Invincible; for 3” air space, specify Classic, Majestic, or Genesis) design, (specify extended picket or flush) bottom rail
treatment, (specify 3-Rail, 4-Rail, or 3-Rail with Double Rings, 4-Rail with Double Rings) style manufactured by Ameristar Fence
Products, Inc., in Tulsa, Oklahoma.
2.02 MATERIAL
A. Steel material for fence panels and posts shall conform to the requirements of ASTM A653/A653M, with a minimum yield
strength of 45,000 psi (310 MPa) and a minimum zinc (hot-dip galvanized) coating weight of 0.60 oz/ft2 (184 g/m2), Coating
Designation G-60.
B. Material for pickets shall be 3/4” square x 14 Ga. tubing. The rails shall be steel channel, 1.5” x 1.4375” x 14 Ga. Picket holes in
the rail shall be spaced (specify 4.675” o.c. for standard picket space or 3.500” o.c. for 3” air space). Fence posts and gate posts shall
meet the minimum size requirements of Table 1.
2.03 FABRICATION
A. Pickets, rails and posts shall be pre-cut to specified lengths. Rails shall be pre-punched to accept pickets.
B. Pickets shall be inserted into the pre-punched holes in the rails and shall be aligned to standard spacing using a specially
calibrated alignment fixture. The aligned pickets and rails shall be joined at each picket-to-rail intersection by Ameristar’s proprietary
fusion welding process, thus completing the rigid panel assembly (Note: The process produces a virtually seamless, spatter-free
good-neighbor appearance, equally attractive from either side of the panel).
C. The manufactured panels and posts shall be subjected to an inline electrode position coating (E-Coat) process consisting of a
multi-stage pretreatment/wash, followed by a duplex application of an epoxy primer and an acrylic topcoat. The minimum
cumulative coating thickness of epoxy and acrylic shall be 2 mils (0.058 mm). The color shall be (specify Black or Bronze). The
coated panels and posts shall be capable of meeting the performance requirements for each quality characteristic shown in Table 2
(Note: The requirements in Table 2 meet or exceed the coating performance criteria of ASTM F2408).
D. The manufactured fence system shall be capable of meeting the vertical load, horizontal load, and infill performance requirements
for Commercial weight fences under ASTM F2408.
E. Gates with an out-to-out leaf dimension less than and including 72 inches shall be fabricated using Montage Commercial
ornamental panel material and 1-3/4” sq. x 14ga. gate ends. Gate leafs greater than 72 inches shall be fabricated using ForeRunner
rails, intermediate uprights, gussets and 1-3/4” sq. x 14ga. gate ends. All rail and upright intersections shall be joined by welding. All
picket and rail intersections shall also be joined by welding.
PART 3 - EXECUTION
3.01 PREPARATION
All new installation shall be laid out by the contractor in accordance with the construction plans.
3.02 INSTALLATION
Fence post shall be spaced according to Table 3, plus or minus 1/4”. For installations that must be raked to follow sloping grades, the
post spacing dimension must be measured along the grade. Fence panels shall be attached to posts with brackets supplied by the
manufacturer. Posts shall be set in concrete footers having a minimum depth of 36” (Note: In some cases, local restrictions of freezing
weather conditions may require a greater depth). The “Earthwork” and “Concrete” sections of this specification shall govern material
requirements for the concrete footer. Posts setting by other methods such as plated posts or grouted core-drilled footers are
permissible only if shown by engineering analysis to be sufficient in strength for the intended application.
3.03 FENCE INSTALLATION MAINTENANCE
When cutting/drilling rails or posts adhere to the following steps to seal the exposed steel surfaces; 1) Remove all metal shavings
from cut area. 2) Apply zinc-rich primer to thoroughly cover cut edge and/or drilled hole; let dry. 3) Apply 2 coats of custom finish
paint matching fence color. Failure to seal exposed surfaces per steps 1-3 above will negate warranty. Ameristar spray cans or paint
pens shall be used to prime and finish exposed surfaces; it is recommended that paint pens be used to prevent overspray. Use of
non-Ameristar parts or components will negate the manufactures’ warranty.
