HomeMy WebLinkAboutWTR2701821.8FIRE HYDRANT
GUARD POST, 9" ROUND REINFORCED CONCRETE - GUARD POST
6'-0" LONG, EQUAL TO RENTON CONCRETE D
PRODUCTS TO BE INSTALL WHERE DIRECTED.
/ O PAINT WITH TWO COATS PRE 5E RVATIVE PAINT -
N0. 43-114, INTERNATIONAL OR APPROVED
12" \ EQUAL
IFIRE HYDRANT
6 CONCRETE
i _ NOTE:
I p _,MINIMUM AREA OF LEVEL
y 12 / GROUND SURFACE IF CONCRETE IS NOT SPECIFIED,
EARTH BACKFILL SHALL BE
\ \ I � COMPACTED IN 6" LAYERS. ,.
GUARD POST
PLAN
3 '®(1
MIN.
\ I MINIMUM CLEARANCE
I EACH SIDE 3'-0" MIN.
O \�
ONE MAN ROCK
CUT
HYDRANT EXTENSION
IF REQUIRED -
3 ® CONCRETE BLOCKING-
nIN, 16"x8"x4"'MINIMUM
,$.�. CONCRETE BLOCK \
I JZ� LEVEL EACH SIDE
ONE MAN ROCK FOR MINIMUM 3'-0"
1
6
o
FILL
FIRE HYDRANT LOCATION IN
CUT OR FILL
ELEVATION
FIRE HYDRANT GUARD POSTS
s
a
�,COREY TYPE FIRE HYDRANT EQUAL TO IOWA F-5110 AS SHOWN,
PACIFIC STATES CAST IRON PIPE CO. MODEL 2, OR APPROVED
EQUAL. 6" MECHANICAL JOINT INLET uITH LUGS. 51" MAIN
VALVE OPENING. TWO 2," HOSE CONNECTIONS NATIONAL
I STANDARD THREADS. 4" PUMPER CONNECTION CITY OF SEATTLE
THREADS, AND i}" PENTAGON OPERATING NUT. FIRE HYDRANT
TO BE PAINTED WITH TWO COATS OF PAINT, PRESERVATIVE
PAINT NO. 43-114, INTERNATIONAL YELLOW OR APPROVED
EO UAL.
II
PUMPER CONNECTION
TO FACE ROADWAY
TWO-PIECE CAST IRON VALVE BOX,
EQUAL TO RICH VALVE CO.,
STANDARD 8" TOP SECTION WITH
REGULAR BASE SECTION. LENGTH
TO FIT
CONCRETE BLOCKING
,e \ CAST IRON TEE, WITH
^� e 6" FLANGESI DE OUTLET
6 " GATE VALVE, FLANGE % MECHANICAL JOINT
EQUAL TO MUELLER CO. A-2380-16
UUC
6".CA&i IRON PIPE, CLASS 22 OR DUCTILE
7 CU. FT. MINIMUM WASHED IRON PIPE, CLASS 52, CEMENT LINED. LENGTH
GRAVEL PASSING 1}" AND TO FIT. TWO 3/4" STEEL TIE RODS, LENGTH
RETAINED ON 1" MESHED FOR TO FIT
DRAIN
FIRE HYDRANT ASSEMBLY
WATER STANDARD DETAIL
CITY OF RENTON
NOT TO SCALE DEPARTMENT OF PUBLIC WORKS
\
O
-PA9-170L l2EVIS�o;.
.2la c l ��
4*mM7AAY 't9'"
TEST .SEQtJE/VCE
2. /PRESSURE TEST
g ,ouPirr TEST
PRECAST CONCRETE VAULT WITH 3 - 3'x3'
HINGED STEEL PLATE COVERS. 4"x4"x6" BULL HEAD TEE, FL
DIMENSIONS 5'8"xll'-2"z7'-2" EQUAL TO
RENTON CONCRETE PRODUCTS, INC.
