HomeMy WebLinkAboutP_110_Model_G_Automatic_Sprinklers_Cut Sheet_170622_v1Bulletin 110 Rev. WBulletin 110 Rev. W
Model G
Automatic Sprinklers
Spray Upright,
Spray Pendent
And Conventional
Product Description
The Reliable Model G Automatic Sprinkler utilizes the
center strut solder in compression principle of construc-
tion. The fusible alloy is captured in the cylinder of the
solder capsule by a stainless steel ball. When the fusible
alloy melts, the ball moves into the cylinder allowing the
cylinder to fall away from the sprinkler. When this happens,
the lever is released to spring free from the sprinkler so
that all of the operating parts clear from the waterway al-
lowing the deflector to distribute the discharging water.
Except for the parts in the cylinder as mentioned above,
the sprinkler components are made from copper based
alloys for maximum corrosion protection. Lead plated, wax
coated or wax over lead plated sprinklers are available for
specially severe environments. Chrome plated sprinklers
are available for decorative purposes.
All sprinklers are individually hydrostatically tested. All
sprinklers are identified as to their fusing point by mark-
ings that appear on several of the operating parts and by
an identifying color that appears on the frame.
Sprinkler Types
Standard Upright – This deflector configuration is normal-
ly used with exposed piping installations. Water is distrib-
uted laterally and downward in a wide pattern approximat-
ing a hemisphere which is completely and uniformly filled
with water in the form of small drops or spray.
Standard Pendent – This deflector configuration is nor-
mally used where the space above the piping is limited
or where a concealed piping installation is employed. The
discharge characteristics of the standard pendent are
virtually identical to the standard upright as described
above.
Large and Small Orifi ce —By varying the orifice size, a
large or small orifice sprinkler is created that will distrib-
ute as much as 40% more water or 65% less water than
the normal ½” (15mm) orifice sprinkler.
Conventional —This deflector configuration is used pri-
marily in those countries where the LPC installation rules
have precedence. The sprinkler is designed to distribute
a portion of its water discharge upward against the ceil-
ing with the balance downward. It may be installed in
either the upright or the pendent position. Sprinklers with
conventional deflectors are available with orifice sizes
corresponding to light, ordinary and extra–high hazard
installations.
Upright Pendent
Application and Installation
Standard sprinklers are used in fixed fire protection sys-
tems: Wet, Dry, Deluge or Preaction. Care must be exer-
cised that the orifice sizes, temperature ratings, deflector
styles and sprinkler spacings are in accordance with the
latest published standards of the National Fire Protection
Association or the approving authority having jurisdiction.
The sprinklers must be installed with the Reliable Model
D Sprinkler Wrench. Any other type of wrench may dam-
age the sprinkler.
The approvals or listings of Reliable Automatic Sprin-
klers by major approving organizations are shown in the
tabulated list provided on the back of this bulletin.
Small Orifice Upright Conventional
Reliable Automatic Sprinkler Co., Inc., 103 Fairview Park Drive, Elmsford, New York 10523
F17002957
RECEIVED
06/22/2017
aalexander
BUILDING DIVISION
By: cthomas
Date: 07/10/2017
FIRE DEPARTMENT
For Construction Subject to
Corrections Noted in Red
APPROVED
Reliable Automatic Sprinkler Co., Inc.(800) 431-1588 Sales Offices
(800) 848-6051 Sales Fax
(914) 829-2042 Corporate Offices
www.reliablesprinkler.com Internet Address
Manufactured by
Recycled
Paper
Revision lines indicate updated or new data.
EG. Printed in U.S.A. 04/15 P/N 9999970005
The equipment presented in this bulletin is to be installed in accordance with the latest published Standards of the National Fire Protection Association, Factory
Mutual Research Corporation, or other similar organizations and also with the provisions of governmental codes or ordinances whenever applicable.
Products manufactured and distributed by Reliable have been protecting life and property for over 90 years, and are installed and serviced by the most highly
qualified and reputable sprinkler contractors located throughout the United States, Canada and foreign countries.
