HomeMy WebLinkAboutWTR2702953.20co Ln N I N 9 7 b 5 4 3 L. 2 w Q Z A B C CONCRETE BLOCKING SIZING PROCEDURE A. GENERAL The amount of concrete required to anchor horizontal bends, tees, and dead ends depends on the strength of the soil. The methods of placing concrete to keep the joint accessible is shown in Figure 1. The area in square feet of concrete which must bear 000inst the side of the trench is found b dividing the thrust in pounds shown in Table 1y by the safe B. RI A bearin food of the soil as shown in Table 2. 1. The sizing procedure is for horizontal or downward thrust only. 2. Height of the thrust block must be equal to or less than 1/2 the depth from the ground surface to the block base. 3. The thrust block bearing face is approximately rectangular. 4. he concrete blockingg shall be as per APWA -5YM,Secification 74-2.14. C.LS d = Outside Diameter of Pipe in Feet T = Thrust in Pounds at the Fitting (Table 1) SBL =Safe Bearing Load in Pounds/ q. Ft. (Table 2) In = Depth of Trench in Feet W = Width of Trench in Feet A = Area of Concrete which must bear against the Side of the Trench in Sq. Ft. Hm = Maximum Height of the Thrust Block in feet Dc = Depth of the Concrete Thrust Block to Bearing Surface in Feet Lm = Maximum Length of the Thrust Block in Feet GROUND SUFACE h "/ d h Hm= 2 T .r. BLOCK BASTE D� W D. CALCULATION EQUATIONS Thrust (In Pounds 1. Area of Concrete (A) = - T Safe Bearing Load (In Pounds/Sq. Ft.) - SBL 2. Maximum Height of Thrust Block (Hm) = Depth of Trench in Feet - h 2 - 2 3. Depth of Concrete Thrust Block Width of Trench in Feet) - �Outside Diameter of Pipe in Feet) W-d = _ 2 z 4. Maximum Length of Thrust Block (Lm) = Area of Concrete - A Maximum Height Hm 5. Required Amount of Concrete (Cu. Yd.) = (Height x Depth x Length) x 0.03704 = (Hm x Lm x Dc) x 0.03704 E. EXAMPLE 1. Problem: Calculation of the amount of concrete required to block a 90' bend in an 8" C.I. water main; the normal operating pressure in the pipe will be 65 psi and the soil condition in the area indicates sand and gravel. 2. Solution: - Maximum testing pressure (See Table 1) = 300 psi. = 0.75 ft. - Outside diameter of 8" pipe = 9.05 in. = 9.05/12 - Go to Table 1: The testing pressure of 300 psi, we see that the thrust on a 90' bend is 21,360 pounds. D - Go to Table 2: Table 2 gives the safe bearing load for sand and gravel: 3,000 lbs./sq. ft. Go to Figure 1: figure 1 indicates the position of the concrete for blocking the 90' bend. - Go to the specifications of the project and find depth of trench (h) = 4 feet - width of trench (W) = 3 feet With the above assembled information, we proceed to the final calculations: - Area of Concrete (A) = Thrust - 21,360 = 712 sq ft. Safe Bearing Load 3,000 - Maximum Height of Thrust Block (Hm) = Depth of Trench in Feet 2 h 4 = 2.0 ft. 2 2 - Depth of Concrete Thrust Block (Dc) Width of Trench in Feet (W) - Outside Diameter of Pipe (d) 2 _ 3-0.75 = 1.13ft. 2 Maximum Length of Thrust Block (Lm) Area of Concrete Height of Concrete = A _ 7.12 = 3.56 ft. Hm 2.0 Required Amount of Concrete = (Height x Depth x Length) x 0.03704 = (Hm x Lm x Dc) x 0.03704 = (2.0 x 3.56 x 1.13) x 0.03704 = 0.30 cu. yd. TABLE 1 Size Pressure PSI Thrust at Fittings in Pounds Tees 90' 45' 22-1/2 11-1/4 Dead Ends Bend Bend Bend Bend 3" 300 2,120 3,000 1,630 830 430 4" 300 3,780 5.370 2,910 1.470 750 6" 300 8,500 12,000 6,510 3,320 1,700 8" 300 15,100 21,360 11,550 5,880 3,020 10" 275 21,620 30,570 16.540 8,430 4,330 12. 