Description
The Gamewell-FCI, S3 Series Intelligent Fire Alarm Control
Panel provides the latest innovative high-end processing
power. The S3 Series is a digital, microprocessor-based
system that offers a simple, intuitive solution for the small
to mid-sized fire alarm applications.
In standalone or network configurations, the S3 Series
complies with most fire alarm application requirements. It
supports either of the following types of networks.
• Up to 64 nodes using the 7100 Series panel.
• Up to 122 nodes using the S3 Series or E3 Series
®
panels.
Use either twisted-pair wire or fiber-optic to network panels
at a high-speed 625K baud ARCNET network bus.
With flexible Boolean logic, intelligent detection, and Ether-
net connectivity, this system provides power and versatility
that surpasses comparable, small addressable fire alarm
systems.
The basic S3 Series consists of an SLP (Smart Loop
Panel) main board, LCD-SLP touchscreen display, SLC
loop personality modules, and 7 amp power supply. The
SLP provides either one or two SLC loops in Class A or B
configuration that supports either of the following protocols:
• Up to 318 devices per loop using the System Sensor
® protocol. If you add a second loop module, it increases the maximum device count to 636 devices.
• Up to 126 devices per loop using the Apollo protocol. If you add a second loop module, it increases the maxi-mum device count to 252 devices.
Four Class B or two Class A NACs can be wired and syn-
chronized using the System Sensor, Cooper-Wheelock, or
Gentex strobes. To retrofit the SLP on the existing audible/
visual appliances, the on-board Electronic EOL (EEOL)
automatically adjusts to the EOL resistor in the field.
A 4.3" (10.92 cm) color touchscreen display screen shows
the following:
• Events on the system
• Status of analog addressable devices
• Complete diagnostic fault codes/messages
• Five programmable function buttons with LED status for
accessibility to the following functions:
- Disable/Enable - Trouble Acknowledge
- Bypass Output - Alarm Acknowledge
- Lamp Test - Custom-defined
E3 Series®, System Sensor® and FocalPoint® are registered trademarks of Honeywell International Inc.
UL® is a registered trademark of Underwriters Laboratories Inc.
Features
S3 Series
• Listed per ANSI/UL
® Standard 864 9th Edition.
• IBC Seismic Certified.
• Allows one SLC loop (expandable to two loops) that supports either System Sensor or Apollo devices in Class A or Class B (Style 4, 6 or 7).
• System Sensor supports up to 318 intelligentdevices and each SLC loop supports the following.- up to 159 detectors.- up to 159 modules (expandable to 636 maximum per panel).
• Apollo supports up to 126 intelligent detectors and
modules per SLC. (Expandable to 252 maximum per
panel).• Includes a high resolution (4.3”) (10.92 cm) color touch-
screen display.• Supports a network system of up to 122 nodes(includes E3 Series® panels) or up to 64 nodes (includes 7100 Series).• Provides 7.0 amp power supply (120VAC or 240VAC).
•Includes four Class B or two Class A built-in Notification Appliance Circuits (NAC). Provides selectable System Sensor, Cooper-Wheelock, or Gentex strobe synchroni-zation.
• Supports up to 32 serial annunciators (LCD, LED-only,
LED Switch).
RECEIVED
09/19/2018 striplett
BUILDING DIVISION
F18005260_V1
By: cthomas
Date: 10/02/2018
FIRE DEPARTMENT
For Construction Subject to
Corrections Noted in Red
APPROVED
GAMEWELL-FCI
12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-71189021-60730 Rev. F1 page 2 of 4 www.gamewell-fci.com
Application
The S3 Series Fire Alarm and Life Safety System is an
easy-to-use intelligent fire alarm solution designed for the
small to mid-sized buildings. Analog technology delivers
the benefits of a simple system installation, while a user-
friendly interface makes panel operation and system main-
tenance quick and intuitive.
Smart Panel Programming
Using Boolean logic programming, the installer may cus-
tomize the system to precisely suit the needs of the build-
ing owner. Auto-programming allows the installer to
instantly locate all the devices on the SLC loop.
Simple, Intuitive Display
The front panel display provides a user-friendly interface
for the operator's control. A 4.3” (10.922 cm) color touch-
screen displays system status, event details and service
modes. On the front of the panel, six LEDs show the follow-
ing conditions.
• Fire • Silenced
• Hazard (Gas or CO) • AC Power
• Supervisory • Trouble
Five custom programmable switches allow the user quick
access to common functions specific to the building like
device disable, output bypass and device status.
Perfect for Retrofits
The S3 Series is well-suited for retrofit applications. TheSLP provides a simple way to upgrade your fire protectionsystem. It is designed to be an upgrade solution for the leg-acy FCI 7100 and Gamewell 602 Series panels. An addedfeature is the SLP's EEOL. Using EEOL, the installers canautomatically identify the EOL for existing audible/visualappliances.
Flexibility for Future Growth
The S3 Series can be expanded to add a second SLC loop
without replacing the entire system. Using the RPT-E3-
UTP Network Repeater, you can network up to 64 nodes
(122 nodes with the ANX node expander) using either
twisted-pair or fiber-optic. The built-in Ethernet port allows
the connection to the Gamewell-FCI’s FocalPoint
Graphical Workstation.
Figure 1 LCD-SLP Display
Features (Continued)
• Offers an Ethernet port for programming, a variety of system reports, and a FocalPoint® Graphic Workstation connectivity.
• Provides two fully-programmable Form-C contacts for
Fire, Trouble, and Supervisory.
• TimeCap - Saves time and date up to 48 hours without
any power or battery.
• Automatically adjusts to any NAC End-of-Line Resistor (EOL) value (1k-55k ohm) for legacy audible/visual appliances.
• Removable display can be used as a remote annunciator.
• Suitable for pre-action deluge applications.
Optional Accessories
DACT-E3 - Dialer
The Digital Alarm Communication Transmitter sends digital
signals over telephone lines to the central station. It con-
nects to the SLP through an RS-485 bus. Using the Con-
tact ID format, the DACT-E3 provides a four-digit account
code followed by the code/numbers listed below:
• Three-digit Event Code
• Two-digit Group Number
• Three-digit Contact Number
All codes are used to provide specific point identification.
The DACT-E3 is compatible with digital alarm communica-
tor receivers (DACRs) that receive the following signaling
formats:
• Contact ID • SIA
•3+1 •4+2
For more information, refer to the following data sheets:
DACT-E3 Data Sheet, P/N: 9020-0610
FML-E3/FSL-E3 Data Sheet, P/N: 9021-60783
RPT-E3-UTP - Network Repeater Card
The Network Repeater allows the SLP fire control panels to
connect to the broadband network from remote locations. It
connects to other networked units using unshielded,
twisted-pair wiring. The RPT-E3-UTP is available with two
add-on fiber modules:
•FML-E3 connects to the network using either 62.5/125 micron multi-mode fiber.
•FSL-E3 connects to the network using 9/125 micron single-mode fiber.
Refer to the RPT-E3-UTP Data Sheet, P/N: 9020-0609.
LCD-7100 - Remote Annunciator
The Remote serial display features an 80-character dis-play. The LCD-7100 can be surface or flush-mounted on astandard 4-gang electrical box. You can use up to fiveLCD-7100 remote annunciators per SLP panel. For moreinformation, refer to the LCD-7100 Data Sheet, P/N: 9020-0486.
ASM-16 - Addressable Switch/LED Module
There are 16 programmable switches available to perform
any function the application requires. Each ASM-16 switch
has 3 LEDs fully programmable in red, yellow, and green.
These LEDs can be programmed to operate with a certain
button press or operate independently as a status signal
(e.g. ON, OFF, Activated, etc).
Up to 16 ASM-16 modules can be connected to the SLP
panel. For more information, refer to the ASM-16 Data
Sheet, P/N: 9020-0554.
ANU-48 - 48 LED Driver Unit
The ANU-48 provides output for eight remote panelswitches and 48 remote LEDs for use in a remotely located
UL® Listed annunciator enclosure. Up to 16 ANU-48 mod-ules can be connected to the SLP panel. For more infor-mation, refer to the ANU-48 Data Sheet, P/N: 9020-0596.
RECEIVED
09/19/2018 striplett
BUILDING DIVISION
F18005260_V1
GAMEWELL-FCI
12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118www.gamewell-fci.com 9021-60730 Rev. F1 page 3 of 4
Figure 2 illustrates the SLP-BB Cabinet Enclosure.
Figure 2 SLP Enclosure
SLP-BB CABINET
OUTER DOOR
SLP-BB CABINET
BACKBOX
1
2
3
4
14 1/2" W
20 1/8"H
4 1/2" D
Specifications
Device Loops Up to two Class A or B, System Sensor units, each loop supporting up to 318 device addresses.Or-Apollo units, each loop supporting up to 126 device addresses per loop.
NAC circuits 4 Class B or 2 Class A (2.0 A each circuit), 6.0 A total
NAC Operating Voltage 24 VDC
NAC Minimum Voltage 19.5 VDC @ 20.4 V battery voltage
SLC Loop Circuit Operating Voltage 24 V peak-to-peak
Input Voltage 120 VAC, 60 Hz 240 VAC 50-60 Hz
Input Current 120 VAC, 2.75 amps max.240 VAC, 1.4 amps max.
Aux Power 1 (Continuous)24 VDC nominal at 1.0A
Aux Power 2 (Resettable)24 VDC nominal at 1.0A
Base Panel Current draw Standby: 0.111 ampsAlarm: 0.243 amps
Operating Temperature 32°-120° F (0°-49° C)
Relative Humidity 93% (non-condensing)
Battery Charger Voltage +24 VDC
Battery Charger Capacity 55 A/H batteries (cabinet accommodates 12 A/H batteries)
Alarm, Trouble & Supervisory Relay Contacts Form-C, 2 amps @ 24VDC (resistive)
Cabinet Dimensions:
SLP-BB Dimensions 14 1/2” W x 20 1/8” H x 4 1/2” D
(36.83 W x 51.18 H x 11.43 D cm)
S3BB-RB Dimensions 19 3/8” W x 19 3/8” H x 4.5” D
(49.22 W x 49.22 H x 11.43 D)
Figure 3 SLP Panel Configuration
Networkable up to 122
panels using twisted
pair wire or fiber optics.
