CONTRACT RESPONSIBILITIES
ITEM
STREET WATER CONNECTION
CITY OF WON
UNDERGROUND WATER MAINS
FW 9RWLR UNTACTOR
EXCAVATIONS
EXCAVAW CONTRACTOR
BACKFILL
EXCAVAX CONTRACTOR
WIRING
PAINTING
39 77
kFcisr��
�IONA5�
Q�
Id3 0/ I I SCALE:
/I I I AS PER DWG
T_ JAHOLKOWSKI
CHECKED BY:
MATS HAREZLAK, P.E.
I ari9 Of T.J_ 1SUEf0RbVJ1LDAIGP£RMI7h1F /F 7M DATE-
)_ I DATE BY REVISIONS - SEE FLAGGED AREA ON PLAN JULY 19. 01
CA UTION:
LOCATION OF EXISTING UTILITIES SHOWN IS
APPROXIMATE AND MAY NOT BE ACCURATE
OR ALL INCLUSIVE. IT IS THE CONTRACTOR'S
RESPONSIBILITY TO FIELD VERIFY LOCATION
OF UNDERGROUND UTILITIES PRIOR TO
PROCEEDING WITH CONSTRUCTION_
SimplexGrinnell a kision of tyco Fire & Security
1220 37TH STREET NW, SUITE 106, AUBURN, WA. 98001
STATE CONTRACTOR
NO. GRINNFP137LE
KC/N/TYMAP
N. T. S
Wln293001
�;F/VFR,4 / UnTFS:
1. ALL SPECIFICATIONS, MATERIALS AND WORKMANSHIP SHALL BE IN ACCORDANCE WITH
THE CITY OF RENTON MUNICIPAL CODE AND STANDARD FOR ROAD AND MUNICIPAL
CONSTRUCTION AND THE MANUAL ON UNIFORM TRAFFIC CONTROL DEVICES.
2. ANY CHANGES FROM DESIGN OR THE CITYS STANDARD SPECIFICATIONS WITHOUT WRITTEN
CITY APPROVAL, MAY JEOPARDIZE ACCEPTANCE OF THE PROJECT BY THE CITY AND
CONTRACTOR PROCEEDS AT OWN RISK_
3. CONNECTION TO EXISTING WATER LINE ("HOT TAP CONNECTION") TO BE BY CITY OF RENTON
WATER DEPARTMENT.
4. RESPONSIBILITY OF THE INSTALLATION OF THE UNDERGROUND FIRE WATER SUPPLY FROM
CITY CONNECTION TO THE FLANGE INSIDE IN THE BUILDING TO BE BY THE "U" LICENSED
UNDERGROUND CONTRACTOR. A 'U' LICENSED UNDERGROUND CONTRACTOR IS RESPONSIBLE
FOR THE PERMIT AND INSTALLATION OF THE UNDERGROUND FIRE WATER SERVICE LINE_
PRIOR TO THE HOOK UP OF THE OVERHEAD FIRE SPRINKLER SYSTEM TO THE UNDERGROUND
THE 'U' LICENSED UNDERGROUND CONTRACTOR SHALL PROVIDE TO FIRE SPRINKLER CONTRACTOR
WITH PROPER DOCUMENTED HYDROSTATIC TEST AND FLUSHING CERTIFICATES AS REQUIRED
BY CITY OF RENTON-
5- FIRE WATER SERVICE PIPE SHALL BE DUCTILE IRON CONFORMING TO AWWA C151 (ANSI A21-51),
CLASS 52_ GATE VALVES SHALL CONFORM TO AWWA C509.
ALL MATERIALS SHALL CONFORM TO THE CITYS STANDARDS AND SPECIFICATIONS.
6_ LOCATION OF EXISTING UTILITIES SHOWN ARE APPROXIMATE AND MAY NOT BE ACCURATE
OR ALL INCLUSIVE. IT IS THE CONTRACTOR'S RESPONSIBILITY TO FIELD VERIFY LOCATION
OF UNDERGROUND UTILITIES PRIOR TO PROCEEDING WITH CONSTRUCTION_
T ALL PAVEMENT CUTS AND PATCHING SHALL CONFORM TO CITY OF RENTON STANDARD REQUIREMENTS.
8. WHERE WATERMAIN CROSSES ABOVE OR BELOW SANITARY SEWER, ONE FULL LENGTH OF WATER
PIPE SHALL BE CENTERED FOR MAXIMUM JOINT SEPARATION,
9, SERVICE LINE SHALL BE HYDROSTATIC TESTED, FL#SH AND CHLORINATED AS PER CITY SPECIFICATION.
10. PRIOR TO ANY EXCAVATION, THE CONTRACTOR SHALL CALL 1-800-425-5555 FOR UTILITY LOCATION
(WATER, GAS, POWER, SANITARY & STORM SEWER, CABLE TV - 48 HOURS BEFORE).
o
Fire &
Security
(253) 737-2200
(253)737-2301 FAX
TRACT NAME_ ROYAL HILLS APARTMENTS
ROYAL HILL CLUBHOUSE
3000 SE ROYAL HILLS DRIVE, RENTON, WA
CONTRACT WITH:. ICON BUILDERS
IDESCRIPnoN: S/TE PLAN - FIRE SERWCE MAIN
SYSTEM DESIGN DATA
THESE PLANS PREPARED AT:I
AUBURN, WA
ENGINEERING DEPARTMENTI
DRAWING NO.
F-1 OF 2
CONTRACT NO:
41,303844 H1
0
N
S..M!til`D �c3 1 5 �L