Loading...
HomeMy WebLinkAboutWTR272878 (6)SUBMITTAL DATA CITY OF RENTON, WASHINGTON NORTH TALBOT PUMP STATION PROJECT DIVISION 16.10 - MOTOR CONTROL CENTER OMEGA CONTRACTORS 11930 308TH NW DUVALL, WA 98019 SO #18898 SUBMITTAL DATE: AUGUST 21, 2002 000 S & B inC. 13200 SE 30th St., Bellevue, Washington 98005 (425) 644-1700 FAX (425) 746-9312 � SIEMENS 1 ' General Design and Structure • Heavy -Duty Construction with up to 100KA. ' Bus Bracing. • NEMA Wiring. • Plug -In Units with Racking Feature through ' Size 5 Starters. • Door/Unit Mounted Pilot Device Panel. • UL Labeling as applicable. ' • 600V 50/60 Hz. • CSA Labeling as applicable when specified. General Description TIASTAR provides an efficient means of grouping electric motor controls and related devices in one compact structure.. A motor control center con- sists of one or more enclosed vertical sections mounted on the floor. It contains incoming line facilities, a common horizontal bus, wireway trough, and conduit facilities for incoming and outgoing wires. Each vertical section typically contains a vertical bus connected to the power bus, a vertical wireway, one or more combination motor control units, and various related devices, including push buttons, selector switches, and many others. Motor Control Centers also might include equipment such as transformers, lighting panels, and special assemblies. TIASTAR, in addition to providing a safe conve- nient housing for system motor controls, is easy to design and install. Modular construction and flexible features allow efficient space utilization and simplify future additions or modifications. IMPORTANT. The dimensions depicted within this document are for reference purposes only and are subject to change without notification. Contact the fac- tory for certified construction drawings. THIS EQUIPMENT CONTAINS HAZARDOUS VOLTAGES. DEATH, SERIOUS PERSONAL INJURY, OR PROPERTY DAMAGE CAN RESULT IF SAFETY INSTRUCTIONS ARE NOT FOLLOWED. ONLY QUALIFIED PERSONNEL SHOULD WORK ON OR AROUND THIS EQUIPMENT AFTER BECOMING THOROUGHLY FAMILIAR WITH ALL WARNINGS, SAFETY NOTICES, AND MAINTENANCE PROCEDURES CONTAINED HEREIN. THE SUCCESSFUL AND SAFE OPERATION OF THIS EQUIPMENT IS DEPENDENT UPON PROPER HANDLING, INSTALLATION, OPERATION AND MAINTENANCE. E I H Figure I - Structure with complete bus assembly. Figure 2 Top horizontal wireway. Figure 3 Bottom. horizontal wireway. Figure 4 Wire tie device in vertical wire - way I I I I I I I I I I I I I I I I ... ... . .... ........ . ........ .. . Figure I - Structure with complete bus assembly. Figure 2 Top horizontal wireway. Figure 3 Bottom. horizontal wireway. Figure 4 Wire tie device in vertical wire - way I I I I I I I I I I I I I I I I ... ... . .... ........ . ........ .. . ' Doors The vertical wireway doors and unit doors are pan type with concealed hinges of the removable pin type. The vertical ' wireway door hinges on the right, the unit door on the left, giv- ing maximum access to the vertical wireway. Individual doors may be removed without removing the door above or below. Doors stay in place even with the hinge pins removed and ' the door fully opened. To remove, take out pins, close door, and pull off. Doors open in excess of 110°. A minimum of two (2)'/4 turn fasteners are used on 12" unit doors and larger. ' 15" and 20" wide MCC doors are available with a plexiglass cutout option. See page B26 for dimensions. Unit Supports ' Two shelf brackets and a separator angle support individual units and provide a retention for a door gasket when so spec- ified. ' Cover Plates The bottom 6" wireway of each section is covered with a formed plate with captive -type screws. There are two 13 ' gauge top plates on 15" sections (three on 20"). The rear top plate on front mounting and the center plate on back-to-back mounting sections permit access to the horizontal bus. The front top plate on front -mounting and the two outside plates ' on back-to-back sections are removable for installation of con- duit. A screw -mounted 16 gauge plates cover the rear of front - mounted MCCs for ease of removal if rear access is desired. Reversible bottom end -cover plates cover the bottom hori- zontal wireway, ground bus opening, and the end channels. They perform this function if the section is mounted on its ' sills or if the section with sills are grouted into the floor, the plates are simply rotated 1800. Finish ' The motor control finish is an electrostatically applied TGIC polyester powder, applied both manually and automatically in an environmentally controlled clean room, cured at 400° F for ' 20 minutes. All painted parts undergo a five -stage prepara- tion process that includes an alkaline wash, water rinse, iron phosphate wash, water rinse and a non -chrome sealer. The minimum film thickness on external surfaces is 2.0 Mils and the finish passes a 600-hour salt spray test per ASTM B117- 94 definitions. Motor control center structures are painted USAS #61 gray to match Siemens distribution products. Units and the rear of ' the vertical wireway are painted white. Figure 5 - 110' opening of unit and vertical wireway door. Figure 6 - Front top cover plate with conduit hole. Figure 8 - Reversible bottom end -cover plates. f ^ s v 1 ! 3 i ^ . . . . . . . . . . . . . . . . . . . . . . . . . .. . .. . . . . .. . .. . .. . . . ... . . . . .. .. . .. ... I I I I I I I I I I I I I I I I I Figure 9 - Blank space with door gasket angle (intermediate angle). I I I I I I I I[] I I I I I I I I I I I I I I I I I I I I I I Figure 11 - Vertical Bus Barrier with Stab Holes and Stab Hole Covers. Optional vertical ground bus with unit ground terminations is also shown. I Figure 12 Figure 13 Figure 14 - Horizontal/vertical ground bus connections. Figure 15 - MLO Vertical 600A 42K Figure 16 - MLO Horizontal 600A 42K Max I ' Bus Drawings Available Locations Of Ground And Full Length Neutral ' Section Neutral Ground Typical CD ABCD ' With Vertical Ground Bus C AC Main Lug Only CD BCD ' Main Disconnect CD BCD Service Entrance C ABCD ' Note: a Location B and D is available on 21 " deep back to back structures only. s When continuous (full length) neutral bus is specified, it must be located in the bottom of the structure. Full length neutral bus requires that the ground be located in the top of the sturcture. The standard location is C. ■ Bus Mounting Dimensions ' Distance from �� —zo Front Edge to 3 0 0 Horizontal Bus ' AMP D 600 10 800 97/8 ' 1200 91/2 1600 91/8 2000 8 90 72 1 Ve tFront View ' All dimensions are shown in inches unless otherwise specified. __.M.. o 0 A j B Horiz. Bus c U- cr C D 0 0 Side View Figure 17 zt zo 6— 1 Dist. to 3'he gnd. bus D I I 1 � I 3 9 9 13'a —• 4Vz Va I 1 I 1 I I I c cl ND NIU T tV T i I R I RIT T O OI L L I I I I I I I I I i Ground or I I I I I I I I I neutral 23r§ 1 I 4 X 2r71/4 �7'/'� — I I I 2" wide 3'/." x F17'32Distance Dist.to to ground32 neutral bus bus Side View Figure 18 Typical Stab -On Connections 600 A Vert. Bus For Back -To -Back Sections Front Rear Figure 19 Bus Drawing A Qty. Phase 21/4 LID V2 Amp Size ( YP. 600 (1) 1/4 x 2 9 800 (1) 3/8 x 2 9 1200 (2) 1/4 x 2 2 (TYP.) 9: 1600 (2) 3/8 x 2 2000 (4) 3/8 x 2 (TYP-) 1.109(Typ.) 0 13/32 Dia. (Typ.) A 1_2*6� Figure 20 Mounting Of Single And Double Bus Bars Horizontal bus Zinsulator supp Bus Sect. A -A W1600A LLJ 800A . Figure 21 All dimensions are shown in inches unless otherwise specified. Sect. A -A W11200A 1600A Vertical Bus Dimensions and Availability Bus Bar Phase Available Vertical Bus Structures Amp Rating Size 15 20 2013/13 300 3/8 X 3/4 X X — 600 3/8 X 1112 X X X L1 L2 0 Front View Figure 22 Horizontal Bus Link (for joining two sections in the field). L1 L2 L3 Figure 23 Ground Lt L2 L3 LYJ Ll Typ L2 iaa•l� Figure 24 All dimensions are shown in inches unless otherwise specified. Incoming Line Termination Arrangements Main Lugs Only I.— 20 —.I Figure 25 -;C 6— 20 --4 Figure 29 n ►— 20 --+ Figure 26 Figure 30 All dimensions are shown in inches unless otherwise specified. .kktit c I.