Montage Commercial Specification Ameristar Perimeter Security USA Inc. Rev. 12/08/2022
3.04 GATE INSTALLATION
Gate posts shall be spaced according to the manufacturers’ gate drawings, dependent on standard out-to-out gate leaf dimensions and
gate hardware selected. Type and quantity of gate hinges shall be based on the application, weight, height, and number of gate cycles.
The manufacturers’ gate drawings shall identify the necessary gate hardware required for the application. Gate hardware shall be
provided by the manufacture of the gate and shall be installed per manufacturer’s recommendations.
3.05 CLEANING
The contractor shall clean the jobsite of excess materials; post-hole excavations shall be scattered uniformly away from posts.
Table 1 – Minimum Sizes for Montage Commercial Posts
Fence Posts Panel Height
2-1/2” x 14 Ga.7’ & 8’ Heights
Gate HeightGate Leaf 7’ & 8’ Heights
Up to 4’2.5” x 12 Ga.
4’1” to 6’3” x 12 Ga.
6’1” to 10’4” x 11 Ga.
10’1” to 16’6” x 3/16” wall
Table 2 – Coating Performance Requirements
Quality Characteristics ASTM Test Method Performance Requirements
Adhesion D3359 – Method B Adhesion (Retention of Coating) over 90% of test area (Tape and knife
test).
Corrosion Resistance B117, D714 & D1654 Corrosion Resistance over 1,500 hours (Scribed per D1654; failure mode
is accumulation of 1/8” coating loss from scribe or medium #8 blisters).
Impact Resistance D2794 Impact Resistance over 60 inch lb. (Forward impact using 0.625” ball).
Weathering Resistance D822 D2244, D523 (60˚ Method)Weathering Resistance over 1,000 hours (Failure mode is 60% loss of
gloss or color variance of more than 3 delta-E color units).
Table 3 – Montage Commercial – Post Spacing By Bracket Type
Span For INVINCIBLE®
8’ Nominal (90.445” Rail)
For CLASSIC, GENESIS, & MAJESTIC
8’ Nominal (91.95” Rail)
Post Size 2-1/2”3”2-1/2”3”2-1/2”3”2-1/2”3”2-1/2”3”
Bracket
Type
Montage
Commercial
Invincible Flat
Mount
(BB118)
Montage Commercial
Invincible Line
2-1/2” (BB119)
3” (BB120)
Montage
Commercial
Universal
(BB112)
Montage
Commercial
Line Blvd.
(BB114)
Montage
Commercial
Flat Mount
(BB111)
Montage
Commercial
Swivel
(BB113)*
Post
Settings
± 1/4” O.C.
94”94-1/2”94”94-1/2”95”95”95”95-1/2”*95”*95-1/2”
*Note: When using BB304 swivel brackets on either or both ends of a panel installation, care must be taken to ensure the spacing between
post and adjoining pickets meets applicable codes. This will require trimming one or both ends of the panel.
Table 4 – Montage Commercial – IBC Compliant System Requirements
Panel Options Post Options Brackets Options
Styles Rail Configuration Steel Post Options Post Plate Options
(Anchorage by others)Line Boulevard Brackets
Classic 2.5” SQ x 14ga 8” x 8” x 3/8” – for 2.5” posts End Boulevard Brackets
Majestic 3” SQ x 12ga Corner Boulevard Brackets
Genesis *Flat Mount Brackets
Invincible
3-Rail & 4-Rail
4” SQ x 12ga
10” x 10” x 3/8” – for 3” posts
*Note: Flat Mount
Brackets require a thru-bolt
installation
Panel, post, and bracket assemblies shall be subjected to structural performance testing according to Chapter 17 - Structural Tests and Special Inspections -
International Building Code (IBC) 2018. Physical testing to be completed by accredited third party testing facility. Completed assembly shall demonstrate
loading capacity of 2.5 times prescribed design loads found in section 1607.8.1, 1607.8.1.1 and 1607.8.1.2 of IBC 2018 for Handrails and Guards.