HomeMy WebLinkAboutWWP5102088.2SANITARY SEWER NOTES & SPECIFICATION 1. ALL WORK MATERIALS SHALL BE IN CONFORMANCE WITH THE STANDARDS A90 SPECIFICATIONS OF THE CITY OF RENTON UTILITY DEPARTMENT AND THE LATEST EDITION OF THE WSDOT/APWA STANDARDS AND SPECIFICATIONS. 2. THE HOURS OF WORK IN THE STREET RIGHT-OF-WAY SHALL BE LIMITED TO 8:30 A.M. TO 3:30 P.M. ON WEEKDAYS UNLESS OTHERWISE APPROVED IN WRITING BY THE DEPARTMENT OF PUBLIC WORKS AT 235-2620. ALL STREET CLOSURES, PARTIAL OR FULL, SHALL BE DEPARTMENT, APPROVED BY THE DEPARTMENT OF PUBLIC WORKS 24 HOURS IN ADVANCE. THE POLICE DEPARTMENT, F IRE AND 911 SHALL BE NOTIFIED 24 HOURS IN ADVANCE 3. ALL CONSTRUCTION SHALL BE IN ACCORDANCE WITH "STANDARD SPECIFICATIONS FOR MUNICIPAL PUBLIC WORKS CONSTRUCTION" PREPARED BY WASHINGTON STATE CHAPTER AMERICAN PUBLIC ''WORKS ASSOCIATION, LATEST EDITION (APWA) AND CITY OF RENTON STANDARD SPECIFICATIONS. 4. ALL LOCATIONS OF EXISTING UTILITIES SHOWN ARE APPROXIMATE AND IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY TO VERIFY THE TRUE AND CORRECT LOCATION SO AS TO AVOID DAMAGE OR DISTURBANCE. 5. A PRECONSTRUCTION CONFERENCE AND A 24 HOER NOTICE SHALL BE RE WIRED PRIOR TO STARTING NEW CONSTRUCTION. IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY TO SECURE ALL NECESSARY PERMITS PRIOR TO STARTING CONSTRUCTION. (INSPECTION WILL BE ACCCMPLISHED BY A REPRESENTATIVE Of THE CITY OF RENTON). IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY TO NOTIFY THE UTILITY DEPARTMENT 24 HOURS IN ADVANCE OF BACKFILLING ALL CONSTRUCTION. 6 CONTRACTOR IS SOLELY RESPONSIBLE FOR THE MEANS, METHODS AND SEQUENCES OF CONSTRUCTION AND FOR THE SAFETY OF WORKERS AND OTHERS ON THE CONSTRUCTION SITE. 7. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO OBTAIN STREET USE AND ANY OTHER RELATED PERMITS PRIOR TO ANY CONSTRUCTION. S. PLANS APPROVED BY THE CITY OF RENTON, PUBLIC WORKS DEPARMEMT SHALL TAKE PRECEDENCE OVER ALL OTHER PLANS. 9. A COPY OF THESE APPROVED PLANS MUST BE ON THE JOB SITE WHENEVER CONSTRUCTION IS IN PROGRESS. 10. THE CONTRACTOR SHALL PROVIDE THE CITY OF RENTON WITH AN AS -BUILT DRAWING OF THE SANITARY SEWER SYSTEM WHICH HAS BEEN STAMPED AND SIGNED BY A LICENSED PROFESSIONAL EMGINEER OR LICENSED PROFESSIONAL SURVEYOR. 11. BACKFIIL SHALL BE PLACED EQUALLY ON BOTH SIDES OF THE PIPE IN LAYERS WITH A LOOSE AVERAGE DEPTH OF 6 INCHES, MAXIMUM DEPTH OF 8 INCHES, THOROUGHLY TAMPING EACH LAYER TO 95 PERCENT OF MAXIMUM DENSITY. THESE COMPACTED LAYERS MUST EXTEND FOR ONE PIPE DIAMETER ON EACH SIDE OeTHE PIPE OR TO THE SIDE OF THE TRENCH. MATERIALS TO COMPLETE THE FILL OVER PIPF SHALL BE THE SAME AS DESCRIBED. 