— 20 -4 6— 20 Figure 27 Figure 28 t C 111 lam— 30 Figure 31 Incoming Line Termination Arrangements Main Circuit Breakers - 80% Rated Thermal magnetic molded case type breakers are used for ' mains in the MCC. Circuit Breaker Incomingt Fig. Ref. Wire Bendingt Total Assembly Required Unit Frame/MaxTrip Location Cable Size Next Pg. Space -Dim. A Height -Dim. B Space -Dim. C ' 125A/125A Top Qty = 10 #3 - 3/0 CU/AL 32 14 24 12 125A/125A Bottom Qty = 10 ' #3 - 3/0 CU/AL 35 8 24 18 250A/250A Top Qty = 1 #6 - 350MCM CU 33 15 30 18 ' 250A/250A Bottom Qty = 1 #6 - 350MCM CU 36 15 36 30 400A/400A0 Top Qty = 2 3/0 - 500MCM CU 33 15 30 18 400A/400A0 Bottom Qty = 2 3/0 - 500MCM CU 37 15 42 36 ' 600A/600A0 Top Qty = 2 3/0 - 500MCM CU 33 15 30 18 600A/600A® Bottom Qty = 2 , 3/0 - 500MCM CU 37 15 42 36 800A/800A* Top Qty = 3 #1 - 500MCM CU/AL 34 15 48 36 800A/800A**0 Bottom Qty = 3 ' #1 - 500MCM CU/AL 38 22 54 48 1200A/1200A* Top Qty = 4 250 - 500MCM CU/AL 34 16 48 36 , 1200A/1200A**O Bottom Qty = 4 250 - 500MCM CU/AL 38 22 54 48 1600A/1600A** Top Qty = 4 , 300 - 600MCM CU/AL 39 16 90 72 1600A/1600A** Bottom Qty = 4 300 - 600MCM CU/AL 40 16 90 72 ' 2000A/2000A** Top Qty = 6 300 - 600MCM CU/AL 39 19 90 72 2000A/2000A** Bottom Qty = 6 300 - 600MCM CU/AL 40 26 90 72 ' Space in rear of structure not available. ' •• Entire rear of structure not available. t Optional lugs available. Contact factory for size and rating. Q 15-25A Lug size 12-10AL, 14-10CU, 30-100A. 10-1/0 CU-AL Q 800A-1200A not available in back to back bottom mounting. ' Q Stab opening at bottom of unit not available in rear. Incoming Line Termination Arrangements Main Circuit Breakers - 80% Rated L L 20 —J Figure 32 I.-- 20 —I Figure 37 L L Figure 33 I B C A 6—20 --d Figure 38 L— 20 J Figure 34 All dimensions are shown in inches unless otherwise specified. 1 't, A I F c B —� L L 20 -J Figure 35 Figure 36 12 12 C C B B A 6 L 6 i-- 30 30 -" Figure 39 Figure 40 I Incoming Line Termination Arrangements Main Fusible Switches Main fusible switches consist of the following: • 60 to 200A Siemens-Furnas switch and class R fuse clips. • 400 to 600A Siemens molded case switch and class R fuse holder. • 800 to1200A Siemens molded case switch and class L fuse holder. Fusible Disconnect Incomingt Fig. Ref. Wire Bendingt Total Assembly Required Unit Switch/Clips Location Cable Size. Next Pg. Space -Dim. A Height -Dim. B Space -Dim. C 60A/30A or 60A Top Qty = 1 #14 - #14 CU/AL 41 14 24 12 60A/30A or 60A Bottom Qty = 1 #14 - #14 CU/AL 46 8 24 18 10OA/100A Top Qty =1 #14 - 1/0 MCM CU 42 13 30 18 10OA/100A Bottom Qty = 1 #14 - 1/0 MCM CU 47 7 30 24 20OA/200A Top Qty = 1 #6 - 350MCM CU 43 16 42 30 20OA/200A Bottom Qty = 1 #6 - 350MCM CU 48 10 48 42 40OA/40OA0 Top Qty = 2 3/0 - 500MCM CU 44 14 48 36 40OA/40OA0 Bottom Qty = 2 3/0 - 500MCM CU 49 14 60 54 60OA/60OA0 Top Qty = 2 3/OMCM - 500MCM CU 44 14 48 36 60OA/60OA0 Bottom Qty = 2 3/OMCM - 500MCM CU 49 14 60 54 80OA/800A Top Qty = 3 250 - 500MCM CU 45 13 60 48 80OA/800A Bottom Qty = 3 250 - 500MCM CU 50 22 90 72 120OA/1200A Top Qty = 4 250 - 500MCM CU 45 13 60 48 120OA/1200A Bottom Qty = 4 250 - 500MCM CU 50 22 90 72 * Space in rear of structure not available. t Optional lugs available. Contact factory for size and rating Q Stab opening at bottom of unit not available in rear. Incoming Line Termination Arrangements Main Fusible Switches 1 I F R#7 A 77 L I L 20 I L 20 A Figure 41 Figure 42 c e L20A 20 Figure 43 L 20 -- Figure 44 Figure 45 12 cl e e c L t 6 I— 20 --d 20 Figure 49 Figure 50 1 1 Incoming Line Termination Arrangements Bus Link Bus Duct Connection Bus links are available for connection to existing System/89 Bus duct connections are supplied on request. They may MCCs. The following information is needed for each order: require a pull box or a special structure depending on the a.Style No. of existing MCC application. b. LH or RH connection to new MCC order Complete bus stub dimensions, bus run drawings, and spec- c. Ampacity of existing bus: e.g., 60OA, 8O0A, etc. ification must be supplied. d.Size of existing ground and neutral bus For Class 89 MCCs, a transition arrangement may be neces- sary. The same information must be provided. Available Space Drawings Blank section HorizenW Bus Compartment 2 LCompartment Horizontal Bus 12 l 2 T 19' e Betweeen 2 sides 18144 Clear opening t Betwe.e en angles 1844 Between Holes (Trp ) 14'i'ifi 19'i'r6 90 4'i56 9'i',6 92'ha 9"ha �— 40, 50, 60 ---el �1 Ly Imo— 20 1Ye 151n, Deep NOTE: For 30, 40, 50, 60 inch wide add 10, 20, 30, 40 inches to all width dimensions. Figure 51 20 M. Deep 21 in. Deep Bah to Back Plug-in Unit Dimensions On units over 18' a Racking lever wider side barrier is assembly used as Indicated with with 90 pivot dashed line 4%' 0 0 i 11 Vi - 12 inch unit 17144' - 18 inch unit i I 231/4' - 24 inch unit i 291AV - 30 inch unit i (Location varies i 35V4" - 36 inch unit with size of unit). Unit ground 41 V4' - 42 inch unit Ground stab clip i (Optional) ; 47V4' - 48 inch unit i 51V4* - 54 inch unit IN 0 0, 57V4' - 60 inch unit 9 The distance from the plug-in unit back plate to the inside of me the unit door is 8%1. 14V'i 9' NOTE: The GND clip on the side is left in place even when adding GND stab, to allow for positive grounding in test position. Figure 52 Fixed Mounting Panel Dimensions �B� A 20" WIDE J * 50" B 60" WIDE A Figure 53 Unit Space 20" W A B 30" W A B 40" W A B 50" W A B 60" W A B 12 9 177/8 18 15 177/8 24 21 177/8 30 27 177/8 36 33 177/8 33 271/2 42 39 177/8 48 45 177/8 54 51 177/8 60 57 177/8 69 69 177/8 70 271/2 70 371/2 70 471/2 70 571/2 Wireway Dimensions 23/4 90 6 38.25 s inche! Vert. wirewa (typ.) 4Yz i 9 40.5 sq. T In. I Front 1 Shelf bracket 4 Vert. reway door typ.) 30 sq. In. 1 Ys Front Right Side View 151n. Deep Figure 54 All dimensions are shown in inches unless otherwise specified. Lift angle . Typ. cross- sect'I O front wireway Compartment top cover (typ.) Front - A/B CID Rear wire space A-4Ys 300A B-33W 600A Horizontal / wireways 30 sq. In. 4 ❑ 71/z 1 4 Right Side View 20 In. Deep Front Only C-10 300A D-91/s 600A IControl R Control I Unit I I Unit Horizontal bus (typ.; sear rireway ame as 1pical 'ont Fro O O 0 0 0 0 0 Screw on rear cover plate 0 0 0 0 0 0 0 0 L-7112—� L--71,12- ' Base channel 3 x 1 Va (typ.) Right Side View Back 21 In. Deep 15 to 201n. Deep Back to Back Front Only Figure 55 All dimensions are shown in inches unless otherwise specified. Rear will accept 6-12' unit modules. Same as front Back 21 In Deep Back to Back Conduit Entry and Transformer Mounting Drawings Top Conduit Entry: 15, 20; and Back -to -Back Rear top plate can be used for conduit on 20" deep MCC. Cables can then be run from rear to front through optional wireway holes to connect units. Openings with Removable Cover Plates (Typ.) Openings with Removable Cover Plates (Typ.) I (5) 2" Conduits I 6�1e I 20 I 10 i Deep i 15 ------ ------ —T Deep 1 (3)1=Coontlulffi 6 i (3) 4' Conduits 1 L I (4) 3' Condults I — I I (4) 3' Condulffi I — 6 /A Unit I 17 Door 17 —�I Wireway Door Wireway Door Door Wireway Unit Door Door (3) 4' Conduits ) 6 V, I or I ( (4) 3- Conduits I Horiz. Bus Back-Tc- Inspection 21 Back LCI Cover ----- (3) 4' Conduits 6'/ I or 1 (4) 3- Conduits I Unit 17 Wireway Door Door Figure 56 Bottom Conduit Entry: 15' 20, and Back -to -Back �20Mfg. Holes 1y2 (TYP) II VeRlcal � 17 3 e e �20�( 1y2 (Typ ) Bus 3 e o o 19't 16"he 17 /is Space Open for 131%6 14� /18 Space Open for8"/14 11"he Conduit Entry Conduit Entry 3' II e Io Ie 3 I e eIe — 123 14S4 �I 5V2 M——'124'i 14y!2" 5Y2 I� Channel Sill Channel Sill I-20 116 (TYP•) I I � Back -To -Back 3 o e o Vertical Bus Vertical Bus 17 I 203/4 173'4 I 1 Typical Space Open for 14�4 I_ J Conduit Entry 6% 3 II e Ie oII �121'i 14Vz I Syz F— Remove bottom unit to pull wire. Channel Sill Conduit should not extend more than All dimensions are for reference and are subject to change 21/2 inches above the floor surface. Not for use for construction. Figure 57 All dimensions are shown in inches unless otherwise specified. Wireway Auto Transformer Mounting And Bottom Conduit Entry Restrictions Size 2 - 4 Reduced Voltage Auto Transformers 21 11 A Auto/)CFMR A 1 SECTION A -A SECTION A -A FRONT VIEV Figure 58 Size 5 and 6 Reduced Voltage Auto Transformers 21 F 3O"W SECTION C-C SECTION C-C C i C 6 Figure 59 All dimensions are shown in inches unless otherwise specified. FRONT VIEW FRONT VIEW Lighting Transformer Mounting And Conduit Entry Restrictions 1 - 5 KVA Single Phase all 4" r 20"D XFMR Is"O XFMR B L h--2D"W -- ] F--20"W — SECTION A -A SECTION A -A Figure 60 71/2 - 15 KVA Single Phase 2 e SECTION A -A SECTION A -A Conduit entry is not recommended below 20-45 KVA single phase and all 3 phase lighting transformers. Figure 61 All dimensions are shown in inches unless otherwise specified. FRONT VIEW FRONT VIEW 5" NEMA 3R Structure Dimensions Width of opening P -7 D 2Ir 1 1 1 I 100 �A Width of sections4 (see chart) Add both dimensions to width for complete section Add for Add for left and section right end section Front View 38% 40 9 space Tor conduit entry Overall length (see chart) Top View —41 4% B �( l� I I i ( I 95 % I I I 1 I 97 C_+ 37 — 451hIn Side View Iltis Mtg. holes 61t 15" Deep = MCC 9" 20" Deep =MCC 14' A D Remarks Note: 40 36 (2) 20" Sections 1. All dimensions given in inches. 50 46 (1) 20" & (1) 30" Section 2. Shaded areas indicate conduit entries. 