M_FIRE_ALARM_EQUIPMENT_DATA_SHEETS_RENTON_DENTAL_ARTS
S3 Series Control Panel Small Addressable Fire Alarm Control Panel GAMEWELL-FCI12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118Specifications are for information only, are not intended for installation purposes, and are subject to change without notice. No responsibility is assumed by Gamewell-FCI for their use. ©2015 by Honeywell International Inc. All rights reserved. www.gamewell-fci.com 9021-60730 Rev. F1 page 1 of 4 FDNY: COA-#6162 MEA S1869 SIGNALING 7165-1703:0176 City of Chicago Approved Class 1Reference Certificate of ComplianceVMA-45894-02C APPROVED FM Description The Gamewell-FCI, S3 Series Intelligent Fire Alarm Control Panel provides the latest innovative high-end processing power. The S3 Series is a digital, microprocessor-based system that offers a simple, intuitive solution for the small to mid-sized fire alarm applications. In standalone or network configurations, the S3 Series complies with most fire alarm application requirements. It supports either of the following types of networks. • Up to 64 nodes using the 7100 Series panel. • Up to 122 nodes using the S3 Series or E3 Series ® panels. Use either twisted-pair wire or fiber-optic to network panels at a high-speed 625K baud ARCNET network bus. With flexible Boolean logic, intelligent detection, and Ether- net connectivity, this system provides power and versatility that surpasses comparable, small addressable fire alarm systems. The basic S3 Series consists of an SLP (Smart Loop Panel) main board, LCD-SLP touchscreen display, SLC loop personality modules, and 7 amp power supply. The SLP provides either one or two SLC loops in Class A or B configuration that supports either of the following protocols: • Up to 318 devices per loop using the System Sensor ® protocol. If you add a second loop module, it increases the maximum device count to 636 devices. • Up to 126 devices per loop using the Apollo protocol. If you add a second loop module, it increases the maxi-mum device count to 252 devices. Four Class B or two Class A NACs can be wired and syn- chronized using the System Sensor, Cooper-Wheelock, or Gentex strobes. To retrofit the SLP on the existing audible/ visual appliances, the on-board Electronic EOL (EEOL) automatically adjusts to the EOL resistor in the field. A 4.3" (10.92 cm) color touchscreen display screen shows the following: • Events on the system • Status of analog addressable devices • Complete diagnostic fault codes/messages • Five programmable function buttons with LED status for accessibility to the following functions: - Disable/Enable - Trouble Acknowledge - Bypass Output - Alarm Acknowledge - Lamp Test - Custom-defined E3 Series®, System Sensor® and FocalPoint® are registered trademarks of Honeywell International Inc. UL® is a registered trademark of Underwriters Laboratories Inc. Features S3 Series • Listed per ANSI/UL ® Standard 864 9th Edition. • IBC Seismic Certified. • Allows one SLC loop (expandable to two loops) that supports either System Sensor or Apollo devices in Class A or Class B (Style 4, 6 or 7). • System Sensor supports up to 318 intelligentdevices and each SLC loop supports the following.- up to 159 detectors.- up to 159 modules (expandable to 636 maximum per panel). • Apollo supports up to 126 intelligent detectors and modules per SLC. (Expandable to 252 maximum per panel).• Includes a high resolution (4.3”) (10.92 cm) color touch- screen display.• Supports a network system of up to 122 nodes(includes E3 Series® panels) or up to 64 nodes (includes 7100 Series).• Provides 7.0 amp power supply (120VAC or 240VAC). •Includes four Class B or two Class A built-in Notification Appliance Circuits (NAC). Provides selectable System Sensor, Cooper-Wheelock, or Gentex strobe synchroni-zation. • Supports up to 32 serial annunciators (LCD, LED-only, LED Switch). RECEIVED 09/19/2018 striplett BUILDING DIVISION F18005260_V1 By: cthomas Date: 10/02/2018 FIRE DEPARTMENT For Construction Subject to Corrections Noted in Red APPROVED GAMEWELL-FCI 12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-71189021-60730 Rev. F1 page 2 of 4 www.gamewell-fci.com Application The S3 Series Fire Alarm and Life Safety System is an easy-to-use intelligent fire alarm solution designed for the small to mid-sized buildings. Analog technology delivers the benefits of a simple system installation, while a user- friendly interface makes panel operation and system main- tenance quick and intuitive. Smart Panel Programming Using Boolean logic programming, the installer may cus- tomize the system to precisely suit the needs of the build- ing owner. Auto-programming allows the installer to instantly locate all the devices on the SLC loop. Simple, Intuitive Display The front panel display provides a user-friendly interface for the operator's control. A 4.3” (10.922 cm) color touch- screen displays system status, event details and service modes. On the front of the panel, six LEDs show the follow- ing conditions. • Fire • Silenced • Hazard (Gas or CO) • AC Power • Supervisory • Trouble Five custom programmable switches allow the user quick access to common functions specific to the building like device disable, output bypass and device status. Perfect for Retrofits The S3 Series is well-suited for retrofit applications. TheSLP provides a simple way to upgrade your fire protectionsystem. It is designed to be an upgrade solution for the leg-acy FCI 7100 and Gamewell 602 Series panels. An addedfeature is the SLP's EEOL. Using EEOL, the installers canautomatically identify the EOL for existing audible/visualappliances. Flexibility for Future Growth The S3 Series can be expanded to add a second SLC loop without replacing the entire system. Using the RPT-E3- UTP Network Repeater, you can network up to 64 nodes (122 nodes with the ANX node expander) using either twisted-pair or fiber-optic. The built-in Ethernet port allows the connection to the Gamewell-FCI’s FocalPoint Graphical Workstation. Figure 1 LCD-SLP Display Features (Continued) • Offers an Ethernet port for programming, a variety of system reports, and a FocalPoint® Graphic Workstation connectivity. • Provides two fully-programmable Form-C contacts for Fire, Trouble, and Supervisory. • TimeCap - Saves time and date up to 48 hours without any power or battery. • Automatically adjusts to any NAC End-of-Line Resistor (EOL) value (1k-55k ohm) for legacy audible/visual appliances. • Removable display can be used as a remote annunciator. • Suitable for pre-action deluge applications. Optional Accessories DACT-E3 - Dialer The Digital Alarm Communication Transmitter sends digital signals over telephone lines to the central station. It con- nects to the SLP through an RS-485 bus. Using the Con- tact ID format, the DACT-E3 provides a four-digit account code followed by the code/numbers listed below: • Three-digit Event Code • Two-digit Group Number • Three-digit Contact Number All codes are used to provide specific point identification. The DACT-E3 is compatible with digital alarm communica- tor receivers (DACRs) that receive the following signaling formats: • Contact ID • SIA •3+1 •4+2 For more information, refer to the following data sheets: DACT-E3 Data Sheet, P/N: 9020-0610 FML-E3/FSL-E3 Data Sheet, P/N: 9021-60783 RPT-E3-UTP - Network Repeater Card The Network Repeater allows the SLP fire control panels to connect to the broadband network from remote locations. It connects to other networked units using unshielded, twisted-pair wiring. The RPT-E3-UTP is available with two add-on fiber modules: •FML-E3 connects to the network using either 62.5/125 micron multi-mode fiber. •FSL-E3 connects to the network using 9/125 micron single-mode fiber. Refer to the RPT-E3-UTP Data Sheet, P/N: 9020-0609. LCD-7100 - Remote Annunciator The Remote serial display features an 80-character dis-play. The LCD-7100 can be surface or flush-mounted on astandard 4-gang electrical box. You can use up to fiveLCD-7100 remote annunciators per SLP panel. For moreinformation, refer to the LCD-7100 Data Sheet, P/N: 9020-0486. ASM-16 - Addressable Switch/LED Module There are 16 programmable switches available to perform any function the application requires. Each ASM-16 switch has 3 LEDs fully programmable in red, yellow, and green. These LEDs can be programmed to operate with a certain button press or operate independently as