GENERAL WATER NOTES:
1. All work materials shall be in conformance with the
standards and specification of the City of Renton Utility
Department and the latest edition of the WSDOT/APWA Standards and
Specifications. A set of approved plans shall be kept on site at
all times during construction.
2. The hours of work in the street right-of-way shall be
limited to 8:30AM to 3:30 PM on weekdays unless otherwise
approved in writing by the Department of Public Works at 235-
2635. All street closures, partial or full, shall be approved by
the Department of Public Works 24 hours in advance. The Police
Department, Fire DEpartment and 911 shall be notified 24 hours in
advance.
3. All locations of existing utilities shown are approximate
and it shall be the contractor's responsibility to verify the
true and correct location so as to avoid damage or disturbance.
For utility locate call 48-Hour Locators. 1-800-424-5555.
4. All water main pipe to be cement lined ductile iron pipe
conforming to AWWA C110 and C111 or latest revision, thickness,
Class 52. Cement mortar lining and seal coating shall conform to
AWWA C104 or latest revision. Pipe joints to be push -on or
mechanical joint. Bedding to be class C. All ductile iron pipe
installed South of Sunset Blvd. (Empire Way, SR 900) and West of
SR 167 (East Valley Freeway) or in soils of high resistivity
shall be polyethylene wrapped per ANSI/AWWA C105-77 Standards.
5. Cast iron and ductile iron fittings shall be cement lined,
pressure rated as noted on plans, and in accordance with
ANSI/AWWA C110-/A21.10-82. Cement lining shall be in accordance
with ANSI/AWWA C110/A21.10-82 or ANSI/AWWA C153/A21.53-84. 3-
inch to 12-inch diameter fittings which have mechanical joints
and/or flanged joints shall be in accordance with ANSI/AWWA
C110/A21.10.82 or a combination of ANSI/AWWA C110/A21.10.82 and
ANSI/AWWA C153/A21.53-84 such that the portion of the fitting
with a mechanical joint(s) may be in accordance with
ANSI/AWWAC153/A21.53-84 and that portion of the fitting with
flanged joint(s) shall be in accordance with ANSI/AWWA
C110/A21.10-82.Acceptance testing in accordance with section 53-
5.3 of ANSI/AWWA C153/A21.53-84 or with section 10-4.3 of
ANSI/AWWA C1120/A21.10-82 shall be obtained by the contractor and
transmitted to the owner.
6. Gate valves shall conform to AWWA C500 and shall be iron
body, bronzed -mounted, double disc with bronze wedging device and
0-ring stuffing box. Valves shall be designed for a minimum
water operating pressure of 200 PSI. Gate valves shall be Clow
List 14, Mueller Company No. A2380, or M&H. All valves 12" in
diameter and larger, shall be installed in a vault. See water
standard detail for 12" Gate Assembly Vault and 1" Bypass
Installation.
7. Fire hydrants shall be Corey type (opening with the
pressure) conforming to AWWA C-504-80 with a 6 inch inlet and a
M.V.O. of 5 inches, two 2 1 /2 inch hose nozzles with national
standard 7 inch, 60 degrees V. threads, O.D. thread 4.875 and
root diameter 4.6263, 1 1/4 inch pentagon operating nut opened by
turning counter clockwise (left).
8. All water main 10 inches and smaller to maintain a minimum
cover of 35 inches below finish grade. All water main 12 inches
and larger shall be at a minimum of 48 inches below finish grade.
Where utility conflicts occur, water mains are to be lowered to
clear.
9. All water mains six (6) inches in diameter and larger shall
be cleaned with pipe cleaning "PIGS" prior to disinfection. The
"Poly Pigs" shall be Girard Industries Aqua Swab -AS or approved
equal, 2 Ib./cu ft density foam with 90A durometer urethane
rubber coating on the rear of "PIG" only. "PIGS" shall be
cylinder shaped with bullet nose or square end.
ate# 'the contracor wh* will perform the cleaning operation.
UNDEL 011'5 SUPERVISION
9a. All water mains and services shall be pressure tested to a
minimum of 200 PSI or 150 PSI over operating pressure, in
accordance with the specifications of the City of Renton and the
Washington State Health Department. All pressure testing shall
be done in the presence of a representative of the City of
Renton.