60 56 (3) 20" or (2) 30" Sections 3. Bottom mounted transformers will reduce conduit entry 80 (2) 36 (4) 20" Sections space. Ref D63535 4. Vertical bus is 105/8" from bottom of base. 5. Bottom ground bus is 7/8" from bottom of base. 6. Drawings not for construction. For construction, obtain certified drawings from the factory. 7. Not available for back-to-back structures. All dimensions are shown in inches unless otherwise specified. Figure 62 Duplex Structure Floor Plan And Clearance Dimensions Dimensions Left -Handed "Structure" Width Right -Handed "Structure" Width Vertical Su ort (Mounting Angle) g Location Panel Orientation A gl o �p rn B 4) m tg ti )"am` rnN �cp ,o 0 a C u M 6 ' "a `o y�jO �cC � o a~ D c 9 •- d = c A O(o �(D � °o v C E c C'- 4) = a "O,o sad it °o v C F c d 0 0: a Co` 0 O�� �oE ' QA� H G C 4. � X m G H C oa •otn V J C oCL 'aca U - - Standard Standard 15 6.35 8.34 - - - - - - - - Standard Standard 20 6.35 8.34 - - - - - - - - Standard Inverted 15 8.85 10.93 - - - - - - - - Standard Inverted 20 8.25 10.93 - - - - - - - - Recessed Standard 15 9.25 11.20 - - - - - - - - Recessed Standard 20 14.25 16.20 - - - - - - - - Recessed Inverted 15 11.77 13.70 - - - - - - - - Recessed Inverted 20 16.75 18.70 - - - - - - 20 20 - - - - - 18 18 38.88 40 17 17 20 30 - - - - - 18 28 48.88 50 17 27 20 30 - - - - - 28 28 58.88 60 17 27 PANEL -(STANDARD M"TING PANEL -(INVERTED) - 7_r(REAR COVERS) E - LOPEN CLEARANCE t (BRACE INSTALLED) F OPEN CLEARANCE (BRACE INSTALLED) {LOLCATION} VERTICAL R SIJPP13RT{LDCATION} (MTG. ANGLES) Figure 63 MCC Door - Plexiglass MID -SECTION VIEW TDOWWARV TNROWN COMPARTMENT AREA/ Iz�Imo-- G G-3 12 SPACE N A FOR //// -g /// -TT 2+ 24�Iz:Z+ LEFT RIGHT STRUCTURE-�� STRUCTURE FLOOR PLAN Mounting Ho 1-( B 1 Cutouts Dimensions Cutout Size Cutout Size �-- D -� Height of Door 05"W Doors) (D) (20" W Doors) (D) . B C B C 12" 5" H x 11.5" W 5" H x 13.29" W 18" 11"H x 11.5 "W 11"H x 13.29 "W 24" 17" H x 11.5" W 17" H x 13.29" W 30" 23" H x 11.5" W 23" H x 13.29" W A B 36" 29" H x 11.5" W 29" H x 13.29" W 42" 35" H x 10.5" W 35" H x 13.29" W 48" 41" H x 10.51,W 41" H x 13.29 "W 54" 47" H x 10.5" W 47" H x 13.29" W 60" 53" H x 10.5" W 53" H x 13.29" W 66" 59" H x 10.5" W 59" H x 13.29" W c 72" - 65" H x 13.29" W Figure 64 All dimensions are shown in inches unless otherwise specified. 11 FIGURE #1 - Bottom Ground Bus Restrictions I iFRONT I Ground 14,.69' Bus 373MM A if FRONT 0,25' 6.35mm 9.5' BOTTOM VIEW 241mm BUS SIZE A SIDE VIEW 300A 3.75' 95mm 600A 3.25' 83mm FIGURE #2 - Bottom Neutral Bus Restrictions FRONT Neutral Neutral Bus — — — — — — Bus Pandult — — — — — — r- — 14.69' Pandult 373mm I L — J FRONT 6.0' 2.5' 8.25' 5.25' 152MM 64mm 210MM 133MM BOTTOM VIEW SIDE VIEW NOTE, DIMENSI❑NS ARE N❑MINAL AND SUBJECT TO CHANGE WITH❑UT N❑TICE A) RELEASED FOR PRODUCTION NEXT ASS'Y TOOL NO. ITYPE OF TOOL WNW n,l,p"left poa•b aon� dawn.■EMWaN Ym. 19srobbaiwda i1 ffw m� ' llor mnifranw— -pomp- d Ej� %� DRAWN BYi RWB SCALE, N/A TITLE, 15' DEEP GROUND AND NEUTRAL BUS C❑NDUIT RESTRICTI❑NS DATE- 12/12/00 CHKD BY1 TOLERANCE UNLESS OTHERYISE SHOWN XX OR XXX t.015 ANGULAR t 2' DWG. N0. D 7 9 6 4 0 REV. APPRD BYt 80amm®ma Enemy AAubmmadong Ulm& F/M Xi\STD\D79\640001-A,DWG . West Chleap, IL 80185-1655 STYLEt * w BE W SHEET 9 1 CODED TO PLANT L❑CATI❑N(S) EPD X 110WA ICLIMCO FEMSA CAD CAM DRAWING - D❑ NOT MANUALLY CHANGE 7 SINGLE DUAL L1 L2 L3 L1 L2 L3 SEE NOTES SEE NOTES 1L1 I 1L1 1L2 1L2 1L3 1L3 1 2 2L1 CKT, BKR, CKT, BKR, CKT, BKR, 2L OR OR OR 2L FU, DISC, FU, DISC, FU, DISC, 1L1 1L2 1L3 1L1 1L2 1L3 2L1 2L2 2L3 NOTES: - -- A, TERMINALS AND WIRE PR❑VIDED ON 12" 30A, & 60A, CLASS "R" FUSIBLE DISC❑NNECT UNITS, 480V, & LARGER B. TERMINALS AND WIRE PR❑VIDED ON ALL 6" UNITS. C. TERMINALS AND WIRE PR❑VIDED ON ALL 12" UNITS WITH HHED BREAKERS (SEE NOTE "E"), D. TERMINALS AND WIRE PR❑VIDED ON ALL 12" BREAKERS WITH C-H CURRENT LIMITERS, E. ALL 70 AMP TERMINAL REQUIREMENTS IN 12" DUAL UNITS MUST USE LOAD BLOCK M❑UNTING BRACKET D67700083, F. WHEN USED WITH MOD DIAGRAMS HAVING CONTROL TERMINALS, MOUNT CONTROL TERMINALS ABOVE LOAD TERMINALS FOR 12" FEEDER OR ON BOTTOM PLATE FOR 12" DUALS. K) ADDED NOTE F CN D) ADD 59 9 ' IN THE NOTE A. G) CND3NOTE 7993 'C' AND NOTE 'D' ��®�®� ISM® CN37597 9-1-99 N.A. LS CA3 n �ISpO�� ��� DRAWN BY, QlStlltil�J0UII(m41II0S1uI �✓ K SCALE, N/A TITLE, 4-9- WK 4-9-01 B) ADD CLASS R & 12' TO NOTE A. DMD 7/5/00 E) ADD NGTE 'B', CLARIFY NOTE 'A' H) REMOVED NOTE 'C' West C 1 � IL 60185-ION CHKD BYE � WK DATE, 1-20-92 TOLERANCE UNLESS OTHERYISE SHOWN FEEDER WIRING DIAGRAM ADDED FDR TO DWG. NO. CN36513 SHERROD 11/25/96 CN 37631 CN 38088 DMD 11/09/99 TLC 09-14-00 NEXT ASS Y APPRD BYi W K DWG. NO, OR R XXX *.2015 REV. D 6 8 5 0 0 F D R K C) UPDATED TITLE BLOCK CN 36626 MJT 5-15-97 F) ADD, '480V. & LARGER' TO NOTE 'A' J) ADDED NOTES 'C' & 'E' CN 37689 CN 38191 aXX )K)K)K Tt& P*lt TOOL NO. TYPE OF TOOL prapergrdslemer■6�ery�►aAubnMtllon,tno, ItknOtlo F/N' tM 1Md a 1wp1OdU08d ti e1q/ 111�1111 . nw e1�f1i11td b ow GQIQ p�tlM for X \STD\D68\500FDR-K.DWG DMD 02/25/00 TLC 11-30-00 *w CAD CAM DRAWING - D ❑ N ❑ T MANUALLY CHANGE wm* =w rmomwm"prbrgvmv orsmm n BMW a/►uMuft ha STYLES CODED TO PLANT LOCAT I ON(S) i JEPD X JIOWA 89B/95+ ISHEET a 1 IFEMSA r L1 L2 L3 r----------------------� 1 01FC r----------------------- I 101FH --- --- I I i i STAB 100A ON MCB , 20A 20A ' WITH GFI �--- 1 2 0WITH GFI I I I 20A 2�q , WITH GFI 0 3 4 0- 1 i 40A ' I 20A 20A I CIRCUIT BREAKER -0 5 6 0 2�A 20A 1 -0 7 8 a 1 I I 20A 20A ' 0 1 0-L----- I I - - - - - ---------- 20A 30A I I 11 I -^ 12 010- T I , ' 20A -0 13 14 o- I I 20A 20A i -------------- 1s 16 0- 101 FJ I I o 17 18 o- i I I 1 I 1 H1 LHy3\H2 H4I I I 1 I I I I I 1 X1 X3 X2 X4 I I 1 I 10KVA I I 1 P4 I 1 OV PRI.. I I I I 120�240V SEC. I I1 I I L - - - -- - -- - ----- - - - --J I I X1 X4 I I NEUTRA I I I BUS 1 1 I 1 I I I L----------------------- I I I i A) RELEASE 8/6/01 BY CB NEXT ASS'Y )K)K TOOL NO, TYPE OF TOOL )K)K )K)K)K *)K 3K)K* )K)K )K)K)K THIS PRINT IS THE CONFIDENTIAL DRAWN BY, SCALE, N/A TITLE, 1 P H 3 W 1 2 0/ 2 4 0 V P N L B D PROPERTY OF SIEMENS-FURNAS T TO BE USE C O N N I E W/ 1 0 0 A M C B A N D DATE, 0 8/ 0 6/ 0 2 OR REPRODUCED IN ANY MANNER, NOR 1 0 K V A X F M R CHKD BY, SUBMITTED TO ANY OTHER PARTIES OTHERWISE SHOWN DWG, NO. REV. FOR EXAMINATION WITHOUT PRIOR APPRD BY, APPROVAL OF SIEMENS-FURNAS XX OR XXX t.015 U O Y 2 S W 5 A CONTROLS. ANGULAR t 2' Siemens—Furnas Controls F/Ni XI\DWG\DU0\Y2SW051A Siemens Energy & Automation, Inc. West Chicago, Illinois STYLE, 89B SHEET # 1 CODED TO PLANT LOCATION(S) EPD X ICLIMCI] IFEMSA LL CAD CAM DRAWING - DO NOT MANUALLY CHANGE J CONNECTION DIAGRAM ELEMENTARY DIAGRAM L1 L2 L3 YYY1ST'B J J J J (L1) (L2) (0) 1CB T1 T��2JJ T3 J J J JJ JJ N� n Q m U J J = `xL 1 A _ as N N� M 1CPT x X2 BY CB OB/06/02 1 # 1 TUN 03FA7 2 2 TO TB# 01H1 UN.003FA 3 3 TUN 01FA7 4 L:�I_ To TB� 01H1 UN. 4FA Ll U N It N x l00 101 102 103 CB ;TAB L1 1L1 104 L1 (L1)1 (T1) 105 L2 -; L2 (L2) (T2) 1 L2 106 L3 L3 0T3 1L3 107 108 109 110 111 112 113 114 115 116 1a 117 XF 118 119 120 121 122 N1J 123 1 "13 VMCR 22 3 3VMCR 44 124 1914 23 1924 125 126 127 128 129 130 131 132 133 134 135 Siemens & Furnas Control Products DATE, FEEDER Siemens Energy & Automation, Inc. RAN BYi WITH West Chicago, Illinois C30CANEGRA PHASE MONITOR ft_ 1 DWG. NO THIS PRINT IS THE CONFIDENTIAL PROPERTY OF SIEMENS 5 FURNAS CONTROL PRODUCTS. IT IS NOT TO BE USED U O Y 2 S W 6 OR REPRODUCED IN ANY MANNER, NOR SUBMITTED TO ANY APPRD BY, . OTHER PARTIES FOR EXAMINATION WITHOUT PRIOR APPROVAL OF SIEMENS 3 FURNAS CONTROL PRODUCTS, STYLE, R 1 OF 1 ELEMENTARY DIAGRAM W N 100 101 CAP 1 FUC 1 PFCC .-. 102 L1 T1 LZ T2 I �L12FUC I 7� .. 3FUC o 103 I T3 L314 70 ci N 104 4 L — _ SEE K2 SHEETJ ¢ N as o 04 CB AB L1 1 qL ISO 2L1 1 M 1 MTR � 106 L1 � Ti)1 (T1)1L1 L1 T1 L1 o q (Ti)(T1 M 3 z¢ u 107 L2 L2 (L2) (T2) 1 L2 B 2L2 �►k� L2 T2 L2 ' ifJ T2 108 L3 > L3 0T3 1L3 C 20 _ L3 T3 L3 T3 (T3) 109 29 153 110 BYPASS 3L1 o L1(Ti)3L2 111 (L2) T L2 T2 112 EASVOSLPECIEFIED 3L3 L3 T3 113 LATE p 38 w SEE NM-2O C Z 114 E-STOP VMCR O1 H 1 1 CPT 01N1 c oa w 115 0100 4747 01H1 01N1 �o $�. w 116 X2 1 PB 40 41 41 CR1 PUMP CALL .� Al A2 FROM TELEMTRY X: W 117 0100 CR1 PU PRE UIRED � U O 5 .. � H ,. �wao� Z 118 1 13 14 A H2 a o W«.q o 119 1 (2) 1LT (X2) o of v ��~�aa a aQcA'oo <LL.1 120 HAND OFF AU AUTO 2 CR2 1 M o �&, C3 L 121 4 Al A2 PUMP CALL O U) a a Q I I 2 j24) 13 CR1 10L (96) o N a�j rn p a$ I z w<z 0- W f- z ze d 122 43 44 95 T.� ) L rnL �Dii� o t- 123 `I'' (33 4) 132 132 Z v PUMP R TOY W v 3c3>.xc"s U a Z W c4 w a a pps� 9l.� w SJZOS W. J 124 �� SS 24N 24N m a� �� '� c 3 o..