CONDUIT SCHEDULE
CON.
CON.
FROM:
TO:
VIA
FOR
SIZE:
S
S
CONDUCTORS:
GROUP:
RUN:
G1
UTILITY POWER
STATION SERVICE
1 A, 1 B, 1 C
1
A
UTILITY TRANSFORMER
UTILITY DISCONNECT
POWER
NOTE 4
2#3, 1#3N,
1
B
UTILITY DISCONNECT
UTILITY METER
POWER
NOTE 4
2#3, 1#3N,
1
C
UTILITY METER
AUTOMATIC TRANSFER SWITCH
POWER
NOTE 4
2#3, 1#3N,
G2
VARIOUS POWER SOURCES
VARIOUS POWER DESTINATIONS
2A, 2B, 2C, 2D, 2E, 2F
2
A
AUTOMATIC TRANSFER SWITCH
SECONDARY DISCONNECT
POWER
2 1 /2"
2#3, 1 #3N, 1 #8G
2
B
SECONDARY DISCONNECT
POWER DISTRIBUTION BLOCK
POWER
2 1 /2"
2#3, 1 #3N, 1 #8G
2
C
POWER DISTRIBUTION BLOCK
CONTROL PANEL HIGH VOLTAGE
OVERHEAD
POWER
2 1 /2"
2#3, 1 #3N, 1 #8G
2
D
POWER DISTRIBUTION BLOCK
480V TO 120/240V XFrmr
OVERHEAD
POWER
2 1 /2"
2#3, 1 #3N, 1 #8G
2
E
480V TO 120/240V XFrmr
LOAD CENTER/PANEL BOARD
UNDERGROUND
POWER
2"
?????????????
2
F
LOAD CENTER/PANEL BOARD
CONTROL PANEL ENCLOSURE -LOW VOLTAGE
UNDERGROUND
POWER
1"
3A, 38, 3C, 3D,
G3
CONTROL PANEL ENCLOSURE
WET WELL
SEAL OFF VAULT
3E, 3F, 3G, 3H
CONTROL PANEL ENCLOSURE
PUMP NO.1
SEAL OFF VAULT
PUMP CONTROLS
2 1/2"
MANUFACTURE SUPPLIED CABLE
3
A
LOW VOLTAGE
& J-BOX
CONTROL PANEL ENCLOSURE
PUMP NO.1
SEAL OFF VAULT
PUMP POWER
2 1 /2"
MANUFACTURE SUPPLIED CABLE
3
B
HIGH VOLTAGE
& J-BOX
CONTROL PANEL ENCLOSURE
WET WELL
SEAL OFF VAULT
FLOAT
1"
2#14
3
C
LOW VOLTAGE
& J-BOX
CONTROL PANEL ENCLOSURE
WET WELL
SEAL OFF VAULT
LEVEL TRANSDUCER
1-1/2"
MANUFACTURE SUPPLIED CABLE
3
D
LOW VOLTAGE
& J-BOX
CONTROL PANEL ENCLOSURE
PUMP NO.2
SEAL OFF VAULT
PUMP CONTROLS
2"
MANUFACTURE SUPPLIED CABLE
3
E
LOW VOLTAGE
& J-BOX
CONTROL PANEL ENCLOSURE
PUMP NO.2
SEAL OFF VAULT
PUMP POWER
2-1/2"
MANUFACTURE SUPPLIED CABLE
3
F
HIGH VOLTAGE
& J-BOX
3
G
CONTROL PANEL ENCLOSURE
WET WELL
SEAL OFF VAULT
SPARE
2„
PULL TWINE, CAP AND MARK
BOTH ENDS OF CONDUIT
LOW VOLTAGE
CONTROL PANEL ENCLOSURE
WET WELL
SEAL OFF VAULT
SPARE
2„
PULL TWINE, CAP AND MARK
3
H
BOTH ENDS OF CONDUIT
HIGH VOLTAGE
4A, 4B, 4C, 4D,
G4
STANDBY GENERATOR
VARIOUS LOCATIONS
4E, 4F,
4
A
STANDBY GENERATOR MAIN BREAKER
AUTOMATIC TRANSFER SWITCH
STANDBY POWER
2-1/2"
2#3, 1 #3N, 1 #8G
4
B
STANDBY GENERATOR CONTROL PANEL
AUTOMATIC TRANSFER SWITCH
CONTROL
1"
6#14, 1#14G
4
C
STANDBY GENERATOR CONTROL PANEL
CONTROL PANEL ENCLOSURE
LOW VOLTAGE
CONTROL
1"
6#14, 1#14G
GENERATOR BLOCK HEATER
PANELBOARD
POWER
1"
1 #10, 1 #10N, 1 #10G
4
D
BATTERY CHARGER
PULL TWINE, CAP AND MARK
4.