a status signal (e.g. ON, OFF, Activated, etc). Up to 16 ASM-16 modules can be connected to the SLP panel. For more information, refer to the ASM-16 Data Sheet, P/N: 9020-0554. ANU-48 - 48 LED Driver Unit The ANU-48 provides output for eight remote panelswitches and 48 remote LEDs for use in a remotely located UL® Listed annunciator enclosure. Up to 16 ANU-48 mod-ules can be connected to the SLP panel. For more infor-mation, refer to the ANU-48 Data Sheet, P/N: 9020-0596. RECEIVED 09/19/2018 striplett BUILDING DIVISION F18005260_V1 GAMEWELL-FCI 12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118www.gamewell-fci.com 9021-60730 Rev. F1 page 3 of 4 Figure 2 illustrates the SLP-BB Cabinet Enclosure. Figure 2 SLP Enclosure SLP-BB CABINET OUTER DOOR SLP-BB CABINET BACKBOX 1 2 3 4 14 1/2" W 20 1/8"H 4 1/2" D Specifications Device Loops Up to two Class A or B, System Sensor units, each loop supporting up to 318 device addresses.Or-Apollo units, each loop supporting up to 126 device addresses per loop. NAC circuits 4 Class B or 2 Class A (2.0 A each circuit), 6.0 A total NAC Operating Voltage 24 VDC NAC Minimum Voltage 19.5 VDC @ 20.4 V battery voltage SLC Loop Circuit Operating Voltage 24 V peak-to-peak Input Voltage 120 VAC, 60 Hz 240 VAC 50-60 Hz Input Current 120 VAC, 2.75 amps max.240 VAC, 1.4 amps max. Aux Power 1 (Continuous)24 VDC nominal at 1.0A Aux Power 2 (Resettable)24 VDC nominal at 1.0A Base Panel Current draw Standby: 0.111 ampsAlarm: 0.243 amps Operating Temperature 32°-120° F (0°-49° C) Relative Humidity 93% (non-condensing) Battery Charger Voltage +24 VDC Battery Charger Capacity 55 A/H batteries (cabinet accommodates 12 A/H batteries) Alarm, Trouble & Supervisory Relay Contacts Form-C, 2 amps @ 24VDC (resistive) Cabinet Dimensions: SLP-BB Dimensions 14 1/2” W x 20 1/8” H x 4 1/2” D (36.83 W x 51.18 H x 11.43 D cm) S3BB-RB Dimensions 19 3/8” W x 19 3/8” H x 4.5” D (49.22 W x 49.22 H x 11.43 D) Figure 3 SLP Panel Configuration Networkable up to 122 panels using twisted pair wire or fiber optics. FocalPoint Workstation LCD-E3 Remote Annunicator LCD-SLP Color Touchscreen Annunicator LCD-7100 emote Annunicator ASM-16 LED Switch Control ANU-48 LED Display Driver RS485DACTRS232EthernetRelay: 3 Form CS3 Series Fire Alarm Control Panel MCS-COF Fire/Carbon Monoxide Detector MS-7AF Pull Station AMM-2RIF Dual Input/Output Module Supports up to 636 Velociti devices or 252 XP95 devices DNR Intelligent Duct Detector ASD-PL2F Photo Detector AOM-2RF Relay Module AMM-2IF Mini Monitor Module ASD-LS Laser Detector Local Energy Trip E3 Series Panel Laptop Programming RECEIVED 09/19/2018 striplett BUILDING DIVISION F18005260_V1 GAMEWELL-FCI 12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-71189021-60730 Rev. F1 page 4 of 4 www.gamewell-fci.com Ordering Information Part Number Description SLP-BLK SLP addressable FACP in black SLP-BBenclosure. Requires either an SLC-PM or an SLC95-PM for SLC loops. SLP-RED SLP addressable FACP with red door and black SLP-BB backbox. Requires either an SLC-PM or an SLC95-PM for SLC loops. SLP-RED-G SLP addressable FACP 240VAC power supply with red door and black SLP-BB backbox. Requires either an SLC-PM or an SLC95-PM for SLC loops. SLC-PM System Sensor Loop Card - 1 loop used for 159 sensors and 159 modules. For use with the SLP-E3 panels only. SLC95-PM Apollo Loop Card-1 loop used for 126 sensors and modules. For use with the SLP-E3 panels only. Ordering Information (Continued) Part Number Description Accessories DACT-E3 Digital Dialer Communicator Transmitter for the S3 or E3 Series. LCD-SLP LCD Color Touchscreen display withfive programmable switches. For use with the S3 Series panels. Remote annunciation requires the E3 Series A2 cabinet. (E3BB-BA2, E3BB-RA2) RPT-E3-UTP Network repeater card with twisted- pair fiber connections require either anFML-E3 or an FSL-E3 card. FML-E3 Multi-mode fiber-optic card for one channel on the RPT-E3-UTP. FSL-E3 Single-mode fiber-optic card for one channel on the RPT-E3-UTP. SLP-RB SLP motherboard For use with the replacement or the retrofit solutions. FLPS-7-RB SLP 120VAC 7A power supply. For use with the replacement or theretrofit solutions. SLP-RETROFIT SLP Retrofit Kit for the 7100 B-Slimand IF602 panels. Includes the new door and the mount- ing plate. Requires the following: • SLP-RB • LCD-SLP •SLC-PM/ SLC95-PM • FLPS-7-RB S3BB-RB SLP red cabinet with an inner door for the mounting display behind the plexiglass. Requires the following: • SLP-RB • LCD-SLP •SLC-PM/ SLC95-PM • FLPS-7-RB LCD-7100 Remote Serial LCD Annunciator ASM-16 Remote Programmable AddressableSwitch/LED Module ANU-48 Remote LED Driver Module RECEIVED 09/19/2018 striplett BUILDING DIVISION F18005260_V1 GAMEWELL-FCI12 Clintonville Road, Northford, CT 06472-1653 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118Specifications are for information only, are not intended for installation purposes, and are subject to change without notice. No responsibility is assumed by Gamewell-FCI for their use. ©2013 by Honeywell International Inc. All rights reserved.www.gamewell-fci.com 9020-0617 Rev. J page 1 of 2 Velociti® Series ASD-PL2F, ASD-PTL2F and ASD-PL2FR Analog, Addressable Photoelectronic Smoke Sensor APPROVED FM 3023594 SIGNALING 7272-1703:0121S1913 MEAApprovedFDNY COA #:219-02-E Vol.VI Description The Gamewell-FCI Velociti® Series, analog address- able plug-in smoke sensors with integral communica- tion provide features that surpass conventional sensors. Sensitivity can be programmed in the con- trol panel software, and is continuously monitored and reported to the panel. Point ID capability allows each sensor’s address to be set, providing exact locations for selective maintenance when the cham- ber contamination reaches an unacceptable level. The ASD-PL2F photoelectric sensor’s unique optical sensing chamber is engineered to sense smoke pro- duced by a wide range of combustion sources. Dual electronic thermistors add 135°F (57°C) fixed-tem- perature thermal sensing on the ASD-PTL2F model. The Velociti® Series use a communication protocol that substantially increases the speed of communica- tion between the sensors and certain Gamewell-FCI analog addressable fire alarm controls. These devices operate in a grouped fashion. If one of the devices in the group has a status change, the panel’s microprocessor stops the group poll and concen- trates on the single device. The net effect is a response speed up to five times greater than earlier designs. Velociti® is a registered trademark of Honeywell International Inc. UL® is a registered trademark of Underwriters Laboratories Inc. Ordering Information Part Number Description ASD-PL2F Analog, addressable photoelectronic smoke sensor ASD-PTL2F Analog, addressable photoelectronic smoke sensor with thermal sensing ASD-PL2FR Analog, addressable photoelectronic smoke sensor used with the DNR duct base when the remote test is required. Features • Sleek, low-profile design. • Visual rotary, decimal switch addressing (01-159). • Built-in functional test switch activated by an external magnet. • Bicolor LEDs flash green whenever the sensor is addressed, and light steady red on alarm.