9b. All water mains and services shall be disinfected by the
injection of a 50 ppm (Minimum concentration)chlorine/water
solution. Dry Calcium Hypochlorite shall NOT be placed in the
pipe as laid. Chlorine shall be metered/injected in accordance
with Section 7-11.3(12)E or 7-11.3(12)F of the Standard
Specification referenced in #1 above.
10. A preconstruction conference is required prior to any
construction/. A minimum of three (3) working days notice is
required for scheduling. Prior to scheduling the precon a permit
information sheet must be supplied to the Utility Engineer's
Office. Twenty-four hour notice will be required prior to
starting new construction.
11. It shall be the contractor's responsibility to secure all
necessary permits prior to starting construction.
12. Installation of corporate stops, water services, lines and
meters shall not be done until all service agreements, meter
applications, construction permits, and payment of fees have been
made to the City of Renton.
13. All connection to existing mains to be accomplished by the
City of Renton, except wet taps which may be made by approved wet
tap contractors with prior approval from the Department of Public
Works. All necessary excavation and materials to be supplied by
the contractor and be on -site prior to City notifications.
14. Inspection will be accomplished by a representative of the
City of Renton. It shall be the contractor's responsibility to
notify the Utility Department 24 hours in advance of backfilling
all construction. The contractor as well as the Engineers shall
keep as -built drawings.
Q I TEMP. BLOCKING
& BLOWOFF ASSYS
0
z
Q
a'
w
�I
Q
SOLID SLEEVE
0
NEW DIP
6AS4 IPON
10" CROSS (MJ x FL) VERTICAL 10" TAPPING TEE & VALVE AFTER PRESSURE AND PURITY
2-BLIND FLANGES ONE TAPPED 2" 2-10" PLUG WITH TEMP. CONNECT TO TAPPING VALVE
2" PLUG BLOWOFF ASSY W/NIPPLES
BLOCK AS REQUIRED SOLID SLEEVE (LP)
BEFORE AFTER
CONNECTION TO EXISTING WATERLINE
N.T.S.
15.Contractor to provide plugs and temporary blow -off assemblies
for testing and purity acceptance prior to final tie-in.
16. All joint restraint systems (shackle rods, nuts. bolts,
etc.) shall be as manufactured by the Star Manufacturing Company
of Columbus, Ohio or equal approved in writing by the Department
of Public Works.
17. Asphalt and concrete street paving shall be sawcut to a
minimum depth of two inches. Oil mat streets may be spade cut.
All surface concrete, pavement, sidewalks, curb, gutters, and
driveway approaches shall be sawcut to a minimum depth of two
inches or removed to an existing expansion joint.
18. A temporary cold mix asphalt patch shall be placed on the
day of initial excavation with a permanent sealed patch to be
placed, to City of Renton policy, within ten days. Call for
subgrade inspection prior to placement of final patch. Trenched
will not be left open over night without prior written approval
of the Inspector.
19. For City projects such as telemetry conduit, the PVC pipe
used shall be schedule 40 in unimproved areas and schedule 80
under improved areas. All chemical process lines shall be
schedule 80 PVC pipe.
APPROVAL
DATE
s 1--�,I
JOB NO.
t,�?"- .,; REV.
C*.4t-�- •
tt P, S 13 0 ! CT
t
6" MIN. DRAIN TO
DAYLIGHT OR STORM
DRAIN SYSTEM.
PRECAST CONCRETE VAULT WITH 3-3"0"
HINGED STEEL PLATE COVERS.
DIMENSIONS 5'8"x11'-2"x7-2" EQUAL TO
RENTON CONCRETE PRODUCTS, INC.
THE BY-PASS ASSEMBLY SHALL BE -
INCLUDED AS PART OF THE DETECTOR
DOUBLE CHECK VALVE ASSEMBLY.
11'-2"
-W
ND, FL.
GRAVEL UNDERVAULTLADDOR FOR ACCESS
END _VIEW
4%4"x6" BULL HEAL, TEE, FL.
"\� - m
18" FOR 10" ASSY-
17.5" FOR 8" ASSY
18.5" FOR 6" ASSY
WLWW_111VrJM
�• �� • � ;1 w 1, �1 ����I-I� I mil, �!
I �
PIPE WITH COLLAR 18" FROM
10", 8" OR 6" FL. x P.E.