FocalPoint
Workstation
LCD-E3
Remote Annunicator
LCD-SLP
Color Touchscreen Annunicator
LCD-7100
emote Annunicator
ASM-16
LED Switch Control
ANU-48
LED Display Driver RS485DACTRS232EthernetRelay: 3 Form CS3 Series
Fire Alarm Control
Panel
MCS-COF
Fire/Carbon Monoxide Detector
MS-7AF
Pull Station
AMM-2RIF
Dual Input/Output Module
Supports up to 636 Velociti devices
or 252 XP95 devices
DNR
Intelligent Duct
Detector
ASD-PL2F
Photo Detector
AOM-2RF
Relay Module
AMM-2IF
Mini Monitor Module
ASD-LS
Laser Detector
Local Energy Trip E3 Series
Panel
Laptop
Programming
RECEIVED
09/19/2018 striplett
BUILDING DIVISION
F18005260_V1
GAMEWELL-FCI
12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-71189021-60730 Rev. F1 page 4 of 4 www.gamewell-fci.com
Ordering Information
Part Number Description
SLP-BLK SLP addressable FACP in black SLP-BBenclosure. Requires either an SLC-PM or an SLC95-PM for SLC loops.
SLP-RED SLP addressable FACP with red door and black SLP-BB backbox. Requires either an SLC-PM or an SLC95-PM for SLC loops.
SLP-RED-G SLP addressable FACP 240VAC power supply with red door and black SLP-BB backbox. Requires either an SLC-PM or an SLC95-PM for SLC loops.
SLC-PM System Sensor Loop Card - 1 loop used for 159 sensors and 159 modules. For use with the SLP-E3 panels only.
SLC95-PM Apollo Loop Card-1 loop used for 126 sensors and modules. For use with the SLP-E3 panels only.
Ordering Information (Continued)
Part Number Description
Accessories
DACT-E3 Digital Dialer Communicator
Transmitter for the S3 or E3 Series.
LCD-SLP LCD Color Touchscreen display withfive programmable switches. For use with the S3 Series panels. Remote annunciation requires the E3 Series A2 cabinet. (E3BB-BA2, E3BB-RA2)
RPT-E3-UTP Network repeater card with twisted-
pair fiber connections require either anFML-E3 or an FSL-E3 card.
FML-E3 Multi-mode fiber-optic card for one channel on the RPT-E3-UTP.
FSL-E3 Single-mode fiber-optic card for one
channel on the RPT-E3-UTP.
SLP-RB SLP motherboard
For use with the replacement or the
retrofit solutions.
FLPS-7-RB SLP 120VAC 7A power supply.
For use with the replacement or theretrofit solutions.
SLP-RETROFIT SLP Retrofit Kit for the 7100 B-Slimand IF602 panels.
Includes the new door and the mount-
ing plate. Requires the following:
• SLP-RB • LCD-SLP
•SLC-PM/
SLC95-PM
• FLPS-7-RB
S3BB-RB SLP red cabinet with an inner door for
the mounting display behind the
plexiglass. Requires the following:
• SLP-RB • LCD-SLP
•SLC-PM/
SLC95-PM
• FLPS-7-RB
LCD-7100 Remote Serial LCD Annunciator
ASM-16 Remote Programmable AddressableSwitch/LED Module
ANU-48 Remote LED Driver Module
RECEIVED
09/19/2018 striplett
BUILDING DIVISION
F18005260_V1
GAMEWELL-FCI12 Clintonville Road, Northford, CT 06472-1653 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118Specifications are for information only, are not intended for installation purposes, and are subject to change without notice. No responsibility is assumed by Gamewell-FCI for their use.
©2013 by Honeywell International Inc. All rights reserved.www.gamewell-fci.com 9020-0617 Rev. J page 1 of 2
Velociti® Series
ASD-PL2F, ASD-PTL2F
and ASD-PL2FR
Analog, Addressable Photoelectronic
Smoke Sensor
APPROVED
FM
3023594
SIGNALING
7272-1703:0121S1913
MEAApprovedFDNY
COA #:219-02-E
Vol.VI
Description
The Gamewell-FCI Velociti® Series, analog address-
able plug-in smoke sensors with integral communica-
tion provide features that surpass conventional
sensors. Sensitivity can be programmed in the con-
trol panel software, and is continuously monitored
and reported to the panel. Point ID capability allows
each sensor’s address to be set, providing exact
locations for selective maintenance when the cham-
ber contamination reaches an unacceptable level.
The ASD-PL2F photoelectric sensor’s unique optical
sensing chamber is engineered to sense smoke pro-
duced by a wide range of combustion sources. Dual
electronic thermistors add 135°F (57°C) fixed-tem-
perature thermal sensing on the ASD-PTL2F model.
The Velociti® Series use a communication protocol
that substantially increases the speed of communica-
tion between the sensors and certain Gamewell-FCI
analog addressable fire alarm controls. These
devices operate in a grouped fashion. If one of the
devices in the group has a status change, the panel’s
microprocessor stops the group poll and concen-
trates on the single device. The net effect is a
response speed up to five times greater than earlier
designs.
Velociti® is a registered trademark of Honeywell International Inc.
UL® is a registered trademark of Underwriters Laboratories Inc.
Ordering Information
Part Number Description
ASD-PL2F Analog, addressable photoelectronic
smoke sensor
ASD-PTL2F Analog, addressable photoelectronic smoke
sensor with thermal sensing
ASD-PL2FR Analog, addressable photoelectronic smoke
sensor used with the DNR duct base when
the remote test is required.
Features
• Sleek, low-profile design.
• Visual rotary, decimal switch addressing (01-159).
• Built-in functional test switch activated by an external
magnet.
• Bicolor LEDs flash green whenever the sensor is
addressed, and light steady red on alarm.*
• Optional relay, isolator, or sounder bases.
• Low standby current.
• Analog addressable communication.
• Stable communication technique with noise immunity.
• Optional remote, single-gang LED Indicator (RA100Z).
• Compatible with Gamewell-FCI analog addressable
panels.
Note: *Only the red LED is operative in panels that do not operate
in Velociti® mode.
ASD-PL2FRASD-PL2F/ASD-PTL2F
RECEIVED
09/19/2018 striplett
BUILDING DIVISION
F18005260_V1
GAMEWELL-FCI
12 Clintonville Road, Northford, CT 06472-1653 USA • Tel: (203) 484-7161 • Fax: (203) 484-71189020-0617 Rev. J page 2 of 2 www.gamewell-fci.com
Installation
ASD-PL2F plug-in sensors use a separate base to
simplify installation, service, and maintenance. A
special tool allows maintenance personnel to plug-in
and remove sensors without using a ladder.
Mount the base on a box which is at least 1.5" (3.8 cm)
deep. Suitable mounting base boxes include:
•4.0" (10.2 cm) square box.
•3.5" (8.9 cm) or 4.0" (10.2 cm) octagonal box.
• Single-gang box (except relay or isolator bases).
• With B200S or B200SR base, mounted on a 4.0"
(10.2 cm) octagonal or square box.
• With B224RB or B224BI base, mounted on a 3.5"
(8.9 cm) octagonal box, or a 4.0" (10.2 cm) octagonal or
square box.
NOTE: Because of the inherent supervision provided
by the SLC, end-of-line resistors are not required.
Wiring “T-taps” or branches are permitted for Style 4
(Class “B”) wiring.
Sensor Spacing
Gamewell-FCI recommends that the spacing sensors
be used in compliance with NFPA 72.
Specifications
ASD-PL2F, ASD-PTL2F, ASD-PL2FR:
Dimensions:2.1” (5.1 cm) height
Diameter:4.1” (10.4 cm) installed in the B501 base
6.1” (15.5 cm) installed in the B210LP base
Shipping Weight:5.2 oz. (147 g)
Operating
Temperature:
ASD-PL2F:
32° F to 120° F (0° C to 49° C)
ASD-PTL2F:
32° F to 100° F (0° C to 38° C)
UL®-Listed
Velocity Range:
0-4000 ft./min. (1,219.2 m/min.),
suitable for installation in ducts.
Relative
Humidity: 10-93% (non-condensing)
Thermal Ratings:Fixed-temperature setpoint
135° F (57° C)
Electrical Specifications
Voltage Range: 15 – 32 volts DC peak
Standby Current: (max. avg.): .0003 A @ 24 VDC
(One communication every 5
seconds with LED blink enabled).
Maximum Alarm-
Current: .0065 A @ 24 VDC (LED) lit).
Bases and Options
B501 Plug-in sensor base without flange
Dimensions:4.1” (10.4 cm) diameter
B210LP Flanged mounting base
Dimensions:6.1” (15.5 cm) diameter
B210LPBP Flanged mounting base bulk pack
Dimensions:6.1” (15.5 cm) diameter
B224RB
Relay Base
Plug-in sensor base with auxiliary
relay, SPDT, rated 2 amps @ 30 VDC
(resistive).
Screw terminals:
Up to 14 AWG (2.0 mm2)
2 coil latching relay 1 Form C contact
UL/CSA Rating:
0.9 A @ 125 VAC, inductive
0.9 A @ 110 VDC, inductive
3 A @ 30 VDC, resistive
Dimensions:6.1” (15.5 cm) diameter
Maximum: 25 devices between
isolator bases.
B200S Intelligent sensor sounder base
Dimensions:6.875” (17.5 cm) diameter
B200SR Standard sounder base, UL 8649th
Edition compliant, ULC Listed
Dimensions:6.875” (17.5 cm) diameter
RA100Z Remote LED Annunciator
BCK-200 Black detector covers (box of 10)
DNR Duct smoke housing
RECEIVED
09/19/2018 striplett
BUILDING DIVISION
F18005260_V1
Velociti™ Series
AMM-2F Monitor Module
INSTALLATION AND MAINTENANCE INSTRUCTIONS
9000-0590 1 I56-3554-001
©2007 Gamewell-FCI
BEFORE INSTALLINg
This information is included as a quick reference installation guide. Refer to
the control panel installation manual for detailed system information. If the
modules will be installed in an existing operational system, inform the opera-
tor and local authority that the system will be temporarily out of service. Dis-
connect power to the control panel before installing the modules.
