CITY OF RENTON
DEPARTMENT OF PUBLIC WORKS
AS -BUILD
-9 2) mir�_
0+ 00
COREY TYPE FIRE HYDRANT EOUAL TO IOWA F-5110 AS SHOWN,
PACIFIC STATES CAST IRON PIPE CO. MODEL 2, OR APPROVED
EQUAL 6" MECHANICAL 101NT INLET WITH LUGS. 5-1/4" MAIN
VALVE OPENING. TWO 2-I/2- HOSE CONNECTIONS NATIONAL
STANDARD THREADS, G" PUMPER CONNECTION CITY
Of SF -A TTLE
THREADS. 1-1/2' PENTAGON OPERATING NU(, FIRE HYDRANT
TO BE PAINTED WITH TWO COATS OF PAINT, PRESERVATIVE
PAINT I.. 6B-114, INTERNATIONAL YELLOW OR APPROVED
00 I le- t. EOUAL. PUMPER CONNECTION TO FACE ROADWAY
0 �u- HYDRANT AS5EM9LY FOR 4-1/2' TRENCH.
" 3 — BLUE TRAFFIC REFLECTOR
/ SEE STANOARO DETAIL
-/ SHEET
TWO-PIECE CAST IRON VALVE BOX,
EQUAL To RICH VALVE CO.,
STANDARD 8" TOP SECTION WITH
j REGULAR BASE SECTION. LENGTH
TO FIT,
CONCRETE BLOCKING -
--CONCRETE BLOCKING
UL
--. �
Rli �
j
I 0
`-CAST IRON TEE, 'NITH
T } 5" FLANGE' SIDE OU TI-ET
6_ GATE VALVE IFL. MA
•'� EQUAL r0 MVELLER CO. A-2360-16
6" DUCTILE IRON PIPE, CLASS 52,
CEMENT LINED, LENGTH TO FIT
TWO 3/[- STEEL TIE RODS,
15" .. 8" . C- MINIMUM LENGTH TO FIT. SEE STU DETAIL
:OH:FcTE BLOCK FOR TIE RODS.
7 CU. FT. MINIMUM WASHED
GRAVEL PASSING 1-1/2' AND
RETAINED ON 1/4. MESH FOR
DRAIN
FIRE HYDRANT ASSEMBLY
FIRE HYDRANT ASSEMBLY DETAIL DATE SHEET X.XX X.XX
N
NOTE: MAINTAIN MINIMUM 5' SEPERATION
BETWEEN STORM AND SANITARY SEWER
W 0
UJ W J
W � 0W Z
LAJ a BUILDING / //�- F-
1 �� N\ � 0
/ / U X � ILL t_
LLJ W I__ CV X IW_ M FW-
X- _Q Q
1 1/2" POLYBUTYLENE o N N a- 3:
Ln
cV 3 Q
i TUBING f- I \` 2" POLYBUTYLENE
SS BETWEEN MANHOLES - - s°ss �s� _ M 9 C ANC PAD � � � TUBING
ANHOI ES -----_ �; -
x DOMESTIC
CATCH BASIN
RIM ELEV = 26,40'
1 E. 12"(N) = 22.90'
I E. 12"(E) = 22.70'
SHUT-OFF
rl1 C
BUILOfNG VALVE -DRAIN & TEST CONNECTION
2" MAIN CONTROL
VALVE !�� DOUBLE CHECK VALVE
1 1 2" WATER
SA SEW MH h / SPRINKLER CONTROL VALVE (OPTION- REFERENCE 3-1.1 EXCEPTION No 1 )
_v..: y S S -
SERVICE &METER
RiMi ELEV.= 27.19' xti' ' q 1 16 Z� TYPE 'K' SOFT COPPER TUBING
I.E. 18"= 23 54'
ALL � fgCT xt1 \ (BY BETYN) STALLED
1 r 5 EX. 6" C.I-
C C i / / 16 WATER MAIN
NOTE:
BUILDING * SUPPLY CONNECTION TO N.F.P,A.-13R
SPRINKLER SYSTEM TO BE DESIGNED
J
o �.. /
BY SPRINKLER SYSTEM DESIGNER &
APPROVED BY RENTON FIRE
' � � � � � � C� ;-:• I f. . PREVENTION DEPT.
4 — PLEX
TJ FIN. FL
BUILDING
II I , r
x
_J
777711
* y6fARAI& WATI15K mercit, 4 VCVA Itftaiuo fog, ILANOWpe. 1Qt;eM%W &Ysre" .
--- - - <
i a CHECKED FOR COMPLIANCE
Q - �� - ': x :L _----- - U ING
-�ANDARDS
PH IL26 97
- - - - 1 - ,•
yNi WALK -- DOMESTIC SYSTEM Dated 4 i�
SPRINKLER SYSTEM ti19 Datef — �!
_L _ _ --- 6- V _ __ _ , +zz ro _.-_..-.--� �� . x
x
3'x3' GARBAGE 'sy
. 6, vERr � %p '---�� I-" 2joy �`,a ENCLOSURE Date
c
WATER NOTES
------------
_ 24'sD { p 1 o!h O '-� �. ��k�' .