* • Optional relay, isolator, or sounder bases. • Low standby current. • Analog addressable communication. • Stable communication technique with noise immunity. • Optional remote, single-gang LED Indicator (RA100Z). • Compatible with Gamewell-FCI analog addressable panels. Note: *Only the red LED is operative in panels that do not operate in Velociti® mode. ASD-PL2FRASD-PL2F/ASD-PTL2F RECEIVED 09/19/2018 striplett BUILDING DIVISION F18005260_V1 GAMEWELL-FCI 12 Clintonville Road, Northford, CT 06472-1653 USA • Tel: (203) 484-7161 • Fax: (203) 484-71189020-0617 Rev. J page 2 of 2 www.gamewell-fci.com Installation ASD-PL2F plug-in sensors use a separate base to simplify installation, service, and maintenance. A special tool allows maintenance personnel to plug-in and remove sensors without using a ladder. Mount the base on a box which is at least 1.5" (3.8 cm) deep. Suitable mounting base boxes include: •4.0" (10.2 cm) square box. •3.5" (8.9 cm) or 4.0" (10.2 cm) octagonal box. • Single-gang box (except relay or isolator bases). • With B200S or B200SR base, mounted on a 4.0" (10.2 cm) octagonal or square box. • With B224RB or B224BI base, mounted on a 3.5" (8.9 cm) octagonal box, or a 4.0" (10.2 cm) octagonal or square box. NOTE: Because of the inherent supervision provided by the SLC, end-of-line resistors are not required. Wiring “T-taps” or branches are permitted for Style 4 (Class “B”) wiring. Sensor Spacing Gamewell-FCI recommends that the spacing sensors be used in compliance with NFPA 72. Specifications ASD-PL2F, ASD-PTL2F, ASD-PL2FR: Dimensions:2.1” (5.1 cm) height Diameter:4.1” (10.4 cm) installed in the B501 base 6.1” (15.5 cm) installed in the B210LP base Shipping Weight:5.2 oz. (147 g) Operating Temperature: ASD-PL2F: 32° F to 120° F (0° C to 49° C) ASD-PTL2F: 32° F to 100° F (0° C to 38° C) UL®-Listed Velocity Range: 0-4000 ft./min. (1,219.2 m/min.), suitable for installation in ducts. Relative Humidity: 10-93% (non-condensing) Thermal Ratings:Fixed-temperature setpoint 135° F (57° C) Electrical Specifications Voltage Range: 15 – 32 volts DC peak Standby Current: (max. avg.): .0003 A @ 24 VDC (One communication every 5 seconds with LED blink enabled). Maximum Alarm- Current: .0065 A @ 24 VDC (LED) lit). Bases and Options B501 Plug-in sensor base without flange Dimensions:4.1” (10.4 cm) diameter B210LP Flanged mounting base Dimensions:6.1” (15.5 cm) diameter B210LPBP Flanged mounting base bulk pack Dimensions:6.1” (15.5 cm) diameter B224RB Relay Base Plug-in sensor base with auxiliary relay, SPDT, rated 2 amps @ 30 VDC (resistive). Screw terminals: Up to 14 AWG (2.0 mm2) 2 coil latching relay 1 Form C contact UL/CSA Rating: 0.9 A @ 125 VAC, inductive 0.9 A @ 110 VDC, inductive 3 A @ 30 VDC, resistive Dimensions:6.1” (15.5 cm) diameter Maximum: 25 devices between isolator bases. B200S Intelligent sensor sounder base Dimensions:6.875” (17.5 cm) diameter B200SR Standard sounder base, UL 8649th Edition compliant, ULC Listed Dimensions:6.875” (17.5 cm) diameter RA100Z Remote LED Annunciator BCK-200 Black detector covers (box of 10) DNR Duct smoke housing RECEIVED 09/19/2018 striplett BUILDING DIVISION F18005260_V1 Velociti™ Series AMM-2F Monitor Module INSTALLATION AND MAINTENANCE INSTRUCTIONS 9000-0590 1 I56-3554-001 ©2007 Gamewell-FCI BEFORE INSTALLINg This information is included as a quick reference installation guide. Refer to the control panel installation manual for detailed system information. If the modules will be installed in an existing operational system, inform the opera- tor and local authority that the system will be temporarily out of service. Dis- connect power to the control panel before installing the modules. NOTICE: This manual should be left with the owner/user of this equipment. gENERAL DESCRIpTION The AMM-2F monitor module can be installed in a single gang junction box directly behind the monitored unit. Its small size and light weight allow it to be installed without rigid mounting (see Figure 1). The AMM-2F is intended for use in intelligent, two-wire systems where the individual address of each module is selected using rotary switches. It provides a two-wire initiating de- vice circuit for normally open contact fire alarm and security devices. COMpATIBILITy REqUIREMENTS To ensure proper operation, this module shall be connected to a compatible Gamewell-FCI system control panel (list available from Gamewell-FCI). FIgURE 1: C1063-00 SpECIFICATIONS Nominal Operating Voltage: 15-32 VDC Average Operating Current: 375µA maximum (Group Poll); 350µA (Direct Poll); 600µA Max (Communicating IDC Shorted) EOL resistance: 47K Ohms Maximum SLC Wiring Resistance: 40 ohms Maximum IDC wiring resistance: 1,500 Ohms Maximum IDC Voltage: 11 Volts Maximum IDC Current: 450µA Temperature Range: 32˚F to 120˚ F (0˚C to 49˚ C) Humidity: 10% to 93% Non-condensing Dimensions: 1.3˝ H x 2.75˝ W x 0.5˝ D Wire length: 6˝ minimum 12 Clintonville Rd., Northford, CT 06472-1653 (203) 484-7161; Fax: (203) 484-7118 I56-3554-001MOUNTINg AND WIRINg NOTE: This module is intended to be wired and mounted without rigid con- nections inside a standard electrical box. All wiring must conform to appli- cable local codes, ordinances and regulations. 1. Connect the red (+) and black (–) wires to the positive and negative loop power leads of the signaling line circuit (SLC). 2. Connect the violet (+) and yellow (–) wires to a two-wire, normally open initiating loop. 3. Install the specified EOL resistor value to terminate the initiating loop. 4. Set the address on the module per job drawings. 5. Install the module in the desired mounting location. FIgURE 2. TypICAL 2-WIRE STyLE B INITIATINg DEvICE CIRCUIT CONFIgURATION: 0 78654321 9101112131415 (+) (–) TONEXTDEVICE BLACKRED(+)(–)(+)(–)VIOLET YELLOW 0123456789 SIGNAL LINE CIRCUIT (SLC) 47k EOLINCLUDED(ELR-47k) UL LISTED COMPATIBLE CONTROL PANEL ALL WIRING SHOWN IS SUPERVISED AND POWER LIMITED C0614-02 RECEIVED 09/19/2018 striplett BUILDING DIVISION F18005260_V1 9000-0592 1 I56-2750-002 Velociti™ Series AMM-2IF Dual Monitor Module INSTALLATION AND MAINTENANCE INSTRUCTIONS BEFORE INSTALLINg This information is included as a quick reference installation guide. Refer to the control panel installation manual for detailed system information. If the modules will be installed in an existing operational system, inform the opera- tor and local authority that the system will be temporarily out of service. Dis- connect power to the control panel before installing the modules. NOTICE: This manual should be left with the owner/user of this equipment. gENERAL DESCRIpTION The Dual Monitor Module is intended for use in intelligent, two wire systems. It provides two independent 2-wire initiating device circuits (IDC), at two sep- arate, consecutive addresses. It is capable of monitoring normally open con- tact fire alarm and supervisory devices, or either normally open or normally closed security devices. The module has a single panel controlled red LED. COMpATIBILITy REqUIREMENTS To ensure proper operation, this module shall be connected to a compatible Gamewell-FCI system control panel (list available from Gamewell-FCI). FIgURE 1. REMOvINg ROTARy SwITCh STOp: 0 7 8654321 9101112131415 9 8 7 6 5 4 3 2 1 0 TENS ONES ADDRESSLOOP 02 4 68 C1032-00 SpECIFICATIONS Normal Operating Voltage: 15 to 32 VDC Maximum Current Draw: 6.4 mA (LED on) Average Operating Current: 750µA (LED flashing) Maximum SLC Wiring Resistance: 40 ohms EOL Resistance: 47K ohms Maximum IDC wiring resistance: 1,500 ohms Maximum IDC Voltage: 11.7 Volts Maximum IDC Current: 240µA Temperature Range: 32˚F to 120˚F (0˚C to 49˚C) Humidity: 10% to 93% Non-condensing Dimensions: 41/2˝ H x 4˝ W x 11/4˝ D (Mounts to a 4˝ square by 21/8˝ deep box.) Accessories: SMB500 Electrical Box I56-2750-002MOUNTINg Mounts directly to 4-inch square electrical boxes (see Figure 2A). The box must have a minimum depth of 21/8 inches. Surface mounted electrical boxes (SMB500) are available from Gamewell-FCI. FIgURE 2A. MODULE MOUNTINg: FIgURE 2B: 0 12349 87650 TENS ONES ADDR ESSLOOP 864 2ISOLATEDQUADRANT 012 3 4 9876 50TENS ONES ADDRE SSLOOP 864 2 09876543 2 1101112131415 09876543 2 110 1112131415 C1028-00 12 Clintonville Road Northford, CT 06472-1653 Phone: 203/484-7161 RECEIVED 09/19/2018 striplett BUILDING DIVISION F18005260_V1 9000-0592 2 I56-2750-002 ©2007 Gamewell-FCI FIgURE 3. TypICAL 2-wIRE INITIATINg CIRCUIT CONFIgURATION, NFpA STyLE B: C0608-02 wIRINg NOTE: All wiring must conform to applicable local codes, ordinances, and regulations. This module is intended for power limited wiring only. 1. Install module wiring in accordance with the job drawings and appropri- ate wiring diagrams. 2. Set the address on the module per job drawings. NOTE: Some panels support extended addressing. In order to set the module above address 99 on compatible systems, carefully remove the stop on the upper rotary switch with thumb in the direction shown in Figure 1. NOTE: Monitor module L (using terminals 6 and 7) responds at the ad- dress set on the code switches. Monitor module H (using terminals 8 and 9) will automatically respond at the next higher address. For example, if the code switches are set to 76, module L will respond at address 76 and module H will respond at address 77. Use caution to avoid duplicate ad- dressing of modules on the system. 3. Secure module to electrical box (supplied by installer), as shown in Figure 2A. 0 78654321 9101112131415 9 8 7 6 5 4 3 2 1 0 TENS ONES ADDRESSLOOP 024 68 H L TWO INITIATING DEVICE CIRCUITS (L&H), EACH POWER LIMITED TO 240 µA @ 11.7 VDC MAX. UL LISTED CONTACT CLOSURE DEVICES MAY BE USED. DO NOT MIX FIRE ALARM INITIATING, SUPERVISORY, OR SECURITY DEVICES ON THE SAME INITIATING DEVICE CIRCUIT. INSTALL CONTACT CLOSURE DEVICES PER MANUFACTURER’S INSTALLATION INSTRUCTIONS. 