12. OPEN CUT ROAD CROSSINGS FOR UTILITY TRENCHES ON EXISTING TRAVELED ROADWAY SHALL BE BACKFILLED WITH CRUSHED ROCK AND MECHANICALLY COMPACTED. CUTS INTO THE EXISTING ASPHALT SHALL BE NEATLINE CUT WITH SAW IN A CONTINUOUS LINE. A TEMPORARY MIX PATCH MUST BE PLACED IMMEDIATELY AFTER BACKFILL AkD COMPACTION. A PERMANENT HOT MIX PATCH SHALL BE PLACED WITHIN 10 DAYS AND SHALL BE PER CITY OF RENTON CURRENT STANDARDS. 13. DATUM SHALL BE CITY OF RENTON, U.S.C. AND G.S. 14. ALL DISTURBED AREAS SHALL BE SEEDED AND MULCHED OR OTHERWISE STABILIZED TO THE SATISFACTION OF THE DEPARTMENT FOR THE PREVENTION OF ON -SITE EROSION AFTER THE COMPLETION OF CONSTRUCTION. 15. ALL PIKE AND APPURTENANCES SHALL BE LAID ON A PROPERLY PREPARED FOUNDATION IN ACCORDANCE WITH SECTION 7-02.3(1) OF THE CURRENT STATE OF WASHINGTON STANDARD SPECIFICATIONS FOR ROAD AND BRIDGE CONSTRUCTION. THIS SHALL INCLUDE NECESSARY LEVELING OF THE TRENCH BOTTOM OR THE TOP OF THE FOUNDATION MATERIAL AS WELL AS PLACEMENT AND COMPACTION OF REQUIRED BEDDING MATERIAL TO UNIFORM GRADE SO THAT THE ENTIRE LENGTH OF THE PIPE WILL BE SUPPORTED ON A UNIFORMLY DENSE UNYIELDING BASE. PIPE BEDDING SHALL BE PEA GRAVEL 6" ABOVE AND BELOW THE PIPE. 16. SANITARY SEWER PIPE SHALL BE POLYVINYL CHLORIDE (PVC) RUBBER GASKETED ASTM D 3034, SDR 35, OR DUCTILE IRON CLASS 17. IN UNIMPROVED AREAS, MANHOLE TO EXTEND MINIMUM 6 INCH AND MAXIMUM 18 INCH ABOVE FINISHED GRADE. IN PAVED AREA, COVER MUST SLOPE IN ALL DIRECTIONS TO MATCH PAVING. SASESPEC:If/acid CQ.3 T LNG-0LYMF)C i DRY " �9 4-"-.M!•-I _:�o D/T•OR E-0u4L. 24" _ 5Ec DI✓ -CAI L e _ AQJU5iMDtJT 4'MIN. GON l:7 M02TA2 JOIt--rm Fes.. c . l 5EC710Q STEFS-3/4"DEr=•DrZyltD 5 .2 51-Er'5 5I.AL.L bi= INC!_UD-D Co 1/2 i1 L lr OMR f9LLET- ` to tvt1N • ; • .., ... - MAX . F i rPE 5rZc-21" I.D. ,LADDE2-5TD. AL-UhANUM OR aA:.YAN IZED 5TF_151_ . COt\-r_R Tc 5w ff.LF FiRE:cA,&T a45E SFLTl0Li OIL CA,5r Ill FLACF- TYPICAL MANHOLE DETAIL N.T.S. 11P* 1510 fotlBB NE. 114 SEC. 3 �, T WN. 23, RGE 5 DIM A" CLEAR ACCESS OPENINGS GROUT BOTH .SIDES -- i-- A A [IJ 0 PRECAST DIVIDER SLOT BOTH SIDES PLAN VIEW 2" LAST IRON - LOCKING FRAME & COVER ADJUST TO GRADE VENT PIPE `S AIR & GAS 77GHT T )'P, -- - - - -- - - - - -- - - -- - - -- - -- -------------- -- IP45PECTION TEE INLET I TYP ­7N�- - r - �- --���- -- OUTLET Tl I�Z 1 TEE - - O U Q GROUT ALL AROUND '\SLOT BOTH SIDES 2/3 LENGTH 1/3 LENGTH SECTION A -A 750 GAL. OIL/ WATER SEPARATOR DETAIL 14" -- X Q R" 0000 z 00 VARIABLE 2' TO 5' 6" 6n NOTES: 1. STEPS -1-0 BE 3 /4" DEFORMED BAR GALVANIZED SAFTEY STEPS OR EQUAL. 