HomeMy WebLinkAboutWWP2701770.1NOTES AND SPECIFICATIONS FOR STORM DRAINS AND SANITARY SEWERS 1. ALL CONSTRUCTION SHALL BE IN ACCORDANCE WITH "STANDARD SPECIFICATIONS FOR MUNICIPAL PUBLIC WORKS CONSTRUCTION" PREPARED BY WASHINGTON STATE CHAPTER AMERICAN PUBLIC WORKS ASSOCIATION, 1981 (APWA) AND CITY OF RENTON STANDARDS. 2. CONTRACTOR SHALL PROVIDE AND MAINTAIN TEMPORARY SEDIMENTATION/COLLECTION FACILITIES TO INSURE THAT SEDIMENT LADEN WATER DOES NOT ENTER NATURAL DRAINAGE SYSTEM. THESE FACILITIES MUST BE IN OPERATION PRIOR TO CLEARING AND CONSTRUCTION AND MUST BE MAINTAINED UNTIL CONSTRUCTION AND LANDSCAPING ARE COMPLETED AND THE POTENTIAL FOR ON -SITE EROSION HAS PASSED. 3. ALL LOCATIONS OF EXISTING UTILITIES SHOWN ARE APPROXIMATE AND IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY TO VERIFY THE TRUE AND CORRECT LOCATION SO AS TO AVOID DAMAGE OR DISTURBANCE. 4. A PRECONSTRUCTION CONFERENCE AND A 24 HOUR NOTICE SHALL BE REQUIRED PRIOR TO STARTING NEW CONSTRUCTION. IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY TO SECURE ALL NECESSARY PERMITS PRIOR TO STARTING CONSTRUCTION. (INSPECTION WILL BE ACCOMPLISHED BY A REPRESENTATIVE OF THE CITY OF RENTON). IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY TO NOTIFY THE UTILITY DEPARTMENT 24 HOURS IN ADVANCE OF BACKFILLING ALL CONSTRUCTION. 5. STORM DRAIN PIPE SHALL BE CONCRETE, RUBBER GASKETED ASTM C14, CL.2 OR ASTM C-76-11 OR 16 GAUGE GALVANIZED STEEL TREATMENT 1 ASPHALT COATED OR 16 GAUGE ALUMINUM HELICAL CORRUGATED METAL PIPE WITH WATER TIGHT CONNECTING BANDS. ALUMINIZED STEEL NOT ALLOWED. 6. BEDDING FOR STORM DRAIN PIPE SHALL BE PER APWA STANDAR PLAN NO. 62. 7. TRENCH WIDTH IN BEDDING ZONE SHALL BE 1-1/2 TIMES THE PI DIAMETER PLUS 18 INCHES. 8. TYPE 1-C CATCH BASINS SHALL BE PER APWA STANDARD PLAN NO. 52, WITH APWA STANDARD PLAN NO. 49 FRAME AND GRATE AND TYPE 60 OUTLET TRAP. TYFEZ40 4 S4 INCH CATCH BASINS SHALL BE APWP STANDARD PLAN NO. 55, WITH APWA STANDARD PLAN NO. 49 FRAME AND GRATE AND TYPE 60 OUTLET TRAP. 7 PR-- g- 54' CA7tA BA5/mot S NA[.L HAiaE APWo& ST;& IN~O PLAAJ Alb. roOA. OUT[:ET TiQAP, 9. CONTRACTOR IS SOLELY RESPONSIBLE FOR THE MEANS, METHODS ANE SEQUENCES OF CONSTRUCTION AND FOR THE SAFETY OF WORKERS ANE OTHERS ON THE CONSTRUCTION SITE. 10. SANITARY SEWER PIPE SHALL BE CONCRETE RUBBER GASKETED AS C14-CL.3 OR ASTM C76-11 OR POLYVINYL CHLORIDE (PVC) RUBB GASKETED ASTM D 3034, SDR 35. 