HomeMy WebLinkAboutC_Response Letter_Logan Six_230807.pdf
PO Box 1478 ⬧ Everett, WA 98206 ⬧ Phone: (425) 303-9363
Email: info@insightengineering.net
February 9, 2023
Nathan Janders, Development Engineer
1055 S. Grady Way
Renton, WA 98057
(425) 430-6400
Re: Logan 6 - LUA22-000283
IECO No. 22-1157
Dear Nathan,
The project referenced above is revised in response to the review comments dated September 2,
2022. The review comments are numbered on the letter and have been addressed in italics as
follows:
1. The water system is insufficient as shown and does not provide sufficient information to
determine feasibility of the proposal as follows:
a. Projects that have a fire flow in excess of 2,500 GPM require a looped water main
around the buildings. Public water mains on private property require a 15-foot
public easement centered over the pipe and the building must be set back 10 feet
from the water main.
Per conversations with the city, looping the water main is not required for this
project.
b. Based on the project information submitted, Renton Regional Fire Authority has
determined that the fire flow to be 3,750 GPM.
Noted.
c. Installation of a fire sprinkler stub a with a detector double check valve assembly
(DDCVA) is required for backflow prevention to the building. The sizing of the
fire sprinkler stub and related piping shall be done by a registered fire sprinkler
designer/contractor. The DDCVA shall be installed on the private property in an
outside underground vault per City Standard Plan 360.2. The DDCVA may be
installed inside the building if it meets the conditions per City Standard Plan
360.5 for the installation of a DDCVA inside a building. The location of the
PO Box 1478 ⬧ Everett, WA 98206 ⬧ Phone: (425) 303-9363
Email: info@insightengineering.net
DDCVA inside the building must be pre-approved by the City Plan Reviewer and
Water Utility.
Comment noted. A fire sprinkler stub is currently shown with the proposed
DDCVA located within the yard.
d. Installation of off-site and on-site fire hydrants. The location and number of
hydrants will be determined by the RRFA based on the final fire flow demand and
final site plan. A hydrant is required within 50 feet of the building’s fire sprinkler
system fire department connection (FDC). A minimum of four fire hydrants are
required for the building. One within 150-feet and three within 300-feet of each of
the proposed building. There are some existing hydrants within 300-feet of the
proposed building that may count towards the requirement provided they meet
current codes. Fire hydrants must meet maximum spacing of 300 feet on center.
Existing fire hydrants are shown across the street on Logan Ave N as well as
across N 4th St. An existing hydrant that has been shown previously is onsite at
the corner of Logan and 4th. A proposed hydrant has been placed in the frontage
of 4th St to be within 50’ of the sprinkler room and FDC. An additional proposed
hydrant has been added to from N 3rd St at the southwest corner of the site.
Please refer to the revised plans for the locations. Fire hydrants will be further
detailed in the civil permit stage.
e. All residential domestic water meters shall have a double check valve assembly
(DCVA) installed behind the meter on private property if the building has 3
stories or more.
DCVA has been added to the residential water meter.
f. All commercial water meters shall have a reduced pressure backflow assembly
(RPBA) installed behind the meter on private property.
RPBA has been added to the commercial water meter.
g. At a minimum the following water main improvements must be provided and
shown. Note, additional improvements may be required based on final
configuration.
i. Show proposed and existing location of fire hydrants.
Please refer to the revised plans for existing and proposed fire hydrant
locations.
ii. A water main extension is required to loop the water system around the
building. The existing water mains in Logan Ave N and N 4th St. are
acceptable for creating a loop, however, the existing 6-inch water main in
Burnett St. N is undersized and cannot support the flow. Therefore, to
create a looped water main, the applicant shall extend a 12-inch water
PO Box 1478 ⬧ Everett, WA 98206 ⬧ Phone: (425) 303-9363
Email: info@insightengineering.net
main from Logan Ave N to the existing 12-inch water main in N 4th St. by
means of an extension east through N 3rd St turning north in Burnett St.
N.
Per conversations with the city, looping the water main is not required for
this project.
iii. It is not clear where the DDCVA will be located, interior or exterior. If the
DDCVA is to be inside, add a note on the civil plan indicating such and
update the architectural plans to conceptually indicate where the fire riser
room will be located. If the DDCVA is to be outside, show the proposed
location of the vault/FDC.
The DDCVA will be placed outside the building at the northeast corner of
the site. The fire riser room will be in the northeast corner of the building.
The FDC is shown along the exterior wall of the riser room.
iv. Backflow prevention is required on both the domestic (DCVA) and
commercial (RPBA) water meters. Backflow prevention assemblies are
required to be on private property. Indicate where the backflow devices
are proposed, interior or exterior. If the backflow device(s) are to be
inside, add a note on the civil plan indicating such and update the
architectural plans to conceptually indicate where they will be positioned.
If the backflow device(s) are to be outside, show the proposed location
ensuring that it is on private property.
Backflow protection for residential and commercial will be located inside
the building. A note has been added to the civil plans. See sheet C2.0.
2. A sewer stub for the commercial and residential portions of the building is required.
Sewer stubs shall comply with COR std. plan 406.1 and RMC 4-6-040.
a. The proposed plan depicts an 8-inch sewer main entering the building. This
portion of the sewer main shall be replaced with sewer stubs connected directly to
the main extension within N 4th St.