�w a C4 U ooweA0 3� c11 Q 125 CR2 4 (3UO4) 6 TR1 OFF 13 2SS Al + A2- c m ISOLATION m •- SET FOR 5 SEC v7 a a zz z 126 2014 H 0 � 127 BYPASS TR1 5 N �.e°�o a 128 A13 15C 18N0 38A14 129 (16NC) ISO 130 TR1 7 25C 28N0 Al A2 ISOLATION CONTACTOR 131 (26NC) Q 132 133 CR2 BYPASS SOFT START RTM 11 8 11 12 9 23 1 2 ELASPED TIME (HOURS) Z 134 2'0<c4 i CR3 8013 R314 24N 8� 24N 135 Al CAPACITOR CALL Q 136 ALARM RESET (X 1) (23�(24) TR2 OFF 18 10 DELAY Q 137 1 2PB 2 153 2SS NOTE:1 1 A1+ A2- 138 CR3 UP TO IIVOLTAGE BYPASS 139 0 33 34 ( 53(48) Al A2 BYPASS CONTACTOR 3 1M 140 FAULT 11 U P RUN f� (37� 53(38) G 141 H2 (2) 2LT 142 10L 12 CR4 01 N 1 01 N 1 2323 CR4 24N 24N 143 97 98 Al A2 PUMP FAIL 43 44 0 4 144 CR4 P P FALL, ALARM 145(13111 14 H2 4 (2) 3RT 146 CAPACITOR 147 OFFS TO CR3 CAP 148 � 13 14 3 l41 23 24 V W POWER CORRECTION 3SS 34 l cAPACIroR Ca 149 im FAULT 150 BYPASS 11 15 1 CNT (35 53(36) 151 B 14 B 13 3 4 START COUNTS 3 152 153 1M 154 TR3 16 15C 18NO (A1 A2) RVSS 1 7 155 (16NC) 156 157 TR2 17 TR3 15C 18N0 Al A2- 158 3 NOTE:1 KEY OPERATED SWITCH (16NC) (A3+) NOTE 2 PUMPS 4 WIRES TO 04FA OF MCC-B 159 160 161 162 163 �s a 1 (14) 010 0100 (13) (22) (21) (32) (31) 2 (44) (43) 3 01N1 (A2 (A1) 41 CR1 4 (14) 0100 (13) 8 (24) (23) 0100 1Nl6 INTO (34) (33) (44) (43) 01 N 1 (A2 (A7) 2 CR2 Ll 24N (14) (13) 80 IW O 14 13 LNLO (24) (23) 18 (34) (33) 0100 (44) (43) 01 N 1 (A2 (A1) 9 9 L CR3 lNlO 11 (14) (13) 12 (22) (21) (32) (31) 24N (44) (43) 23 01N1 (�i (A1) 12 12 CR4 .. .. v O 00 N O 00 C < 00 j r, _ = C tDCG• O 00 y Z 0 00 = 00 ^ w wp9z': WO 00 41 Oo OD OD t� Oo0(2)w o 1w1w -- N �� W-o w m p mX = D N N X = C NN ��+} D N �F+! Nn {K� _q N� 3 N Z W -i NI D n N f� fn N ^� N 15 0 (3) -i N N o �+q c a p Y A 00, � � m `�I _O O�v pv N L.�v -C N O_O_ O_O OO c0 00 O_O_ O_O 0 00 zz 00 zz 00 ZZ 01N1 0(4) 00 o w w N o 00 00 00 ZZ V w O > N OD ON9 L �p Sa �0 M wT. 0m wm z 15. -0En m< + LV ON9Z 9 A ONBI ON9Z m O -ZV OS L 9 9 OSZ ON9 L vo Ln v, n Nm v 3 em wm I ;0z ms CnN + LVd ON9Z 0 0 ON9 L ON9Z 0 m -ZV OS L B m OSZ F� OOLO OOLO ON9 L IV 3N9Z 0 ,p 0 +£V ON9l Ln No ; �K °1M (ACAM m< �� ON9Z m -ZV OSl 0 9 OSZ LL 00l0 Ll£ 11~� 6 (LVd) 6 Zl£ (Z) 0 Zll lNlO (ZV) L SSVd,,a -------------------- Sl £La L* 191,Al fo Oto Ize ZZ8 2 UP (�) 1 1 L1 J L1 v Co v 1UP (L1) 1L1 1 L1 ^ n 3FUS ® 1 L2 L2 N m L2 L2�F�D _ S 14 X2) (1) w 5-L3 L3-CFw .. L1 1 L1 II o 0 110 L3 z 1 L2 1:401N1 .. w 01N1 O`er 1 L3 c c i C z C z z VA c z 0 0 0 Z Z O_ 0 N 0 0 Z z D p D D D '� y Z 0 D '� D Z 0 C C C m m n C) f) Z O m Z 0 Z 0 Z 0 0 0� 0 O O O� p roco oD OOLO Z L 0"--i F -"'O 00 L 0 CD v IN10 01,1*- �, LN10 v ^ A D m 0 r 120 00 -00-- rn ��aoou 00 zz zz ha ha _ o o 00000 O 4L 4L w Co -1� j O O 4L N 00 zz ZZ = V Z Z N O O O Z GW 00 -- N Z N Z - N CD O V N Z N w 0 O z O z O 2 Siemens & Furnas Control Products 08/09/02 30 HP RVSS Siemens Energy & Automation, Inc. DRAWN BY, WITH BYPASS West Chicago, Illinois C,BOCANEGRA AND ISOLATION THIS PRINT IS THE CONFIDENTIAL PROPERTY OF SIEMENS Yi DWG NIL Ey, & FURNAS CONTROL PRODUCTS, IT IS NOT TO BE USED U O Y 2 S W Z OR REPRODUCED IN ANY MANNER, NOR SUBMITTED TO ANY APPRD BY. OTHER PARTIES FOR EXAMINATION WITHOUT PRIOR APPROVAL OF SIEMENS & FURNAS CONTROL PRODUCTS, STYLE, PHEET 0 2 OF 2 ELEMENTARY DIAGRAM CU 100 101 CAP _ L1 Tt _ i 1 FUC 1 PFCC i w x I TL1 E2FUC La 102 L2 T2 I TL2 . .L N 103 L3 T3 3�'-' TL3 C z CIO 104 55 L _ _ SEE K2 SHEETJ ¢ 105 C ono N N o 106 1 CB 1L1 (L1) (T1) (x l) 3210E 33 (X2) L1 T1 ISO 1 M 1MTR �'-' p 107 TO HBO' (L2) (T2) 1 L2 34 35 1 CT (X1) L2 T2 (X2) L1 (Ti)T1 ( Lr� 3 z c � (X1) (X2) "T2 T2 _ M (T2)3CT 108 L3(T3).1L3 L3 T3 2CT 109 L3 2911 T3 159 (T3) 110 BYPASS 3L1 a 111 L1 FFTl)3L2 o L2 T2 112 DNAMEPLATE L3 3L3 T3 x 113 45 wSEE 114 NOTE 2 1 CPT o U—) z - 115 01 H 1 E-STOP47 47 VMCR O1H1 F- O1N1 01N1 W� ~ CO � " IL w 1 2 1 1P8 X2 - 0. v 116 40 41 41 CR1 PUMP CALL U) b a 117 0100 Al A2 FROM TELEMTRY j uj ti _ 0100 CR1 PU PRE UIRED o 5 Q�WOQ 118 1 0- z 119 (1311,16(14)A H2 (2) c o CF�G ��~F0. o f- HAND OFF AUTO CR2 (1M) �'o �$F�o a� 120 2 c O.G a2 `'� is 1p 1 j( 4 Al A2 PUMP CALL U Q ;e— x u z Z Q 121 (96) y rn N Z W1—z J S 122 (23104) 3 CR1 10L v v ary-�zz= �U (334) 43 44 95) C >,•v �ii�` O ~ 123 132 132 c.U�iww 124 1 SS PUMP READY 24N SIGNAL TO L'- L�.I �' a a of w o x LLLJ = J 24N 1ELEMTRY �i c 3 OU 125 CR2 (31) (4) TR 1 OFF N E y F A Vl ti L) A 0 o Q 126 4 13 14 DELAY 2SS Al + A2- ISOLATION SET FOR 5 SEC C a) N H o < C i Ix W o Z 20 m sa Q 127 BYPASS 5 TR1 N -i°9oa 128 A13 4 A14 15CWl 18N0 129 6NC) 7 ISO TR 1 130 131 132 133 134 135 25C 28N0 ^ CR2 (86NC) 23 20 24 CR2 9 33 34 20 Al A2 _ TR2 DELAY Al A2- (A3+) TR3 OFF Al + A2- ISOLATION CCTR PUMP CONTROL VALVE SET FOR 15 SEC CONTROL VALVE LOGIC SET FOR 5 SEC O Q l� F 4 3 0100 0102 0102 TR3 CR3 136 15C 18N0 01030103 � Al A2 PUMP CONTROL VALVE CR3 Q 137 (16NC) PUMP CONTROL L 136 4 24N 24N 43 44 138 CR3 3 10 G 139 13 3 11 14 H2 (2) U 140 TR3 11 BYPASS SOFT START 12 RTM 141 25C 28N0 11 12 1 2 SPED TIME (HOURS) Q 142 3 (26NC) i CR4 7171 _ CR4244N" 2 4 N U Al A2 CAPACITOR CALL 33 34 143 ALARM RESET220 (Xl) (23l j,24) TR4 42 13 DELAY 144 1 2P6 2 115 2SS NOTE:1 A1+ A2- 145 CR4 UP TO VOLTAGE BYPASS 13 14 BYPASS CONTACTOR 146 42 (47� 59(48) Al A2 147 FAULT 14 U P RUN 148 (37)159(38) H2 149 (2) 150 1 OL 97 98 14A Al CR5 01 N 1 A2 PUMP FAIL 22 22 CR5 24INI 43 44 06 50 151 CR5 P t�P AIL ALARM 152 13 5014 R H2 (2) 153 TR2 0104 0104 0105 O1N1 154 15C 18N0 PUMP CONTROL CAPACITOR 1 1 VALVE SOLENOID 155 OFFS TO i CR4 CAP 19(16NC) 15 156 3 4 23 24 V W POWER CORRECTION CAPACITOR CALL 3SS 42 157 BYPASS 11 16 1CNT 158 B14 B13 3 4 START COUNTS 4 FAULT 159 TR5 1 M 0-41-0 (35 160 115C 18N0 17 (Al A2) 159(36) RVSS 1 2 161 (16NC) TR4 1 g TR5 ON DELAY 162 15C 18N0 Aly A2- NOTE:1 KEY OPERATED SWITCH 163 4 NOTE' PUMP 3S WIRES TO 04FFAA OF MCCBCC-A 16NC ( ) 3+ ) �a a 100 1 (14) (13) 01 0 (22) (21) (32) (31) 2 (44) (43) 3 01N1 A2 (A1) 41 CR1 i4 (14) (13) 0100 $100 (24) (23) 0100 i 9 (34) (33) 00 0100 (44) (43) i01N1 A2 (A1) 2 i CR2 i(22) 10 (14) (13) 0100 (21) i (32) (31) 24N (44) (43) 136 i 01N1 01 N 1 (A2 (A1) 0103 CR3 20 (14) (13) 0100 ' 15 (24) (23) 19 24N (34) (33) 71 i(44) (43) 01N1 12 01N1 b2�(Al) 12 CR4 Ir M0 LNLO *OLO LNLO LNLO 6 MID MO 8L LNLO MO LL MO ON9L �p +Lt/ ON9Z 0 m Om 1 wm � m� C * Ln t9 ONBI ONSZ m 0 -zv OSL B 0 OSZ ON91 Ly AS OW 6) vo +£V ON8l No --I N j� �' �N a)- ONSZ (9 B -Zd OSl Gj (S) m 09Z ON9 I �p N wm 1 ;0Z m� -0N +IV OW B OWL ONBZ Dom B t9 —zv OSl 0 0 39Z ON9 I �p j�jo N om wm I ;GZ co it N + 1v 6N9Z 0 m ON8L ONBZ 0 m —ZV OS l m � OSZ ON9 I Ly 0N9Z a �p ONBL No �K �'� L' (,jz ao CnN ONSZ 0 m -zv O9l 6) OSZ 0(1) 0 (2) c� 16 0 (3) -z+ 01N1 0(4) 01N1 9 O 22 m NN 00 < N O 00 00 ^ 0 oOj n I �� N Z O 00 = 00 1D- 0 W R1 W^�'II 0� 0 j�+'� 1 N-' N I+W }I"N�- 0 D IF C N^ I D n N — 0 W N6 W 6 W (, 0 NJ O� . QI 1 m N p p N^ mN N m 00 00 00 0 ZZ V co O W N D W (AN 0 p v 00 ZZ M ha 0010 (t,Ld) 1 (£Ld) 0010 ONO S v �� OOLO VicL1~� Lit�llLit Z1 (lV) 8 Zl£—�' (Z1) (Z�)„ Zl L L N l0 (Ztf) MO (£1) � ()- OOlO £1£ r-- £lL 00 L O ssvdlla -------------------- 91 £l8 �Lg 00 to OOLO 6 lZ8 ZZ8 6 ^ r C (Awu— Wm 0 xZ-Zi � x 00 0 00 0 00 00 K0 000 0 0 Z Z O O N 00 ?? O O Z Z 00 F--0 14 N ca w v -0 2FUP 14 (14) (13) 14A 0 v 11 1FUP (22) (21) S 15 X2) 3FUS (32) (31) �---{ 1L1 24N (44) (43) 22 1 L2 z 0 1 N 1 w 01 N 1 01N1 (� (A1) 14A L 1 L3 CR5 1 s, Lv) LY� 0010 Liz 1�-- 1-It 0010 L (LV) Z-1Z (Z-0(Z-1) „ ��� Zzl l £ L M 0 (Zy) MO l0 (£1) (_)0 £lZ 0- �— 211 OSI--------- ONO ------- F lZa ZZ8 "rf-� vtl C+ 0010 8L OD 14 LN10 tN10 to co a) v ( L1)££ 0—,Dc ^Q ( -1)Z£ (W92 (£1)L£ 0—JDCr-0 (£1)9£ w �W � p v r W E 0 C � Z N C Z Z 4 C Z ?5 0 0 0 0 (� . 0 qh N 0 0 C ZZ C D < D 1 D ? D ? n p �DDmNp -4 m Z zm o o Si 0-4 0 gD 0 00o X P � N N 0 moo 00 VO00 O 00 00 zz ZZ 00 N X_ v ^ � 1L1 o 1L1 1L2 �. 1 L2 N �, � 1L2 alv N 1L1 1L3 w ^�,, 0 X w 1L3 �- N N X LIU (A w x x ha w X a)N X_ ^ v W tJ ^ v � v w X N ^ N G V X N oo o o 0 oo 00 oo oo O W W j � j O � � � � N O p 0 N V O Z Z Z Z N ?Z W N3 00 00 ZZ ZZ 2 N j V O N Z N Z N Z N Z N N O O � O O O O W O O N O O 00 O O O Z O Z O 2 Siemens & Furnas Control Products Siemens Energy & Automation, Inc. West Chicago, Illinois THIS PRINT IS THE CONFIDENTIAL PROPERTY OF SIEMENS L FURNAS CONTROL PRODUCTS, IT IS NOT TO BE USED OR REPRODUCED IN ANY MANNER, NOR SUBMITTED TO ANY OTHER PARTIES FOR EXAMINATION WITHOUT PRIOR APPROVAL OF SIEMENS R FURNAS CONTROL PRODUCTS. WITH BYPASS C,BOCANEGRA AND ISLOATION Aff-' DWG NO, PPFD ar, UOY2SW1 2 OF SIEMENS General Service 3Ph 3W Voltage 480 Frequency 60 Hz Avail Fault Curr 42K AIC sym Service Entrance Not applicable Labels UL All units/sects CSA Waived General Notes None Structure Nana Type 1A Height 91.125" / 2315rrm Depth 15" / 381mn Plan View DUOY2SP003 Paint USAS 61 light gray General Options Seismic Zone 4 UBC Special Diagrams None TIASTAR Motor Control Center Specifications Bus Units Bracing 42K AIC sym Min Withstand Ratings CB Ccmbination Sane as available Horizontal Bus CB Feeder Same as available Mfg Series 3 Rating 1200A (2 - 1/4 x 2) Caroonents (except as noted) Material Copper Starter Type ITAKR7A Plating Tin Pilot Devices 30mn Barriers Standard