WATER UTILITY - GENERAL NOTES
THESE NOTES SHALL APPEAR ON ALL PLANS SUBMITTED
1. All work material shall be in conformance with the standards and specifications
of the City of Renton Utility Department and the latest edition of the
WSDOT/APWA Standards and Specifications, as approved by the City of
Renton. A set of approved plans shall be kept on site at all times during
construction.
2. The hours of work in the street right-of-way shall be limited to 8:30 am to 3:30
pm on weekdays unless otherwise approved in writing by the Transportation
Division at 277-6222. All street closures, partial or full, shall be approved by
the Transportation Division at 277-6222 24 hours in advance. The Police
Department, Fire Department, and 911 shall be notified 24 hours in advance.
3. All locations of existing utilities shown are approximate and it shall be the
contractor's responsibility to verify the true and correct location so as to avoid
damage or disturbance. For utility locate call 48-Hours Locators, 1-800-424-
5555.
4. All water
main pipe to be cement
lined ductile
iron pipe conforming to
AWWA
C110 and C111 or latest revision,
thickness Class 52. Cement mortar
lining
and seal
coating shall conform to
AWWA C104
or revision. Pipe joints
to be
push -on
or mechanical joint. Bedding to be
Class C. All ductile iron
pipe
shall be
polyethylene wrapped per
ANSI/AWWA
C105-77 Standards.
5. Cast iron and ductile iron fittings shall be cement lined, pressure rated as noted
on plans, and in accordance with ANSI/AWWA C110/A21.10-82. Cement
lining shall be in accordance with ANSI/AWWA C104/A21.4-85. if fittings are
3 inches to 12 inches in diameter and have mechanical joints, the fittings shall
be in accordance with either ANSI/AWWA C110/A21.10-82 or ANSI/AWWA
C153/A21.53-84. Three inch to 12 inch diameter fittings which have
mechanical joints and/or flanged joints shall be in accordance with
ANSI/AWWA C110/A21.10.82 or a combination of ANSI/AWWA
C110/A21.10.82 and ANSI/AWWA C153/A21.53-84 such that the portion of
the fitting with a mechanical joint(s) may be in accordance with ANSI/AWWA
C153/A21.53-84 and that portion of the fitting with flanged joint(s) shall be in
accordance with ANSI/AWWA C110/A21.10-82. Acceptance testing in
accordance with section 53.53 of ANSI/AWWA C153/A21.53-84 or with
section 10-4.3 of ANSI/AWWA C110/A21.10-82 shall be obtained by the
contractor and transmitted to the owner.
6. Gate valves shall conform to AWWA C500 and shall be iron body, bronzed -
mounted, double disc with bronze wedging device and 0-ring stuffing box.
Valves shall be designed for a minimum water operating pressure of 200 PSI.
Gate valves shall be Clow List 14, Mueller Company No A2380, or M & H. All
valves 12" in diameter and larger, shall be installed in a vault. See water
standard detail for 12" Gate Valve Assembly Vault and 1" Bypass Installation.
7. Fire hydrants shall be Corey type (opening with the pressure) conforming to
AWWA C-504-80 with a six inch inlet and a M.V.O. of five inches, two 2-1/2
inch hose nozzles with national standard seven inch, 60 degrees V, threads,
O.D. thread 4.875 and root diameter 4.6263, 1-3/4 inch pentagon operating
nut opened by turning counter clockwise (left).
8. All water main 10 inches and smaller to maintain a minimum cover of 36 inches
below finish grade. All water mains 12 inches and larger shall be at a minimum
of 48 inches below finish grade. Where utility conflict occur, water mains are
to be lowered to clear.
9. All water mains six (6) inches in diameter and larger shall be cleaned with pipe
cleaning "PIGS" prior to disinfection. The "Poly Pigs" shall be Girard industries
Aqua Swab -AS or approved equal, 2 Ib/cu ft. density foam with 90A durometer
urethane rubber coating on the rear of "PIG" only. "PIGS" shall be cylinder
shaped with bullet nose or square end. The contractor shall perform the cleaning
operation.
9a. All water mains and services shall be pressure tested to a minimum of 200 PSI
or 150 PSI over operating pressure, in accordance with the specifications of the
City of Renton and the Washington State Health Department. All pressure
testing shall be done in the presence of a representative of the city of Renton.