The main has been extended and the sewer stubs now connect directly to the
main. See revised sheet C2
3. An Oil/Water Separator (OWS) is required to connect the covered parking lot to sewer. A
pump may be needed to bring the basement garage flows to the surface level for gravity
drainage.
a. Show and/or indicate the proposed location of the OWS and pump (if needed).
Provided by others.
PO Box 1478 ⬧ Everett, WA 98206 ⬧ Phone: (425) 303-9363
Email: info@insightengineering.net
4. A transportation scoping memo was provided in lieu of a TIA. Applicant shall provide a
TIA and make the following considerations:
a. TIA should be based on the current ITE manual, 11th edition. The scoping memo
references the 10th edition.
Provided by others.
b. TIA should include the following subject intersections:
i. Logan Ave N / N 4th St.
ii. Logan Ave N / N 3rd St.
iii. Logan Ave N / N 6th St.
iv. Logan Ave N / N 8th St.
v. Burnett Ave N / N 3rd St.
vi. Burnett Ave N / N 4th St.
vii. Park Ave N / N 4th St.
viii. Park Ave N / N 3rd St.
ix. Park Ave N / N 6th St.
x. Park Ave N / N 8th St.
Provided by others.
c. TIA should include the following pipeline projects
i. Topgolf Phase II – LUA22-000291
ii. Southport West – LUA22-000284
Provided by others.
d. TIA traffic distribution should be adjusted such that the trips leaving the project
headed north are split evenly between Park Ave N and Logan Ave N.
Provided by others.
5. A street modification is required for each street that is not conforming to City Standards.
The proposal shows all streets as being sub-standard and a modification is required.
Listed below are the recommended modifications.
a. Logan Ave N is classified as a Principal Arterial street with an existing right-of-
way (ROW) width of approximately 100 feet. To meet the City’s complete street
standards for Principal Arterial streets with 5 lanes a minimum ROW width of
103 feet is required. Per RMC 4-6-060 half of street improvements as taken from
the ROW centerline shall be required and include a minimum 66 foot paved road
(33 feet each side), a 0.5 foot curb, an 8 foot planting strip, an 8 foot sidewalk, 2
foot clear space at back of walk and storm drainage improvements. Dedication of
approximately 1.5 feet will be required pending final survey.
i. The City is in support of a modified section that includes retention of the
existing improvements provided 1.5 feet of dedication is provided.
PO Box 1478 ⬧ Everett, WA 98206 ⬧ Phone: (425) 303-9363
Email: info@insightengineering.net
1. The applicant shall submit a street modification for the
recommended section and update the plans as appropriate.
Plans have been updated per recommendations listed.
b. N 3rd St classified as a Principal Arterial street with an existing right-of-way
(ROW) width of approximately 110 feet. To meet the City’s complete street
standards for Principal Arterial streets with 4 lanes a minimum ROW width of 91
feet is required. Per RMC 4-6-060 half of street improvements as taken from the
ROW centerline shall be required and include a minimum 54 foot paved road (27
feet each side), a 0.5 foot curb, an 8 foot planting strip, an 8 foot sidewalk, 2 foot
clear space at back of walk and storm drainage improvements. The parcel is not
parallel to the roadway centerline and thus a minimum dedication to install
improvements as determined by final survey will be required.
i. The City is in support of a modified section that includes retention of the
existing curb-curb width with a 0.5 foot curb, 8 foot planting strip, 8 foot
sidewalk and 2 foot clear space are required. Dedication as needed for the
listed improvements will be required.
1. The applicant shall submit a street modification for the
recommended section and update the plans as appropriate.
Plans have been updated per recommendations listed.
c. N 4th St classified as a Principal Arterial street with an existing right-of-way
(ROW) width of approximately 42 feet. To meet the City’s complete street
standards for Principal Arterial streets with 4 lanes a minimum ROW width of 91
feet is required. Per RMC 4-6-060 half of street improvements as taken from the
ROW centerline shall be required and include a minimum 54 foot paved road (27
feet each side), a 0.5 foot curb, an 8 foot planting strip, an 8 foot sidewalk, 2 foot
clear space at back of walk and storm drainage improvements. The parcel is not
parallel to the roadway centerline and thus dedication of approximately 24.5-28.5
feet will be required pending final survey.
i. The City is in support of a modified section that includes retention of the
existing curb-curb width, however a 0.5 foot curb, 8 foot planting strip, 8
foot sidewalk and 2 foot clear space are required. Dedication as needed for
the listed improvements will be required.
1. The applicant shall submit a street modification for the
recommended section and update the plans as appropriate.
Plans have been updated per recommendations listed.
PO Box 1478 ⬧ Everett, WA 98206 ⬧ Phone: (425) 303-9363
Email: info@insightengineering.net
6. In April of 2022 a new surface water design manual was adopted. The TIR included with
the submittal has been prepared for compliance with the 2017 surface water design
manual.
a. The applicant shall update the TIR such that it is compliant with the 2022 surface
water design manual.
TIR has been updated.
Please feel free to contact me with any questions or comments you may have.
Sincerely,
Brian Kalab, P.E.