' 2 xT - WAA 3+-3f►,_ 21. 0 'a �gt,� _ +2 .4� +2' S?
TER Mf TER 2�-5 �Y ���
r
CATCH BASIN #2
Z
RIM EL.=27.06 I tiSTORM DRAIN MH _ = _ _ A
I.E. 8"(SE)=24 66 RIM EL =26 85
1 , All work materials shall be in conformance with the stand-
ards and specifications of the City of Renton Utility Depart-
ment and the latest edition of the WSDOT/APWA Standards and
Specifications, as approved by the City of Renton. A set of
approved plans shall be kept on site at all times during
construction
2- The hours of work in the street right-of-way shall be limited
to 8:30 AM to 3:30 PM on weekdays unless otherwise approved
in writing by the Department of Public Works at 235-2635.
All street closures, partial or full, shall be approved by
the Department of Public Works 24 hours in advance, The
Police Department, Fire Department, and 911 shall be notified
24 hours in advance
1 All locations of existing utilities shown are approximate and
it shall be the contractor's responsibility to verify the
true and correct location so as to uvoid damage or disturb-
ance For utility locate coil 48-Hour Locators, 1-800-424-
5555
4. All water main pipe to be cement lined ductile iron pipe
conforming to AWWA C110 and C111 or latest revision, thick-
ness Class 52. Cement mortar lining and seal coating shall
conform to AWWA C104 or latest revision, Pipe joints to be
push -on or mechanical joint. Bedding to be class C. All
ductile iron pipe installed South of Sunset Blvd. (Empire
Way, SR 900) and West of SR 167 (East Valley Freeway) or in
soils of high resistivity shall be polyethylene wrapped per
ANSI/AWWA C105-77 Standards.
5. Cost iron and ductile iron fittings shall be cement lined,
pressure rated as noted on plans, and in accordance with
ANSI/AWWA C110/A21.10-82. Cement lining shall be in accord -
once with ANSI/AWWA C104/A21 4-85 If fittings are 3 inches
to 12 inches in diameter and hove mechanical joints, the
fittings shall be in accordance with either ANSI/AWWA
C110/A21-10-82 or ANSI/AWWA C153/A21.53-84 3 inch to 12
inch diameter fittings which have mechanical joints and/or
flanged joints shall be in accordance with ANSI/AWWA
C110/A21.10-82 or a combination of ANSI/AWWA C110/A21.10.82
and ANSI/AWWA C153/A21.53-84 such that the portion of the
fitting with a mechanical joint(s) may be in accordance with
ANSI/AWWA C153/A21.53-84 and that portion of the fitting with
flanged joint(s) shall be in accordance with ANSI/AWWA
C11O/A21.10-82- Acceptance testing in accordance with sec-
tion 53-5.3 of ANSI/AWWA C153/A21.53-84 or with section 10-
4.3 of ANSI/AWWA C110/A21-10-82 shall be obtained by the
contractor and transmitted to the owner_
6. Gate valves shall conform to AWWA C500 and shall be iron
body, bronzed -mounted, double disc with bronze wedging device
and 0-ring stuffing box. Valves shall be designed for a
minimum water operating pressure of 200 PSI_ Gate valves
shall be Clow List 14, Mueller Company NO. A2380, or M&H
All valves 12" in diameter and larger, shall be installed in
a vault- See water standard detail for 12' Gave Valve Assem-
bly Vault and 1" Bypass Installation.
7. Fire hydrants shall be Corey type (opening with pressure)
conforming to AWWA C-504-80 with a 6 inch inlet and a M_V.O.
of 5 inches, two 2-1 inch hose nozzles with national standard
7 inch, 60 degrees V. threads, O.D. thread 4.875 and root
diameter 4.6263, 1-1 inch pentagon operating nut opened by
turning counter clockwise (left).
8. All water main 10 inches and smaller to maintain a minimum
cover of 36 inches below finish grade. All water main 12
inches and larger shall be at a minimum of 48 inches below
finish grade Where utility conflicts occur, water mains are
to be lowered to clear-
9 All water mains six (6) inches in diameter and larger shall
be cleaned with pipe cleaning "PIGS" prior to disinfection.
The "Poly Pigs" shall be Girard Industries Aqua Swab -AS or
approved equal, 2 Ib/cu ft density foam with 90A durometer
urethane rubber coating on the rear of "PIG" only. "PIGS"
shall be cylinder shaped with bullet nose or square end. The
City will assist the contractor who will perform the cleaning
operation.
9a All water mains and services shall be pressure tested to a
minimum of 200 PSI or 150 PSI over operating pressure, in
accordance with the specifications of the City of Renton and
the Washington State Health Department. All pressure testing
shall be done in the presence of a representative of the City
of Renton.
9b All water mains and services shall be disinfected by the
injection of a 50 ppm (Minimum concentration) chlorine/water
solution, Dry Calcium Hypochlorite shall NOT be placed in
the pipe as laid Chlorine shall be metered/injected in
accordance with Section 7-11.3(12)E or 7-11 3(12)F of the
Standard Specifications referenced in 1 above.