47k EOL RESISTOR ELR-47k 47k EOL RESISTOR ELR-47k TO NEXT DEVICE (+) (-) (+) (-) (+) (-)FROM PANEL OR PREVIOUS DEVICE CONNECT MODULES TO LISTED COMPATIBLE CONTROL PANELS ONLY MONITOR A (TERMINALS 6 & 7) RESPONDS AT ADDRESS SET ON CODE SWITCHES. MONITOR B (TERMINALS 8 & 9) RESPONDS AT NEXT HIGHER ADDRESS. SIGNAL LINE CIRCUIT (SLC)32 VDC MAX. SHIELDED-TWISTED PAIR IS RECOMMENDED MONITOR MODULE ALL WIRING SHOWN IS SUPERVISED AND POWER LIMITED RECEIVED 09/19/2018 striplett BUILDING DIVISION F18005260_V1 ATD-L2F Veloticit® Series ATD-L2F, ATD-RL2F Addressable Thermal Sensor Addressable Devices GENERAL The Gamewell-FCI, Velociti® Series addressable plug-in thermal sensors with integral communication provide features that surpass conventional sensors. Point ID capability allows each sensor’s address to be set, providing exact locations for pinpointing alarm locations and used for selective maintenance. ATD thermal sensors use an innovative thermistor sensing circuit to produce 135°F/57°C fixed- temperature (ATD-L2F). The ATD-RL2F provides a combination 15°/minute rate-of- rise with 135° fixed thermal detection that is included in a low-profile package. The ATD-HL2F provides fixed high-temperature detection at 190°F/88°C. These thermal sensors provide cost-effective, addressable property protection in a variety of applications. The Velociti® Series uses a communication protocol that substantially increases the speed of communication between the sensors and Gamewell-FCI analog addressable fire alarm controls. These devices operate in a grouped fashion. If one of the devices in the group has a status change, the panel’s microprocessor stops the group poll and identifies the single device with the status change. The net effect is response speed up to five times greater than earlier designs. Installation The ATD plug-in sensors use a separate base to simplify installation, service, and maintenance. A special tool allows maintenance personnel to plug-in and remove sensors without using a ladder. Mount the base on a box which is at least 1.5" (3.8 cm) deep. Suitable mounting base boxes include: • 4.0" (10.2 cm) square box • 3.5" (8.9 cm) or 4.0" (10.2 cm) octagonal box • Single-gang box (except relay or isolator base) With B200S or B200SR base, mounted on a 4.0" (10.2 cm) octagonal or square box. With B224RB or B224BI base, mounted on a 3.5" (8.9 cm) octagonal box, or a 4.0" (10.2 cm) octagonal or square box. NOTE: Due to the inherent supervision provided by the SLC, the end-of-line resistors are not required. Wiring “T-taps” or branches are permitted for Style 4 (Class “B”) wiring. Ordering Information ATD-L2F: Addressable thermal sensor, fixed, 135° F ATD-RL2F: Addressable thermal sensor, combination fixed,135° F and 15°/minute rate-of-rise ATD-HL2F: Addressable thermal sensor, fixed, 190° F FEATURES & BENEFITS • Sleek, low-profile design • Visual rotary switch addressing • Built-in functional test switch activated by an external magnet •Bi-color LEDs flash green whenever the sensor is addressed, and light steadily red on alarm* • Optional relay, isolator, or sounder bases • Low standby current • Addressable communication • Stable communication technique with noise immunity • Optional remote, single-gang LED accessory (RA-100Z) • Suitable for installation in ducts Note: *Only the red LED is operative in panels that do not operate in Velociti® mode. RECEIVED 09/19/2018 striplett BUILDING DIVISION F18005260_V1 Veloticit® Series ATD-L2F, ATD-RL2F Technical Specifications 9020-0620 | F | 11/17 ©2017 Honeywell International Inc. For a complete listing of all compliance approvals and certifications, please visit: http://www.gamewell- fci.com/en-US/ documentation/Pages/ Listings.aspx Gamewell-FCI®, Velociti® and E3 Series® are registered trademarks of Honeywell International Inc. UL® is a registered trademark of Underwriters Laboratories Inc. ULC® is a registered trademark of Underwriters Laboratories Canada Inc. This document is not intended to be used for installation purposes. We try to keep our product information up-to- date and accurate. We cannot cover all specific applications or anticipate all requirements. All specifications are subject to change without notice. Honeywell Gamewell-FCI 12 Clintonville Road Northford, CT 06472-1610 203.484.7161 www.honeywell.com For more information Learn more about Gamewell-FCI’s Veloticit® Series ATD-L2F, ATD-RL2F and other products available by visiting www.Gamewell-FCI.com SYSTEMS ATD-L2F/ATD-RL2F: Dimensions: 2.1" (5.3 cm) Height 4.1" (10.4 cm) diameter installed in the B501 base 6.1" (15.5 cm) diameter installed in the B210LP base Shipping Weight: 4.8 oz. (137 g) Operating Temperature: ATD-L2F or ATD-RL2F: –4° F to 100° F (–20° C to 38°C) ATD-HL2: –4° F to 150°F (–20 C to 66°C) Sensor Spacing: UL® approved for 50 ft. (15.2 m) center to center FM approved for 25 x 25 ft. (7.6 x 7.6 m) spacing Relative Humidity: 10 – 93% (non-condensing) ATD-L2F: Fixed-temperature setpoint 135°F (57°C) ATD-RL2F: Combination 135° F fixed temperature and 15° F(8.3°c)/per minute rate-of-rise° ATD-HL2F: Fixed-temperature setpoint 190°F (88°C) Electrical Specifications Voltage Range: 15 - 32 Volts DC peak Standby Current: 200 mA @ 24 VDC (without communication) (max. avg.) .0003 A @ 24 VDC (one communication every 5 seconds with LED blink enabled) LED Current (max.) .0065 A @ 24 VDC (LED lit) Bases and Options B501: Plug-in sensor base without flange Dimensions: 4.1” (10.4 cm) diameter B210LP: Flanged mounting base Dimensions: 6.1” (15.5 cm) diameter B210LPBP: Flanged mounting base bulk pack Dimensions: 6.1” (15.5 cm) diameter B224RB: : Plug-in sensor base with auxiliary relay SPDT 2 coil latching relay 1 Form C contact UL/CSA Rating: 0.9 A @ 125 VAC (inductive) 0.9 @ 110 VDC (inductive) 3.A @ 30 VDC (resistive) Dimensions: 6.1” (15.5 cm) diameter B224BI: Plug-in sensor isolator base for Style 7 operation Dimensions: 6.1” (15.5 cm) diameter Maximum 25 devices between isolator bases B200S: Intelligent sensor sounder base Dimensions: 6.875” (17.5 cm) diameter B200SR: Standard sounder base, UL 864 9th Edition compliant, ULC Listed Dimensions: 6.875” (17.5 cm) diameter RA-100Z: Remote LED Annunciator BCK-200: Black detector covers (box of 10) TEMPERATURE AND HUMIDITY RANGES This system meets NFPA requirements for operation at 0 – 49°C/32 – 120°F and at a relative humidity 93% ± 2% RH (noncondensing) at 32°C ± 2°C (90°F ± 3°F). However, the useful life of the system's standby batteries and the electronic components may be adversely affected by extreme temperature ranges and humidity. Therefore, it is recommended that this system and its peripherals be installed in an environment with a normal room temperature of 15 – 27°C/60 – 80°F. STANDARDS The ATD-L2F/ATD-RL2F are designed to comply with the following standards: UL Standard: UL 864 9th Edition AGENCY LISTINGS AND APPROVALS These listings and approvals apply to the modules specified in this document. In some cases, certain modules or applications may not be listed by certain approval agencies, or listing may be in process. Consult factory for latest listing status. UL: S2332 FM: 3023594 MEA FDNY: 219-02-E Vol. VI CSFM: 7270-1703:0115 ISO 9001 Certification RECEIVED 09/19/2018 striplett BUILDING DIVISION F18005260_V1 MS-7 Series MS-7 Series Manual Fire Alarm Pull Stations Addressable Devices General The Gamewell-FCI, MS-7 Series manual fire alarm pull stations are available in a wide variety of configurations. The pull stations comply with the Americans with Disabilities Act (ADA) 5-lb. maximum pull force requirement. Operating instructions and Braille text are engraved in the handle. All pull stations include a key lock/reset which is keyed alike with the Gamewell-FCI fire alarm control panels and other manual fire alarm pull stations. MS-7AF Velociti Addressable Station The MS-7AF Velociti® Series addressable station is a double action pull station designed for installation in the signaling line circuit of Gamewell-FCI analog addressable control panels. Activation of the pull station causes its assigned address to register at the fire alarm control panel. The door contains an LED which flashes green in normal condition and lights steady red when the station has been activated.