HomeMy WebLinkAboutWWP2702900.16INSULATED ENCLOSURE WITH
LOCK, TS. HEAT SOURCE, AND DRAIN
PORLOK BOX, MODEL HB75
3/4" DIA. REDUCED PRESSURE
VALVE/BACKFLOW PREVENTER DEVICE
EQUAL TO FEBCO MODEL 880.
OR APPROVED EQUAL CENTER
ENCLOSURE OVER PIPING.
3/4' DIA. ISOLATION VALVE,
EACH SIDE
AIR GAP DRAIN, ROUTE TO
DRAIN PORTS
3/4" DIA. "Y STRAINER
3/4' HOSE BIB
WSDOT TYPE 2 BOLLARD.
INSTALL PER WSDOT
STANDARD PLAN H-13o. 1'-6- MIN, �1
GFI RECEPTACLE
ANCHOR ENCLOSURE TO PAD
VENT DISCHARGE ELBOW
4' SHORT RADIUS
WITH (4) SS 1/2" ANCHOR
BOLTS.
12• MI/I
9H ELBOW (2) ,�
BEEHIVE
3' ACP TOP COURSE STRAINER
1/4•
CONCRETE FOUNDATION 10*00-xl/2"
HED STEEL PLATE
SURFACING STOP l FINISH GRADE
COURSE \
10" MIN.
4' STAINLESS STEEL
PIPE
(4) 5/8' SS HILTI CONDUIT TO LOAD PANELKWIK-BOLI \
S.
EMBEDDED 4" I I PIPE TO VALVE VAULT.
MINIMUM, PIPE FROM WATER METER.
BACKFLOW PREVENTION AND
ENCLOSURE DETAIL
1'— \/\//\�
NATIVE OR DISTURBED V-21" VENT PIPE (TYPICAL)
SOIL 6'x1/4' DIAMETER STEEL BAR.
VENT PIPE DISCHARGE DETAIL
NOT TO SCALE
I , '
0 o NON -SHRINK GROUT, TYP.
k'
VENT IN WET WELL
NOT TO SCALE
! r r
r
NON -SHRINK GROUT, TYP.
Zxw
VENT IN DRY WELL
NOT TO SCALE
!4'W?"L 2 7 - 2.9 cc
NOT TO SCALE
DYNARAIL' ISOFR SQUARE TUBE
LADDER SYSTEM CONSISTING OF
1}' DIAMETER FLUTED RUNGS, 1
r SQUARE TUBE RAILS AND
316 STAINLESS STEEL
HARDWARE
BRACKET ALLOWS RUNGS TO PASS
THROUGH UNOBSTRUCTED. FILE
EDGES SMOOTH.
LOWER LADDER
NOT TO SCALE
3'
)f• DIAMETER SS
4" HIGH "1 w11—
STANDON ADJUSTABLE
PIPE SUPPORT
2" GALVANIZED STEEL PIPE
AS
REQUIRED
TOPPING GROUT
(2) 5/8"0 SS DRILL AND EPDXY VALVE VAULT FLOOR
ANCHOR SYSTEM EOUAL TO HILTI„,;
'HIT C100• WITH SS NUT AND
WASHER, EMBED 4" MINIMUM.
VERTICAL PIPE SUPPORT
2"x%" BENT STAINLESS STEEL.
ANCHOR BOLT TO WALL WITH
HILT] ANCHORS AND EPDXY.
LENGTH AS NECESSARY FOR 8'
OFFSET FROM WALL.
STAINLESS STEEL CHANNEL OR
BENT STAINLESS STEEL, 6-
LENGTH. SELECT TO PROVIDE
INSIDE CLEARANCE OF }" ON
ALL SIDES.
"x3-W BASE PLATE
LOWER LADDER SLIDE
SAFETY RAIL DETAIL
2,_D.,
NOT TO SCALE
ACCESS TO LOWER ACCESS LAD ;!=R
SAFETY CHAIN 2 EACH w/
SNAP RING AT MANHOLE WALL.
m
NOT TO SCALE
MECHANICAL PIPING NOT
SHOWN THIS NEW FOR
CLARITY.
ACCESS HATCH
o v �
4
4�
4
WET WELL 9
QII
v
d
o
4
CLEANING PAD
LADDER UP EXTENDER
WET WELL UPPER LADDER
PVC COATED
GRC CONDUIT J
TO TELEMETRY.
f
i
10
4 4 4i
4
v
FLOAT NG BRACKET
r EQUAL 101, OR ACCULIFE.
a.
v
4' 0 SCH 80 PVC
-
4 -
PIPE. MOUNT FLUSH
4
PATH BOTTOM OF
c 4
STAINLESS
STEEL ANCHOR
FBERG,.ASS BASIN.
CONNECTED TO
TRANSDUCER CABLE
WALL.
-
a
4 - SECURE TO WALL AND
-
CLEANING PAD WITH
- 4 STAINLESS STEEL
-v CLAMPS AT 3'-0. O.C._v
LEVEL 1RANSDUCER
I
a
a:
a
a
�
p
45'IE,EL-CUT hOTTOM
OF PIPE STARING AT
TOP FIBERGLASS BASIN
CENTERLINE
LEVEL TRANSMITTER DETAIL
NOT TSCALE
%- DIA SS BAR BENT INTO 'U"
SHAPE. ANCHOR MIN. 4' INTO
WET WELL WALL.
I 3/4• SS TUBE FOR HINGE.
WELD TO NOOK BAR.
14"x2"xt/f' SS BAR. BEND
END INTO HOOK TO CAPTURE
LADDER FILING.
LOWER LADDER HOLD HOOK
NOT TO SCALE
S •sscal6
REVISED TO CONFORM
TO CONSTRUCTION RECORDS
SCANNED OCT 0 8 2eQ
MARK MILLER JAN 24, 2003
RH2 ENGINEERING INC. DATE
Qj I AS-BUILTS
NO. I REVISION
Z
Ny QE-I J
zz N W
0�
A J N
20 D
Vy W
LV Z
E'+ H W
�U
�Z co
y
40
EN(31 NEE RS
PLANNERS
SCIENTISTS
RH2 ENGINEERING.INC.
http: //.—.rh2,—
maA6oAh2.—
I.800.720.8052
BELLINGHAM OFFICE
360. 676. 0836
454 Meal Hvlw Rood
BOTHELL OFFICE
425951.5400
12100 RE 1951h Street, Suite 100
EAST WENATCHEEOFFICE
509S86.2900
300 S IM Street, Site 5
PORT ORCHARD OFFICE
360.876, 7960
600 Kitwp Street, Suite 101
SCALE: SHOWN
0 1" 2"
DRAWING IS NOT TO SCALE
IF BAR IS NOT 2' LONG
nm: 1 - wn
uluMne DMB G-2
JAN 24, 2003
PAG
w 101,082
we KCC-G