Lexan Light Type Transformer Bulb Type LED Vertical Bus Rating See section schedule Wiring Class I Material Copper Type Bd (ctrl term blks) Plating Tin Ctrl Term Blocks Screw, stationary Stab Plating Tin Extra Unused Pts 6 Power Term Blocks Not applicable Horiz Ground sus Control Wire 16 ga Miw Rating 300A (1/4 x 1) Control Terminals Ring tng, both ends Material Copper Wire Markers Control only Plating Unplated Type Heat shrink Location Front bottom Lugs (1) 6-300 MCM Cenral Options None Incoming Main Entry Type Cable entry unit Location Top Section 01F Unit A Incoming cables (3) 600 1,M / PHASE Naneplates Master 2 x 6 Color (face/text) White / black Text Size 1/2 Text Line 1 MO -A Unit Standard Color (face/text) White / black Text Size 3/16 Text See unit schedule Attachment Stainless screws See General Information and Options and Notes page(s) for explanation of asterisks, option codes, legends, and detailed notes. Revision History CoRrercial Information I Siemens Energy & Automation, Inc. West Chicago, IL O1 08/07/02 Release Oust: S & B INC Sierens Order: UOY2S Item: 003 User: Drawn By: CB Date: 08/07/02 Proj: NORTH TALBOT PUI2 STATION Approved By: CB Date: 08/07/02 PO: B4591 IBC: = 70: CUOY25A003 PAGE: 1 of 1 Front of Mx (in/mn) 12/305 90/ 2286 — 72/ — 1829 01F A MCD 02F 03F 04F A FCB A RVSS A RVSS DL R DFC3 FCB F SPAC G SPAC H SPACE I SFCL K SPAC K SPCL 6/153 1.I— 20/508 20/508 —� 20/508 — 30/762 20/508 1 UWA ® Sections II O1 1 02 1 03 1 04 1 1 1 1 ■ Depth (in/mn) Width (in/nn) Vertical Bus Type Barriers General Notes 15/381 15/361 15/381 20/508 20/508 30/762 600A front 600A front None Insul/Isol Insul/Isol None 15/381 20/508 600A front Insul/Isol See General Infom ation and Options and Notes page(s) for e)mlanation of asterisks, ootion codes, legends, and detailed notes. SITS Cust: S & B INC Siemens Order: UOY2S Item: 003 User: Drawn By: CB /CB Date: 08/07/02 TIASTAR [CC MCC: Section Schedule Rev: Ol 08/07/02 Release DRAWIING NO: DUOY2SL003 PAM 1 end r Not to scale F: E 1.50" 38mm .69•'/18mm Diameter Mounting Holes IT 0 eSection O1 0 o Section 02 e e Section 03 e o Section 04 4.69" 73mm 2.75" 2.75" 2.75" 2.75" 70mm o 70mm 70mm ��' � 'Omm o7I49j 19r—TK9mm�1'49mm� 38mm 622mm � ont Side 30.'m SOBmm 508rtvn 762m 50 ANCHOR DETAIL 3" �76mm .69.69„/ CONDUIT ENTRY CONDUIT ENTRY CONDUIT ENTRY CONDUIT ENTRY 7 917" �17" 627" 17 �32mm 38mm 38mm 38mm 38mm MAXIMUM BOTTOM CONDUIT ENTRY 7.19. 19"/T 183— 6. 8"/8 175mm CONDUIT CONDUIT CONDUIT CONDUIT ENTRY ENTRY ENTRY J�174� ENTRY 432 432 627" I16��32 1.50" 1.10" 1.50" 1.50" 38mm 38mm 38mm 38mm MAXIMUM TOP CONDUIT ENTRY - This MCC is provided with a bottom mounted ground bus. Bottom conduit space is restricted; see drawing D79640 Figure 1. - For additional general detail applicable to all sections, see drawing SFFM-15470- — . SI=S Cust: S & B I C Sienens Order: U0Y2S Itern: 003 PrOj: NORTH TA= 7XP STATION Drawn By: CB Date: 08/15/02 L..TLIAST-AkRit�CC NX;C: VRev: DRAWING NO: DUOY2SP003 PAC--: 1 end L 1 UNIT NO UNIT DESCRIPTION M: - DATA *1 CIRCUIT BREAKF-VDISCON=- SWITCH *3 OVERLOAD PRCITECTION *4 CUST SEA TY1` /SUB HT SZ KW HP FLA SF REM FRANC; or DS TRIP or CLIP RNG or FUSE TYPE RNG/HTR FROG DATA - 01FA - MM 18 1200 - - 01FD L DFC3 12 - - - - - -D4 125 30 - - - - - - - - R LEN 125 30 - - - - - - - 01FF - SPACE 12 - - - O1FH - SPACE 18 - - - 01FK - SPACE 12 - - - 02EP - ECB 24 - - - - - - HJD6 400 300 - - - - - - - 02FE - FC3 12 - - - - - - HEID4 125 15 - - - - - - - 02FG - SPACE 12 - - - 02FI - SPCL 15W 12 - 50KVAR - 02FK - SPCL 15W 12 - 37.5KVAR - 03FA - RVSS 3R35 72 361 - 250 302 - - LXD6 600 500 - - - FS20 200-540 - - 04E'A - RVSS 3R35 72 248 - 200 240 - - JXD6 400 400 - - - ES20 100-270 - See General Information and Options and Notes page(s) for explanation of asterisks, option codes, legends, and detailed notes. SI NLIQS Cust: S & B INC Siemens Order: UOY2S Iten: 003 User: Drawn By: CB /CB Date: 08/07/02 TIASTAR ICC MCC: DRAWING NO: DUOY2SO003 PAGE: 1L Unit Schedule - Left Rev: 01 08/07/02 Release CONTROL =>=T TOT *2 FACTORY USE ONLY UNIT WIRING AUX INT PILOT OPTION CODES NAM=-DLAT' INFJRNVMON UNIT =::,S NO DIAGRAM TY FU VOLT CDT NO WC DEVICES NOTES PUC O1FA - - - - - - - - - - - - - 01FD L D68500FDR - - - - - - - - PUMP R'XS7 ic= - - - R - - - - - - - - - - - - 01FF - - - - - - - - - - - - - 01FH - - - - - - - - - - - - - 01FK - - - - - - - - - - - - - 02FA - D68500FDR - - - - - - - - 300 AM° MCC B - - MUN DISCCN<E.T 02FE - UOY2SW6 UT 2/1 120 50 - - - R340 ?HASE MJNITCR - - PANEL 02FG - - - _ - _ - - - 02FI - UOY2SW1 - - - - - - - - - - 02FK - UOY2SW1 - - - - - - - - - - - 03FA - UOY2SW1 UT 2/1 120 750 2 0 BFA BKG BKG C04 R322 R340 PUI2 1 - - EER ES H 11-132 7N133 OL2 NC P2 P2 04FA - UOY2SWI UT 2/1 120 500 2 0 aFA aKG BKG C04 R322 P340 PUMP 2 - - EXR ES H TI132 U 33 OL2 NC P2 P2 See General Infoanation and Options and Notes page(s) for explanation of asterisks, option codes, legends, and detailed notes. SI73�L3QS Cust: S &BIN Siemens Order: UOY2S Item: 003 User: Drawn By: CB /CB Date: 08/07/02 TIASTAR NEC M,C: DRAWING NO: rUOY2SU003 PASS. 1R end Unit Schedule - Right Rev: O1 08/07/02 Release Unit Options C04. Selectable isolation and bypass contactors. OL2. Extra NO alarm contact on overload relay. R3xy. 3RH relay with minimum xNO and yNC contacts. TM32. 3RP1525 solid state 2PDT on delay tirrer (.05s-100h); see diagram. TM33. 3RP1540 solid state 2PDT off delay tirrer (.05s-100s); see diagram. Pilot Device Options BFA. Push -to -Test Pilot Light with amber lens and blank or special legend. BKG. Push -to -Test Pilot Light with green lens and blank or special legend. BKR. Push -to -Test Pilot Light with red lens and blank or special legend. FS. Pushbutton mushroom with NO/NC contact and z - G STOP legend. H. Selector Switch 3 position with HI ND OFF AUTO legend. NC. Pushbutton with NC contact and blank or special legend. P2. Selector Switch 2 position with blank or special legend. Other Device Legends FS20. FSP100 solid state, class 20 overload relay. UT. Unit transformer provides control power; x/y shows primary/secondary fuses. Some note numbers may be intentionally omitted. SLzNIIVS Cust: S & B INC Siemens Order: UOY2S Item: 003 User: Drawn By: CB /CB Date: 08/07/02 TIASTAR tCC NEC: Options and Notes Rev: 01 08/07/02 Release DRAWING NO: DUOY2SZ003 PACE 1 end SII�TQS TIASTAR Motor Control Center Specifications General Bus Units Service 3Ph 3W Bracing 42K AIC sym Min Withstand Ratings Voltage 480 CB Corbination Sarre as available Frequency 60 Hz Horizontal Bus CB Feeder Same as available Avail Fault Curr 42K AIC sym Mfg Series B Service Entrance Not applicable Rating 600A (1/4 x 2) Ccrrponents (except as noted) Material Copper Starter Type INNOVA Labels Plating Tin Pilot Devices 30mm UL All units/sects Barriers Standard Lexan Light Type Transformer CSA Waived Bulb Type LED Vertical Bus General Notes None Rating See section schedule Wiring Class I Material Copper Type Bd (ctrl term blks) Plating Tin Ctrl Term Blocks Screw, stationary Stab Plating Tin Extra Unused !:Its 6 Structure Power Term Blocks Not applicable Horiz Ground Bus Control Wire 16 ga MIW Nema Type 1A Rating 300A (1/4 x 1) Control Terminals Ring tng, both ends Material Copper Wire Markers Control only Height 91.125" / 2315rtm Plating Unplated Type Heat shrink Location Front bottom Depth 15" / 381rrm Lugs (1) 6-300 NKr] General Options None Plan View DUOY2SP004 Paint USAS 61 light gray Incoming Nameplates General Options Main Entry Type 600A MLO Master 2 x 6 Seismic Zone 4 UBC Section 01F Color (face/text) White / black Incoming cables (2)350 NKr] /PHASE Text Size 1/2 Special Diagrams None Text Line 1 MCC-B Unit Standard Color (face/text) White / black Text Size 3/16 Text See unit schedule Attachment Stainless screws See General Information and Options and Notes page(s) for explanation of asterisks, option codes, legends, and detailed notes. Revision History I Commercial Information I Siemens Energy & Automation, Inc. West Chicago, IL O1 08/08/02 Release t: S & 3 INC Siemens Order: UOY2S Item: 004 r: Drawn By: CB Date: 08/08/02 j: Ft�Elc-: NORTH TALBOT PUMP STATION Approved By: CB Ante: 08/08/02 34591 DRAWING NO: DUOY2SA004 PAGE: 1 of 1 Front of MCC (in/run) 12/305 01F 02F 03F 04F 90/ 2286 72/ 1829 - - A SPCL A RVSS A RVSS A FCB C PNLBD C SPACE E SPACE G SPACE H FCB I SPACE i XFNFZ 7S-11� SPACu 6/153 11..12/2861 �- 20/508 20/508 420/508 �- 20/508 — •r ■ Sections II 01 1 02 1 03 1 04 1 1 1 1 d Depth (in/nm) 15/381 15/381 15/381 15/381 Width (in/um) 20/508 20/508 20/508 20/508 Vertical Bus Type 600A front 600A front 600A front 600A front Barriers Insul/Isol Insul/Isol Insul/Isol Insul/Isol General Notes I- - - - See General Information and Options and Notes page(s) for explanation of asterisks, option codes, legends, and detailed notes. SI=I S Cust: S & B INC Sien?ns Order: UOY2S Item: 004 User: Drawn By: CB /CB Date: 08/08/02 TIASTAR NLC N C: Section Schedule Rev: 01 08/08/02 Release DRAWING NO: DU0Y2SL004 PAG : 1 end Not to scale F'. B 1.50" 38— .69"/18mm Diameter Mounting Holes 0 0 0 0 0 0 0 0 IT Sec[ion O1 Sec[ion 02 Sec[ion 03 Sec[ion 04 1.69" 73mm 2.75" 2.75" 2.75" 2.75" I � 70mm o�J149mm� � 70mm 0�1+49mm o � 70mm � 70mm o�I49mm� 3150"8mm ? on[ Side 20" S OBmm 20" SOBmm 7-449mm� 20" 508mm 20" 508mm ANCHOR DETAIL 3" �76mm C .69.69"/� CONDUIT LEI [T.'EE] 7��17" 32�17" 32�1111 32�11;q 32 38mm 38mm 38mm 38mm MAXIMUM BOTTOM CONDUIT ENTRY 7.19. 