NOTICE: This manual should be left with the owner/user of this equipment.
gENERAL DESCRIpTION
The AMM-2F monitor module can be installed in a single gang junction box
directly behind the monitored unit. Its small size and light weight allow it to
be installed without rigid mounting (see Figure 1). The AMM-2F is intended
for use in intelligent, two-wire systems where the individual address of each
module is selected using rotary switches. It provides a two-wire initiating de-
vice circuit for normally open contact fire alarm and security devices.
COMpATIBILITy REqUIREMENTS
To ensure proper operation, this module shall be connected to a compatible
Gamewell-FCI system control panel (list available from Gamewell-FCI).
FIgURE 1:
C1063-00
SpECIFICATIONS
Nominal Operating Voltage: 15-32 VDC
Average Operating Current: 375µA maximum (Group Poll); 350µA (Direct Poll); 600µA Max (Communicating IDC Shorted)
EOL resistance: 47K Ohms
Maximum SLC Wiring Resistance: 40 ohms
Maximum IDC wiring resistance: 1,500 Ohms
Maximum IDC Voltage: 11 Volts
Maximum IDC Current: 450µA
Temperature Range: 32˚F to 120˚ F (0˚C to 49˚ C)
Humidity: 10% to 93% Non-condensing
Dimensions: 1.3˝ H x 2.75˝ W x 0.5˝ D
Wire length: 6˝ minimum
12 Clintonville Rd., Northford, CT 06472-1653
(203) 484-7161; Fax: (203) 484-7118 I56-3554-001MOUNTINg AND WIRINg
NOTE: This module is intended to be wired and mounted without rigid con-
nections inside a standard electrical box. All wiring must conform to appli-
cable local codes, ordinances and regulations.
1. Connect the red (+) and black (–) wires to the positive and negative
loop power leads of the signaling line circuit (SLC).
2. Connect the violet (+) and yellow (–) wires to a two-wire, normally
open initiating loop.
3. Install the specified EOL resistor value to terminate the initiating loop.
4. Set the address on the module per job drawings.
5. Install the module in the desired mounting location.
FIgURE 2. TypICAL 2-WIRE STyLE B INITIATINg DEvICE
CIRCUIT CONFIgURATION:
0
78654321
9101112131415
(+)
(–)
TONEXTDEVICE
BLACKRED(+)(–)(+)(–)VIOLET
YELLOW
0123456789
SIGNAL LINE CIRCUIT (SLC)
47k EOLINCLUDED(ELR-47k)
UL LISTED COMPATIBLE CONTROL PANEL
ALL WIRING SHOWN IS SUPERVISED AND POWER LIMITED
C0614-02
RECEIVED
09/19/2018 striplett
BUILDING DIVISION
F18005260_V1
9000-0592 1 I56-2750-002
Velociti™ Series
AMM-2IF Dual Monitor Module
INSTALLATION AND MAINTENANCE INSTRUCTIONS
BEFORE INSTALLINg
This information is included as a quick reference installation guide. Refer to
the control panel installation manual for detailed system information. If the
modules will be installed in an existing operational system, inform the opera-
tor and local authority that the system will be temporarily out of service. Dis-
connect power to the control panel before installing the modules.
NOTICE: This manual should be left with the owner/user of this equipment.
gENERAL DESCRIpTION
The Dual Monitor Module is intended for use in intelligent, two wire systems.
It provides two independent 2-wire initiating device circuits (IDC), at two sep-
arate, consecutive addresses. It is capable of monitoring normally open con-
tact fire alarm and supervisory devices, or either normally open or normally
closed security devices. The module has a single panel controlled red LED.
COMpATIBILITy REqUIREMENTS
To ensure proper operation, this module shall be connected to a compatible
Gamewell-FCI system control panel (list available from Gamewell-FCI).
FIgURE 1. REMOvINg ROTARy SwITCh STOp:
0
7 8654321
9101112131415
9
8
7
6
5 4
3
2
1
0
TENS
ONES ADDRESSLOOP
02
4
68
C1032-00
SpECIFICATIONS
Normal Operating Voltage: 15 to 32 VDC
Maximum Current Draw: 6.4 mA (LED on)
Average Operating Current: 750µA (LED flashing)
Maximum SLC Wiring Resistance: 40 ohms
EOL Resistance: 47K ohms
Maximum IDC wiring resistance: 1,500 ohms
Maximum IDC Voltage: 11.7 Volts
Maximum IDC Current: 240µA
Temperature Range: 32˚F to 120˚F (0˚C to 49˚C)
Humidity: 10% to 93% Non-condensing
Dimensions: 41/2˝ H x 4˝ W x 11/4˝ D (Mounts to a 4˝ square by 21/8˝ deep box.)
Accessories: SMB500 Electrical Box I56-2750-002MOUNTINg
Mounts directly to 4-inch square electrical boxes (see Figure 2A). The box
must have a minimum depth of 21/8 inches. Surface mounted electrical boxes
(SMB500) are available from Gamewell-FCI.
FIgURE 2A. MODULE MOUNTINg: FIgURE 2B:
0
12349
87650
TENS
ONES
ADDR
ESSLOOP
864
2ISOLATEDQUADRANT 012
3
4 9876
50TENS
ONES
ADDRE
SSLOOP 864
2 09876543
2
1101112131415
09876543
2
110
1112131415
C1028-00
12 Clintonville Road
Northford, CT 06472-1653
Phone: 203/484-7161
RECEIVED
09/19/2018 striplett
BUILDING DIVISION
F18005260_V1
9000-0592 2 I56-2750-002
©2007 Gamewell-FCI
FIgURE 3. TypICAL 2-wIRE INITIATINg CIRCUIT CONFIgURATION, NFpA STyLE B:
C0608-02
wIRINg
NOTE: All wiring must conform to applicable local codes, ordinances, and
regulations. This module is intended for power limited wiring only.
1. Install module wiring in accordance with the job drawings and appropri-
ate wiring diagrams.
2. Set the address on the module per job drawings.
NOTE: Some panels support extended addressing. In order to set the
module above address 99 on compatible systems, carefully remove the
stop on the upper rotary switch with thumb in the direction shown in
Figure 1.
NOTE: Monitor module L (using terminals 6 and 7) responds at the ad-
dress set on the code switches. Monitor module H (using terminals 8 and
9) will automatically respond at the next higher address. For example, if
the code switches are set to 76, module L will respond at address 76 and
module H will respond at address 77. Use caution to avoid duplicate ad-
dressing of modules on the system.
3. Secure module to electrical box (supplied by installer), as shown in
Figure 2A.
0
78654321
9101112131415
9
8
7
6
5 4
3
2
1
0
TENS
ONES ADDRESSLOOP
024
68
H
L
TWO INITIATING DEVICE CIRCUITS (L&H), EACH POWER LIMITED TO 240 µA @ 11.7 VDC MAX.
UL LISTED CONTACT CLOSURE DEVICES MAY BE USED. DO NOT MIX FIRE ALARM INITIATING, SUPERVISORY, OR SECURITY DEVICES ON THE SAME INITIATING DEVICE CIRCUIT.
INSTALL CONTACT CLOSURE DEVICES PER MANUFACTURER’S INSTALLATION INSTRUCTIONS.
47k EOL RESISTOR ELR-47k
47k EOL RESISTOR ELR-47k
TO NEXT DEVICE (+)
(-)
(+)
(-)
(+)
(-)FROM PANEL OR PREVIOUS DEVICE
CONNECT MODULES TO LISTED COMPATIBLE CONTROL PANELS ONLY
MONITOR A (TERMINALS 6 & 7) RESPONDS AT ADDRESS SET ON CODE SWITCHES. MONITOR B (TERMINALS 8 & 9) RESPONDS AT NEXT HIGHER ADDRESS.
SIGNAL LINE CIRCUIT (SLC)32 VDC MAX. SHIELDED-TWISTED PAIR IS RECOMMENDED
MONITOR MODULE
ALL WIRING SHOWN IS SUPERVISED AND POWER LIMITED
RECEIVED
09/19/2018 striplett
BUILDING DIVISION
F18005260_V1
ATD-L2F
Veloticit® Series ATD-L2F, ATD-RL2F
Addressable Thermal Sensor
Addressable Devices
GENERAL
The Gamewell-FCI, Velociti® Series addressable plug-in thermal sensors with integral
communication provide features that surpass conventional sensors. Point ID
capability allows each sensor’s address to be set, providing exact locations for
pinpointing alarm locations and used for selective maintenance. ATD thermal sensors
use an innovative thermistor sensing circuit to produce 135°F/57°C fixed-
temperature (ATD-L2F). The ATD-RL2F provides a combination 15°/minute rate-of-
rise with 135° fixed thermal detection that is included in a low-profile package. The
ATD-HL2F provides fixed high-temperature detection at 190°F/88°C. These thermal
sensors provide cost-effective, addressable property protection in a variety of
applications.
The Velociti® Series uses a communication protocol that substantially increases the
speed of communication between the sensors and Gamewell-FCI analog addressable
fire alarm controls. These devices operate in a grouped fashion. If one of the devices
in the group has a status change, the panel’s microprocessor stops the group poll and
identifies the single device with the status change. The net effect is response speed
up to five times greater than earlier designs.
Installation
The ATD plug-in sensors use a separate base to simplify installation, service, and
maintenance. A special tool allows maintenance personnel to plug-in and remove
sensors without using a ladder.
Mount the base on a box which is at least 1.5" (3.8 cm) deep. Suitable mounting base boxes include:
• 4.0" (10.2 cm) square box
• 3.5" (8.9 cm) or 4.0" (10.2 cm) octagonal box
• Single-gang box (except relay or isolator base)
With B200S or B200SR base, mounted on a 4.0" (10.2 cm) octagonal or square box.
With B224RB or B224BI base, mounted on a 3.5" (8.9 cm) octagonal box, or a 4.0" (10.2 cm) octagonal or square box.
NOTE: Due to the inherent supervision provided by the SLC, the end-of-line resistors are not required. Wiring “T-taps” or branches are
permitted for Style 4 (Class “B”) wiring.