THE BY-PASS ASSEMBLY SHALL BE
I NCLUDEDAS PART OF THE DETECTOR
DOUBLE CHECK VALVE ASSEMBLY,
•/� 6" PIPE, FL. X FL.
CONCRETE BLOCKING / 2'-0" LONG-1�
18" FOR 10" ASSEMBLY
171 FOR 8" ASSEMBLY _
s 18i" fOR 6" ASSEMBLY 7 F
� I
6" 900 BEND, FL.
.•.IF �O� �_� �1�
�w
CONCRETE ISUPeE18T�AQi
UNDER CHECK VALVE
1011,
8" OR 6" FL. X P.E. .
ALL DETECTOR DOUBLE CHECK
►IRE
WITH COLLAR 18" FROM
VALVE ASSEMBLIES SHALL
P.E.INCLUDE
RESILIENT SEATED
I
LONG
SHUTOFF VALVES AND TEST
8� _3'-0"
3'-6" LONG
COCKS, AND BE APPROVED
6" -
4'-6" LONG
CROSS -CONNECTION CONTROL
ASSEMBLIES PER D.S.N.S.
APPROVED LIST.
NOTE:
1. LOCATE VAULT IN PLANTING AREA NOT IN
PAVING,
2. 4" AND LARGER BENDS AND TEES TO BE CAST I
CEMENT LINED.
3, TEMPORARY SUPPORT SHALL BE PROVIDED
UNDER VALVES AT THE TIME OF INSTALLATION
TO CENTER THE PIPE IN VAULT OPENING.
AFTER COMPLETE INSTALLATION REMOVE
THE TEMPORARY SUPPORT AND INSTALL
CONCRETE SUPPORT PAD.
4. 4" AND LARGER PIPE TO BE DUCTILE IRON
CEMENT LINED CLASS 52 PIPE, EQUAL TO
THOSE SUPPLIED BY PACIFIC WATER WORKS
SUPPLY COMPANY INC.
4" ADAPTER, FL.x SCREWED
ONE EACH SIDE
4"x21" FIRE DEPARTMENT DOUBLE
CONNECTION FOR STAND PIPE WITH
BREAKABLE CAST IRON HOSE CAPS.
ONE EACH SIDE EQUAL TO GAINNEL '
FIG. 1682 WITH HOSE CAPS FIG. 1333
6' SWING TYPE GRAVITY OPERATED
CHECK VALVE. FL. EQUAL TO
2-1 MUELLER CO. A-2600-6
6"PIPE, FL. x FL.
3'-0" LONG
AND 8- ASSEMBLY.
6SHORT RADIUS 90" BEND FL.
0" ASSEMBLY
8"x6" REDUCING 90' BEND, FL.
DEADMAN BLOCK REQUIRED,
` ASSEMBLY
6' TEE, FL.-� 1,
' SEMBLY �
INSTALL EPDXY Bg•zAS6'z6' TEE° =-FL.
NON SHRINK GROUT.
DOUBLE CHECK VALVE ASSEMBLY
INCLUDES TWO RESILIENT SEATED
SHUTOFF VALVES.
10". 8'. OR 6" DUCTILE IRON -
CLASS 52 NIPPLE PIPE, CEMENT
L
PLAN • LINED, LENGTH TO FIT.
10' ASSEMBLY
30"x10'.8" TEE FL.
\ 10', 8', OR 6" GATE VALVE.
FLxMJ. WITH INDICATOR POST.
INDICATOR POST VALVE SAME
SIZE AS DOUBLE CHECK VALVE
(MUELLER CO. OR EQUAL).