19"/T 783 6. 8^/� CONDUIT CONDUIT CONDUIT CONDUIT `! ENTRY ENTRY ENTRY ENTRY 432 432 �JI III{{,��, 4174 432 16� 1 .50" 1.50^ 1.50" 1.50" 38mm 38mm 38mm 38mm MAXIMUM TOP CONDUIT ENTRY -2 Conduit space may be restricted by transformers in sections where indicated. -- This MCC is provided with a bottom mounted ground bus. Bottom conduit space is restricted; see drawing D79640 Figure 1. -- For additional general detail applicable to all sections, see drawing SFFM-15470--' . SMIENS Cust: S & B INC SiEnens Order: UOY2S Item: 004 oroj: NORTH TALB:7i' PUMP STATION Drawn Bv: CB Date: 08/15/02 TIASTAR IUC MCC: Plan View Rev: DRAWING NO: DUOY2SPOO4 PACs: 1 end 1 UNIT NO UNIT DESCRIPTION M7IC)R DATA *1 CIRCUIT BR A:ER/DISCCX= SWIM-1 *3 OVL-KDAD ?RCI=- ION *4 CUST SEA TYPE/SUB HT SZ :(W ELv ETA SF RPM FRAM; or DS TRIP or CLIP R% or FUSE TYPE R4G/HTR FROG DATA - 01FA - S_Pa 15W 12 - 25(VAR - 01FC - PNLBD 30 - 240/120v 1Ph 3W 18Ckt 100A MIB Al Bot Feed (11)20/1 (1)30/2 (3)20/1 W/GFI - 01Fr1 - FCB 12 - - - I - - - LIEN 125 40 - - - - - - - 01FJ - XFMR 18 10 120/240v 1Ph 3W - 02FA - RVSS 3R35 72 195 - 125 156 - - FD6 250 250 - - - ES20 100-210 - - 03FA - RVSS 3R35 60 57 - 30 40 - - EN 125 70 - - - FS20 30-60 - - 03F-K - S_PCI, 15W 12 - 11KVAR - - 04FA - FCB 12 - - - - - - FIED4 125 15 - - - - - - - 04FC - SPACE 12 - - - 04FE - SPACE 12 - - - 04M - SPACE 12 - - - 04FI - SPACv 12 - - - 04FK - SPACE 12 - - See General Information and Options and Notes page(s) for explanation of asterisks, option codes, legends, and detailed notes. SL-Ig1QS Cust: S & 3 INC Sierens Order: UOY2S Item: 004 User: Drawn By: CB /CB Date: 08/08/02 TIASTAR NCC IBC: DRAWING NO: DUOY2SO004 PAC 1L Unit Schedule - Left Rev: 01 08/08/02 Release I CONTROL CIRCUIT TOT *2 FACTORY USE ONLY UNIT WLRING AUX TNT PILOT OPTION CODES NAMEPLATE INFOPPATION UNIT NCT.S NO DIAGRAM TY FU VOLT CPT NO NC DEVICES NOTES PUCx O1FA - UOY2SWl - - - - - - - - - - - 01FC - UOY2SW5 - - - - - - - - LIGHTING PANEL L - - 01FH - UOY2SW5 - - - - - - - - PRDPJPY BREAKER - - 01FJ - UOY2SW5 - - - - - - - - LIGHTING - - TRANSFOR11ER 10KVA 240/120V 02FA - U0Y2SW1 UT 2/1 120 500 2 0 BKA BKG 3KG C04 R322 R340 Pao 3 - - BKR FS H TM32 TM33 OL2 NC P2 P2 03FA - UOY2SW2 UT 2/1 120 306 2 0 BKA BKG BKR C04 R322 R340 Pub 4 - - ES H NC 7M32 TN33 OL2 n2 D2 03FK - UOY2SW2 - - - - - - - - - - - 04FA - UOY2SW6 UT 2/1 120 50 - - - R340 PHASE MONITOR - - PANyL 04FC - - - - - - - - - - - - - 04FE - - - - - - - - - - - - - 04FG - - - - - - - - - - - - - 04FT - - - - - - - - - - - - - 04FK - - - - - - - - - - - - - See General Infomation and Options and Notes pages) for e>aDlanation of asterisks, option codes, legends, and detailed notes. SIF21IIQS : S & B INC Siemns Order: UOY2S Itan: 004 Fger: Drawn By: CB /CB Date: 08/08/02 TIASTAR I,UC DRAWING N0: DUOY2SU004 PAGE: 1R end Unit Schedule -Right O1 08/08/02 Release Unit Options C04. Selectable isolation and bypass contactors. OL2. Extra NO alarm contact on overload relay. R3xy. 3RH relay with minimum xNO and yNC contacts. T1432. 3RP1525 solid state 2PDT on delay timer (.05s-100h); see diagram. TNM . 3P-01540 solid state 2PDT off delay timer (.05s-100s); see diagram. Pilot Device Options BKA. Push -to -Test Pilot Light with amber lens and blank or special legend. BKG. Push -to -Test Pilot Light with green lens and blank or special legend. BKR. Push -to -Test Pilot Light with red lens and blank or special legend. FS. Pushbutton mushroom with NO/NC contact and ESERG STOP legend. H. Selector Switch 3 position with HAND OFF AUTO legend. NC. Pushbutton with NC contact and blank or special legend. P2. Selector Switch 2 position with blank or special legend. Other Device Legends ES20. ESP100 solid state, class 20 overload relay. UT. Unit transformer provides control power; x/y shows primary/secondary fuses. Some note numbers may be intentionally anitted. SIL S Cust: S & B INC Siemens Order: UOY2S Item: 004 User: Drawn By: CB /CB Date: 08/08/02 TIPSTAR NCC W-C: Options and Notes Rev: 01 08/08/02 Release DRAWING NO: DUOY2SZ004 PAGE: 1 end E V-2110 ' 534nn 20,10 508mm 5 ' -►I 38inn PO OR E (] �) oN J V Y (U c °' _V o N p o � Q o ED J J Y p ED T Y Yo N 0 0 � N1 H Z D W Q af W E o a) W Q p Q ru coo O j N Q � W I C W p % O p o N Depth Weight (Single Section) 1. Spare combination starters will be sized for Max. HP if not otherwise specified. 2. Total aux. Interlocks show the min. number of interlocks and include the holding pole. If the quantity listed exceeds those on the starter/contactor a relay will be provided. 3. Magnetic trip settings. Factory set at low. Adjust per NEC Art. 430 as required. 4. Overloads with Heaters: If motor nameplate data is not supplied by customer, Siemens will pick heater coils for FLA per table for 1800 RPM and service factor of 1.15. Motor nameplate data must be checked by user before energizing unit. Check heater coil for proper size. ESP 100 Overloads: Overload current range is shown followed by number of passes thru sensing window, if more than one. Effective overload range equals overload current range divided by number of passes. 5. 80" Max. Shipping Split. 6. Dimensions shown are nominal and subject to change. Areas may be restricted due to horizontal ground bus, vertical bus, or sections with transformers. Request certified dimension drawings for installation. For NEMA 3R dimensions reference D63535 outlines. 7. All fractional millimeters are rounded up to the next higher mm. Ex: 124.1 = 125. 8. With lighting transformers and autotransformers, NEMA 12 bottom plates are non -removable and conduit entry is severely reduced. 9. For 2 Speed starters, variable torque is assumed to be the type unless otherwise indicated by the customer. 10. If kW is the only rating provided, the Amps are based on the following calculation: Kw to AMPS = (Kw x 1000) / (1.73xExP.F.) P.F. will vary based on motor size. E = System Voltage P.F. = Power Factor. 11. Sections 30" - 60" wide never have vertical wireway doors. 12. A pull box is generally used to provide additional cable bending space for incoming main feeds or bus duct connections. They are shipped as a separate item, which must be mounted on the MCC in the field. 13. A top hat is a pull box supplied with incoming line bus extensions for mounting inverted main lugs only. They are shipped as a separate item, which must be mounted on the MCC in the field. 14. If nameplate data is not supplied for units, blank nameplates will be supplied. 15. Pilot devices are 22mm as standard. (30mm optional) 16. For NEMA Type 2 MCC's, lifting devices are supplied bolted to the shipping skid. If the lifting device is required, the drip shield must be temporarily removed to install the lifting device. S Motor Control Center General Information 1500 W. Harvester Rd. TIASTAR W. Chicago, 111. 60185 Model 95 Plus MCC Page 1 of 2 Tel. 630-231-6200 Form # SFFM-15470-0201 17. Lifting device mounted to top of MCC increases the shipping height to 98" / 2490mm. 18. In general, MCCs may contain components, which require derating above 6000 feet. In addition, distribution transformers require derating above 3,300 feet. VFD and RVSS devices require derating at altitudes above 3000 feet. 19. On NEMA 12, MCC's, all 800a or larger disconnect devices use a door mounted bustle, which increases the MCC depth by 8" (203mm). 20. The sloped roof of the Nema 3R structure is not designed or intended to support or seal top entry. 21. Fuse clip sizes are based on time delay fuses, unless otherwise shown. 22. When specified, ring tongue termination is used on devices where possible. S ITIASTAR Model 95 Plus MCC Motor Control Center General Information Page 2 of 2 1500 W. Harvester Rd. W. Chicago, Ill. 60185 Tel. 630-231-6200 Form # SFFM-15470-0201 ' To: Siemens 13112 NE 20th St. Sutie A Bellevue, WA 98005 Attn: Craig Schulz ' E-mail: To: E-mail: To: E-mail: To: E-mail: ' To: ' E-mail: To: E-mail: Special Requirements: ' N/A Catalog Cut Sheets N/A Customer Inspection Checklists N/A MCC Instruction Manual N/A Certified Testing Reports N/A Bill of Materials N/A Custom Binders ISO Paperwork 'N/A N/A N/A Quality Assurance / Testing Procedures N/A Other Customer: S & B P.O.