* The station features screw terminals. MS-7ASF Velociti Addressable Station The MS-7ASF Velociti® Series addressable pull station is a single action station designed for installation in the signaling line circuit of Gamewell-FCI analog addressable control panels. Activation of the station causes its assigned address to register at the control panel. The door contains an LED which flashes green in normal condition and lights steady red when the pull station is activated.* The station features screw terminals. The Velociti® Series pull stations use a communication protocol that substantially increases the speed of communication between the sensors and certain Gamewell-FCI analog addressable fire alarm controls. These devices operate in a grouped fashion. If one of the devices in the group has a status change, the panel’s microprocessor stops the group poll and focuses on the single device. The net effect offers a response speed up to five times greater than earlier designs. MS-7 Double Action Station The MS-7 double action pull station is used with conventional fire alarm control panels. It features a set of single pole contacts and screw terminals for connection to an initiating circuit. FEATURES & BENEFITS • Addressable stations compatible with all Gamewell-FCI analog addressable fire alarm controls • Conventional stations suitable for use with any UL® Listed control panel • The pull stations (MS- 7LOB) are Listed for outdoor applications • Complies with ADA pull force requirements • Offers surface or semi- flush mounting • Shock and vibration resistant • Both single and double action pull stations available • Includes a tumbler lock for test and reset keyed alike with analog addressable fire alarm controls *Only the red LED is operative in panels that do not operate in Velociti mode RECEIVED 09/19/2018 striplett BUILDING DIVISION F18005260_V1 2 MS-7S Single Action Station The MS-7S single action pull station is used with conventional fire alarm control panels. It features a set of single pole contacts and wire leads for connection to an initiating circuit. MS-7SP Double Action Station The MS-7SP is a double action pull station similar to the MS-7 station, with the additional feature of including both English and Spanish instructions molded into the unit. MS-7LR Dual-action Agent Release Station The MS-7LR is designed for use with the Gamewell-FCI fire alarm control panels with releasing capabilities and Flex Series releasing systems. It features a set of single pole contacts and screw terminals used to connect to an initiating circuit. MS-7LRA Agent Release Station with Abort The MS-7LRA is designed for use with the Gamewell- FCI fire alarm control panels with releasing capabilities and Flex Series releasing systems where system abort capabilities are required. It consists of the following: • An MS-7LR mounted on a plate with an abort switch • LED indicators that signal system normal and system activated status MS-7LOB Double Action Station (Listed for Outdoor Applications) The MS-7LOB station must be mounted on a Model SB-I/O backbox. In retrofit applications, the pull station is UL Listed for use with the WP-10 backbox. It is intended for use with conventional control panels and has a set of single pole contacts and screw terminals. Mounting The MS-7 interior pull stations may be surface mounted or semi-flush mounted on a standard double-gang, or 4-inch (10.2 cm) square electrical box. An optional trim ring (BG12TR) may also be used for semi-flush mounting. NYC-Plate The NYC-Plate provides the backplate for the manual pull station. (See Figure 1). Figure 1 NYC-Plate Ordering Information MS-7: Double action station MS-7AF**: Velociti addressable double action station MS-7ASF**: Velociti addressable single action station MS-7S: Single action station, wire leads MS-7SP: Double action station, English and Spanish instructions MS-7LR: Agent release station, dual-action MS-7LRA: Agent release station with abort switch, LED indicators, dual- action MS-7LOB: Double action station, outdoor use (Includes SB-I/O - Indoor/outdoor use backbox) SB-I/O: Indoor/outdoor use backbackbox SB-10: Surface backbox BG12TR: Trim ring for semi-flush mount, plastic NY-PLATE: NYC backplate for manual pull station **For use with the Gamewell-FCI analog addressable control panels only. RECEIVED 09/19/2018 striplett BUILDING DIVISION F18005260_V1 MS-7 Series Technical Specifications 9020-0616 | F | 11/17 ©2017 Honeywell International Inc. For a complete listing of all compliance approvals and certifications, please visit: http://www.gamewell- fci.com/en-US/ documentation/Pages/ Listings.aspx LEXAN® is a registered trademark of GE Plastics, a subsidiary of General Electric Company. Velociti® and Gamewell-FCI are registered trademarks of Honeywell International Inc. UL® is a registered trademark of Underwriter’s Laboratories Inc. This document is not intended to be used for installation purposes. We try to keep our product information up-to- date and accurate. We cannot cover all specific applications or anticipate all requirements. All specifications are subject to change without notice. Honeywell Gamewell-FCI 12 Clintonville Road Northford, CT 06472-1610 203.484.7161 www.honeywell.com For more information Learn more about Gamewell-FCI’s MS-7 Series and other products available by visiting www.Gamewell-FCI.com SYSTEMS Material: Lexan® Contact Ratings: 0.25 amps. @ 30 VAC/VDC (resistive) Dimensions: 5 5/8” H x 4 1/4” W x 1 1/4” D (14 x 10.1 x 3.2 cm) Operating Temperature: (MS-7AF, MS-7ASF): 32° to 120° F (0° to 49° C) (MS-7LOB): -30° to 150° F (-35° to 66° C) Relative Humidity : (MS-7AF, MS-7ASF): 10 to 93% (non-condensing) (MS-7LOB): 85% ± 5% @ 86° ± 3.6° (30° ± 2° C) Alarm Current: .0030 amp. 0.007 for LED Supervisory Current: (MS-7AF, MS-7ASF): .00030 amps. TEMPERATURE AND HUMIDITY RANGES This system meets NFPA requirements for operation at 0 – 49°C/32 – 120°F and at a relative humidity 93% ± 2% RH (noncondensing) at 32°C ± 2°C (90°F ± 3°F). However, the useful life of the system's standby batteries and the electronic components may be adversely affected by extreme temperature ranges and humidity. Therefore, it is recommended that this system and its peripherals be installed in an environment with a normal room temperature of 15 – 27°C/60 – 80°F. STANDARDS The MS-7 Series is designed to comply with the following standard: UL Standard: UL 864 9th Edition AGENCY LISTINGS AND APPROVALS These listings and approvals apply to the modules specified in this document. In some cases, certain modules or applications may not be listed by certain approval agencies, or listing may be in process. Consult factory for latest listing status. UL: S2465 FM: 3023594 MEA FDNY: 67-02-E Vol. VII CSFM: 7160-1703:0119 7160-1703:0170 7160-1703:0109 ISO 9001 Certification RECEIVED 09/19/2018 striplett BUILDING DIVISION F18005260_V1 Features • Plug-in design with minimal intrusion into the back box • Tamper-resistant construction • Automatic selection of 12- or 24-volt operation at 15 and 30 candela • Field-selectable candela settings on ceiling units: 15, 30, 75, 95, 115, 150, and 177 • Horn rated at 88+ dBA at 16 volts • Rotary switch for horn tone and two volume selections • Universal mounting plate for ceiling units • Mounting plate shorting spring feature checks wiring continuity before device installation • Electrically Compatible with legacy SpectrAlert and SpectrAlert Advance devices • Compatible with MDL3 sync module • Listed for ceiling mounting only The System Sensor L-Series offers the most versatile and easy-to-use line of horns, strobes, and horn strobes in the industry with lower current draws and modern aesthetics. With white and red plastic housings, wall and ceiling mounting options, System Sensor L-Series can meet virtually any application requirement. The entire L-Series product line of ceiling-mount strobes and horn strobes include a variety of features that increase their application versatility while simplifying installation. All devices feature a plug-in design with minimal intrusion into the back box, making installations fast and foolproof while virtually eliminating costly and time- consuming ground faults. To further simplify installation, the L-Series utilizes a universal mounting plate so installers can mount them to a wide array of back boxes. With an