10". 8% OR 6" FLANGED
COUPLING ADAPTER EQUAL TO
ROCKWELL INTERNATIONAL 912.
x SCREW
INSTALL GALVANIZED
6' MIN. DRAIN TO - - LADDER FOR ACCESS
DAYLIGHT OR STORM
DRAIN SYSTEM. END VIEW
10"', d'& 6" DETECTOR DOUBLE CHECK VALVE ASSEMBLY
6" STANDPIPE WITH FOUR 2.1/2" NOZZLE
CROSS CONNECTION - BACKFLOW PROTECTION ASSEMBLY
WATER STANDARD DETAIL
CITY OF RENTON
NOT TO SCALE DEPARTMENT OF PUBLIC WORKS APRIL 1987
S o4c.
GENERAL NOTES
i cD 2
1. ALL WORK MATERIALS SHALL BE IN CONFORMANCE WITH THE STANDARDS AND 100 a 2
SPECIFICATIONS OF THE CITY OF RENTON UTILITY DEPARTMENT AND THE LATEST'� P
EDITION OF THE WSDOT/APWA STANDARDS AND SPECIFICATIONS. A SET OF
APPROVED PLANS SHALL BE KEPT ON -SITE AT ALL TIMES DURING CONSTRUCTION, ySng
2. THE HOURS OF WORK IN THE STREET RIGHT-OF-WAY SHALL BE LIMITED TO 8:30 AM
TO 3:30 PM ON WEEKDAYS UNLESS OTHERWISE APPROVED IN WRITING BY THE
DEPARTMENT OF PUBLIC WORKS AT 235-2635. ALL STREET CLOSURES, PARTIAL OR . N
0
FULL, SHALL BE APPROVED BY THE DEPARTMENT OF PUBLIC WORKS 24 HOURS IN �-o
ADVANCE. THE POLICE DEPARTMENT, FIRE DEPARTMENT, AND 911 SHALL BE M
NOTIFIED 24 HOURS IN ADVANCE. Z Q
3. ALL LOCATIONS OF EXISTING UTILITIES SHOWN ARE APPROXIMATE AND IT SHALL BE a
Cn Lli
THE CONTRACTOR'S RESPONSIBILITY TO VERIFY THE TRUE AND CORRECT LOCATION (� Q
SO AS TO AVOID DAMAGE OR DISTURBANCE. cw
W
4. ALL WATER MAIN PIPE TO BE CEMENT LINED DUCTILE IRON PIPE CONFORMING TO Z >
AWWA C110 AND C111 OR LATEST REVISION, THICKNESS CLASS 52. CEMENT MORTAR D
LINING AND SEAL COATING SHALL CONFORM TO AWWA C104 OR LATEST REVISION. _ (
PIPE JOINTS TO BE PUSH -ON OR MECHANICAL JOINT. BEDDING TO BE CLASS C.
ALL DUCTILE IRON PIPE INSTALLED SOUTH OF SUNSET BOULEVARD (EMPIRE WAY, SR
900) AND WEST OF SR 167 (EAST VALLEY FREEWAY) OR IN SOILS OF HIGH Q
RESISTIVITY SHALL BE POLYETHYLENE WRAPPED PER ANSI/AWWA C105-77 EE
STANDARDS. 06 co
5. CAST IRON AND DUCTILE IRON FITTINGS SHALL BE CEMENT LINED, PRESSURE RATED O� CE oN
AS NOTED ON PLANS, AND IN ACCORDANCE WITH ANSI/AWWA C110/A21.10-82. 0 W
CEMENT LINING SHALL BE IN ACCORDANCE WITH ANSI/AWWA C104/A21.4-85. IF Z
FITTINGS ARE 3 INCHES TO 12 INCHES IN DIAMETER AND HAVE MECHANICAL uj
JOINTS, THE FITTINGS SHALL BE IN ACCORDANCE WITH EITHER ANSI/AWWA 0
C110/A21.10-82 OR ANSI/AWWA C153/A21.53-84. 3-INCH TO 12-INCH DIAMETER O Z U)
FITTINGS WHICH HAVE MECHANICAL JOINTS AND/OR FLANGED JOINTS SHALL BE IN W w
ACCORDANCE WITH ANSI/AWWA C110/A21.10.82 OR A COMBINATION OF ANSI/AWWA _J Lu
C110/A21.10.82 AND ANSI/AWWA C153/A21.53-84 SUCH THAT THE PORTION OF THE T� % Q
FITTING WITH A MECHANICAL JOINT(S), MAY BE IN ACCORDANCE WITH ANSI/AWWA i cr
O
C153A/A21.53-84 AND THAT PORTION OF THE FITTING WITH FLANGED JOINTS) cn z
SHALL BE IN ACCORDANCE WITH ANSI/AWWA C110/A21.10-82. ACCEPTANCE TESTING D
IN ACCORDANCE WITH SECTION 53-5.3 OF ANSI/AWWA C153/A21.53-84 OR WITH
SECTION 10-4.3 OF ANSI/AWWA C110/A21.10-82 SHALL BE OBTAINED BY THE m o
CONTRACTOR AND TRANSMITTED TO THE OWNER.