250 33,930 48,000 25,950 13,260 6,780 14" 250 46,200 65,370 35,340 18,030 9,240 16" 225 45,250 64,000 34,620 17,650 9,050 18" 200 50,900 72,000 38,940 19,860 10,180 20" 200 62,840 88,900 48,080 24,520 12,560 24' 200 90,480 127,980 69,200 35,320 18,100 30" 200 141,370 199,960 108,150 55,140 28,280 36' 200 203,580 287,950 155,740 79,400 40,720 TABLE 2 Safe Bearing Loads in Lb./Sq. Ft. The safe bearing loods given in the following table are for horizontal thrusts when the depth of cover over the pipe exceeds 2 feet. Safe Bearing Load -5QL Lb. per So. Ft. 'Muck, peat, etc. 0 Soft Clay 1,000 Sand 2,000 Sand and Gravel 3,000 Sand and Grovel Cemented with Clay 4,000 Hard Shale 10,000 -In muck or peat, all thrusts shall be restrained by piles or tie rods to solid foundations or by removal of muck or peat and replacement with ballast of sufficient stability to resist thrusts. 12 96 REFORMAT TO 11"x17" DCV DIRT 3/6/95 CORRECTED COLUMN HEADINGS DCV AG DATE REVISION IBY APPR'D Where shown on the plans or in the specifications or required by the Engineer, joint restraint sy� ii, �„ ��he rods) shall be used. joints restraint materials used shall be those manufactured by Star National Products, 1323 Holly Avenue, PO Box 258, Columbus, Ohio 43216 unless an equal alternate is approved in writing by the Engineer. Materials Steel Types: High strenggth low -allay steel (cor-ten), ASTM AM heat -treated; Superstar "SST" series High strength low -allay steel (cor-ten), ASTM A242, Superstar 'SS" series 1. Tiebolt: ASTM A242, Type 2, hot -dipped galvanized. SST 7: 5/8" for 2" and 3" mechanical joints, 3/4" for 4' to 12" mechanical joints ASTM A325, Type 3D, except tensite strength of full -body threaded section shall be increased to 40,000 lbs. minimum for 5/8" and 60,000 lbs. minimum for 3/4: by heat treating (quenching and tempering) to Manufacturer's reheat and hardness specifications. SST 756: 3/4' for 14" to 24" mechanical joints. Same ASTM specification CIS SST 7. SST 747: 3/4" same as SST 7, except 1" eye for 7/8" rod. Some ASTM specification as SST 7. 2. Tienut: Heavy Hex Nut for Each Tiebolt. SS8: 5/8" and 3/4", ASTM A563, Grade C3, hot -dip galvanized. 3. Tiecoupling: Used to extend continuous threaded rods and are provided with Grade C3. center stop to aid installation, hot -dip galvanized. SS 10: for 5/8" and 3/4" tierods, ASTM A563, 4. Tierod: Continuous threaded rod for cutting to desired lengths, hot -dip galvanized. SS 12: 5/8' and 3/4' diameter, ASTM A242, Type 1 or Type 2; ANSI B1.1. 