Ordering Information
ATD-L2F: Addressable thermal sensor, fixed, 135° F
ATD-RL2F: Addressable thermal sensor, combination fixed,135° F and 15°/minute rate-of-rise
ATD-HL2F: Addressable thermal sensor, fixed, 190° F
FEATURES & BENEFITS
• Sleek, low-profile
design
• Visual rotary switch
addressing
• Built-in functional test
switch activated by an
external magnet
•Bi-color LEDs flash
green whenever the
sensor is addressed,
and light steadily red
on alarm*
• Optional relay, isolator,
or sounder bases
• Low standby current
• Addressable
communication
• Stable communication
technique with noise
immunity
• Optional remote,
single-gang LED
accessory (RA-100Z)
• Suitable for installation
in ducts
Note: *Only the red LED
is operative in panels that
do not operate in
Velociti® mode.
RECEIVED
09/19/2018 striplett
BUILDING DIVISION
F18005260_V1
Veloticit® Series ATD-L2F, ATD-RL2F Technical Specifications
9020-0620 | F | 11/17
©2017 Honeywell International Inc.
For a complete listing of all
compliance approvals and
certifications, please visit:
http://www.gamewell-
fci.com/en-US/
documentation/Pages/
Listings.aspx
Gamewell-FCI®, Velociti® and
E3 Series® are registered
trademarks of Honeywell
International Inc.
UL® is a registered trademark
of Underwriters Laboratories
Inc.
ULC® is a registered trademark
of Underwriters Laboratories
Canada Inc.
This document is not intended
to be used for installation
purposes. We try to keep our
product information up-to-
date and accurate. We cannot
cover all specific applications
or anticipate all requirements.
All specifications are subject to
change without notice.
Honeywell Gamewell-FCI
12 Clintonville Road
Northford, CT 06472-1610
203.484.7161
www.honeywell.com
For more information
Learn more about Gamewell-FCI’s Veloticit® Series ATD-L2F,
ATD-RL2F and other products available by visiting
www.Gamewell-FCI.com
SYSTEMS
ATD-L2F/ATD-RL2F:
Dimensions: 2.1" (5.3 cm) Height
4.1" (10.4 cm) diameter installed in the B501 base
6.1" (15.5 cm) diameter installed in the B210LP base
Shipping Weight: 4.8 oz. (137 g)
Operating Temperature:
ATD-L2F or ATD-RL2F: –4° F to 100° F
(–20° C to 38°C)
ATD-HL2: –4° F to 150°F (–20 C to 66°C)
Sensor Spacing:
UL® approved for 50 ft. (15.2 m) center to center
FM approved for 25 x 25 ft. (7.6 x 7.6 m) spacing
Relative Humidity: 10 – 93% (non-condensing)
ATD-L2F: Fixed-temperature setpoint 135°F (57°C)
ATD-RL2F: Combination 135° F fixed temperature and
15° F(8.3°c)/per minute rate-of-rise°
ATD-HL2F: Fixed-temperature setpoint 190°F (88°C)
Electrical Specifications
Voltage Range: 15 - 32 Volts DC peak
Standby Current:
200 mA @ 24 VDC (without communication) (max. avg.)
.0003 A @ 24 VDC (one communication every 5 seconds
with LED blink enabled)
LED Current (max.) .0065 A @ 24 VDC (LED lit)
Bases and Options
B501: Plug-in sensor base without flange
Dimensions: 4.1” (10.4 cm) diameter
B210LP: Flanged mounting base
Dimensions: 6.1” (15.5 cm) diameter
B210LPBP: Flanged mounting base bulk pack
Dimensions: 6.1” (15.5 cm) diameter
B224RB: : Plug-in sensor base with auxiliary relay
SPDT 2 coil latching relay 1 Form C contact UL/CSA
Rating: 0.9 A @ 125 VAC (inductive)
0.9 @ 110 VDC (inductive)
3.A @ 30 VDC (resistive)
Dimensions: 6.1” (15.5 cm) diameter
B224BI: Plug-in sensor isolator base for Style 7 operation
Dimensions: 6.1” (15.5 cm) diameter
Maximum 25 devices between isolator bases
B200S: Intelligent sensor sounder base
Dimensions: 6.875” (17.5 cm) diameter
B200SR: Standard sounder base, UL 864 9th Edition
compliant, ULC Listed
Dimensions: 6.875” (17.5 cm) diameter
RA-100Z: Remote LED Annunciator
BCK-200: Black detector covers (box of 10)
TEMPERATURE AND HUMIDITY RANGES
This system meets NFPA requirements for operation at 0
– 49°C/32 – 120°F and at a relative humidity 93% ± 2%
RH (noncondensing) at 32°C ± 2°C (90°F ± 3°F).
However, the useful life of the system's standby batteries
and the electronic components may be adversely affected
by extreme temperature ranges and humidity. Therefore,
it is recommended that this system and its peripherals be
installed in an environment with a normal room
temperature of 15 – 27°C/60 – 80°F.
STANDARDS
The ATD-L2F/ATD-RL2F are designed to comply with the
following standards:
UL Standard: UL 864 9th Edition
AGENCY LISTINGS AND APPROVALS
These listings and approvals apply to the modules
specified in this document. In some cases, certain
modules or applications may not be listed by certain
approval agencies, or listing may be in process.
Consult factory for latest listing status.
UL: S2332
FM: 3023594
MEA FDNY: 219-02-E Vol. VI
CSFM: 7270-1703:0115
ISO 9001 Certification
RECEIVED
09/19/2018 striplett
BUILDING DIVISION
F18005260_V1
MS-7 Series
MS-7 Series
Manual Fire Alarm Pull Stations
Addressable Devices
General
The Gamewell-FCI, MS-7 Series manual fire alarm pull stations are available in a wide
variety of configurations. The pull stations comply with the Americans with Disabilities
Act (ADA) 5-lb. maximum pull force requirement. Operating instructions and Braille
text are engraved in the handle. All pull stations include a key lock/reset which is keyed
alike with the Gamewell-FCI fire alarm control panels and other manual fire alarm pull
stations.
MS-7AF Velociti Addressable Station
The MS-7AF Velociti® Series addressable station is a double action pull station
designed for installation in the signaling line circuit of Gamewell-FCI analog
addressable control panels. Activation of the pull station causes its assigned address
to register at the fire alarm control panel. The door contains an LED which flashes
green in normal condition and lights steady red when the station has been activated.*
The station features screw terminals.
MS-7ASF Velociti Addressable Station
The MS-7ASF Velociti® Series addressable pull station is a single action station
designed for installation in the signaling line circuit of Gamewell-FCI analog
addressable control panels. Activation of the station causes its assigned address to
register at the control panel. The door contains an LED which flashes green in normal condition and lights steady red when the pull station is
activated.* The station features screw terminals.
The Velociti® Series pull stations use a communication protocol that substantially increases the speed of communication between the sensors
and certain Gamewell-FCI analog addressable fire alarm controls. These devices operate in a grouped fashion. If one of the devices in the
group has a status change, the panel’s microprocessor stops the group poll and focuses on the single device. The net effect offers a response
speed up to five times greater than earlier designs.
MS-7 Double Action Station
The MS-7 double action pull station is used with conventional fire alarm control panels. It features a set of single pole contacts and screw
terminals for connection to an initiating circuit.
FEATURES & BENEFITS
• Addressable stations
compatible with all
Gamewell-FCI analog
addressable fire alarm
controls
• Conventional stations
suitable for use with
any UL® Listed control
panel
• The pull stations (MS-
7LOB) are Listed for
outdoor applications
• Complies with ADA pull
force requirements
• Offers surface or semi-
flush mounting
• Shock and vibration
resistant
• Both single and double
action pull stations
available
• Includes a tumbler lock
for test and reset keyed
alike with analog
addressable fire alarm
controls
*Only the red LED is
operative in panels that
do not operate in Velociti
mode
RECEIVED
09/19/2018 striplett
BUILDING DIVISION
F18005260_V1
2
MS-7S Single Action Station
The MS-7S single action pull station is used with
conventional fire alarm control panels. It features a set
of single pole contacts and wire leads for connection to
an initiating circuit.
MS-7SP Double Action Station
The MS-7SP is a double action pull station similar to
the MS-7 station, with the additional feature of
including both English and Spanish instructions
molded into the unit.
MS-7LR Dual-action Agent Release Station
The MS-7LR is designed for use with the Gamewell-FCI
fire alarm control panels with releasing capabilities
and Flex Series releasing systems. It features a set of
single pole contacts and screw terminals used to
connect to an initiating circuit.
MS-7LRA Agent Release Station with Abort
The MS-7LRA is designed for use with the Gamewell-
FCI fire alarm control panels with releasing capabilities
and Flex Series releasing systems where system abort
capabilities are required. It consists of the following:
• An MS-7LR mounted on a plate with an abort switch
• LED indicators that signal system normal and
system activated status
MS-7LOB Double Action Station (Listed for Outdoor
Applications)
The MS-7LOB station must be mounted on a Model
SB-I/O backbox. In retrofit applications, the pull
station is UL Listed for use with the WP-10 backbox. It
is intended for use with conventional control panels
and has a set of single pole contacts and screw
terminals.
Mounting
The MS-7 interior pull stations may be surface
mounted or semi-flush mounted on a standard
double-gang, or 4-inch (10.2 cm) square electrical box.
An optional trim ring (BG12TR) may also be used for
semi-flush mounting.
NYC-Plate
The NYC-Plate provides the backplate for the manual
pull station. (See Figure 1).
Figure 1 NYC-Plate
Ordering Information
MS-7: Double action station
MS-7AF**: Velociti addressable double action station
MS-7ASF**: Velociti addressable single action station
MS-7S: Single action station, wire leads
MS-7SP: Double action station, English and Spanish
instructions
MS-7LR: Agent release station, dual-action
MS-7LRA: Agent release station with abort switch,
LED indicators, dual- action
MS-7LOB: Double action station, outdoor use
(Includes SB-I/O - Indoor/outdoor use backbox)
SB-I/O: Indoor/outdoor use backbackbox
SB-10: Surface backbox
BG12TR: Trim ring for semi-flush mount, plastic
NY-PLATE: NYC backplate for manual pull station
**For use with the Gamewell-FCI analog addressable
control panels only.
