HomeMy WebLinkAboutPN_PROJECT_NARRATIVE_RENTON_DENTAL_ARTSFIRE PROTECTION, INC.
PO BOX 12642
MILL CREEK, WA 98082
(425) 290-9600 OR 1-800-681-1125 FAX (425) 353-4546 September 14, 2018
City of RENTON - PLAN REVIEW
RE; FIRE ALARM SYSTEM
Please find enclosed plans for a Fire Alarm Installation in a new
B-OCCUPANCY. The system has been designed per NFPA 72, 2016
edition requirements as well as WAC, IBC, IFC 2012, NEC current
and your additional requirements.
The building is fully-sprinkled. The system shall monitor by zone
activation as well as separate trouble signals. Monitoring shall
be provided via the FACP’s onboard DACT and retransmitting signals
to the Central Station, The Alarm Center LACEY, WA. Audibility
shall be in compliance with NFPA standards. A full service and
monitoring agreement is in force for the proper service and
maintenance per NFPA requirements. A full pre-test and NFPA form
shall be conducted and completed prior to calling the AHJ for
acceptance testing.
INSTALLATION COMPANY
Fire Protection, Inc.
1730 Gibson Rd. Everett, WA 98204
WSCL# FIREPI*021ML UL CERT #608242-002
JOB SITE ADDRESS
Renton Dental Arts
17816 180th Ave SE
Renton, WA 98055
APPROVED UL MONITORING COMPANY
Alarm Center, Inc./FPI
4300 3rd Ave. SE Lacey, WA 800-429-0991
UL CERT #902799-02
RECEIVED
09/19/2018 striplett
BUILDING DIVISION
F18005260_V1
By: cthomas
Date: 10/02/2018
FIRE DEPARTMENT
For Construction Subject to
Corrections Noted in Red
APPROVED
CONTRACTUAL RESPONSIBLE PARTIES
Installation; Monitoring; Service; Testing;
Fire Protection, Inc.
AMBIENT TEMPERATURES
No area with alarm service equipment shall
fall below 40 degrees, common areas shall
be at 68 degrees per builder
AMBIENT NOISE RANGE
All areas serviced by the Fire Alarm Control and
notification system will be as listed for
per UBC listings, per builder.
SEQUENCE OF OPERATIONS
All Alarm and Trouble conditions shall enunciate at FACP as well
as remote notify UL listed Central Station. Zones of alarm shall
cause for all notification circuits to activate, send alarm zone
to CS, re-dispatch to Fire and dispatch FPI runner service.
Trouble and supervisory signals shall transmit to CS which will
dispatch FPI runner service to site, (no notification circuits
shall activate.) On site emergency contact personnel shall be
notified. Wet Waterflow ALARMS shall be retarded by a period of
not more than 45 seconds. Low air shall activate at 25lbs,
causing for a supervisory signal. A short on FACP smoke, Waterflow
Switches, (wet and dry) and pull station shall cause alarm. Shorts
on PIV, tamper and Hi-low air zones shall cause a Supervisory
condition. Opens on any zones shall cause for a trouble signal.
Should you have any further questions, please feel free to contact
me directly.
DAVID MOW
VP of Operations/Designer
*NICET-IV #120904
**CITY OF REDMOND DoR #16-B-141
RECEIVED
09/19/2018 striplett
BUILDING DIVISION
F18005260_V1