onboard shorting spring, installers can test wiring continuity before the device is installed. Installers can also easily adapt devices to a suit a wide range of application requirements using field-selectable candela settings, automatic selection of 12- or 24-volt operation, and a rotary switch for horn tones with two volume selections. Indoor Selectable- Output Strobes and Horn Strobes for Ceiling Applications System Sensor L-Series audible visible notification products are rich with features guaranteed to cut installation times and maximize profits with lower current draw and modern aesthetics. Agency Listings 7125-1653:0504 7135-1653:0503 S5512 S4011 FM approved except for ALERT models 3057383 RECEIVED 09/19/2018 striplett BUILDING DIVISION F18005260_V1 AVDS86800 L-Series Specifications Architect/Engineer Specifications General L-Series ceiling-mount strobes and horn strobes shall mount to a standard 4 × 4 × 1½-inch back box, 4-inch octagon back box, or double- gang back box. Two-wire products shall also mount to a single-gang 2 × 4 × 17⁄8-inch back box. A universal mounting plate shall be used for mounting ceiling and wall products. The notification appliance circuit wiring shall terminate at the universal mounting plate. Also, L-Series products, when used with the Sync•Circuit™ Module accessory, shall be powered from a non-coded notification appliance circuit output and shall operate on a nominal 12 or 24 volts. When used with the Sync•Circuit Module, 12-volt-rated notification appliance circuit outputs shall operate between 8.5 and 17.5 volts; 24-volt-rated notification appliance circuit outputs shall operate between 16.5 and 33 volts. Indoor L-Series products shall operate between 32 and 120 degrees Fahrenheit from a regulated DC or full-wave rectified unfiltered power supply. Ceiling strobes and horn strobes shall have field-selectable candela settings including 15, 30, 75, 95, 115, 150, and 177. Strobe The strobe shall be a System Sensor L-Series Model _______ listed to UL 1971 and shall be approved for fire protective service. The strobe shall be wired as a primary-signaling notification appliance and comply with the Americans with Disabilities Act requirements for visible signaling appliances, flashing at 1 Hz over the strobe’s entire operating voltage range. The strobe light shall consist of a xenon flash tube and associated lens/reflector system. Horn Strobe Combination The horn strobe shall be a System Sensor L-Series Model _______ listed to UL 1971 and UL 464 and shall be approved for fire protective service. The horn strobe shall be wired as a primary-signaling notification appliance and comply with the Americans with Disabilities Act requirements for visible signaling appliances, flashing at 1 Hz over the strobe’s entire operating voltage range. The strobe light shall consist of a xenon flash tube and associated lens/reflector system. The horn shall have two audibility options and an option to switch between a temporal three pattern and a non-temporal (continuous) pattern. These options are set by a multiple position switch. The horn on horn strobe models shall operate on a coded or non-coded power supply. Synchronization Module The module shall be a System Sensor Sync•Circuit model MDL3 listed to UL 464 and shall be approved for fire protective service. The module shall synchronize L-Series strobes at 1 Hz and horns at temporal three. Also, while operating the strobes, the module shall silence the horns on horn strobe models over a single pair of wires. The module shall mount to a 4 11⁄16 × 4 11⁄16 × 2 1⁄8-inch back box. The module shall also control two Style Y (class B) circuits or one Style Z (class A) circuit. The module shall synchronize multiple zones. Daisy chaining two or more synchronization modules together will synchronize all the zones they control. The module shall not operate on a coded power supply. Physical/Electrical Specifications Standard Operating Temperature 32°F to 120°F (0°C to 49°C) Humidity Range 10 to 93% non-condensing Strobe Flash Rate 1 flash per second Nominal Voltage Regulated 12 VDC or regulated 24 DC/FWR1 Operating Voltage Range2 8 to 17.5 V (12 V nominal) or 16 to 33 V (24 V nominal) Operating Voltage Range (MDL3)8.5 to 17.5V (12 V nominal) or 16.5 to 33 V (24V nominal) Input Terminal Wire Gauge 12 to 18 AWG Ceiling-Mount Dimensions (including lens)6.8" diameter × 2.5" high (173 mm diameter × 64 mm high) Ceiling-Mount Surface Mount Back Box Skirt Dimensions (SBBCRL, SBBCWL) 6.9" diameter x 3.4" high (175 mm diameter x 86 mm high) Notes: 1. Full Wave Rectified (FWR) voltage is a non-regulated, time-varying power source that is used on some power supply and panel outputs. 2. P, S, PC, and SC products will operate at 12 V nominal only for 15 and 30 cd. RECEIVED 09/19/2018 striplett BUILDING DIVISION F18005260_V1 AVDS86800 Horn and Horn Strobe Output (dBA) Switch Position Sound Pattern dB 8–17.5 Volts 16–33 Volts DC DC FWR 1 Temporal High 84 89 89 2 Temporal Low 75 83 83 3 Non-Temporal High 85 90 90 4 Non-Temporal Low 76 84 84 5 3.1 KHz Temporal High 83 88 88 6 3.1 KHz Temporal Low 76 82 82 7 3.1 KHz Non-Temporal High 84 89 89 8 3.1 KHz Non-Temporal Low 77 83 83 UL Max. Strobe Current Draw (mA RMS) Candela 8–17.5 Volts 16–33 Volts DC DC FWR 15 87 41 60 30 153 63 86 75 N/A 111 142 95 N/A 134 164 115 N/A 158 191 150 N/A 189 228 177 N/A 226 264 UL Max. Current Draw (mA RMS), 2-Wire Horn Strobe DC Input 8-17.5 Volts 16-33 Volts 15cd 30cd 15cd 30cd 75cd 95cd 115cd 150cd 177cd Temporal High 103 167 71 90 143 165 187 217 254 Temporal Low 96 165 54 71 137 161 185 211 249 Non-Temporal High 106 173 71 90 141 165 187 230 273 Non-Temportal Low 95 166 54 71 124 161 170 216 258 3.1K Temporal High 111 164 69 94 147 163 184 229 257 3.1K Temporal Low 103 163 54 88 143 155 185 212 252 3.1K Non-Temporal High 111 172 69 94 144 164 202 229 271 3.1K Non-Temporal Low 103 169 54 88 131 155 187 217 259 FWR Input 16-33 Volts 15cd 30cd 75cd 95cd 115cd 150cd 177cd Temporal High 107 135 179 198 223 254 286 Temporal Low 78 101 151 172 199 229 262 Non-Temporal High 107 135 179 198 223 254 286 Non-Temportal Low 78 101 151 172 199 229 262 3.1K Temporal High 108 135 179 200 225 255 289 3.1K Temporal Low 79 101 150 171 196 229 260 3.1K Non-Temporal High 108 135 179 200 225 255 289 3.1K Non-Temporal Low 79 101 150 171 196 229 260 UL Current Draw Data Horn Strobe Tones and Sound Output Data RECEIVED 09/19/2018 striplett BUILDING DIVISION F18005260_V1 3825 Ohio Avenue • St. Charles, IL 60174 Phone: 800-SENSOR2 • Fax: 630-377-6495 ©2017 System Sensor. Product specifications subject to change without notice. Visit systemsensor.com for current product information, including the latest version of this data sheet. AVDS86801 • 03/17 L-Series Dimensions Model Description Ceiling Horn Strobes PC2RL 2-Wire, Horn Strobe, Red PC2WL 2-Wire, Horn Strobe, White L-Series Ordering Information Ceiling-Mount Horn Strobes Ceiling Surface Mount Back Box Model Description Ceiling Strobes SCRL Strobe, Red SCWL Strobe, White SCWL-CLR-ALERT Strobe, White, ALERT Accessories TRC-2 Universal Ceiling Trim Ring Red TRC-2W Universal Ceiling Trim Ring White SBBCRL Ceiling Surface Mount Back Box, Red SBBCWL Ceiling Surface Mount Back Box, White Ceiling Mount Horn Strobes with Ceiling Surface Mount Back Box RECEIVED 09/19/2018 striplett BUILDING DIVISION F18005260_V1 Agency Listings Features t 8FBUIFSQSPPGQFS/&."9 *1 t -JTUFEUP6- TUSPCF BOE6- IPSO t $PNQBUJCMFXJUI4ZTUFN4FOTPSTZODISPOJ[BUJPOQSPUPDPMBOE MFHBDZ4QFDUS"MFSUQSPEVDUT t 'JFMETFMFDUBCMFDBOEFMBTFUUJOHT BOE t "VUPNBUJDTFMFDUJPOPGPSWPMUPQFSBUJPOBUBOE DBOEFMB t 3PUBSZTXJUDIGPSIPSOUPOFBOEUISFFWPMVNFTFMFDUJPOT t )PSOSBUFEBUE#"BUWPMUT t 3BUFEGSPNo¡'UP¡' t 6OJWFSTBMNPVOUJOHQMBUFXJUIBOPOCPBSETIPSUJOHTQSJOHUIBU UFTUTXJSJOHDPOUJOVJUZCFGPSFEFWJDFTBSFJOTUBMMFE t 1MVHJOEFTJHOXJUINJOJNBMJOUSVTJPOJOUPUIFCBDLCPY t 5BNQFSSFTJTUBOUDPOTUSVDUJPO t -JTUFEGPSDFJMJOHPSXBMMNPVOUJOH SpectrAlert Advance PGGFSTUIFCSPBEFTUMJOFPGPVUEPPSIPSOT TUSPCFT BOEIPSOTUSPCFTJOUIFJOEVTUSZ8JUIXIJUFPSSFEQMBTUJD IPVTJOHT XBMMPSDFJMJOHNPVOUJOHPQUJPOT BOEQMBJOPS'*3&QSJOUFE EFWJDFT 4QFDUS"MFSU"EWBODFDBONFFUWJSUVBMMZBOZBQQMJDBUJPO SFRVJSFNFOU JODMVEJOHJOEPPS PVUEPPS XFU BOEESZBQQMJDBUJPOTJO UFNQFSBUVSFTGSPN¦¡'UP¡' -JLFUIFFOUJSF4QFDUS"MFSU"EWBODFMJOF PVUEPPSIPSOT TUSPCFT BOEIPSOTUSPCFTGPSXBMMBQQMJDBUJPOTJODMVEFBWBSJFUZPGGFBUVSFT UIBUJODSFBTFBQQMJDBUJPOnFYJCJMJUZBOETJNQMJGZJOTUBMMBUJPO'JSTU m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nBOHFTBOEJNQSPWFESFTJTUBODFUPTBMUXBUFS DPSSPTJPO,OPDLPVUTMPDBUFEPOUIFCBDLFMJNJOBUFUIFOFFEUPESJMM IPMFTGPSTDSFXJONPVOUJOH1MBTUJDBOENFUBMXFBUIFSQSPPGCBDL CPYFTDPNFXJUI£JODIUPQBOECPUUPNDPOEVJUFOUSJFTBOE£JODI LOPDLPVUTBUUIFCBDL"TDSFXJO/15QMVHXJUIBO0SJOHHBTLFU GPSBXBUFSUJHIUTFBMJTJODMVEFEXJUIFBDICBDLCPY Outdoor Selectable- Output Horns, Strobes, and Horn Strobes for Wall Applications SpectrAlert® Advance outdoor audible visible products are rich with features that cut installation times and maximize profits. .