6. GATE VALVES SHALL CONFORM TO AWWA C500 AND SHALL BE IRON BODY, BRONZED -
MOUNTED', DOUBLE DISC WITH BRONZE WEDGING DEVICE AND 0-RING STUFFING BOX. 3:
VALVES SHALL BE DESIGNED FOR A MINIMUM WATER OPERATING PRESSURE OF 200
PSI. GATE VALVES SHALL BE CLOW LIST 14, MUELLER COMPANY NO. A2380, OR
M&H. ALL VALVES 12" IN DIAMETER AND LARGER, SHALL BE INSTALLED IN A
VAULT. SEE WATER STANDARD DETAIL FOR 12" GATE VALVE ASSEMBLY VAULT AND m
1" BYPASS INSTALLATION.
7. FIRE HYDRANTS SHALL BE COREY TYPE (OPENING WITH THE PRESSURE) CONFORMING
TO AWWA C 504-80 WITH A 6 INCH INLET AND A M.V.O. OF 5 INCHES, TWO, 2-1/2 a
INCH HOSE NOZZLES WITH NATIONAL STANDARD 7 INCH, 60 DEGREES V. THREADS,
O.D. THREAD 4.875 AND ROOT DIAMETER 4-6263, 1-1/4" PENTAGON OPERATING NUT
OPENED BY TURNING COUNTER CLOCKWISE (LEFT).
8. ALL WATER MAIN 10 INCHES AND SMALLER TO MAINTAIN A MINIMUM COVER OF 36
INCHES BELOW FINISH GRADE. ALL WATER MAIN 12 INCHES AND LARGER SHALL BE
AT A MINIMUM OF 48 INCHES BELOW FINISH GRADE. WHERE UTILITY CONFLICTS
OCCUR, WATER MAINS ARE TO BE LOWERED TO CLEAR.
Z
9. ALL WATER MAINS SHALL BE PRESSURE TESTED AND DISINFECTED IN ACCORDANCE 7 Ln
0
WITH THE SPECIFICATIONS OF THE CITY OF RENTON AND THE WASHINGTON STATE w
HEALTH DEPARTMENT. ALL PRESSURE TESTING SHALL BE DONE IN THE PRESENCE OF a
A REPRESENTATIVE OF THE CITY OF RENTON.
10. A PRECONSTRUCTION CONFERENCE IS REQUIRED PRIOR TO ANY CONSTRUCTION. A 1�
r MINIMUM OF 3 (THREE) WORKING DAYS NOTICE IS REQUIRED FOR SCHEDULING. �
PRIOR TO SCHEDULING THE PRECONSTRUCTION MEETING A PERMIT INFORMATION lil
SHEET MUST BE SUPPLIED TO THE UTILITY ENGINEER'S OFFICE. TWENTY-FOUR
HOUR NOTICE WILL BE REQUIRED PRIOR TO STARTING NEW CONSTRUCTION. PROPER
TO STARTING NEW CONSTRUCTION. Z
11. IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY TO SECURE ALL NECESSARY
PERMITS PRIOR TO STARTING CONSTRUCTION.