10_ A preconstruction conference is required prior to any con-
struction_ A minimum of 3 (three) working days notice is
required for scheduling. Prior to scheduling the precon a
permit information sheet must be supplied to the Utility
Engineer's Office. Twenty-four hour notice will be required
prior to starting new construction.
I.E. 8"(NW)=2�,61 =
1.E. 24"(W)=19 69 - _ E. 24"(N)=19 56
Bt T)?XeTT
11. It shall be the contractor's responsibility to secure all
necessary permits prior to starting construction.
12. Installation of corporate stops, water services, lines and
meters shall not be done until all service agreements, meter
applications, construction permits, and payment of fees have
been made to the City of Renton.
13 All connection to existing mains to be accomplished by the
City of Renton, except wet tops which may be made by approved
wet top contractors with prior approval of, from the Depart-
ment of Public Works. All necessary excavation and materials
to be supplied by the contractor and be on -site prior to City
notifications-
14. Inspection will be accomplished by a representative of the
City of Renton. It shall be the contractor's responsibility
to notify the Utility Department 24 hours in advance of
backfilling all construction. The contractor as well as the
Engineers shall keep as -built drawings.
15 Contractor to provide plugs and temporary blow -off assemblies
for testing and purity acceptance prior to final tie-in
16. All joint restraint systems (shackle rods, nuts, bolti;, etc-)
shall be as manufactured by the Star Manufacturing Company of
Columbus Ohio or equal approved in writing by the Department
of Public Works.
17 Asphalt and concrete street paving shall be sawcut to a
minimum depth of two inches Oil mat streets may be space
cut. All surface concrete, pavement, sidewalks, curb, gut-
ters, and driveway approaches shall be sawcut to a minimum
depth of two inches or removed to an existing expansion
joint.
18 A temporary cold mix asphalt patch shall be placed on the day
of initial excavation with a permanent, sealed patch to be
placed, to City of Renton policy, within ten days. Call for
subgrode inspection prior to placement of final patch.
Trenches will not be left open over night without prior
written approval of the Inspector.
19. For City projects such as telemetry conduit, the PVC pipe
used shall be schedule 40 in unimproved areas and schedule 80
under improved areas. Ali chemical process lines shall be
schedule 80 PVC pipe.
re
i
r'
NOTE:
CUT -IN BY CITY OF RENTON
REVISED PER CITY OF RENTON
REVISED PER CITY OF RENTON
'_D PER CITY OF RENTON
NO. REVISION
,G
4
r�
STA. 3+46.9, 19' LT,
1-6"x6"x6" TEE (FLxFL)
1-6' G.V (FLxMJ)
1-6' G.V. (FLxFL)
1-6' 90- BEND (FLxMJ)
1-STD- H YD. ASSY
(LOCATED IN PLANTER)
PER CITY OF RENTON
1-6' ADAPTOR (FLxMJ)
2-C._ SOLID SLEEVES (RO-MAC ADAPTORS)
2-CONC, BLOCKINGS
MERIDIAN
MERIDIAN = ASSUMED
BASIS OF BEARING:
MONUMENTED CENTER LINE OF
WELLS AVE. N_ (WELLS ST)
DATUM = CITY OF RENTON
BENCH MARK:
CHISELED SQUARE IN BACK OF WALK
AT THE INTERSECTION OF THE S-W.
CORNER WILLIAMS AVE. N. AND N.
15th STREET
ELEVATION = 27.89'
LEGAL DESCRIPTION_
LOT 20, BLOCK 15, RENTON FARM PLAT #4, AS PER PLAT RECORDED IN
VOLUME 13 OF PLATS, PAGE 90, RECORDS OF KING COUNTY, WASHINGTON.
LEGEND
RECOMMENDED
FO APPR AL
BY
-SAN. SEWER MANHOLE Fl E PREV TION
- WATER METER RECOMMENDED
-STORM MAN HOLE FOR APPROVAL
-STORM CATCH BASIN BY AfttXkL/ 6—
WATER UTILITry_10_4r
-POWER/UTILITY POLE
r.` -SPOT ELEVATION RECOMMENDEDFOR APPROVAL
50- SET 1 /2" DIA. REBAR WITH PLASTIC SURVEY
CAP LICENSE No's- 9634/10356 BY A// N -�
PI -AN REV III W S/IF/91
_ -FENCE
if
TO WNSF,ND — CHASTAIN & ASSOC, INC.
K K MILD 5- 3- 91 SURVEYORS - ENGINEERS
DEVELOPMENT CONSULTANTS
KK MILE, 3-15-91
DGL V L D 2-18-91 409 SOUTH 3rd AVENUE
KENT, WASHINGTON 98C32
BY I APPR DATE (206) 854-2043
FIFTY OF'
DEPARTMENT OF
REN`r(DN
PUBLIC WORKS
t`^
WA TER PLA Ar
B URNETT AVE. N. LOT 20, BLK. 15
DESIGNED_ MD
DATE: 2/ 1 8/91 ) FILE NAME: 90090
DRAWN: D G L
SCALE. 1" - 20' HORZ_ FIELD Baox PAGE
CHECKED: MD
APPROVED-
SHEET 1 0F.- I