E
STANDBY GENERATOR CONTROL PANEL
EAST CONTROL BUILDING WALL
SPARE
2"
BOTH ENDS OF CONDUIT
PULL TWINE, CAP AND MARK
4
F
STANDBY GENERATOR CONTROL PANEL
EAST CONTROL BUILDING WALL
SPARE
2"
BOTH ENDS OF CONDUIT
G5
VARIOUS LOCATIONS
VARIOUS LOCATIONS
5A, 5B, 5C
4
A
YARD LIGHT
PANEL BOARD
POWER
1"
1 #12, 1 #12N, 1 #12G
4
B
TELEMETRY ANTENNA
CONTROL PANEL ENCLOSURE - LOW VOLTAGE
RADIO
1"
OWNER SUPPLIED CABLE
PLEASE PROVIDE THE FOLLOWING ADDITIONAL PARTS FOR THE PUMP STATION CONTROL BUILDING ANDINSTALL PER THE ENCLOSED REVISED ONE -LINE DIAGRAM. PART
DESCRIPTIONS ARE SUGGESTIONS ANDTHE ELECTRICAL CONTRACTOR MAY USE OR -EQUAL SUBSTITUTIONS. PLEASE PROVIDE INVOICE DOCUMENTATION FOR ADDITION
PARTS TO BE BILLED USING FORCE ACCOUNT GUIDELINES.
-3-PHASE POWER DISTRIBUTION BLOCK - IN PUMP POWER PANEL. (GOULD 63133
195 AMP MINI -POWER BLOCK)
-480 VOLT 3-PHASE LIGHTNING ARRESTOR (DITEK DTG-480-3CM SURGE ARRERSTOR)
-WALL MOUNTED 15 KVA 480 VOLT TO 240 /120 VOLT TRANSFORMER
-240 /120 VOLT 1-PHASE LOAD CENTER W/100 AMP MAIN AND 20 CIRCUITS (SQUARE D HOMELINE LOAD CENTER PART #HOM20M100C)
WE WOULD ALSO LIKE TO HAVE THE ELECTRICAL SUBCONTRACTOR PROVIDE AND INSTALL A 30 AMP 1-PHASE CIRCUIT BREAKER (COMPATIBLE WITH THE INTALLED 1-
HARDWARE) IN THE MAIN PANELBOARD AS SHOWN IN THE REVISED ON LINE DIAGRAM. THIS BREAKER WILL BE UTILIZED TO PROTECT AND PROVIDE A DISCONNECT FOR
THE 480 TO 240 /120 VOLT TRANSFORMER.
THE CITY AGREES TO PAY FOR THE ADDITIONAL TIME NECESSARY TO MOUNT THESE ITEMS ON A FORCE ACCOUNT BASIS. PLEASE GIVE ADVANCED NOTIFICATION FOR
THE WORK TO COMMENCE TO ALLOW OUR FIELD STAFF TO TRACK THE PROGRESS AND TIME.
REQUIRED ADDITIONS:
AADD 480A, 3 PHASE POWER DISTRIBUTION BLOCK. WIRE TO SOFT
START BREAKERS AND PMR FUSES.