RECEIVED
09/19/2018 striplett
BUILDING DIVISION
F18005260_V1
MS-7 Series Technical Specifications
9020-0616 | F | 11/17
©2017 Honeywell International Inc.
For a complete listing of all
compliance approvals and
certifications, please visit:
http://www.gamewell-
fci.com/en-US/
documentation/Pages/
Listings.aspx
LEXAN® is a registered
trademark of GE Plastics, a
subsidiary of General Electric
Company.
Velociti® and Gamewell-FCI
are registered trademarks of
Honeywell International Inc.
UL® is a registered trademark
of Underwriter’s Laboratories
Inc.
This document is not intended
to be used for installation
purposes. We try to keep our
product information up-to-
date and accurate. We cannot
cover all specific applications
or anticipate all requirements.
All specifications are subject to
change without notice.
Honeywell Gamewell-FCI
12 Clintonville Road
Northford, CT 06472-1610
203.484.7161
www.honeywell.com
For more information
Learn more about Gamewell-FCI’s MS-7 Series and other
products available by visiting www.Gamewell-FCI.com
SYSTEMS
Material: Lexan®
Contact Ratings: 0.25 amps. @ 30 VAC/VDC (resistive)
Dimensions: 5 5/8” H x 4 1/4” W x 1 1/4” D
(14 x 10.1 x 3.2 cm)
Operating Temperature:
(MS-7AF, MS-7ASF): 32° to 120° F (0° to 49° C)
(MS-7LOB): -30° to 150° F (-35° to 66° C)
Relative Humidity :
(MS-7AF, MS-7ASF): 10 to 93% (non-condensing)
(MS-7LOB): 85% ± 5% @ 86° ± 3.6° (30° ± 2° C)
Alarm Current: .0030 amp. 0.007 for LED
Supervisory Current:
(MS-7AF, MS-7ASF): .00030 amps.
TEMPERATURE AND HUMIDITY RANGES
This system meets NFPA requirements for operation at 0
– 49°C/32 – 120°F and at a relative humidity 93% ± 2%
RH (noncondensing) at 32°C ± 2°C (90°F ± 3°F).
However, the useful life of the system's standby batteries
and the electronic components may be adversely affected
by extreme temperature ranges and humidity. Therefore,
it is recommended that this system and its peripherals be
installed in an environment with a normal room
temperature of 15 – 27°C/60 – 80°F.
STANDARDS
The MS-7 Series is designed to comply with the following
standard:
UL Standard: UL 864 9th Edition
AGENCY LISTINGS AND APPROVALS
These listings and approvals apply to the modules
specified in this document. In some cases, certain
modules or applications may not be listed by certain
approval agencies, or listing may be in process.
Consult factory for latest listing status.
UL: S2465
FM: 3023594
MEA FDNY: 67-02-E Vol. VII
CSFM:
7160-1703:0119
7160-1703:0170
7160-1703:0109
ISO 9001 Certification
RECEIVED
09/19/2018 striplett
BUILDING DIVISION
F18005260_V1
Features
• Plug-in design with minimal intrusion into the back box
• Tamper-resistant construction
• Automatic selection of 12- or 24-volt operation
at 15 and 30 candela
• Field-selectable candela settings on ceiling units:
15, 30, 75, 95, 115, 150, and 177
• Horn rated at 88+ dBA at 16 volts
• Rotary switch for horn tone and two volume selections
• Universal mounting plate for ceiling units
• Mounting plate shorting spring feature checks wiring continuity
before device installation
• Electrically Compatible with legacy SpectrAlert and SpectrAlert
Advance devices
• Compatible with MDL3 sync module
• Listed for ceiling mounting only
The System Sensor L-Series offers the most versatile and
easy-to-use line of horns, strobes, and horn strobes in the industry
with lower current draws and modern aesthetics. With white and red
plastic housings, wall and ceiling mounting options, System Sensor
L-Series can meet virtually any application requirement.
The entire L-Series product line of ceiling-mount strobes and horn
strobes include a variety of features that increase their application
versatility while simplifying installation. All devices feature a plug-in
design with minimal intrusion into the back box, making installations
fast and foolproof while virtually eliminating costly and time-
consuming ground faults.
To further simplify installation, the L-Series utilizes a universal
mounting plate so installers can mount them to a wide array of back
boxes. With an onboard shorting spring, installers can test wiring
continuity before the device is installed.
Installers can also easily adapt devices to a suit a wide range of
application requirements using field-selectable candela settings,
automatic selection of 12- or 24-volt operation, and a rotary switch
for horn tones with two volume selections.
Indoor Selectable-
Output Strobes and
Horn Strobes for
Ceiling Applications
System Sensor L-Series audible visible notification
products are rich with features guaranteed to cut
installation times and maximize profits with lower
current draw and modern aesthetics.
Agency Listings
7125-1653:0504
7135-1653:0503
S5512
S4011
FM approved except
for ALERT models
3057383
RECEIVED
09/19/2018 striplett
BUILDING DIVISION
F18005260_V1
AVDS86800
L-Series Specifications
Architect/Engineer Specifications
General
L-Series ceiling-mount strobes and horn strobes shall mount to a standard 4 × 4 × 1½-inch back box, 4-inch octagon back box, or double-
gang back box. Two-wire products shall also mount to a single-gang 2 × 4 × 17⁄8-inch back box. A universal mounting plate shall be used
for mounting ceiling and wall products. The notification appliance circuit wiring shall terminate at the universal mounting plate. Also, L-Series
products, when used with the Sync•Circuit™ Module accessory, shall be powered from a non-coded notification appliance circuit output
and shall operate on a nominal 12 or 24 volts. When used with the Sync•Circuit Module, 12-volt-rated notification appliance circuit outputs
shall operate between 8.5 and 17.5 volts; 24-volt-rated notification appliance circuit outputs shall operate between 16.5 and 33 volts. Indoor
L-Series products shall operate between 32 and 120 degrees Fahrenheit from a regulated DC or full-wave rectified unfiltered power supply.
Ceiling strobes and horn strobes shall have field-selectable candela settings including 15, 30, 75, 95, 115, 150, and 177.
Strobe
The strobe shall be a System Sensor L-Series Model _______ listed to UL 1971 and shall be approved for fire protective service. The strobe
shall be wired as a primary-signaling notification appliance and comply with the Americans with Disabilities Act requirements for visible
signaling appliances, flashing at 1 Hz over the strobe’s entire operating voltage range. The strobe light shall consist of a xenon flash tube and
associated lens/reflector system.
Horn Strobe Combination
The horn strobe shall be a System Sensor L-Series Model _______ listed to UL 1971 and UL 464 and shall be approved for fire protective
service. The horn strobe shall be wired as a primary-signaling notification appliance and comply with the Americans with Disabilities Act
requirements for visible signaling appliances, flashing at 1 Hz over the strobe’s entire operating voltage range. The strobe light shall consist
of a xenon flash tube and associated lens/reflector system. The horn shall have two audibility options and an option to switch between a
temporal three pattern and a non-temporal (continuous) pattern. These options are set by a multiple position switch. The horn on horn strobe
models shall operate on a coded or non-coded power supply.
Synchronization Module
The module shall be a System Sensor Sync•Circuit model MDL3 listed to UL 464 and shall be approved for fire protective service. The module
shall synchronize L-Series strobes at 1 Hz and horns at temporal three. Also, while operating the strobes, the module shall silence the horns
on horn strobe models over a single pair of wires. The module shall mount to a 4 11⁄16 × 4 11⁄16 × 2 1⁄8-inch back box. The module shall also
control two Style Y (class B) circuits or one Style Z (class A) circuit. The module shall synchronize multiple zones. Daisy chaining two or more
synchronization modules together will synchronize all the zones they control. The module shall not operate on a coded power supply.
Physical/Electrical Specifications
Standard Operating Temperature 32°F to 120°F (0°C to 49°C)
Humidity Range 10 to 93% non-condensing
Strobe Flash Rate 1 flash per second
Nominal Voltage Regulated 12 VDC or regulated 24 DC/FWR1
Operating Voltage Range2 8 to 17.5 V (12 V nominal) or 16 to 33 V (24 V nominal)
Operating Voltage Range (MDL3)8.5 to 17.5V (12 V nominal) or 16.5 to 33 V (24V nominal)
Input Terminal Wire Gauge 12 to 18 AWG
Ceiling-Mount Dimensions (including lens)6.8" diameter × 2.5" high (173 mm diameter × 64 mm high)
Ceiling-Mount Surface Mount Back Box Skirt Dimensions
(SBBCRL, SBBCWL)
6.9" diameter x 3.4" high (175 mm diameter x 86 mm high)
Notes:
1. Full Wave Rectified (FWR) voltage is a non-regulated, time-varying power source that is used on some power supply and panel outputs.
2. P, S, PC, and SC products will operate at 12 V nominal only for 15 and 30 cd.
RECEIVED
09/19/2018 striplett
BUILDING DIVISION
F18005260_V1
AVDS86800
Horn and Horn Strobe Output (dBA)
Switch Position Sound Pattern dB
8–17.5
Volts
16–33
Volts
DC DC FWR
1 Temporal High 84 89 89
2 Temporal Low 75 83 83
3 Non-Temporal High 85 90 90
4 Non-Temporal Low 76 84 84
5 3.1 KHz Temporal High 83 88 88
6 3.1 KHz Temporal Low 76 82 82
7 3.1 KHz Non-Temporal High 84 89 89
8 3.1 KHz Non-Temporal Low 77 83 83
UL Max. Strobe Current Draw (mA RMS)
Candela
8–17.5 Volts 16–33 Volts
DC DC FWR
15 87 41 60
30 153 63 86
75 N/A 111 142
95 N/A 134 164
115 N/A 158 191
150 N/A 189 228
177 N/A 226 264
UL Max. Current Draw (mA RMS), 2-Wire Horn Strobe
DC Input
8-17.5 Volts 16-33 Volts
15cd 30cd 15cd 30cd 75cd 95cd 115cd 150cd 177cd
Temporal High 103 167 71 90 143 165 187 217 254
Temporal Low 96 165 54 71 137 161 185 211 249
Non-Temporal High 106 173 71 90 141 165 187 230 273
Non-Temportal Low 95 166 54 71 124 161 170 216 258
3.1K Temporal High 111 164 69 94 147 163 184 229 257
3.1K Temporal Low 103 163 54 88 143 155 185 212 252
3.1K Non-Temporal High 111 172 69 94 144 164 202 229 271
3.1K Non-Temporal Low 103 169 54 88 131 155 187 217 259
FWR Input
16-33 Volts
15cd 30cd 75cd 95cd 115cd 150cd 177cd
Temporal High 107 135 179 198 223 254 286
Temporal Low 78 101 151 172 199 229 262
Non-Temporal High 107 135 179 198 223 254 286
Non-Temportal Low 78 101 151 172 199 229 262
3.1K Temporal High 108 135 179 200 225 255 289
3.1K Temporal Low 79 101 150 171 196 229 260
3.1K Non-Temporal High 108 135 179 200 225 255 289
3.1K Non-Temporal Low 79 101 150 171 196 229 260
UL Current Draw Data
Horn Strobe Tones and Sound Output Data
RECEIVED
09/19/2018 striplett
BUILDING DIVISION
F18005260_V1
3825 Ohio Avenue • St. Charles, IL 60174
Phone: 800-SENSOR2 • Fax: 630-377-6495
©2017 System Sensor.