2. STEPS ARE TO BE IN PLACE BEFORE MH SECTIONS ARE INSTALLED. 3. CASTING TO BE OLYMPIC FOUNDARY MH30 WITH MH30 D/T OR EQUAL. SEE DETAIL 5.14 �+. k AANJHOLE E("TIONS TO BE OF REINFORCED PRECAST CONCRETE. 5. OPENING SHOULD BE ON DOWNSTREAM SIDE. SANITARY >HALLOW MANHOLE TYPE"A" SIZING CHART GALLON CAPACITY UV CO. MODEL NO. UV Co. D WG No. DIM "A' DIM B' DIM "C" DIM 'D" whx De"N DIM E" 600 577-GA B60-136 7'-0" 4'-8" 7'-O' 3'-6" 3'-2" 750 577-GA 360-136 7'-O' 4'-8 7'-O" 4'-3' 3'-11 " 950 577-GA 960-136 7�-O' 4'-8' 7'-O" 5'-3' 4'-11 " 1000 4484-GA 960-137 9'-O' 5'-O' 7'-2' 4'-2' 3'-10" 1250 4484-GA 960-137 9'-0" 5'-0' 7'-2" 5'-2" 4'-10" 1500 5106-GA B60-138 ll'-2" 5'-8' 7'-2" 4'-4" 4'-O" 1750 5106-GA 860-138 11 '-2 5'-8' 7I - 2p 4'-11 " 4'-- 7" 2000 612-GA B60-140 12'-8' 6'-8" 8'-0' 4'-7' 3'-10" 2500 612-GA 860-140 12'-8" 6'-8. 8'-0 5'-6" 4'-9" 2750 612-GA 360-140 12'-8' 6'-8' 8'-0" 6'-0' 5'-3' 3000 914-GA 960-149 15'-7' 9'-7" '-61/2 5'-O" 3'-9"^ 4000 814-GA BOO-149 15'-7" 9'-7- 8'-61/2 6'-3' 5'-0" 5000 818-GA �B60-150 19'-11 " 9'-11 " 8'-11 " 6'-2" 4'-9" 6000 818-GA 860-150 19'-11' 9'-11' 10'-5" 1 7'-2" 5'-9" NO TES 1. CONCRETE 28 DAY COMPRESSIVE STRENGTH f'c=4500 psi. 2. REBAR ASTM A-675 GRADE 60. J. MESH ASTM A-185 GRADE 65. 4. DESIGN: ACI-318-83 BUILDING CODE ASTM C-857 MINIMUM STRUCTURAL DESIGN LOADING FOR UNDERGROUND PRECAST CONCRETE UTILITY STRUCTURES. 5. LOADS H-20 TRUCK WHEEL w/30X IMPACT PER AASHTO. 6. FILL W/CLEAN WATER PRIOR TO START-UP OF SYSTEM. 7. CONTRACTOR TO SUPPLY AND INSTALL ALL PIPING & SAMPLING TEES. 8. GRAY WATER ONLY, BLACK WATER SHALL BE CARRIED BY SEPARATE SIDE SEWER. * 2" CAST IRO'v VENT PIPE TO 31JILDING VENT SYSTEM I/z `----i --- rig"RASE-l�z°'V�IDE --� i---III �Ir2 -�Q• aC�s SPACEfD-5J4' A5 INDICATED- ut. I/8` &I CQ5T120K RIC.G AND GM12 F95ER JOIQT PACKING V8 DEMO FIFE MATERIAL - AS SPEClf�1=0. '. 1+--'PL.UG To E5t5EALffD W Nil✓ Ni ;iJ�!>� CS }'�IAtN SEYv1rR JO(1>�'i5. 6" SANITARY CLEAN -OUT DETAIL N.T.S. I.........+......... ..:...::: :" .. ..... ;: ........ ......... ...... ......... ......i_J . }...... : M s ..................................._.. __.... _.................. _........ - - .... .. . . . . . . : : . . . . . . . . . ' . . . . . . . . . . . . . . . . . . . . . . . . } i � N................... h 4 5........................................_._............._..-----....._.._....._--..._....._...._...._......... .._......_...._._._........ ......... . . . . . . . 'CONCRETE WALL'' - } ' ' :... i . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . E .. ...... ........ ......... 4 0 .... } E I, ji ED— PROFt>__ _ OVER P•Ir?E:I{........ I ..... .I........ ....... { i { .. ..... .. .... : . . . . . . . . . . . . . . . . .. ......... ...........:.. ... ..... 35 .__.........._..-__.........__._..._._.......___ __:.....:_.,............:....:..:._._.._ ........ ........ ........ 6" TEE.: dd'�TEE ...... I ..... 48LF 8" D.1.' CL 'S0 ! r +....... { . i : CEMEI�'T : L' I NED. ......... _ .. I ..... ' .... (.. . i i..CEMENT�INED.. ......... .. .. ...... '... ....}.........} $.rJ.ON►........:..... ... } . SSMH 1 .......:••� 25 . . . . . . . . . . . . . . . . . . .RIM. EFL..: 35,95 . . . . . . . . . . . .-. . . . . . .... i .. I.E._29.05-IN `::::::: 5S ... { .. .. .... . 1;E. =; 2 . . . OUT' I ....... RIM. EL. • = 4350 . ......... . . . . . . . . I . . . . . . . . . i .. . . . . .. . . . . . 4.E.- �' 29,50 � 6" IN. I . . ... . .. . . . . . :: :.................I..... ::. :::::::: :::::::::'/. _.�to- OUT:':::::::::f::: }...... . . . . . . . . . . . . . . . . : . . . 2O ° :...:_.:...:_.:_ ...:_. EX." SSMH { ; _ ' ... `BAN SE'ww�,� �RoEJ.L�__.__� `_:.: I ._ _...: .L... �:_: ; � .! �fl ' .RIM EL ._. 36.30. .. i .... } VERT- SCALE' l" =• 5- i E ........ LE = 23.60 } .... . ... - I HORIZ :SCALE:. J'.' _: Q'.::::::: ::::::::: .... RECHANNEE. ........:{... .......}.................. ......... . . . . . } . . . . . . . . . . . . . . . . . . { . . . . . ° . . . ' . . . . . . . _ . . . . . . .. . . . , ................... { ' ; .............. ........ i: . . . . . . . . . . . . . . i . . . . . . . . 17- ,r-)•• -_ 11• c•• .. c ncc-o SANITARY SUMP DETAIL N. T. S. 'AS -BUILT' ' BASED ON FIELD SJRVEY BY TOUM,4 ENGINEERS RECOMMENDED RECOMMENDED F(.R - '-",-,-!AL FOR APPROVAL H. Se� A n �' 0 ! '' al/656e9 f e7 Grl 10- NO. ( REVISION I BY I APPR. DATE S- 208802 CITY OF RENTON DEPARTMENT OF PUBLIC WORKS VALLEY MEDICAL CENTER SANITARY SEWER NOTES & DETAILS DESIGNED, G.S. DATE: MARCH 21, 1991 FILE NO.635-002-901 DRAWN: D.O. CHECKED: G.S. SCALE: NOTED FIELD BOOK: PAGE: APPROVED: SHEET: C c5 OF. 9 DIRECTOR OF PUBIJC WORKS d erq d �, 1 Ittri end dz z� 1 r-i O