#: B4591 Project Name: North Talbot Pump Station Siemens Order#: UOY2S Omnis #: 9834642 Z 'lid O d ? O d�4 CO,Q s'CN fps C^0 �0• `�°r 0�! cad/ ��f G�4' O01 7�fe Approval N/A. N/A VA Re -Approval N/A. N/A '.N/A Advanced Record 5 N/A N/A .N/A N/A N/A Record (As Built) 5 N/A N/A N/A. Approval N/A N/A N/A Re -Approval N/A N/A N/A Advanced Record N/A N/A N/A N/A N/A Record (As Built) N/A N/A N/A Approval N/A N/A . N/A Re -Approval N/A: N/A ::N/A Advanced Record N/A N/A N/A N/A N/A Record (As Built) N/A N/A N/A . Approval N/A N/A N/A. Re -Approval N/A N/A N/A: Advanced Record N/A N/A N/A. N/A N/A Record (As Built) N/A N/A N/A Approval N/A N/A N/A Re -Approval :N/A N/A :N/A Advanced Record N/A N/A N/A N/A N/A. Record (As Built) N/A N/A N/A Approval :N/A. N/A :N/A Re -Approval N/A< N/A ;N/A. Advanced Record N/A N/A .N/A N/A N/A Record (As Built) N/A N/A N/A Notes: IAdditional Charges may be incurred for any items needed that are marked N/A. Contact factory for pricing. Siemens Energy Automation, 1500 West Harvester Road, West Chicago, IL 60185 n -- - - - -- -------- 1 01FC I , I I 100A I MCB I 20A 20A WITH GFI 1 t-- WITH GFI 20A 20A WITH GFI I 3 I I I 20A I 20A 1 5 I 6 1 1 20A 20A 20A 20A I 9 ]0 , I 1 20A I 30A 1 11 1 12 � I I I 20A I 13 14 1 20A 20A I 15 I 16 I I I 17 I I I I I I I I Is I I 1 I I 1 I I I I I I I NEUTRA I I I i 1 I I I I BUS I 1 I I I I----------------------- 1 I I J A) RELEASE 8/6/01 BY CB THIS PRINT IS THE CONFIDENTIAL DRAWN BY, SCALE, N / A PROPERTY OF SIEMENS-FURNAS CONNIE DATE, 08/00/02 CONTROLS. NOT TO BE USED OR REPRODUCED IN ANY MANNER, NOR CHKD BY, TOLERANCE UNLESS SUBMITTED TO ANY OTHER PARTIES OTHERWISE SHOWN FOR EXAMINATION WITHOUT PRIOR APPRD BY APPROVAL OF SIEMENS-FURNAS XX OR XXX t.015 CONTROLS. ANGULAR t 2- Siemens—Furnas Controls Siemens Energy & Automation, Inc. West Chicago, Illinois CODED TO PLANT LOCATIONS) EPD CAD CAM DRAWING - DO Ll L2 L3 r- - - - -- - -- - ---------- 101 FH --- --- I STAB I I I ON , I , I , I , I , I , 40A CIRCUIT , 1 BREAKER I I , I , I , I , I , i I L-----I ------- -------I 101 FJ I I I I , I I I I I I 1 1 I I I I 1OKVA 1 1PH 3W 60HZ 1 I 480V PRI. I I 120/240V SEC. t L- - - -- - - -- - - --- - - - --J X1 X4 NEXT ASS'Y X X X TOOL NO. TYPE OF TOOL N*x ww* TITLE- 1PH 3W 120/240V PNLBD W/ 100A MCB AND 10KVA XF-MR DWG. NO. REV. UOY2SW5 A F/Nt X:\DWG\DU0\Y2SW051A STYLE: 8 9 B SHEET # 1 X IOWA CLIMCO FEMSA NOT MANUALLY CHANGE FIGURE #1 - Bottom Ground Bus Restrictions 14„69' 373mm 9,5' 241mr, BOTTOM VIEW i Ground Bus BUS SIZE A 300A 3.75' 95mm 600A 3,25' 83mm c TTl \ /Tr\ 25' tD.JJMM I FIGURE #2 - Bottom NeutraC Bus Restrictions i i- 14,6 9' 373mm i 8,25' S,25' 210mm 133mm FRONT BOTTOM VIEW Neutral Bus Panduit t t 6.0' 2,5' 152mm 64mm SIDE VIEW Neutral Bus Panduit NOTE: DIMENSIONS ARE NOMINAL AND SUBJECT TO CHANGE WITH❑UT NOTICE A) RELEASED FOR PRODUCTION NEXT ASS'Y X X ' TOOL NO. TYPE OF TOOL OWN :E 3[31f ' trxlK �rre srsrx x��r This Vint is the coftentel property of DRAWN BY, SCALE- N / A TITLE, 15 " DEEP siemens Energy & Aul omadon, Im d is not to R W B DATE, 12112100 GROUND AND NEUTRAL B U S ' be used dled to any other or reproduced in any manner, nor CHKD BY, TOLERANCE UNLESS subrnher parbes for winunabon OTHERWISE SHOWN CONDUIT RESTRICTIONS without prior approval ofSiernmEnergy & DWG. NO. REV. Aummedon, Ina APPRD BY, XX OR XXX t .015 D 7 9 6 4 0 ANGULAR t 2- ' Siemens Energy $ Automation, Inc. F'N, X;\STD\D79\640001-A,DWG West Chicago, IL 60185-1655 STYLE: X X X X SHEET # 1 CODED TO PLANT LOCATION(S)EPD X IOWA CLIMCO FEMSA CAD CAM DRAWING - D❑ NOT MANUALLY CHANGE readme.txt MCC Electronic Drawing Transmittal Siemens Order Number: 00-u0Y2s Item Number(s) Included: 3-4 Customer: S & B INC Cust Po: B4591 User: Project: NORTH TALBOT PUMP STATION - indicates the drawing is not available electronically and is not included in this package. Drawing Title ----------------------------------------------------------------------------- ---------------------------------- I Drawing Number Rev I File Name MCC specifications I I DUOY2SA003 01 I I u0Y2S003.PDF Section Schedule I Du0Y2SL003 01 I u0Y2S003.PDF Plan view I DU0Y25P003 I PLANv003.PDF unit Schedule I DUOY2SU003 01 I UOY2S003.PDF Options and Notes I DUOY2SZ003 01 I u0Y2s003.PDF MCC Specifications I Du0Y2SA004 01 I UOY2s004.PDF section Schedule I DU0Y2SL004 01 I u0Y2S004.PDF Plan view I DUOY2SP004 I PLANv004.PDF unit Schedule I Du0Y2Su004 01 I u0Y2S004.PDF Options and Notes I Du0Y2Sz004 01 I u0Y2S004.PDF wiring Diagram i i D68500FDR K I 1500FDR-K.DWG wiring Diagram I UOY2Sw1 I u0Y2SW1.dwg Wiring Diagram I u0Y2swl I uOYW1.dwg wiring Diagram I u0Y2SW2 I u0Y2sw2.dwg Wiring Diagram I UOY2SW2 I uOYW2.dwg Wiring Diagram I UOY2SW5 A I Y2Sw051A.dwg wiring Diagram I UOY2SW6 I UOY2Sw6.dwg i MCC General Information i SFFM-15470-0201 I I BOILER2.DOC Installation and Maintenance I SFIS-70060-0901 Drawing Transmittal - Customer I UOY2ST I U0Y2ST.XLS Conduit Restricts - Gnd/neut I D79640 A 1640001-A.DWG End of transmittal Page 1 7 ELEMENTARY DIAGRAM w 100 CAP 1 FUC 1 PFCC h 101 L1 (Tl)I — I— I TL1 w 102 2FUC TT ~ 1-2 T2 2�I- I I TL2 ✓; W 103 3FUC r ✓ , c,- L3155 T3 I TL3 I 104 L — — SEE K2 SHEETJ �_•. <;c 32105 10�33 _ Y-; �_- o 106 1CB (1-1) (Ti) 1L1 (X 1) L1 T1 (X2) 1M ISO 2L1 , 1 MTR :.1 I-- C7.) 34 35 1L2 (Xl) (X2) L1 T1 L1 T1 ';l-) f7 T1 J T.. D u 107 HOR°Iz. L2) (T2) BUS ( 1CT L2 1 2L2 � — M 1L3 (X1)36 37(X2) L2 T2 L2 T2 (T2) 10$ L3 T3 L3 T3 2CT 2L3 — L3 T3 L3 T3 (T3) 109 3CT 129 159 BYPASS d Z W a 110 3L1 W 30 L1 T1 N 111 (1-1) (1-2) 31-2 � CONNECT � L2 T2 112 Lt VOLTAGE 3L3 AS SPECIFIED L3145 T3 x li3 PER NAMEPLATE 0 SEE NOTE:2 O ^u C` �-� i^ 114 E-STOP VMCR 01 H 11 CPT 115 47 47 01N1 01 N1 L 01H1 ���-L(X2) c;z; ¢':.4:' x a d 1 2 ` 1a`::::>Qc..._?� ¢ w 116 1P8 40 41 CR1 z 41 PUMP CALL v FROM TELEMTRY r ww 117 0100 ql A2 0100 CR1 1 PUMP REQUIRED O c w�Qo? 118 (1311,16(l4 ) A H2 0- c o w a Zo C,-WO 119 (2) (xM) 0 ���aa F <LLJ HAND OFF AUTO CR2 L- E o oz=scl 120 2 C o .� i���z -j 1 1( 4 Al A2 PUMP CALL O j = wli�wa Z 121 I I U Q n- Z z � Q o 96 rn rn � 0 Z WI-Z J 122 (2324) 3 CR1 tOL wvizaM 43 44 (95) i T zca aaa r- 123 (33)k34) 132 132 C v UMZLJ , A }. 1 SS PUMP READY w w a a o w w ~ z o W 124 24N 24N TIEL MTRYO o�f V) a� C C3 U 125 CR2 (331L(,34) TR1 OFF V) E v, H q v! v, ZUQ�o Q 126 13 2SS A1+ A2- ISOLATION C O SET FOR 5 SEC N h o a d�W�o Z 2014 v,cxww� Q 127 BYPASS 5 TR 1 11 (n I a C3 o a 128 A13 15C 18N0 45A14 12 129 (16NC) 0 TR1 7 ISO 130 25C 28N0 Al A2 ISOZ CONTACTOR CTR 125 O 131 CR2 (26NC) TR2 132 8 23 24 DELAY Al A2- VAL VE PUSET MP FOR R15 SEC 20 133 (A3+) L3 134 C11 R2 TR3 OFF 9 DELAY CONTROL VALVE LOGIC 135 33 34 20 A1+ A2- SET FOR 5 SEC 3 0100 0102 0102 TR3 CR3 Q 136 15C 18NO 01030103 13 Al A2 PUMP CONTROL VALVE 36 CR3 1 N � 137 (16NC) PUMP CONTROL 136 24N 43 44 36 138 CR3 SAL E PEN 10 139 13 3614 (2) (1-12)U 140 TR3 11 BYPASS SOFT START 12 RTM (� 141 25C 28N0 11 12 1 2 ELASPED TIME (HOURS) Q 13 (26NC) CR4 7171 N 24N 142 I CAPACITOR CALL Al A2 3CR434 143 ALARM RESET 23`'^4 ( ) TR4 OFF 42 20 (X1) -[(2 13 DELAY 144 (1 2P8 2 2SS NOTE:1 Al+ A2- 1159 145 CR4 UP TOVOLTAGEBYPASS 146 11 13 11 (47)1, 4S) Al A2 BYPASS CONTACTOR 4214 im 147 FAU LT 14 U RUN 148 (37)1 ) H2 (2) 149 150 10L 14A CR5 01 N 1 24N 2222 CR5 24N PUMP FAIL 43 44 97 98 Al A2 50 os 151 CR5 P MP FAIL ALARM 152(13111 R H2 5014 (2) 153 TR2 0104 0104 0105 01N1 154 15C 18N0 PUMP CONTROL VALVE SOLENOID CAPACITOR 41,1 155 OFF TO I (16NC) CR4 CAP 19 1115 156 3 4 23 24 V w POWER CORRECTION CAPACITOR CALL 3SS 42 157 BYPASS 16 1CNT 15$ 814 B13 3 4 START COUNTS 45 FAULT 159 1M (35 (36) 159 160 TR5 17 15C 18NOVSS (AlA1 A2) 1 2 161 (16NC) TR4 18 TR5 ON DELAY 16 NOTE:1 KEY OPERATED SWITCH 15C 18N0 Al A2- .a u 163 14 NOTE: 2 PUMPS 1 & 2 WIRES TO 02FE MCC -A 'I (16NC) (A3+) PUMP 3 WIRES TO 04FA OF MCC-B Sri• F-T-c 0100 1 (14) (13) 0100 (22) (21) (32) (31) 2 (44) (433 )01141 01N1 (A2 (A1) 41 CR1 4 0100 (14) (13) 0100 $ 0100 (24) (23) 0100 9 0100 (34) (33) 0100 (44) (43) 2 0 1 N 1 (A2 (A1) CR2 10 0100 (14) (13) (22) (21) (32) (31) 24N (44) (43) 136 01N1 (A2 (A1) 0103 CR3 20 0100 20 (14) (13) 0100 15 19 (24) (23) 24N 71 (34) (33) (44) (43) 01N1 12 CR4 'Y C3 :ICI Q�i ryl b INTO INTO MIK91■ LNIO INTO 6 INTO LNIO 2L M0 INLO Ll INTO B ON9L +1V0 ON9Z 0 �p - 0 9 ONS l 6;j' V) �O 0 3 ON8Z 0 0111 AZ 0 9 -ZV co cfnN OSl 0 0 OSZ 0 ON9 L lb ON9Z 0 'mo in iN 0 +£V 0 ON8l No 7 NK ON9Z 0 C"r' '' �Z 0 0 -ZV _� W N OS l 0 0 0 OSZ 0 ON9L +LV 0N9Z 0 Xo 0 0 ONBL Zo NM ON9Z 0 Om " wZ 0 0 -ZV W� OSl LnN 0 0 OSZ 0 ON9L +1V0 ON9Z 022 �p A B ON@ L Z, N ON9Z Dom +' ;0Z 0 9 -ZV m� N0 OS l 0 0 OSZ 0 ON9l LV ON9Z 0 �o �N 0 +£V 0 ON8l No A �� ON8Z 0 U'm L"�Nm. 0 0 -ZV m� N OSl 0 0 OSZ 0o W 0 0 00 00 _ v _ 0 (1 ) N N O O�, O, o (n z 0 00 D 00 D 0 (.