11. BACKFILL SHALL BE PLACED EQUALLY ON BOTH SIDES OF THE PIPE IN LAYERS WITH A LOOSE AVERAGE DEPTH OF 6 INCHES, MAXIMUM DEPTH OF 8 INCHES, THOROUGHLY TAMPING EACH LAYER TO 95 PERCENT OF MAXIMUM DENSITY. THESE COMPACTED LAYERS MUST EXTEND FOR ONE PIPE DIAMETER ON EACH SIDE OF THE PIPE OR TO THE SIDE OF THE TRENCH. MATERIALS TO COMPLETE THE FILL OVER PIPE SHALL BE THE SAME AS DESCRIBED. 12. ALL ROOF DOWNSPOUTS SHALL BE TIGHTLINED TO THE STORM DRAIN SYSTEM. 13. SANITARY SEWER MANHOLES SHALL CONFORM TO APWA SPECIFICATIONS, SECTION 63. MANHOLES SHALL BE APWA STANDARD PLAN NO. 34. 14. IT SHALL BE THE RESPONSIBILITY OFF THE CONTRACTOR TO OBTAIN STREET USE AND ANY OTHER RELATED PERMITS PRIOR TO ANY CONSTRUCTION. 15. PLANS APPROVED BY THE DIRECTOR OF PUBLIC WORKS SHALL TAKE PRECEDENCE OVER ALL OTHER PLANS. 16. THE STORM DRAINAGE SYSTEM AND SANITARY SEWER SHALL BE CONSTRUCTED ACCORDING TO THE APPROVED PLANS WHICH ARE ON FILE AT THE CITY OF RENTON DEPARTMENT OF PUBLIC WORKS. ANY DEVIATION FROM THE APPROVED PLANS WILL REQUIRE WRITTEN APPROVAL FROM THE CITY OF RENTON DEPARTMENT OF PUBLIC WORKS. 17. A COPY OF THESE APPROVED '-'LANS MUST BE ON THE JOB SITE WHENEVER CONSTRUCTION IS IN PROGRESS. 18. ALL CATCH BASIN GRATES SHALL BE DEPRESSED 0.10 FEET BELOW PAVEMENT LEVEL. 19. OPEN CUT ROAD CROSSINGS FC2 UTILITY TRENCHES ON EXISTING TRAVELED ROADWAY SHALL BE BAC:KFILLED ONLY WITH PEA GRAVEL OR 5/8 MINUS CRUSHED ROCK AND MECHANICALLY COMPACTED. CUTS INTO THE EXISTING ASPHALT SHALL BE NEATLINE CUT WITH SAW OR JACKHAMMER IN A CONTINUOUS LINE. A TEMPORARY MIX PATCH MUST BE PLACED IMMEDIATELY AFTER BACKFILL AND COMPACTION. A PERMANENT HOT MIX PATCH SHALL BE PLACED WITHIN 30 DAYS AND SHALL BE THE THICKNESS OF THE ORIGINAL ASPHALT OR TWO INCHES WHICHEVER IS GREATER. THIS DOCUMENT: HAS BEEN REVIEWED BY .GOVERNMENTAL. AGENCIES AND IS APPROVED FOR CONSTRUCTION. X L S I I hJ / " s - 5 . c� lArV. 5.45 ch5Lo - 4r PRIOR- 7�0 CDNSTRc 7_1o" APPROVED FOR CONSTRUCTION CIT OF RENTON DEFT OF60USLIC WORKS DAVIIE CALL 48 HOURS BEFORE YOU DIG 1-800-424-5555 THE CONTRACTOR SHALL PROVIDE THE CITY OF RENTON WITH AN AS -BUILT DRAWING OF THE STORM DRAINAGE SYSTEM, THE SANITARY SEWER SYSTEM AND THE SITE GRADING WHICH HAS BEEN STAMPED AND SIGNED BY A LICENSED PROFESSIONAL ENGINEER. NOTE= LOCATE ONSITE SIoEWe&L_ _ YEP-_ dT-C" 1077 0 0 • U o 00 ZQ m �r �0 C7) w W Z' rr T� V � z T .i. Q C- v c� od QLU W Wz Oz W Q J � Q � U O z_ o 0 N W W 0 z V DRAWN Ell PG z O W Ln � 3 Q I Lo 0 V Ld z Q 0 > z Li CHECKED By kSC)AL DATE 40 12 31 85 85213 SHFf ')F