2 ADD 480A, 3 PHASE LIGHTING ARRESTOR TO MAIN PANELBOARD.
3 ADD 30AMP, 1 PHASE CIRCUIT BREAKER TO MAIN PANELBOARD.
AADD 15KVA 480V, 1 PHASE TO 240 /120V, 1 PHASE WALL MOUNT
• NEMA 1 TRANSFORMER.
oor" A5 ADD 120 /240V, 1 PHASE LOAD CENTER, 100A MAIN, 20 CIRCUITS.
AUXILIARY
GENERATOR
PRIMARY POWER
25 KW, 31 KVA
48OV, 3PH
CONTROL PANEL
UNDERGROUND PRIMARY CONDUCTORS
ON GENERATOR SET
BY PUGET SOUND ENERGY
MAIN SERVICE
AMS A
I
PAD MOUNT
JV
BREAKER ON
480V, 3PH
GENERATOR SET
I VMS V I
SECONDARY VOLTAGE
I I
TRANSFORMER BY PUGET SOUND ENERGY
S N
SERVICE DISCONNECT
- -
PER PUGET SOUND ENERGY STANDARD
PUMP POWER PANEL
POWER
DISTRIBUTION
BLOCK
i CONTRACTOR TO
Ar1T
KWH PUGET SOUND ENERGY
I STANDARDS (NOTE 3)
---
FUSE
AUTOMATIC
Z TRANSFER SWITCH
PHASE
480V, 3PH
MONITOR
V)
RELAY
3P
3P
60A
60A(
MAIN PANELBOARD
LIGHTING
100A( 480V, 3PH 22KAIC
LOCKABLE
A
A2
3
T
ARRESTOR 0
LA
OOA 80A
F�_
RTM
-
P
SOFT
SOFT
START
START
ANTENNA
ER
TELEMETRY
480VS 1 PHMTO L4\
&CONTROL PANEL
120/24OV, 1PH
CT
AM
CT AM
100A( LOAD
CENTER
120/240VA5
100A MAIN
OL
OL
C) BREAKER
N\ N` N�
20 CIRCUIT
LEVEL
PMU PMU XMTR
EISR
MISC LOADS GEN BLOCK 2.6 KW
PUMP DISCONNECT
(SEE LOAD HEATER & HEATER
VAULT
SCHEDULE BATTERY
ON C44A) CHARGER
20
20
LT
F
PUMP No.
1
PUMP No. 2
LEVEL
HIGH
20 HP
20 HP WETWELL
SENSOR
LEVEL
FLOAT
DUMP STATION ONE -LINE DIAGRAM -
SCALE: N.T.S.
m
JAW I Lq
]PT..JB LI C A/V(=)1Z1[<S U)]E]Prr.
o 1�1 -ENGINEERING-STREETS-WATER-SEWER-PARKS-BUILDING-
Z
1908
by
date
CONSULTANTS
PUMP STATION PROPOSED ONE -LINE DIAGRAM
C41 BB
shee4lBBf144
designed
MD
2/20/01
oo 33301 9TH AVENUE SOUTH
FEDERAL WAY, WASHINGTON
BERGER/ABAM 98003-2600,proj
E N G N E E R $ N VOICE: (206)431-2300
�t FAX: 206 31-2250
(�
drawn
BJA
2/20/01
3/11/o5
RECORD
checked
GLP
2 20 01
/ /
SOUTH 180th STREET GRADE SEPARATION
±8/20/01
2/17/01
ADDENDUMP5
'ob no A00084
proj eng
CCW
2/20/01
ADDENDUM 1
scale AS SHOWN
date 20-Feb-200
dir
GLP
2/2a/01
no
date
1
_
revisions
6-
field bk no
IN
Lost Saved on Wed May 18 2005 at 03.•05PM by Hamilton File Nome.- 0- I2000I A00084ICADD I dwgs I C-418B.dwg Scale.- 1
S`CA1Nb 00T 2 8 FQS