&"& PVUEPPSTUSPCFT IPSOTUSPCFT DIJNFTUSPCFT IPSOT DIJNFT 4 DIJNFT IPSOTUSPCFT IPSOT 4 PVUEPPSBOEBMFSUTUSPCFT RECEIVED 09/19/2018 striplett BUILDING DIVISION F18005260_V1 "7%4 SpectrAlert Advance Outdoor Horn, Strobe, and Horn Strobe Specifications Architect/Engineer Specifications General 4QFDUS"MFSU"EWBODFPVUEPPSIPSOT TUSPCFT BOEIPSOTUSPCFTTIBMMNPVOUUPBXFBUIFSQSPPGCBDLCPY"VOJWFSTBMNPVOUJOHQMBUFTIBMM CFVTFEGPSNPVOUJOHDFJMJOHBOEXBMMQSPEVDUT5IFOPUJmDBUJPOBQQMJBODFDJSDVJUXJSJOHTIBMMUFSNJOBUFBUUIFVOJWFSTBMNPVOUJOHQMBUF "MTP 4QFDUS"MFSU"EWBODFQSPEVDUT XIFOVTFEXJUIUIF4ZODt$JSDVJU™.PEVMFBDDFTTPSZ TIBMMCFQPXFSFEGSPNBOPODPEFEOPUJmDBUJPO BQQMJBODFDJSDVJUPVUQVUBOETIBMMPQFSBUFPOBOPNJOBMPSWPMUT8IFOVTFEXJUIUIF4ZODt$JSDVJU.PEVMF WPMUSBUFEOPUJmDBUJPO BQQMJBODFDJSDVJUPVUQVUTTIBMMPQFSBUFCFUXFFOBOEWPMUTWPMUSBUFEOPUJmDBUJPOBQQMJBODFDJSDVJUPVUQVUTTIBMMPQFSBUFCFUXFFO BOEWPMUT0VUEPPS4QFDUS"MFSU"EWBODFQSPEVDUTTIBMMPQFSBUFCFUXFFO¦BOEEFHSFFT'BISFOIFJUGSPNBSFHVMBUFE%$PSGVMMXBWF SFDUJmFEVOmMUFSFEQPXFSTVQQMZ4USPCFTBOEIPSOTUSPCFTTIBMMIBWFmFMETFMFDUBCMFDBOEFMBTFUUJOHTJODMVEJOH BOE Strobe 5IFTUSPCFTIBMMCFB4ZTUFN4FOTPS4QFDUS"MFSU"EWBODF.PEFM@@@@@@@MJTUFEUP6-BOETIBMMCFBQQSPWFEGPSmSFQSPUFDUJWFTFSWJDF 5IFTUSPCFTIBMMCFXJSFEBTBQSJNBSZTJHOBMJOHOPUJmDBUJPOBQQMJBODFBOEDPNQMZXJUIUIF"NFSJDBOTXJUI%JTBCJMJUJFT"DUSFRVJSFNFOUTGPS WJTJCMFTJHOBMJOHBQQMJBODFT nBTIJOHBU)[PWFSUIFTUSPCFTFOUJSFPQFSBUJOHWPMUBHFSBOHF5IFTUSPCFMJHIUTIBMMDPOTJTUPGBYFOPOnBTI UVCFBOEBTTPDJBUFEMFOTSFnFDUPSTZTUFN5IFTUSPCFNVTUCFJOTUBMMFEXJUIJUTXFBUIFSQSPPGCBDLCPYJOPSEFSUPSFNBJOPVUEPPSBQQSPWFE QFS6-5IFTUSPCFTIBMMCFTVJUBCMFGPSVTFJOXFUFOWJSPONFOUT Horn Strobe Combination 5IFIPSOTUSPCFTIBMMCFB4ZTUFN4FOTPS4QFDUS"MFSU"EWBODF.PEFM@@@@@@@MJTUFEUP6-BOE6-BOETIBMMCFBQQSPWFEGPS mSFQSPUFDUJWFTFSWJDF5IFIPSOTUSPCFTIBMMCFXJSFEBTBQSJNBSZTJHOBMJOHOPUJmDBUJPOBQQMJBODFBOEDPNQMZXJUIUIF"NFSJDBOTXJUI %JTBCJMJUJFT"DUSFRVJSFNFOUTGPSWJTJCMFTJHOBMJOHBQQMJBODFT nBTIJOHBU)[PWFSUIFTUSPCFTFOUJSFPQFSBUJOHWPMUBHFSBOHF5IFTUSPCF MJHIUTIBMMDPOTJTUPGBYFOPOnBTIUVCFBOEBTTPDJBUFEMFOTSFnFDUPSTZTUFN5IFIPSOTIBMMIBWFUISFFBVEJCJMJUZPQUJPOTBOEBOPQUJPOUP TXJUDICFUXFFOBUFNQPSBMUISFFQBUUFSOBOEBOPOUFNQPSBM DPOUJOVPVT QBUUFSO5IFTFPQUJPOTTIBMMCFTFUCZBNVMUJQMFQPTJUJPOTXJUDI 0OGPVSXJSFQSPEVDUT UIFTUSPCFTIBMMCFQPXFSFEJOEFQFOEFOUMZPGUIFTPVOEFS5IFIPSOPSIPSOTUSPCFNPEFMTTIBMMPQFSBUFPOBDPEFEPS OPODPEFEQPXFSTVQQMZ5IFIPSOTUSPCFNVTUCFJOTUBMMFEXJUIJUTXFBUIFSQSPPGCBDLCPYJOPSEFSUPSFNBJOPVUEPPSBQQSPWFEQFS6-5IF IPSOTUSPCFTIBMMCFTVJUBCMFGPSVTFJOXFUFOWJSPONFOUT Physical/Electrical Specifications Operating Temperature o¡'UP¡' o¡$UP¡$ Strobe Flash Rate nBTIQFSTFDPOE Nominal Voltage 3FHVMBUFE%$'83PSSFHVMBUFE%$'83 Operating Voltage Range2 UP7 7OPNJOBM PSUP7 7OPNJOBM Input Terminal Wire Gauge UP"8( Wall-Mount Dimensions (including lens)-¨8¨% NN-¨NN8¨NN% Horn Dimensions -¨8¨% NN-¨NN8¨NN% Wall-Mount Weatherproof Back Box Dimensions (SA-WBB)-¨8¨% NN-¨NN8¨NN% Notes: 'VMM8BWF3FDUJmFE '83 WPMUBHFJTBOPOSFHVMBUFE UJNFWBSZJOHQPXFSTPVSDFUIBUJTVTFEPOTPNFQPXFSTVQQMZBOEQBOFMPVUQVUT 1 4 1$ BOE4$QSPEVDUTXJMMPQFSBUFBU7OPNJOBMPOMZGPSBOEDE RECEIVED 09/19/2018 striplett BUILDING DIVISION F18005260_V1 "7%4 Horn and Horn Strobe Output (dBA) Switch Position Sound Pattern dB 8–17.5 Volts 16–33 Volts 24-Volt Nominal Reverberant Anechoic DC FWR DC FWR DC FWR DC FWR 5FNQPSBM )JHI 88 88 2 5FNQPSBM .FEJVN 3 5FNQPSBM -PX 83 /PO 5FNQPSBM )JHI 82 82 88 88 5 /PO 5FNQPSBM .FEJVN 85 85 /PO 5FNQPSBM -PX 88 †$PEFE )JHI 82 82 88 88 8†$PEFE .FEJVN 85 85 †$PEFE -PX 88 85 †4FUUJOHT BOEBSFOPUBWBJMBCMFPOXJSFIPSOTUSPCF UL Max. Strobe Current Draw (mA RMS) Candela 8–17.5 Volts 16–33 Volts DC FWR DC FWR Standard Candela Range /" /" /" /" /" /" /" /" /" /" High Candela Range /" /"228 /" /" /" /" /" /" 258 UL Max. Current Draw (mA RMS), 2-Wire Horn Strobe, Standard Candela Range (15–115 cd) DC Input 8–17.5 Volts 16–33 Volts 15 15/75 15 15/75 30 75 95 110 115 5FNQPSBM)JHI 5FNQPSBM.FEJVN 5FNQPSBM-PX /PO5FNQPSBM)JHI /PO5FNQPSBM.FEJVN 85 /PO5FNQPSBM-PX FWR Input 5FNQPSBM)JHI 88 5FNQPSBM.FEJVN 88 5FNQPSBM-PX /PO5FNQPSBM)JHI /PO5FNQPSBM.FEJVN 85 /PO5FNQPSBM-PX UL Max. Current Draw (mA RMS), 2-Wire Horn Strobe, High Candela Range (135–185 cd) DC Input 16–33 Volts FWR Input 16–33 Volts 135 150 177 185 135 150 177 185 5FNQPSBM)JHI 5FNQPSBM)JHI 258 5FNQPSBM.FEJVN 235 253 288 5FNQPSBM.FEJVN 258 5FNQPSBM-PX 232 282 5FNQPSBM-PX /PO5FNQPSBM)JHI 255 /PO5FNQPSBM)JHI 233 /PO5FNQPSBM.FEJVN /PO5FNQPSBM.FEJVN 232 /PO5FNQPSBM-PX 238 /PO5FNQPSBM-PX UL Max. Horn Current Draw (mA RMS) Sound Pattern dB 8–17.5 Volts 16–33 Volts DC FWR DC FWR 5FNQPSBM )JHI 55 5FNQPSBM .FEJVN 58 5FNQPSBM -PX 38 /PO5FNQPSBM )JHI /PO5FNQPSBM .FEJVN /PO5FNQPSBM -PX $PEFE )JHI 55 $PEFE .FEJVN $PEFE -PX 52 UL Current Draw Data Horn Tones and Sound Output DataCandela Derating 'PS,TFSJFTQSPEVDUTVTFEBUMPXUFNQFSBUVSFT MJTUFE DBOEFMBSBUJOHTNVTUCFSFEVDFEJOBDDPSEBODFXJUI UIJTUBCMF Strobe Output (cd) Listed Candela Candela rating at –40°F %POPUVTFCFMPX¡' RECEIVED 09/19/2018 striplett BUILDING DIVISION F18005260_V1 0IJP"WFOVFt4U$IBSMFT *- 1IPOF4&/403t'BY ª4ZTUFN4FOTPS 1SPEVDUTQFDJmDBUJPOTTVCKFDUUPDIBOHFXJUIPVUOPUJDF7JTJUTZTUFNTFOTPSDPN GPSDVSSFOUQSPEVDUJOGPSNBUJPO JODMVEJOHUIFMBUFTUWFSTJPOPGUIJTEBUBTIFFU "7%4t SpectrAlert Advance Diagrams Model Description Wall Horn Strobes 13,†8JSF)PSO4USPCF 4UBOEBSEDE 3FE 0VUEPPS JODMVEFTQMBTUJDXFBUIFSQSPPGCBDLCPY 13),†8JSF)PSO4USPCF )JHIDE 3FE 0VUEPPS JODMVEFTQMBTUJDXFBUIFSQSPPGCBDLCPY 18,†8JSF)PSO4USPCF 4UBOEBSEDE 8IJUF 0VUEPPS JODMVEFTQMBTUJDXFBUIFSQSPPGCBDLCPY 18),†8JSF)PSO4USPCF )JHIDE 8IJUF 0VUEPPS JODMVEFTQMBTUJDXFBUIFSQSPPGCBDLCPY 13,†8JSF)PSO4USPCF 4UBOEBSEDE 3FE 0VUEPPS JODMVEFTQMBTUJDXFBUIFSQSPPGCBDLCPY 18, 8JSF)PSO4USPCF 4UBOEBSEDE 8IJUF 0VUEPPS JODMVEFTQMBTUJDXFBUIFSQSPPGCBDLCPY 13), 8JSF)PSO4USPCF )JHIDE 3FE 0VUEPPS 7 JODMVEFTQMBTUJDXFBUIFSQSPPGCBDLCPY Wall Strobes 43,†4USPCF 4UBOEBSEDE 3FE 0VUEPPS JODMVEFTQMBTUJDXFBUIFSQSPPGCBDLCPY 43),†4USPCF )JHIDE 3FE 0VUEPPS JODMVEFTQMBTUJDXFBUIFSQSPPGCBDLCPY 48,†4USPCF 4UBOEBSEDE 8IJUF 0VUEPPS JODMVEFTQMBTUJDXFBUIFSQSPPGCBDLCPY 48),†4USPCF )JHIDE 8IJUF 0VUEPPS JODMVEFTQMBTUJDXFBUIFSQSPPGCBDLCPY Horns )3,†)PSO 3FE 0VUEPPS JODMVEFTQMBTUJDXFBUIFSQSPPGCBDLCPY Accessories 4"8## 3FE .FUBM8FBUIFSQSPPG#BDL#PY 4"8##8 8IJUF .FUBM8FBUIFSQSPPG#BDL#PY SpectrAlert Advance Ordering Information Notes: "EEi1wUPNPEFMOVNCFSGPSQMBJOIPVTJOH OPi'*3&wNBSLJOHPODPWFS FH 13,1 p"EEi3wUPNPEFMOVNCFSGPSXFBUIFSQSPPGSFQMBDFNFOUEFWJDF OPCBDLCPYJODMVEFE POMZGPSVTFXJUIXFBUIFSQSPPGPVUEPPSnVTINPVOUJOHQMBUF 851BOE8518 i4UBOEBSEDEwSFGFSTUPTUSPCFTUIBUJODMVEF BOEDBOEFMBTFUUJOHTi)JHIDEwSFGFSTUPTUSPCFTUIBUJODMVEF BOE DBOEFMBTFUUJOHTWhen replacing standard outdoor units both the device and back box must be replaced. 