Product specifications subject to change without notice. Visit systemsensor.com
for current product information, including the latest version of this data sheet.
AVDS86801 • 03/17
L-Series Dimensions
Model Description
Ceiling Horn Strobes
PC2RL 2-Wire, Horn Strobe, Red
PC2WL 2-Wire, Horn Strobe, White
L-Series Ordering Information
Ceiling-Mount Horn Strobes Ceiling Surface Mount Back Box
Model Description
Ceiling Strobes
SCRL Strobe, Red
SCWL Strobe, White
SCWL-CLR-ALERT Strobe, White, ALERT
Accessories
TRC-2 Universal Ceiling Trim Ring Red
TRC-2W Universal Ceiling Trim Ring White
SBBCRL Ceiling Surface Mount Back Box, Red
SBBCWL Ceiling Surface Mount Back Box, White
Ceiling Mount Horn Strobes with Ceiling Surface Mount Back Box
RECEIVED
09/19/2018 striplett
BUILDING DIVISION
F18005260_V1
Agency Listings
Features
t 8FBUIFSQSPPGQFS/&."9
*1
t -JTUFEUP6- TUSPCF
BOE6- IPSO
t $PNQBUJCMFXJUI4ZTUFN4FOTPSTZODISPOJ[BUJPOQSPUPDPMBOE
MFHBDZ4QFDUS"MFSUQSPEVDUT
t 'JFMETFMFDUBCMFDBOEFMBTFUUJOHT
BOE
t "VUPNBUJDTFMFDUJPOPGPSWPMUPQFSBUJPOBUBOE
DBOEFMB
t 3PUBSZTXJUDIGPSIPSOUPOFBOEUISFFWPMVNFTFMFDUJPOT
t )PSOSBUFEBUE#"BUWPMUT
t 3BUFEGSPNo¡'UP¡'
t 6OJWFSTBMNPVOUJOHQMBUFXJUIBOPOCPBSETIPSUJOHTQSJOHUIBU
UFTUTXJSJOHDPOUJOVJUZCFGPSFEFWJDFTBSFJOTUBMMFE
t 1MVHJOEFTJHOXJUINJOJNBMJOUSVTJPOJOUPUIFCBDLCPY
t 5BNQFSSFTJTUBOUDPOTUSVDUJPO
t -JTUFEGPSDFJMJOHPSXBMMNPVOUJOH
SpectrAlert Advance PGGFSTUIFCSPBEFTUMJOFPGPVUEPPSIPSOT
TUSPCFT
BOEIPSOTUSPCFTJOUIFJOEVTUSZ8JUIXIJUFPSSFEQMBTUJD
IPVTJOHT
XBMMPSDFJMJOHNPVOUJOHPQUJPOT
BOEQMBJOPS'*3&QSJOUFE
EFWJDFT
4QFDUS"MFSU"EWBODFDBONFFUWJSUVBMMZBOZBQQMJDBUJPO
SFRVJSFNFOU
JODMVEJOHJOEPPS
PVUEPPS
XFU
BOEESZBQQMJDBUJPOTJO
UFNQFSBUVSFTGSPN¦¡'UP¡'
-JLFUIFFOUJSF4QFDUS"MFSU"EWBODFMJOF
PVUEPPSIPSOT
TUSPCFT
BOEIPSOTUSPCFTGPSXBMMBQQMJDBUJPOTJODMVEFBWBSJFUZPGGFBUVSFT
UIBUJODSFBTFBQQMJDBUJPOnFYJCJMJUZBOETJNQMJGZJOTUBMMBUJPO'JSTU
mFMETFMFDUBCMFTFUUJOHT
JODMVEJOHDBOEFMB
BVUPNBUJDTFMFDUJPOPG
PSWPMUPQFSBUJPO
IPSOUPOFT
BOEUISFFWPMVNFPQUJPOTFOBCMF
JOTUBMMFSTUPFBTJMZBEBQUEFWJDFTUPNFFUSFRVJSFNFOUT
/FYU
4QFDUS"MFSU"EWBODFEFWJDFTVTFBVOJWFSTBMNPVOUJOHQMBUF
GPSCPUIXBMMBOEDFJMJOHBQQMJDBUJPOT5IJTNPVOUJOHQMBUFJODMVEFT
BOPOCPBSETIPSUJOHTQSJOHUIBUFOTVSFTXJSJOHDPOUJOVJUZCFGPSF
EFWJDFTBSFJOTUBMMFE
TPJOTUBMMFSTDBOWFSJGZQSPQFSXJSJOHXJUIPVU
NPVOUJOHUIFEFWJDFTBOEFYQPTJOHUIFNUPQPUFOUJBMDPOTUSVDUJPO
EBNBHF0ODFUIFQMBUFTBSFNPVOUFE
BMM4QFDUS"MFSU"EWBODF
EFWJDFTVUJMJ[FBQMVHJOEFTJHOXJUIBTJOHMFDBQUVSFETDSFXUP
TQFFEJOTUBMMBUJPOBOEWJSUVBMMZFMJNJOBUFDPTUMZHSPVOEGBVMUT
0VUEPPSEFWJDFTTIJQXJUIXFBUIFSQSPPGQMBTUJDCBDLCPYFT NFUBM
CBDLCPYFTBSFBWBJMBCMFTFQBSBUFMZ
UIBUBDDPNNPEBUFJOBOE
PVUXJSJOHGPSEBJTZDIBJOJOHEFWJDFT1MBTUJDCBDLCPYFTGFBUVSF
SFNPWBCMFTJEFnBOHFTBOEJNQSPWFESFTJTUBODFUPTBMUXBUFS
DPSSPTJPO,OPDLPVUTMPDBUFEPOUIFCBDLFMJNJOBUFUIFOFFEUPESJMM
IPMFTGPSTDSFXJONPVOUJOH1MBTUJDBOENFUBMXFBUIFSQSPPGCBDL
CPYFTDPNFXJUI£JODIUPQBOECPUUPNDPOEVJUFOUSJFTBOE£JODI
LOPDLPVUTBUUIFCBDL"TDSFXJO/15QMVHXJUIBO0SJOHHBTLFU
GPSBXBUFSUJHIUTFBMJTJODMVEFEXJUIFBDICBDLCPY
Outdoor Selectable-
Output Horns,
Strobes, and
Horn Strobes for
Wall Applications
SpectrAlert® Advance outdoor audible visible products
are rich with features that cut installation times and
maximize profits.