5. Tiewasher: Round flat washers, hot -dip galvanized. SS 17: ASTM A242, F436. Pressure Force Size PSI Pounds 2 3 4 6 8 10 12 14 16 24 3" 300 2,120 2-3/8" 4" 300 3,780 3/8" 6" 300 8,500 5/8" 1 2" 3 8" 8" 300 15,100 3/4" 5/8" 1 /2" 10" 275 21,62 3/4" 5/8" 1 2" 12" 250 33,930 3/4" 5/8" 14" 250 46,200 3/4" 16" 225 45,250 3/4" 5/8" 18" 200 50,900 3/4" 5/8" 20" 200 62,840 3/4" 5/8" 24" 200 90,480 3/4" 30" 200 141,370 7/8" 36" 200 203,580 7/8" 2 RECORD DRAWINGS 1 ISSUED FOR CONSTRUCTION NO. REVISION A B L I G -Ell CAP 22-1/2� 45'BEND TEE 90 BEND 11-1/4 FIGURE 1 NOTE: FOR CONVEX VERTICAL BENDS BLOCKING SEE APWA STANDARD PLAN NO. 73. CONCRETE BLOCKING SIZING PROCEDURE Y ADOPTED U/� �� CITY OF RENTON STANDARD PLANS F N 1 O LST DATE: 12/96 DWG. NAME: BR26 SP PAGE: B085 Galvanized ASTM A153 for galvanizing iron and steel hardware ASTM A123 for galvanizing rolled, pressed and forged steel shapes. Joint Restrainer System Components: Installation: Install the joint restraint system in accordance with the Manufacturer's instructions so all joints are mechanically locked together to prevent joint separation. Tiebolts shall be installed to pull against the mechanical joint body and not the M.J. follower. Torque nuts at 75-90 foot pounds for 3/4" nuts. Install tiecouplings with both rods threaded equal distance into tiecouplings. Arrange tierods symmetrically around the pipe. Where a Manufacturer's mechanical joint valve or fitting is supplied with slots for "T" bolts instead of holes, a flanged valve with a flange by mechanical joint adaptor shall be used instead, so as to provide adequate space for locating tiebolt. Where a continuous run of pipe is required to be restrained, no run of restrained pipe shall be greater than 60 feet in length betwee fittings. Insert long body solid sleeves as required on longer runs to keep tierod lengths to the 60 foot maximum. Pipe used in continuously restrained runs shall be mechanical joint pipe and tiebolts shall be installed as rod guides at each joint. Where poly wrapping is not required, all tiebolts, tienuts, tiecouplings, tierods shall be galvanized. All disturbed sections will be painted, to the inspector's satisfaction, with ATCO #2221, or approved equal. Where poly wrapping is not required, all tiebolts, tienuts, tiecouplings, tierods, and tiewashers may be galvanized, as specified above, or plain and painted in their 4-97 EDIT TEXT DCV DT DATE REVISION BY APPR'D SURVEYED: - DESIGNED: J.E. DRAWN: R.B. CHECKED: G.P. APPROVED: - RB 1/06 GP RB 10/03 GP BY DATE APPR C D SCALE: AS SHOWN ONE INCH AT FULL SCALE IF NOT ONE INCH SCALE ACCORDINGLY E SHACKLE RODDING AND TIE BOLTS Y �o ADOPTED CITY OF RENTON ART= STANDARD PLANS NLST DATE: 4/97 DWG. NAME: BR27 SP PAGE: BO89 VERTICAL: NAVD 1988 HORIZONTAL: NAD 1983/1991 DATUM Kennedy/Jenks Consultants 32001 32nd Ave. S., Suite 100 Federal Way, Washington 98001 G H J I K FIRE HYDRANT SHALL BE COREY-TYPE EQUAL TO IOWA F-5110 OR COMPRESSION TYPE SUCH AS CLOW MEDALLION; M & H 929, MUELLER SUPER CENTURION 200, AND WATEROUS PACER WITH 6" MECHANICAL JOINT INLET WITH LUGS. 5-1/4" MAIN VALVE OPENING. TWO 2-1/2" HOSE CONNECTIONS NATIONAL STANDARD THREADS. 4" PUMPER CONNECTION CITY OF SEATTLE THREADS WITH A STORZ ADAPTOR, 4" SEATTLE THREAD X 5" STORZ, ATTACHED WITH 1 /8" STAINLESS STEEL CABLE. I 1-1/4" PENTAGON OPERATING NUT. FIRE HYDRANT TO BE PAINTED WITH TWO COATS OF PAINT. KELLY-MOORE/PRESERVATIVE MAX 4" PAINT No. 5780-563 DTM ACRYLIC GLOSS, SAFETY YELLOW OR MIN 2"� APPROVED EQUAL. PUMPER CONNECTION TO FACE ROADWAY ASSEMBLY. FIRE HYDRANT EXTENSION TO BE USED IF REQUIRED. CONCRETE BLOCKING M N 0 18" TO 20" BEHIND BACK OF CURB OR 12" BEHIND BACK OF SIDEWALK THAT IS ADJACENT TO CURB TWO-PIECE CAST IRON VALVE BOX WITH LUG TYPE COVER. EQUAL TO OLYMPIC FOUNDRY CO. STANDARD 8" TOP SECTION WITH REGULAR BASE SECTION LENGTH TO FIT. VALVE NUT EXTENSION AS REQUIRED (SEE DWG BR46 / PAGE B090). RAISED PAVEMENT MARKER TYPE 88 A8 STIMSONITE TWO-WAY BLUE. CONCRETE BLOCKING P ��- CAST IRON TEE. WITH 6" FLANGE SIDE OUTLET. 