4.7˝ 5.6˝ 2.5˝ Wall-Mount Horn Strobes Wall Plastic Weatherproof Back Box Wall-Mount Horn Strobe with Plastic Weatherproof Back Box RECEIVED 09/19/2018 striplett BUILDING DIVISION F18005260_V1 Fire Alarm Documents Cabinet Fire Alarm Documents (FAD) Cabinet Fire Alarm Storage Cabinet Accessories Description The Gamewell-FCI Fire Alarm Documents Cabinet (FAD) is the perfect solution to meet the demanding code standards required today. Gamewell-FCI's primary goal is to manufacture code compliant solutions and this product allows you to do just that. This cabinet is the answer to comply with the NFPA 72 2007, Section 6.2.2.1 requirements which states, "A record of installed software and firmware version numbers shall be maintained at the location of the fire alarm control unit. The Fire Alarm Documents cabinet may be used as a storage box for both printed and digital documentation, enabling you to store the system’s test and certified inspection documents, service records, manuals and AS built drawings. This cabinet is constructed of durable 16 gauge steel with a solid piano hinge and key lock. The cabinet includes a 4GB USB memory flash drive interface. Using a standard USB B connector, the USB flash drive interface allows you to use any standard USB printer cable to upload or download information. This feature allows you to store the fire alarm software in one secure place, so that the Technician can easily access the software and service the system. The Fire Document Box (FDB) interior is designed to contain critical manuals and documents. It is constructed with a durable steel retainer. The FDB has two key ring hooks to hold system keys, and a frame to insert Authorized personnel business cards. In the inner door, you can add the Legend Sheet to record property, system, service, code and AHJ certification information, as well as required documentation. (See Figure 2). Ordering Information: GW-FAD: Fire Alarm Storage Cabinet, Red FEATURES & BENEFITS • Installed with a 4 gigabyte digital flash drive interface with USB B connector • Overall Dimensions 12”Width x 13” Height x 2 ¼” Depth (30.48 W x 33.02 H x 5.71 D cm) • Offers two, key ring hooks to hold the system keys • Contains a frame plate to insert Authorized Personnel business cards •Constructed with 16 gauge steel box and cover for added security with a solid stainless steel hinge • Coated with a durable, baked-on finish (other colors available) • Built with a stainless steel piano hinge with standard ¾”cat 30 key lock (other lock assemblies available) • Includes a Legend Sheet to record passwords and system information • Imprinted with white indelible ink, 1" high lettering labeled, "FIRE ALARM DOCUMENTS” RECEIVED 09/19/2018 striplett BUILDING DIVISION F18005260_V1 2 Figure 1 shows the interior enclosure of the Fire Alarm Documents cabinet. . Figure 1 Fire Alarm Documents Cabinet Figure 2 shows the Legend Sheet attached to the inner door of the Fire Alarm Document Cabinet (See Figure 2). Figure 2 Legend Sheet Property Information Minimum Required Documentation Name of Property:_______________________________ 1 Written narrative providing intent and system description. Address:_______________________________________ N/A Enclosed or Alt. Location:_____________________________________ Description of Property: ___________________________ 2 Riser diagram Occupancy Type:________________________________ N/A Enclosed or Alt. Location:_____________________________________ Certification and Approvals 3 Floor plan layout showing location of all devices and control equipment. 16.1 System Installation Contractor:N/A Enclosed or Alt. Location:_____________________________________ This system, as specified herein, has been installed and tested according to all NFPA Standards cited therein. 4 Sequence of operation in either an input/ output matrix or narrative form. N/A Enclosed or Alt. Location:_____________________________________ Signed:________________________________________ 5 Equipment technical data sheets. Printed Name:__________________________________ N/A Enclosed or Alt. Location:_____________________________________ Date: ______/______/______ 6 Manufacturers published instructions, including operation and maintenance instruction. Organization:___________________________________ N/A Enclosed or Alt. Location:_____________________________________ Title:__________________________________________ 7 Battery calculations (where batteries are provided). Phone:________________________________________ N/A Enclosed or Alt. Location:_____________________________________ 16.5 Authority Having Jurisdiction:8 Voltage drop calculations for notification appliance circuits. I have witnessed a satisfactory acceptance test of this with N/A Enclosed or Alt. Location:_____________________________________ system and find it to be installed and operating properly in 9 Completed record of inspection and testing in accordance with 7.6.6 and 7.8.2. accordance with its approved plans and specifications, N/A Enclosed or Alt. Location:_____________________________________ its approved sequence of operations, and with all NFPA 10 Completed record of completion in accordance with 7.5.6 and 7.8.2. standards cited herein. N/A Enclosed or Alt. Location:_____________________________________ Signed:________________________________________ 11 Copy of site specific software, where applicable. Printed Name:__________________________________ N/A Enclosed or Alt. Location:_____________________________________ Date: ______/______/______ 12 Record (as-built) drawings. Organization:___________________________________ N/A Enclosed or Alt. Location:_____________________________________ Title:__________________________________________ 13 Periodic inspection, testing, and maintenance documentation in accordance with Phone:________________________________________ Section 7.6. Equipment Information:___________________________ N/A Enclosed or Alt. Location:_____________________________________ ID No. 1:_______________________________________ 14 Records, record retention, and record maintenance in accordance with 7.7. Serial: ________________________________________ N/A Enclosed or Alt. Location:_____________________________________ Access Code: __________________________________ ID No. 2:_______________________________________ Serial: ________________________________________ Access Code: __________________________________ Signed:___________________________________Date:______/______/______ USB Storage Interface requires Standard USB-B Connector Key Ring Hooks Business Card Holder Legend sheet used to store system information including the following: - Contacts - Sign-off - Maintenance - Test information - Alternate locations of additional records RECEIVED 09/19/2018 striplett BUILDING DIVISION F18005260_V1 Fire Alarm Documents (FAD) Cabinet Technical Specifications 9021-61027 | A | 05/18 ©2018 Honeywell International Inc. For a complete listing of all compliance approvals and certifications, please visit: http://www.gamewell- fci.com/en-US/ documentation/Pages/ Listings.aspx Gamewell-FCI® is a registered trademark of Honeywell International Inc. Space Age Electronics, Inc. is a ©copyright. UL® is a registered trademark of Underwriter’s Laboratories Inc. This document is not intended to be used for installation purposes. We try to keep our product information up-to- date and accurate. We cannot cover all specific applications or anticipate all requirements. All specifications are subject to change without notice. Honeywell Gamewell-FCI 12 Clintonville Road Northford, CT 06472-1610 203.484.7161 www.honeywell.com For more information Learn more about Gamewell-FCI’s Fire Alarm Documents (FAD) Cabinet and other products available by visiting www.Gamewell- FCI.com SYSTEMS FAD: Fire Alarm Documents Cabinet Dimensions: 12” W x 13” H x 2 1/4” D (30.48 W x 33.02 H x 5.71 D cm) Door Keylock: Barrel lock and piano hinge Dimensions: 3/4” barrel lock and 12” (30.48 cm) piano hinge FAD Cabinet: UL® Listed, constructed of 18 gauge cold rolled steel Cabinet Finish: Red powder coat epoxy finish Cabinet Cover Label: Silkscreen imprinted with white indelible ink, 1" high lettering labeled, "FIRE ALARM DOCUMENTS" Cabinet Keylock: Keylocked with 3/4" barrel lock and 12" (30.48 cm) width stainless steel piano hinge Cabinet Backbox: The backbox includes a 4-hole knockout mounting pattern. Cabinet Frame Plate: insert frame plate accommodates and protects standard 8 1/2 x 11 manuals and document records. Cabinet Inner Door Label: Legend Sheet attached to the inner door frame for system required documentation, key contacts and code information. Cabinet Flash Drive Interface: 4 Gigabyte (minimum) digital flash memory drive with a standard USB B connector (used to upload and download information) is securely assembled to the interior cabinet. The drive is restricted to Authorized personnel with permission to use secure hardware devices to access the records. Cabinet Key Holder: Two key ring holders and a pre- assembled frame plate to insert Authorized Personnel business cards. STANDARDS The Fire Alarm Documents (FAD) Cabinet is designed to comply with the following standard: UL Standard: S2580 AGENCY LISTINGS AND APPROVALS These listings and approvals apply to the modules specified in this document. In some cases, certain modules or applications may not be listed by certain approval agencies, or listing may be in process. Consult factory for latest listing status. UL: S2580, Vol. 3 CSFM: 7300-0553-0110 NFPA: 72 2007 NEMA ISO 9001 Certification RECEIVED 09/19/2018 striplett BUILDING DIVISION F18005260_V1