P.E. d d
10" - 3'-0" LONG
8" - 3'-6" LONG
6" - 4'-6" LONG CONCRETE
BLOCKING
CONCRETE SUPPORT PADS
UNDER CHECK VALVE.
L_ -Z J__
ALL DETECTOR DOUBLE CHECK-,
VALVE ASSEMBLIES SALL
INCLUDE RESILIENT SEATED
SHUTOFF VALVES AND TEST
COCKS, AND BE APPROVED
CROSS -CONNECTION CONTROLL
ASSEMBLIES PER D.S.H.S.
APPROVED LIST.
PLAN
4" ADAPTOR, FL x SCREWED
ONE EACH SIDE
4"x2.5" FIRE DEPARTMENT DOUBLE
��_�CONNECTION FOR STAND PIPE WITH
BREAKABLE CAST IRON HOSE CAPS.
ONE EACH SIDE EQUAL TO GRINNEL
% FIG. 1682 WITH NOSE CAPS FIG. 1333
\ 6" PIPE FLxFL
1-2'-0" LONG
6" SWING TYPE GRAVITY OPERATED
--� CHECK VALVE, FL. EQUAL TO
MUELLER CO, A-2600-6
6" PIPE FL x FL
3'-0"
6" AND 8" ASSEMBLY
d 6" SHORT RADIUS 90' BEND FL
•. 10" ASSEMBLY
10118"x6" REDUCING 90' BEND, FL
6" ASSY
6" TEE FL
",0Z+ + DEADMAN BLOCK
T M I A REQUIRED
0
+. 10" ASSEMBLY
10"x10"x8" TEE FL.
8" ASSEMBLY
DOUBLE CHECK VALVE ASSY 8"x8"x6" TEE, FL.
INCLUDES TWO RESILIENT 10", 8", OR 6" GATE VALVE
SEATED SHUTOFF VALVES. FLxMJ, WITH INDICATOR POST.
INDICATOR POST VALVE SAME
SIZE AS DOUBLE CHECK VALVE
(MUELLER CO., OR EQUAL).
long 8", OR 6" DUCTILE IRON
CLASS 52 NIPPLE PIPE. CEMENT long 8", OR 6' FLANGED
LINED, LENGTH TO FIT. COUPLING ADAPTOR EQUAL TO
ROCKWELL INTERNATIONAL 912.
NOTES:
1. LOCATE VAULT IN PLANTING AREA NOT IN PAVING.
2. 4" AND LARGER BENDS AND TEES TO BE CAST IRON
CEMENT LINED.
3. TEMPORARY SUPPORT SHALL BE PROVIDED UNDER
VALVES AT THE TIME OF INSTALLATION TO CENTER
THE PIPE IN VAULT OPENING. AFTER COMPLETE
INSTALLATION REMOVE THE TEMPORARY SUPPORT
AND INSTALL CONCRETE SUPPORT PAD.
4. 4" AND LARGER PIPE TO BE DUCTILE IRON CEMENT
LINED CLASS 52 PIPE, EQUAL TO THOSE SUPPLIED
BY PACIFIC WATER WORKS SUPPLY COMPANY INC.
i
9E60MMENDED �OQ A?NoVAL
AmouL LSAvurL
WA 611 U(itili ENUIrIEC�Qi►J6�
long 8" OR 6" DETECTOR DOUBLE CHECK VALVE ASSEMBLY
�av 6c� � �.�� ,,,�,,,6 , 6 STANDPIPE WITH FOUR 2-1 /2 NOZZLE
�Alw
WSSy Naz A-S 13 w CROSS CONNECTION - BACKFLOW PROTECTION ASSEMBLY
AT R (5a Cifl Of R606H WA1E2
S(ANDARO T)6TAis) RENTON FILE NO. SA-J49-90
BY ICHECKEDI DATE
PREPARED BY
Balma & Holmberg Inc.
ENGINEERS & SURVEYORS
1505 N.W. GMMAN BLVD., SUITE 7 ISSAQUAH, WASHINGTON 98027 (206) 392 - 0250
DESIGNED BY DRAWN BY CHECKED BY
JAT I SLL
CRAIG JOHNSON
P.O. BOX 66285 SEATTLE, WA 9,-1E6,
PROJECT
RENTON RETAIL BUILDING
SHEET CONTENT
DETAIL SHEET •
SHEET
5
OF
5