.&"&
PVUEPPSTUSPCFT
IPSOTUSPCFT
DIJNFTUSPCFT
IPSOT
DIJNFT
4 DIJNFT
IPSOTUSPCFT
IPSOT
4 PVUEPPSBOEBMFSUTUSPCFT
RECEIVED
09/19/2018 striplett
BUILDING DIVISION
F18005260_V1
"7%4
SpectrAlert Advance Outdoor Horn, Strobe, and Horn Strobe Specifications
Architect/Engineer Specifications
General
4QFDUS"MFSU"EWBODFPVUEPPSIPSOT
TUSPCFT
BOEIPSOTUSPCFTTIBMMNPVOUUPBXFBUIFSQSPPGCBDLCPY"VOJWFSTBMNPVOUJOHQMBUFTIBMM
CFVTFEGPSNPVOUJOHDFJMJOHBOEXBMMQSPEVDUT5IFOPUJmDBUJPOBQQMJBODFDJSDVJUXJSJOHTIBMMUFSNJOBUFBUUIFVOJWFSTBMNPVOUJOHQMBUF
"MTP
4QFDUS"MFSU"EWBODFQSPEVDUT
XIFOVTFEXJUIUIF4ZODt$JSDVJU™.PEVMFBDDFTTPSZ
TIBMMCFQPXFSFEGSPNBOPODPEFEOPUJmDBUJPO
BQQMJBODFDJSDVJUPVUQVUBOETIBMMPQFSBUFPOBOPNJOBMPSWPMUT8IFOVTFEXJUIUIF4ZODt$JSDVJU.PEVMF
WPMUSBUFEOPUJmDBUJPO
BQQMJBODFDJSDVJUPVUQVUTTIBMMPQFSBUFCFUXFFOBOEWPMUTWPMUSBUFEOPUJmDBUJPOBQQMJBODFDJSDVJUPVUQVUTTIBMMPQFSBUFCFUXFFO
BOEWPMUT0VUEPPS4QFDUS"MFSU"EWBODFQSPEVDUTTIBMMPQFSBUFCFUXFFO¦BOEEFHSFFT'BISFOIFJUGSPNBSFHVMBUFE%$PSGVMMXBWF
SFDUJmFEVOmMUFSFEQPXFSTVQQMZ4USPCFTBOEIPSOTUSPCFTTIBMMIBWFmFMETFMFDUBCMFDBOEFMBTFUUJOHTJODMVEJOH
BOE
Strobe
5IFTUSPCFTIBMMCFB4ZTUFN4FOTPS4QFDUS"MFSU"EWBODF.PEFM@@@@@@@MJTUFEUP6-BOETIBMMCFBQQSPWFEGPSmSFQSPUFDUJWFTFSWJDF
5IFTUSPCFTIBMMCFXJSFEBTBQSJNBSZTJHOBMJOHOPUJmDBUJPOBQQMJBODFBOEDPNQMZXJUIUIF"NFSJDBOTXJUI%JTBCJMJUJFT"DUSFRVJSFNFOUTGPS
WJTJCMFTJHOBMJOHBQQMJBODFT
nBTIJOHBU)[PWFSUIFTUSPCFTFOUJSFPQFSBUJOHWPMUBHFSBOHF5IFTUSPCFMJHIUTIBMMDPOTJTUPGBYFOPOnBTI
UVCFBOEBTTPDJBUFEMFOTSFnFDUPSTZTUFN5IFTUSPCFNVTUCFJOTUBMMFEXJUIJUTXFBUIFSQSPPGCBDLCPYJOPSEFSUPSFNBJOPVUEPPSBQQSPWFE
QFS6-5IFTUSPCFTIBMMCFTVJUBCMFGPSVTFJOXFUFOWJSPONFOUT
Horn Strobe Combination
5IFIPSOTUSPCFTIBMMCFB4ZTUFN4FOTPS4QFDUS"MFSU"EWBODF.PEFM@@@@@@@MJTUFEUP6-BOE6-BOETIBMMCFBQQSPWFEGPS
mSFQSPUFDUJWFTFSWJDF5IFIPSOTUSPCFTIBMMCFXJSFEBTBQSJNBSZTJHOBMJOHOPUJmDBUJPOBQQMJBODFBOEDPNQMZXJUIUIF"NFSJDBOTXJUI
%JTBCJMJUJFT"DUSFRVJSFNFOUTGPSWJTJCMFTJHOBMJOHBQQMJBODFT
nBTIJOHBU)[PWFSUIFTUSPCFTFOUJSFPQFSBUJOHWPMUBHFSBOHF5IFTUSPCF
MJHIUTIBMMDPOTJTUPGBYFOPOnBTIUVCFBOEBTTPDJBUFEMFOTSFnFDUPSTZTUFN5IFIPSOTIBMMIBWFUISFFBVEJCJMJUZPQUJPOTBOEBOPQUJPOUP
TXJUDICFUXFFOBUFNQPSBMUISFFQBUUFSOBOEBOPOUFNQPSBM DPOUJOVPVT
QBUUFSO5IFTFPQUJPOTTIBMMCFTFUCZBNVMUJQMFQPTJUJPOTXJUDI
0OGPVSXJSFQSPEVDUT
UIFTUSPCFTIBMMCFQPXFSFEJOEFQFOEFOUMZPGUIFTPVOEFS5IFIPSOPSIPSOTUSPCFNPEFMTTIBMMPQFSBUFPOBDPEFEPS
OPODPEFEQPXFSTVQQMZ5IFIPSOTUSPCFNVTUCFJOTUBMMFEXJUIJUTXFBUIFSQSPPGCBDLCPYJOPSEFSUPSFNBJOPVUEPPSBQQSPWFEQFS6-5IF
IPSOTUSPCFTIBMMCFTVJUBCMFGPSVTFJOXFUFOWJSPONFOUT
Physical/Electrical Specifications
Operating Temperature o¡'UP¡' o¡$UP¡$
Strobe Flash Rate nBTIQFSTFDPOE
Nominal Voltage 3FHVMBUFE%$'83PSSFHVMBUFE%$'83
Operating Voltage Range2 UP7 7OPNJOBM
PSUP7 7OPNJOBM
Input Terminal Wire Gauge UP"8(
Wall-Mount Dimensions (including lens)-¨8¨% NN-¨NN8¨NN%
Horn Dimensions -¨8¨% NN-¨NN8¨NN%
Wall-Mount Weatherproof Back Box Dimensions (SA-WBB)-¨8¨% NN-¨NN8¨NN%
Notes:
'VMM8BWF3FDUJmFE '83
WPMUBHFJTBOPOSFHVMBUFE
UJNFWBSZJOHQPXFSTPVSDFUIBUJTVTFEPOTPNFQPXFSTVQQMZBOEQBOFMPVUQVUT
1
4
1$
BOE4$QSPEVDUTXJMMPQFSBUFBU7OPNJOBMPOMZGPSBOEDE
RECEIVED
09/19/2018 striplett
BUILDING DIVISION
F18005260_V1
"7%4
Horn and Horn Strobe Output (dBA)
Switch
Position
Sound
Pattern dB
8–17.5
Volts
16–33
Volts
24-Volt Nominal
Reverberant Anechoic
DC FWR DC FWR DC FWR DC FWR
5FNQPSBM )JHI 88 88
2 5FNQPSBM .FEJVN
3 5FNQPSBM -PX 83
/PO
5FNQPSBM
)JHI 82 82 88 88
5 /PO
5FNQPSBM
.FEJVN 85 85
/PO
5FNQPSBM
-PX 88
†$PEFE )JHI 82 82 88 88
8†$PEFE .FEJVN 85 85
†$PEFE -PX 88 85
†4FUUJOHT
BOEBSFOPUBWBJMBCMFPOXJSFIPSOTUSPCF
UL Max. Strobe Current Draw (mA RMS)
Candela
8–17.5 Volts 16–33 Volts
DC FWR DC FWR
Standard
Candela
Range
/" /"
/" /"
/" /"
/" /"
/" /"
High
Candela
Range
/" /"228
/" /"
/" /"
/" /" 258
UL Max. Current Draw (mA RMS), 2-Wire Horn Strobe, Standard Candela Range (15–115 cd)
DC Input
8–17.5 Volts 16–33 Volts
15 15/75 15 15/75 30 75 95 110 115
5FNQPSBM)JHI
5FNQPSBM.FEJVN
5FNQPSBM-PX
/PO5FNQPSBM)JHI
/PO5FNQPSBM.FEJVN 85
/PO5FNQPSBM-PX
FWR Input
5FNQPSBM)JHI 88
5FNQPSBM.FEJVN 88
5FNQPSBM-PX
/PO5FNQPSBM)JHI
/PO5FNQPSBM.FEJVN 85
/PO5FNQPSBM-PX
UL Max. Current Draw (mA RMS), 2-Wire Horn Strobe, High Candela Range (135–185 cd)
DC Input
16–33 Volts
FWR Input
16–33 Volts
135 150 177 185 135 150 177 185
5FNQPSBM)JHI 5FNQPSBM)JHI 258
5FNQPSBM.FEJVN 235 253 288 5FNQPSBM.FEJVN 258
5FNQPSBM-PX 232 282 5FNQPSBM-PX
/PO5FNQPSBM)JHI 255 /PO5FNQPSBM)JHI 233
/PO5FNQPSBM.FEJVN /PO5FNQPSBM.FEJVN 232
/PO5FNQPSBM-PX 238 /PO5FNQPSBM-PX
UL Max. Horn Current Draw (mA RMS)
Sound Pattern dB
8–17.5 Volts 16–33 Volts
DC FWR DC FWR
5FNQPSBM )JHI 55
5FNQPSBM .FEJVN 58
5FNQPSBM -PX 38
/PO5FNQPSBM )JHI
/PO5FNQPSBM .FEJVN
/PO5FNQPSBM -PX
$PEFE )JHI 55
$PEFE .FEJVN
$PEFE -PX 52
UL Current Draw Data
Horn Tones and Sound Output DataCandela Derating
'PS,TFSJFTQSPEVDUTVTFEBUMPXUFNQFSBUVSFT
MJTUFE
DBOEFMBSBUJOHTNVTUCFSFEVDFEJOBDDPSEBODFXJUI
UIJTUBCMF
Strobe Output (cd)
Listed Candela Candela rating at –40°F
%POPUVTFCFMPX¡'
RECEIVED
09/19/2018 striplett
BUILDING DIVISION
F18005260_V1
0IJP"WFOVFt4U$IBSMFT
*-
1IPOF4&/403t'BY
ª4ZTUFN4FOTPS
1SPEVDUTQFDJmDBUJPOTTVCKFDUUPDIBOHFXJUIPVUOPUJDF7JTJUTZTUFNTFOTPSDPN
GPSDVSSFOUQSPEVDUJOGPSNBUJPO
JODMVEJOHUIFMBUFTUWFSTJPOPGUIJTEBUBTIFFU
"7%4t
SpectrAlert Advance Diagrams
Model Description
Wall Horn Strobes
13,†8JSF)PSO4USPCF
4UBOEBSEDE
3FE
0VUEPPS JODMVEFTQMBTUJDXFBUIFSQSPPGCBDLCPY
13),†8JSF)PSO4USPCF
)JHIDE
3FE
0VUEPPS JODMVEFTQMBTUJDXFBUIFSQSPPGCBDLCPY
18,†8JSF)PSO4USPCF
4UBOEBSEDE
8IJUF
0VUEPPS JODMVEFTQMBTUJDXFBUIFSQSPPGCBDLCPY
18),†8JSF)PSO4USPCF
)JHIDE
8IJUF
0VUEPPS JODMVEFTQMBTUJDXFBUIFSQSPPGCBDLCPY
13,†8JSF)PSO4USPCF
4UBOEBSEDE
3FE
0VUEPPS JODMVEFTQMBTUJDXFBUIFSQSPPGCBDLCPY
18, 8JSF)PSO4USPCF
4UBOEBSEDE
8IJUF
0VUEPPS JODMVEFTQMBTUJDXFBUIFSQSPPGCBDLCPY
13), 8JSF)PSO4USPCF
)JHIDE
3FE
0VUEPPS
7 JODMVEFTQMBTUJDXFBUIFSQSPPGCBDLCPY
Wall Strobes
43,†4USPCF
4UBOEBSEDE
3FE
0VUEPPS JODMVEFTQMBTUJDXFBUIFSQSPPGCBDLCPY
43),†4USPCF
)JHIDE
3FE
0VUEPPS JODMVEFTQMBTUJDXFBUIFSQSPPGCBDLCPY
48,†4USPCF
4UBOEBSEDE
8IJUF
0VUEPPS JODMVEFTQMBTUJDXFBUIFSQSPPGCBDLCPY
48),†4USPCF
)JHIDE
8IJUF
0VUEPPS JODMVEFTQMBTUJDXFBUIFSQSPPGCBDLCPY
Horns
)3,†)PSO
3FE
0VUEPPS JODMVEFTQMBTUJDXFBUIFSQSPPGCBDLCPY
Accessories
4"8## 3FE
.FUBM8FBUIFSQSPPG#BDL#PY
4"8##8 8IJUF
.FUBM8FBUIFSQSPPG#BDL#PY
SpectrAlert Advance Ordering Information
Notes:
"EEi1wUPNPEFMOVNCFSGPSQMBJOIPVTJOH OPi'*3&wNBSLJOHPODPWFS
FH
13,1
p"EEi3wUPNPEFMOVNCFSGPSXFBUIFSQSPPGSFQMBDFNFOUEFWJDF OPCBDLCPYJODMVEFE
POMZGPSVTFXJUIXFBUIFSQSPPGPVUEPPSnVTINPVOUJOHQMBUF
851BOE8518
i4UBOEBSEDEwSFGFSTUPTUSPCFTUIBUJODMVEF
BOEDBOEFMBTFUUJOHTi)JHIDEwSFGFSTUPTUSPCFTUIBUJODMVEF
BOE
DBOEFMBTFUUJOHTWhen replacing standard outdoor units both the device and back box must be replaced.