12. INSTALLATION OF CORPORATE STOPS, WATER SERVICES, LINES AND METERS SHALL Z
NOT BE DONE UNTIL ALL SERVICE AGREEMENTS, METER APPLICATIONS, ZO Is --
CONSTRUCTION PERMITS, AND PAYMENT OF FEES HAVE BEEN MADE TO THE CITY OF Y U Q
RENTON. Q w C7 X
J Q Z O
CL
13. ALL CONNECTION TO EXISTING MAINS TO BE ACCOMPLISHED BY THE CITY OF CL _ cc
RENTON, EXCEPT WET TAPS WHICH MAY BE MADE BY APPROVED WET TAP CONTRACTORS cn O
WITH PRIOR APPROVAL FROM THE DEPARTMENT OF PUBLIC WORKS. ALL NECESSARY F- Q V
EXCAVATION AND MATERIALS TO BE SUPPLIED BY THE CONTRACTOR AND BE ON -SITE Q 3
PRIOR TO CITY NOTIFICATIONS. Lv
�- O cf3 z
14. INSPECTION WILL BE ACCOMPLISHED BY A REPRESENTATIVE OF THE CITY OF Q a > w
RENTON. IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY TO NOTIFY THE 3., x z �•
UTILITY DEPARTMENT 24 HOURS IN ADVANCE OF BACKFILLING ALL CONSTRUCTION. ® LtJ O
15. CONTRACTOR TO PROVIDE PLUGS AND TEMPORARY BLOW -OFF ASSEMBLIES FOR TESTING J < W
AND PURITY ACCEPTANCE PRIOR TO FINAL TIE-IN. Q w m W W
16 ALL JOINT RESTRAINT SYSTEMS (SHACKLE RODS, NUTS, BOLTS, ETC.) SHALL BE AS < o
MANUFACTURED BY THE STAR MANUFACTURING COMPANY OF COLUMBUS OHIO OR EQUAL L W >-
APPROVED IN WRITING BY THE DEPARTMENT OF PUBLIC WORKS. Y J F--
U < U
17. ASPHALT AND CONCRETE STREET PAVING SHALL BE SAWCUT TO A MINIMUM DEPTH OF ()5 Q z
TWO INCHES. OIL MAT STREETS MAY BE SPADE CUT. ALL SURFACE CONCRETE, J Oco
PAVEMENT, SIDEWALKS, CURB, GUTTERS, AND DRIVEWAY APPROACHES SHALL BE cn (�
SAWCUT TO A MINIMUM DEPTH OF TWO INCHES OR REMOVED TO AN EXISTING LLl Y z
EXPANSION JOINT. < W
O O tY
Z
18. A TEMPORARY COLD MIX ASPHALT PATCH SHALL BE PLACED ON THE DAY OF INITIAL O
EXCAVATION WITH A PERMANENT, SEALED PATCH TO BE PLACED, TO CITY OF RENTON V-
POLICY, WITHIN TEN DAYS. CALL FOR SUBGRADE INSPECTION PRIOR TO PLACEMENT
OF FINAL PATCH. TRENCHES WILL NOT BE LEFT OPEN OVER NIGHT WITHOUT PRIG
WRITTEN APPROVAL OF THE INSPECTOR. DRAWN BY CHECKED BY
19. FOR CITY PROJECTS SUCH AS TELEMETRY CONDUIT, THE PVC PIPE USED SHALL B to CS RGG
SCHEDULE 40 IN UNIMPROVED AREAS AND SCHEDULE 80 UNDER IMPROVED AREAS. SCALE DATE
JJX ALL CHEMICAL PROCESS LINES SHALL BE SCHEDULE 80 PVC PIPE. NOTE] 9 1 88