+ (.,� r� U W C 0(2) l m W`� �D ° °wOuff �bW w o m F mU r v 16 0 (3) ? N m p I�� o U)-�,, cn ��� x x o x D x Z (n N N �'I W .Z7 N N Rl Z N N N v .p N O .p. ? N m rri Z O1 N1 0 4" -�" — -c rN*i oo o0 0 00 o0 0 00 oo oo oo_ () 0 0 --� -i Q O - r {a N 01N1 zz rn � W N o N 00 zz 00 zz 00 zz 00 zz J v W N D W O N 9 IZ�-Z�y(� lZV)O OOLO OOLO S (tilV) (2w) OOLO 00L0 ll� -� (lam 11£ -� - L1L ZL (lV) 8 ZL (Zi) L- (Z-1)Zll nT ��' LNLO (ZV) L£10 OOlO £1L OOLO SSVdlke 9l "Le4l8 OOLO OOLO 6 LZ8 ZZ8 6 14 14A (14) (13) (22) (21) (32) (31) 24N (44) (43) 22 01N1 (AZ (A1)14A CR5 CA 0 2FUP (L2) 1 L2 1 FUP (L1) 1 L1 3FUS X2) (1) 'Ij 0 0 Z S /T (l � (� £�L r- c W c z z ZO l0 J------ - (L- -1) ll l n 00t0 LIZ Li~l �--� L1l N ^' n n n N z n a n z OOLO 0Z 0 Z Z Z 0 0 N O p 0 (ty) Z z ,i z D L �),, D 0p D ➢ Z1Z (Zl) i � Z1 L z v z c z c z M z Z z p D o £t INIO (ZV) o m on o o o o o L N L 0 £1Z w OSI _ NN O 4100 ----------- OOLO £l8) til8) 0 0 OOLO Lze ZZ9 y-vL �� �p 00t0 8l o• • jl N r 5 r N N r c c z z n C N � n n 0 0 m G ;0 r N x W N r- W 00 -O ON N Z Z Z Z O N N N N 00 O O_ O O_O O_O_ Op 00 O W W J A as O � A N ZZ O 0 NO 00 00 f O) NJ J O Z Z Z Z N ? W 00 00 ZZ Zz 2 N N N N 0 0 0 0 0 0 0 0 0 V j N N f O Z Z Z Z O O O O O O Z Z 2 U� W N O O Siemens & Furnas Control Products °ATE` r� Siemens Energy & Automation, Inc. DRAWN BY, West chicago, Illinois t3 , THIS PRINT IS THE CONFIDENTIAL PROPERTY OF SIEMENS CHKD BY, 6 FURNAS CONTROL PRODUCTS. IT IS NOT TO BE USED OR REPRODUCED IN ANY MANNER, NOR SUBMITTED TO ANY APPRD BY - OTHER PARTIES FOR EXAMINATION WITHOUT PRIOR APPROVAL OF SIEMENS R FURNAS CONTROL PRODUCTS. CODED TO PLANT LOCATION(S): EPD X t,\ v ...) Pt' - -_I`i U 0 # OF -EMSA r� DO NOT MANUALLY CHANGF- 100 101 102 103 104 105 106 L15106 STAB L1 (L1)(T1)iLl 107 L2 -- L2 (1-2) (T2) 11-2 108 L3 ?> L3 L3 T3 1L3 109 110 111 112 113 SEE NOTE:2 114 01 H 1 0100-STO 47 47 VMCR 01 H 115 1 1 PB 2 116 1 117 T0100 118 119 120 121 122 123 124 125 126 127 128 129 130 131 132 133 CR 11 134 23 2 135 136 ALARM RESET18 (X1) 137 1 2PB 2 11 3 138 CR3 139 33 35 34 1M 140 FAUtLT� 141 (37)153(38�e ) 142 10L 143 97 11 06 sa 144 145 146 CAPACITOR 147 OFF To I 148 3 7 4)s 3SS 149 150 ELEMENTARY DIAGRAM r-------� 1cNt O1N1 X2 40 41 CR1 41 TA113 A2 CR1 PUMP RE UIRED (131111,(14) (2) 1LT H2 HAND OFF AUTO CR2 I I 2 1 4 Al A2 (23)-04) 3 CR1 (33)(34) 43 44 132 0�6 i SS 24N CR2 (331L(34) TR1 OFF 4 6 DELAY 13 2014 2SS A1+ A2- BYPASS11 5 TR1 A13 11 38A14 15C 1BN0 12 (16NC) TR1 7 ISO 25C 28N0 Al A2 w1 � F 1 (26NC) 2 BYPASS SOFT START RTM a s 11 12 1 2 024 CR3 Al A2 TR2 OFF (23lb4) 10 Y 2SS NOTE:1 Al + A2- 1M UP TO VOLTAGE (47)15 3(48 BYPASS 01N I W 0J 0 Ld W 5] fl ) L_ } (14 O 1 MTR L_..... C) (T1) > i u (T2) M (T3) d 1 PUMP CALL ` ,z r LL zLLJ x V) FROM TELEMTRY U i } � Ewa ujw O C W cx L L-mgOp Z C c q W. q ormo o O ~ ~ a a ~ XM) o c, o sir W E o ozN=F old C O.c m-!�.-z --� PUMP CALL O : _ Z U Q -j�z�ou ¢- z zQ (96) 0 � r- a < z W !- z = 10L N Q' o wviz¢c —1 (95) 0 L M:E zazaaa 132 c ooax "aa`'z A PUMP ETOY C` w W wca J 24N SIGNAL TELEMTRY Q o�f m 0z�� � O C � v! H q vl ti U vn E ~ZOU.W+L HU71-O ISOLATION C v1 o Q -1 SET FOR 5 SEC N azw�o Z N v'L�=a Q V) = m�a �.aoo¢ ISOLATION CONTACTOR ELASPED TIME (HOURS) CAPACITOR CALL 80 B&R3 24N 24N 13 3514 BYPASS CONTACTOR (2) I2LT -' 12 CR4 01N1 01N1 Al A2 PUMP FAIL CIR4 P )P FAIL ALARM 14314 R H2 jj (2) 3LT 35(24 14 BYPASS11 15 1CNT 151 B14 813 3 4 38 152 153 1 M TR3 16 154 15C 18No (Al A2) 1 7 155 (16NC) 156 TR2 17 TR3 157 15C 18N0 Al A2- 158 13 (16NC) (A3+) 159 160 161 162 163 POWER CORRECTION CAPACITOR CALL START COUNTS RVSS 2323 CR4 24N 24N 43 43 44 1M FAULT (35 153(36) NOTE:1 KEY OPERATED SWITCH NOTE: 2 PUMPS 4 WIRES TO 04FA OF MCC-9 mo 1 (14) 0100 0100 (13) (22) (21) (32) (31) 2 3 (44) (43) 41 01N1 (A2 (A1) CR1 4 (14) 0100 0100 (13) 8 (24) (23) 0100 lNl0 LNLO (34) (33) (44) (43) O 1 N 1 (A2 (A 1) 2 CR2 LL 24N 80 (14) (13) LNLO 14 13 LNLO (24) (23) 18 0100 18 (34) (33) 0100 (44) (43) 01 N 1 (A2 (A 1) 9 91 CR3 LNl0 11 12 11 (14) (13) (22) (21) (32) (31) 24N 23 (44) (43) 01N1 (� (A1) 12 CR4 3Y C3 _ m _ _ c � O o0 m N O 00 00 2 K 2 2 0(1) co co Oo 00 ++� co CO CO D z o 0o D oo %+ f v w c i+_D ��,��, I I _ _ Z O O D Q I r D r ��QQ j— �1 0(2) n l W. O D NO (A �{W— 0 W_ J N�� W _ �O N� � ZJ �IF X �N F � X �2 C 15 0(3) N N C1 O W —� D WN �T1 00 00 K 00 c0 00 00 00 O 01 N 1 0 4 -Ovvv N — — -� m oo l zz oo zz oo zz 01N1 () oo 41 rn o f w W N o J o0 00 00 Z Z v W O D N co 9 ON9L +lV ON9Z A AO A 0 9 ONBI �o M N ONBZ 0 om �z 0 9 -ZV co �N OSl ON9L +LV ON9Z 0 xO Cn 0 E9 ON8 L � wM ON8Z 0 om Az -00 0 9 -ZV co OS L 0 10 OSZ 0 K" 9 ON9 L LV ON9Z 0 vo �N 0 +EV 9 ON8l No A NM ONBZ 0 `�'� (A�Z 0 9 -ZV E0 OS L 0 0 OSZ o• • mm LL Kw Ko • v�Z�l SC ( )O 001,0 OOLO ----- L1 LSE —� Ll L 6 (LV) 6 (Z1) Zl£ Zll LNLO L EEO " 2-1 l SSVdlke S 1 -------------------- £l8) til8) 00000 to lZ8 ZZ8 41(� ( L�Z Z �---I �---� Lit L l t L (lV) Z�Z (Zl) ,ZIL LNIO (ZV) LNLO (E10—d £�Z k_--0 M L OSI --- ------ -til--------- ' EL8 8 LZ8 ZZ8 0—d f _- W c� > � 14 -�(L-2)1 L2 01N1 W 01N1 0� i L3 1L3 �a X c c W N c z zut z N N Z J Z Z OO 0 0 (7 O C� 0 O 0 n 0 O n O N Z V O5 V Z V Z 1 N Z 1 M -9 Z V D ;q I D _ D D , D D O D Z N D O D Z N Z 0 Z r Z Z Z -O-i Z O o m n� o -1 0� Z O� Z O� Z O-i r- L4 r W 00 ZL C. -i� 00L0 � v LNL0 O—.4�—�. IN1.0 � D v 0 r im (�) 1 L2 j 2FUP 1L1 L1 � 1FUP 1L1 1L1 3FUS (L1) 1LL22 N m N L2 X2) (1) 1 L3 w w L3 1 L3 0 0 z 2 r N r � � N c c Z Z a a n 0 N Z O 0 0 M o X D N N P WrLE 00 --� rn2%6, HE ZZ N N O 0 N _0_ 00 00 O ? _p� W co O o N 00 ZZ ZZ 2 Z Z N O `I O .0 Z W 00 0 0 0 0 v Z Z N O O O Z W O Z Z 2 O Siemens & Furnas Control Products DATE Siemens Energy & Automation, Inc. DRAWN BY - West Chicago, Illinois THIS PRINT IS THE CONFIDENTIAL PROPERTY OF SIEMENS CHKD BY- FURNAS CONTROL PRODUCTS. IT IS NOT TO BE USED OR REPRODUCED IN ANY MANNER, NOR SUBMITTED TO ANY APPRD BY - OTHER PARTIES FOR EXAMINATION WITHOUT PRIOR APPROVAL OF SIEMENS 6 FURNAS CONTROL PRODUCTS. CODED TO PLANT LOCATION(S) 1EPD X AM aNO 1 0mil f=I CONTROL DEVICES L1 L2 L3 Y_ Y Y 1 STAB J J J N M J J J (L1) (L2) (L3) 1CB (T1) (T2) (T3) N N M JJ JJ J a m 0 BY -_ 38105l0 CONNECTION DIAGRAM a r7 N rz-:7- N M d < C U d D Q N N X 1 1 TO TB# 47 UN.O FA 2 2 TO T8 01H1 UN. 3FA 3 3 TO TB 47 UN.O FA 4 4 TO TB$ 01H1 UN.004FA 100 ELEMENTARY DIAGRAM 101 102 103 104 L1 105 L2 106 L3 107 108 109 110 ill 112 113 114 115 116 117 118 119 120 121 122 123 1 I VMCR 2 2 124 13 1914 125 126 127 128 129 130 131 132 133 134 135 Siemens & Furnas Control Products DAT';� ,, Siemens Energy & Automation, Inc. DRAWN BY, West Chicago, Illinois �;hj R; THIS PRINT IS THE CONFIDENTIAL PROPERTY OF SIEMENS CHKD BY- 6 FURNAS CONTROL PRODUCTS. IT IS NOT TO BE USED OR REPRODUCED IN ANY MANNER, NOR SUBMITTED TO ANY APPRD BY - OTHER PARTIES FOR EXAMINATION WITHOUT PRIOR APPROVAL OF SIEMENS 8 FURNAS CONTROL PRODUCTS. CODED TO PLANT LOCATION(S): EPD X aHIM luz�Mly'm[o 1 CPT 3 3 VMCR 4 4 23 19 24 .. T. _ t �i Ire -f LI0Y2SZ w6 I OF SINGLE L1 L2 L3 SEE NOTES N❑TES: A, TERMINALS AND WIRE PR❑VIDED ON 1211 30A, & 60A, CLASS "R" FUSIBLE DISC❑NNECT UNITS, 480V, & LARGER B. TERMINALS AND WIRE PR❑VIDED ON ALL 6" UNITS, C. TERMINALS AND WIRE PR❑VIDED ON ALL 12" UNITS WITH HHED BREAKERS (SEE NOTE "E"), D. TERMINALS AND WIRE PR❑VIDED ON ALL 12" BREAKERS WITH C-H CURRENT LIMITERS, E. ALL 70 AMP TERMINAL REQUIREMENTS IN 12" DUAL UNITS MUST USE LOAD BLOCK M❑UNTING BRACKET D67700083, F. WHEN USED WITH MOD DIAGRAMS HAVING CONTROL TERMINALS, MOUNT CONTROL TERMINALS ABOVE LOAD TERMINALS FOR 12" FEEDER OR ON BOTTOM PLATE FOR 12" DUALS, K) ADDED NOTE F D) ADD '6' OR ' IN THE NOTE A. G) ADD NOTE 'C' AND NOTE 'D' CN 38369 CN37597 9-1-99 N.A. CN 37993 VK 4-9-01 DMD 7/5/00 B) ADD CLASS R & 12' TO NOTE A. E) ADD NOTE 'B', CLARIFY NOTE 'A' H) REMOVED NOTE 'C' ADDED FDR TO DWG. NO. CN 37631 CN 38088 CN36513 SHERROD 11/25/96 DMD 11/09/99 TLC 09-14-00 C) UPDATED TITLE BLOCK F) ADD, '48OV. L LARGER' TO NOTE 'A' J) ADDED NOTES 'C' & 'E' CN 36626 CN 37689 CN 38191 MJT 5-15-97 DMD 02/25/00 TLC 11-30-00 CAD CAM DRAWING - D❑ NOT MANUALLY CHANGE L1 L2 L3 DUAL I I 1 2 CKT, BKR, CKT. BKR OR OR FU, DISC. FU, DISC. 1L1 1L2 1L31 12L1 2L2 2L3 Siemens Energy & Automation, Inc. DRAWN BY, SCALE, N/A TITLE, WK DATE- 1-20-92 West o, Chica IL 60185-1655 CHKD BY, TOLERANCE UNLESS g W K OTHERWISE SHOWN DWG. NO. NEXT ASS'Y APPRD BY- . XX OR . XXX t.015 X X X WK ANGULAR ±2" TOOL NO. TYPE OF TOOL This print is the confiderdal property of Siemens Energy & Automation, Inc It is rat to be used or reproduced F/N- x X xt sr K x In any manner, nor submitted to any other parties for examination without prior approval of Siemens Energy & STYLE, IK X X Ow xr Automation, Inc. X*3K NIX* CEDED TO PLANT LOCAT I ON(S) ; EPD X I OWA SEE NOTES 1L1 1L2 1L3 2L1 2L2 2L3 FEEDER WIRING DIAGRAM REV. D68500FDR K X;\STD\D68\500FDR—K.DW6 89B/95+ SHEET # I CLIMCO FEMSA