4.7˝
5.6˝
2.5˝
Wall-Mount Horn Strobes Wall Plastic Weatherproof Back Box
Wall-Mount Horn Strobe with Plastic Weatherproof Back Box
RECEIVED
09/19/2018 striplett
BUILDING DIVISION
F18005260_V1
Fire Alarm Documents Cabinet
Fire Alarm Documents (FAD) Cabinet
Fire Alarm Storage Cabinet
Accessories
Description
The Gamewell-FCI Fire Alarm Documents Cabinet (FAD) is the perfect solution to
meet the demanding code standards required today. Gamewell-FCI's primary goal is
to manufacture code compliant solutions and this product allows you to do just that.
This cabinet is the answer to comply with the NFPA 72 2007, Section 6.2.2.1
requirements which states, "A record of installed software and firmware version
numbers shall be maintained at the location of the fire alarm control unit.
The Fire Alarm Documents cabinet may be used as a storage box for both printed and
digital documentation, enabling you to store the system’s test and certified inspection
documents, service records, manuals and AS built drawings.
This cabinet is constructed of durable 16 gauge steel with a solid piano hinge and key
lock. The cabinet includes a 4GB USB memory flash drive interface. Using a standard
USB B connector, the USB flash drive interface allows you to use any standard USB
printer cable to upload or download information. This feature allows you to store the
fire alarm software in one secure place, so that the Technician can easily access the
software and service the system.
The Fire Document Box (FDB) interior is designed to contain critical manuals and
documents. It is constructed with a durable steel retainer. The FDB has two key ring hooks to hold system keys, and a frame to insert Authorized
personnel business cards. In the inner door, you can add the Legend Sheet to record property, system, service, code and AHJ certification
information, as well as required documentation. (See Figure 2).
Ordering Information:
GW-FAD: Fire Alarm Storage Cabinet, Red
FEATURES & BENEFITS
• Installed with a 4
gigabyte digital flash
drive interface with
USB B connector
• Overall Dimensions
12”Width x 13” Height
x 2 ¼” Depth
(30.48 W x 33.02 H x
5.71 D cm)
• Offers two, key ring
hooks to hold the
system keys
• Contains a frame plate
to insert Authorized
Personnel business
cards
•Constructed with 16
gauge steel box and
cover for added
security with a solid
stainless steel hinge
• Coated with a durable,
baked-on finish (other
colors available)
• Built with a stainless
steel piano hinge with
standard ¾”cat 30 key
lock (other lock
assemblies available)
• Includes a Legend
Sheet to record
passwords and system
information
• Imprinted with white
indelible ink, 1" high
lettering labeled, "FIRE
ALARM DOCUMENTS”
RECEIVED
09/19/2018 striplett
BUILDING DIVISION
F18005260_V1
2
Figure 1 shows the interior enclosure of the Fire Alarm Documents cabinet.
.
Figure 1 Fire Alarm Documents Cabinet
Figure 2 shows the Legend Sheet attached to the inner door of the Fire Alarm Document Cabinet (See Figure 2).
Figure 2 Legend Sheet
Property Information Minimum Required Documentation
Name of Property:_______________________________ 1 Written narrative providing intent and system description.
Address:_______________________________________ N/A Enclosed or Alt. Location:_____________________________________
Description of Property: ___________________________ 2 Riser diagram
Occupancy Type:________________________________ N/A Enclosed or Alt. Location:_____________________________________
Certification and Approvals 3 Floor plan layout showing location of all devices and control equipment.
16.1 System Installation Contractor:N/A Enclosed or Alt. Location:_____________________________________
This system, as specified herein, has been installed and
tested according to all NFPA Standards cited therein.
4 Sequence of operation in either an input/ output matrix or narrative form.
N/A Enclosed or Alt. Location:_____________________________________
Signed:________________________________________ 5 Equipment technical data sheets.
Printed Name:__________________________________ N/A Enclosed or Alt. Location:_____________________________________
Date: ______/______/______ 6 Manufacturers published instructions, including operation and maintenance instruction.
Organization:___________________________________ N/A Enclosed or Alt. Location:_____________________________________
Title:__________________________________________ 7 Battery calculations (where batteries are provided).
Phone:________________________________________ N/A Enclosed or Alt. Location:_____________________________________
16.5 Authority Having Jurisdiction:8 Voltage drop calculations for notification appliance circuits.
I have witnessed a satisfactory acceptance test of this with N/A Enclosed or Alt. Location:_____________________________________
system and find it to be installed and operating properly in 9 Completed record of inspection and testing in accordance with 7.6.6 and 7.8.2.
accordance with its approved plans and specifications, N/A Enclosed or Alt. Location:_____________________________________
its approved sequence of operations, and with all NFPA 10 Completed record of completion in accordance with 7.5.6 and 7.8.2.
standards cited herein. N/A Enclosed or Alt. Location:_____________________________________
Signed:________________________________________ 11 Copy of site specific software, where applicable.
Printed Name:__________________________________ N/A Enclosed or Alt. Location:_____________________________________
Date: ______/______/______ 12 Record (as-built) drawings.
Organization:___________________________________ N/A Enclosed or Alt. Location:_____________________________________
Title:__________________________________________ 13 Periodic inspection, testing, and maintenance documentation in accordance with
Phone:________________________________________ Section 7.6.
Equipment Information:___________________________ N/A Enclosed or Alt. Location:_____________________________________
ID No. 1:_______________________________________ 14 Records, record retention, and record maintenance in accordance with 7.7.
Serial: ________________________________________ N/A Enclosed or Alt. Location:_____________________________________
Access Code: __________________________________
ID No. 2:_______________________________________
Serial: ________________________________________
Access Code: __________________________________ Signed:___________________________________Date:______/______/______
USB Storage Interface requires
Standard USB-B Connector
Key Ring Hooks
Business Card Holder
Legend sheet used to store system
information including the following:
- Contacts
- Sign-off
- Maintenance
- Test information
- Alternate locations of additional records
RECEIVED
09/19/2018 striplett
BUILDING DIVISION
F18005260_V1
Fire Alarm Documents (FAD) Cabinet Technical Specifications
9021-61027 | A | 05/18
©2018 Honeywell International Inc.
For a complete listing of all
compliance approvals and
certifications, please visit:
http://www.gamewell-
fci.com/en-US/
documentation/Pages/
Listings.aspx
Gamewell-FCI® is a registered
trademark of Honeywell
International Inc.
Space Age Electronics, Inc. is a
©copyright.
UL® is a registered trademark
of Underwriter’s Laboratories
Inc.
This document is not intended
to be used for installation
purposes. We try to keep our
product information up-to-
date and accurate. We cannot
cover all specific applications
or anticipate all requirements.
All specifications are subject to
change without notice.
Honeywell Gamewell-FCI
12 Clintonville Road
Northford, CT 06472-1610
203.484.7161
www.honeywell.com
For more information
Learn more about Gamewell-FCI’s Fire Alarm Documents (FAD)
Cabinet and other products available by visiting www.Gamewell-
FCI.com
SYSTEMS
FAD: Fire Alarm Documents Cabinet
Dimensions: 12” W x 13” H x 2 1/4” D
(30.48 W x 33.02 H x 5.71 D cm)
Door Keylock: Barrel lock and piano hinge
Dimensions: 3/4” barrel lock and 12” (30.48 cm) piano
hinge
FAD Cabinet: UL® Listed, constructed of 18 gauge cold
rolled steel
Cabinet Finish: Red powder coat epoxy finish
Cabinet Cover Label: Silkscreen imprinted with white
indelible ink, 1" high lettering labeled, "FIRE ALARM
DOCUMENTS"
Cabinet Keylock: Keylocked with 3/4" barrel lock and 12"
(30.48 cm) width stainless steel piano hinge
Cabinet Backbox: The backbox includes a 4-hole
knockout mounting pattern.
Cabinet Frame Plate: insert frame plate accommodates
and protects standard 8 1/2 x 11 manuals and document
records.
Cabinet Inner Door Label: Legend Sheet attached to the
inner door frame for system required documentation, key
contacts and code information.
Cabinet Flash Drive Interface: 4 Gigabyte (minimum)
digital flash memory drive with a standard USB B
connector (used to upload and download information) is
securely assembled to the interior cabinet.
The drive is restricted to Authorized personnel with
permission to use secure hardware devices to access the
records.
Cabinet Key Holder: Two key ring holders and a pre-
assembled frame plate to insert Authorized Personnel
business cards.
STANDARDS
The Fire Alarm Documents (FAD) Cabinet is designed to
comply with the following standard:
UL Standard: S2580
AGENCY LISTINGS AND APPROVALS
These listings and approvals apply to the modules
specified in this document. In some cases, certain
modules or applications may not be listed by certain
approval agencies, or listing may be in process. Consult
factory for latest listing status.
UL: S2580, Vol. 3
CSFM: 7300-0553-0110
NFPA: 72 2007
NEMA
ISO 9001 Certification