Technical Data
Sprinkler Type “K” Factor Sprinkler
Height Approvals
Sprinkler Identifi cation
Number (SIN)
US Metric SSU SSP
Standard–Upright (SSU) and Pendent (SSP)
Deflectors Marked to Indicate Position
5.624.24
2.82
1.98
7.96
8.208.20
4.10
81.061.0
40.6
28.5
114.7
118.2118.2
59.1
2 7/8” (73 mm)2 7/8” (73 mm)
2 7/8” (73 mm)
2 7/8” (73 mm)
2 7/8” (73 mm)
2 15/16” (75 mm)75.4 mm
73 mm
1, 2, 3, 4, 5, 6, 71, 5
1, 2, 5
1, 5
1, 2, 5
1, 2, 53, 4, 5
3, 4, 5
R1025R1023
R1021
R1022
R1026
R1027R1027
R1024
R1015R1013
R1011
R1012
R1016
R1017R1017
R1014
1/2” (15 mm) Standard Orifice with 1/2” NPT (R1/2) Thread
7/16” (11 mm) Small Orifice with 1/2” NPT (R1/2) Thread
3/8” (10 mm) Small Orifice with 1/2” NPT (R1/2) Thread
5/16” (8 mm) Small Orifice with 1/2” NPT (R1/2) Thread
17/32” (20 mm) Large Orifice with 1/2” NPT (R1/2) Thread
17/32” (20 mm) Large Orifice with 3/4” NPT (R3/4)Thread
20 mm XHH with 20 mm Thread
10 mm XLH with 10 mm Thread
Conventional—Installed in Upright or Pendent Position
4.105.62
8.20
59.181.0
118.2
73 mm73 mm
75.4 mm
43, 4, 5, 7
3, 4
R1074R1075
R1077
10mm XLH with 10mm Thread15mm Standard Orifice with (R1/2) Thread
20mm XHH with (R3/4) Thread
Temperature Ratings
Classification
Sprinkler
Rating
Maximum
AmbientTemperature Frame (1)
Color
°F °C °F °C
Ordinary
Ordinary
IntermediateHigh
135
165
212286
57
74
100141
100
100
150225
38
38
66107
Black
Uncolored
WhiteBlue
(1) Frame color does not apply to painted or plated sprinklers
–Use sprinkler rating as identified on operating parts.
Finishes (1)
Standard Finishes
Bronze
Chrome White (2)
—All Temperature Ratings
—All Temperature Ratings—All Temperature Ratings
Only Frame and Deflector are Painted
Special Application Finishes
Bright Brass Plated
Black Plated
Polyester Coated (2)(4)
Lead PlatedWax-Coated (3)
Wax-Coated Over
Lead Plated (3)
—Only frame, deflector and cap are plated. 135°F (57°C), 165°F
(74°C), 212°F (100°C) Temp. Rating.
—Only frame, deflector and cap are plated. All Temp. Ratings.
—Only frame and deflector are coated.
—165°F (74°C), 212°F (100°C) and 286°F (141°C) Temp. Ratings.—165°F (74°C) Clear Wax, 212°F (100°C) Brown Wax.
—165°F (74°C) Clear Wax, 212°F (100°C) Brown Wax.
(1) Other colors and finishes are available. Consult factory for details.
(2) UL listed and NYC MEA Approved only.
(3) 212°F (100°C) brown wax may be used on 286°F (141°C) sprinklers when maximum ambient temperatures do not exceed 150°F
(66°C). UL Listed, FM Approved, NYC MEA 258-93-E.
(4) FM Approved for R1027 only.
Maintenance
Model G Sprinklers should be inspected and the sprinkler
system maintained in accordance with NFPA 25. Do not clean
Approval Organizations
1. Underwriters Laboratories, Inc. and UL
Certified for Canada (cULus).
2. Factory Mutual Research Corporation
3. Loss Prevention Council
4. Pleniere Assemblee
5. VdS Schadenverhütung GmbH
6. N.Y.C. BS&A No. 587–75–SA or
N.Y.C. MEA 258-93-E
7. EC Certificate: 1438-CPD-0054 (R1015)
1438-CPD-0053 (R1025)
1438-CPD-0052 (R1075)
1438-CPD-0056 (R1077)
Ordering Information
Specify
1. Model G
2. Deflector
• Upright
• Pendent
• Conventional
3. Nominal Orifice
4. Inlet Thread
5. Temperature Rating
6. Finish
sprinklers with soap and water, ammonia or any other clean-
ing fluids. Remove any sprinkler that has been painted (other
than factory applied) or damaged in any way. A stock of spare
sprinklers should be maintained to allow quick replacement of
damaged or operated sprinklers. Prior to installation, sprinklers
should be maintained in the original cartons and packaging un-
til used to minimize the potential for damage to sprinklers that
would cause improper operation or non-operation. Use only the
Model D Sprinkler Wrench for sprinkler removal and installation.
Any other type of wrench may damage the sprinkler.