6" GATE VALVE (FL X MJ) AWWA C-509, RESILIENT SEAT 1��`....,....,���,...%\ 6" DUCTILE IRON PIPE, CLASS 52 CEMENT LINED, LENGTH TO FIT TWO 3/4" STEEL TIE RODS. SEE STD DETAIL FOR TIE RODS. 16" x 8" x 4" MININUM CONCRETE BLOCK UNDER HYDRANT 1 /3 CU. YD. WASHED DRAIN ROCK (3" TO 3/8") FIRE HYDRANT ASSEMBLY LEVEL ALL GROUND MIN 3' RADIUS o W=2953 5 ONE MAN ROCK o 6 617 CUT HYDRANT LOCATION IN CUT OR FILL "^, ' "E OPERA T'":C T EXTENSION ^DOTE: r'L EXTENSIONS ARE REQUIRED WHEN VALVE NUT IS MORE THAN 3' BELOW FINISHED GRADE. EXTENSIONS ARE TO BE A MIN. OF 12" LONG ONLY ONE EXTENSION TO BE USED PER VALVE. NOTE: ALL EXTENSIONS ARE TO BE MADE OF STEEL, SIZED AS NOTED, AND PAINTED WITH TWO COATS OF METAL PAINT. VALVE MARKING POST ECONOMIC AND ENGINEERING SERVICES, INC. 10900 NE 4TH STREET, SUITE 1110 BELLEVUE, WASHINGTON 98004 PORTLAND, OR / BELLEVUE, WA / KENNEWICK, WA / OLYMPIA, WA J K FILL 6/4/03 ADD WATEROUS & CHANGE PAINT MANUF. LC 6/4/03 ADD WATEROUS & CHANGE PAINT MANUF. LC AG DATE REVISION BY APPR'D 2" nDr7nATlnl� ^li IT , SQ. .�, '0 STEEL (LENGTH AS REQ'D.) 4 1 /4"0, 1 /8" MIN. THICKNESS 1 /8" MIN. THICKNESS VALVE STEM I 2 1 /4" I/S MEASUREMENT 2 1 /4" DEPTH VALVE OPERATING NUT WHITE POST VALVE STEM EXTENSION LEGEND TO BE USED WHEN THE VALVE NUT IS MORE THAN 3' FIRE HYDRANT ASSEMBLY DETAIL Y p ADOPTED CITY OF RENTON STANDARD PLANS LST DATE: 12/96 DWG. NAME: BR24 SP PAGE: B 102 R1910 VALVE BOX WITH "WATER" CAST IN LID. 6 4 o / / 3'x3'x8" CLASS 3000 CONCRETE FINISHED GRADE 777 6" CAST IRON RISER PIPE TO BE PLUMB AND CENTERED > OVER VALVE STEM. SEE CITY STD. B090 FOR ADDITIONAL DETAILS. 1 /4" VALVE STEM RISER 2 1 "0 ROD, CS (LENGTH VARIES) N 3 GATE VALVE SHOWN -SIMILAR INSTALLATION REQUIRED FOR BUTTERFLY VALVES. C, C J �1 7 4 3 BELOW FINISHED GRADE. TRENCH BOTTOM STANDARD VALVE BOX DETAIL 4 0 VALVE OPERATING NUT OR 1 NTS 7/8%1 7/8%2" HIGH GRADE STEEL WELDED TO GUIDE CONSTRUCTION RECORD DRAWING NOTICE PLATE. 2O 3/16" THK.X 5 1 /5" DIA These record drawings have been prepared based upon information contained in addenda, change orders, or 2 STEEL GUIDE PLATE WELDED TO RISER SHAFT. other available construction information, and information provided by the Contractor, and by others. HDR has not verified the accuracy or completeness of the information 03 2>>2xxJ>3/16 " SQUARE STRUCTURAL STEEL provided to it and does not warrant the accuracy or completeness of these record drawings. Users of this information shall be solely responsible to verify any and TUBING TO FIT OPERATING all information represented herein prior to any such use NUT. LENGTH AS REQUIRED. of the information. "'ME, CITY OF RENTON =■ W Planning/Building/Public Works De t. P DATE: OCTOBER, 2003 PROJECT No. 3-01-358 MAPLEWOOD WATER TREATMENT AND GOLF COURSE IMPROVEMENTS REVISION NO. 2 WATER DETAILS 1 OF 2 sHT No. °° NO.C38 W 2953AA.