9b. All water mains and services shall be disinfected by the
injection of a 50 ppm
(minimum concentration)
chlorine/water
solution. Dry Calcium Hypochlorite
shall NOT be placed in the pipe as laid.
Chlorine shall
be metered/injected in
accordance with Section
7-11.3(12)E or
7-11.3(12)F of
the Standard
specifications referenced
in 1 above.
10. A preconstruction conference is required prior to any construction. A minimum
of 10 (ten) working days notice is required for scheduling. Prior to scheduling
the precon a permit information sheet must be supplied to the Utility Engineer's
Office. Twenty-four hour notice will be required prior to starting new
construction.
11. it shall be the contractor's responsibility to secure all necessary permits prior
to starting construction.
12. Installation of corporate stops, water services, lines and meters shall not be
done until all service agreements, meter applications, construction permits, and
payment of fees have been made to the City of Renton.
13. All connection to existing mains to be accomplished by the city of Renton,
except wet taps which may be made by approved wet tap contractors with
prior approval from the Water Utility Section. All necessary excavation and
materials to be supplied by the contractor and be on -site prior to City
notifications.
14. Inspection will be accomplished by a representative of the city of Renton. It
shall be the contractor's responsibility to notify the City Inspector 24 hours in
advance of backfilling all construction. The contractor as well as the Engineers
shall keep as -built drawings.
15. Contractor to provide plugs and temporary blow -off assemblies for testing and
purity acceptance prior to final tie-in.
16. All joint restraint systems (shackle rods, nuts, bolts, etc.) shall be as
manufactured by the Star Manufacturing Company of Columbus Ohio or equa
approved in writing by the Water Utility Section.
17. Asphalt and concrete street paving shall be sawcut to a minimum depth of two
inches. Oil mat streets may be spade cut. All surface concrete, pavement,
sidewalks, curb, gutters, and driveway approaches shall be sawcut to a
minimum depth of two inches or removed to an existing expansion joint.
18. A temporary cold mix asphalt patch shall be placed on the day of initial
excavation with a permanent, sealed patch to be placed, to City of Renton
policy, within ten days. Call for subgrade inspection prior to placement of final
patch. Trenches will not be left open overnight without prior written approval
of the inspector.
19. For City projects such as telemetry conduit, the PVC pipe used shall be
schedule 40 in unimproved areas and schedule 80 under improved areas. All
chemical process lines shall be schedule 80 PVC pipe.
20. The existing 12 inch asbestos cement water main along the east side of the
new building has several existing domestic water meters and service lines from
the main to the meters. The contractor shall remove the meters and install
plugs at the tees. The existing 2 inch gate valves shall be removed.
21. There are several 8 inch stubs to the existing fire sprinkler vaults adjacent to
the existing building. The contractor shall remove the branch valves and install
mechanical joint plugs at the tees on the main line.
22. The contractor shall return all abandoned valves and fire hydrants to the
City of Renton Water Department shop.
gft Leonard, Boudinot & Skodie Inc.
PROFESSIONAL ENGINEERS & LAND SURVEYORS
�d 603 South First Street; P.O. Box 1228
Mount Vernon, WA 98273
Tel: 206-336-5751 Fax: 206-336-3981
FR
was��ctio
_ �� _ r✓'
28519 w
RFcis TV,
E) PiRES 5/2- &, 1 s
CITY OF RENTON
DEPARTMENT OF PUBLIC WORKS
FRED MEYER
RENTON CENTER
CONSTRUCTION NOTES
3
REVISIONS PER CITY COMMENTS
DEL
I HAF
9/30/94
2
REVISIONS PER CITY COMMENTS
DEL
HAF
8/12/94
1
REVISIONS PER CITY COMMENTS
DEL
HAF
7 14 94
NO.
REVISION
BY
APPR.
DATE
DESIGNED__ DATE: 8/8/94 FILE NAME:94058
DRAWN: SBK
CHECKED: HAF SCALE: N/A FlELD BOOK: PAGE:
APPROVED: SHEET: C- 23 OF: 36
DIRECTOR OF PUBLIC WORKS