HomeMy WebLinkAboutWTR2703020.41— MAIN LINE TEE (RJ) WITH CONCRETE BLOCKING (WATER MAIN LOCATED IN EASEMENT ON PRIVATE PROPERTY SHALL NOT BE MORE THAN 50 FEET TO BUILDING) 2— BRANCH VALVE (RJ) WITH VALVE BOX AND COVER 3— CLASS 52 DUCTILE IRON PIPE (8 INCH MINIMUM) ALL PIPE AND FITTINGS SHALL BE RESTRAINED WITH SHACKLE RODS AND CONCRETE THRUST BLOCKS PER NFPA AND AWWA STANDARDS. 4— WALL POST INDICATOR VALVE WITH TAMPER SWITCH 5— 2-90' BENDS (FL x FL) WITH FLANGED DUCTILE IRON PIPE SPOOL 6— 18" LONG SPOOL (FL x PE) 7— FLANGE COUPLING ADAPTOR 8— APPROVED DDCVA ON MAIN LINE IN HORIZONTAL POSITION ONLY. (PER LATEST DEPT. OF HEALTH APPROVED LIST OF BACKFLOW PREVENTION DEVICES) BOTTOM OF DDCVA SHALL BE A MINIMUM OF 24 INCH ABOVE FLOOR LEVEL AND NOT HIGHER THAN 3 FEET MAXIMUM. INSTALL 3 CONCRETE PADS OR ADJUSTABLE PIPE SUPPORT COLUMNS UNDER DDCVA 9— O.S & Y VALVES TO BE RESILIENT SEATED WITH TAMPER SWITCHES. ADD WIRING IN ACCORDANcE WITH L & I 10— METERED 3/4 INCH BY—PASS DCVA — BY—PASS METER SHALL BE A 3/4 INCH "SENSUS—ECR" SR POSITIVE DISPLACEMENT METER EQUIPPED WITH A REMOTE READ SENSOR PLATE MOUNTED ON THE OUTSIDE OF THE BUILDING WALL. 11— SWING TYPE GRAVITY CHECK VALVE, FLANGE WITH BALL DRIP IN SIDE BUILDING. 12— 4"x 4" x 6" BULL, ELBOW, THREADED 13— UL LISTED FIRE DEPT. CONNECTION, UL LISTED BREAK AWAY CAPS, LOCATE WITHIN 50 FEET MAXIMUM OF A PUBLIC FIRE HYDRANT. MOUNTED ON WALL. AFTER FIELD INSTALLATION, MAIN DDCVA AND BY—PASS DCVA MUST BE TESTED SATISFACTORILY BY A DEPARTMENT OF HEALTH CERTIFIED BACKFLOW ASSEMBLY TESTER. TEST REPORT MUST BE SUBMITTED TO CITY OF RENTON WATER UTILITY ENGINEERING DEPARTMENT PRIOR TO ACTIVATION OF NEW LINE. INSTALL BRASS PLUGS AT ALL TEST COCKS. Q W Q C? CITY OWNED AND MAINTAINED I 15' WIDE WATER LINE EASEMENT TO BUILDING FIRE SPRINKLER SYSTEM REFER TO SPRINLKER RISER DETAIL 0 2 CONCRETE BOLLARDS 10 PRIVATELY OWNED AND MAINTAINED MAXIMUM PIPE LENGTH FROM EASEMENT TO DDCVA MUST NOT EXCEED 50 FEET TO BUILDING FIRE SPRINKLER SYSTEM INCH 48 INCH 7 9 BUILDING WALL 0 0 W V Q Y v 0 m H O z O c PERIMETERS OF MINIMUM CLEARANCES TO BE PAINTED ON FLOOR IN WHITE ENAMEL PAINT STRIPE, WITH 2 INCH STENCILED BLACK LETTERS TO SAY: "DO NOT BLOCK ACCESS" DDCVA MUST BE INSTALLED IMMEDIATELY AFTER PIPE PENETRATION THROUGH BUILDING FLOOR SLAB. ROOM IN WHICH DDCVA IS LOCATED SHALL: A. HAVE FLOOR DRAIN CONNECTED TO THE SANITARY SEWER SYSTEM. B. HAVE A HEATING SYSTEM (40' F MIN. TEMP.) NO HEAT TAPE C. NOT BE USED FOR STORAGE AROUND THE DDCVA D. HAVE CLEARLY DELINEATED ACCESS WAYS TO DDCVA AND PIVs. A RIGHT —OF —ENTRY AGREEMENT MUST BE GRANTED TO THE CITY OF RENTON FOR INSPECTION OF THE DDCVA AND METER. SEPARATE FIRE SPRINKLER PLANS INCLUDING INSTALLATION OF DDCVA MUST BE SUBMITTED TO RENTON FIRE PREVENTION DEPARTMENT FOR REVIEW AND APPROVAL. A SEPARATE FIRE SPRINKLER PERMIT IS REQUIRED. 24 INCH MINIMU 36 INCH MAXIML ELEVATION VIEW OF DDCVA CITY Or FA NTM BTANDARD IPLM La M. NAME: . INSIDE BUILDING INSTALLATION FOR 3 INCH AND LARGER DETECTOR DOUBLE CHECK VALVE ASSEMBLY D. E. 1144 Eastlake Ave. E. T (206) 522-9510 �sSroxAL E�'�'l �SSIoxAL E��� Suite 601 F (206) 522-8344 Seattle, WA 98109 WWW.PACLAND.COM EXPIRES DULY 7, 20 EXPIRES AUGUST 5, 2003 vvrP-s7_.?"6 N TS SP PAGE: . NOTE: THESE DETAILS ARE SHOWN FOR REFERENCE ONLY. SEE ARCHITECTURAL/MECHANICAL AND FIRE PROTECTION PLANS FOR ACTUAL INSTALLATION INFORMATION. CHECKED FOR COMPLIANCE RECOMMENDED TO CITY STANDARDS FOR APPROVAL DATE BY G DATE s IS o BY 2 l✓ DATE gJ10 BY DATEc— n-„n BY N0. i VANE TYPE WATER FLOW SWITCH TYP PIPE SUPPORT MINIMUM 2" DIAMETER TYP O.S.&Y VALVE WITH TAMPER SWITCH TYP SLEEVE THROUGH FLOOR. SIZE TO PROVIDE 2" CLEAR SPACE AROUND PIPE AND FILL WITH MASTIC TIE RODS EXTERIOR REMOTE READER FOR BACKFLOW DEVICE PER CITY OF RENTON REQUIREMENTS fi N mot' 2" TEST AND DRAIN VALVE WITH SIGHT GLASS AND SMOOTH BORE CORROSION RESISTANT ORIFICE WITH FLOW EQUAL TO ONE SPRINKLER. VALVE SHALL INCLUDE PRESSURE RELIEF VALVE PIPE TO MANIFOLD DRAIN TYP 1" AUXILIARY DRAIN PIPE TO MANIFOLD DRAIN ELEVATION VIEW B 24" MINIMUM, 36" MAXIMUM PER CITY OF RENTON REQUIREMENTS AMES 3000 SS BACKFLOW PREVENTER ELEVATION VIEW A CROSSED HATCH AREA IS THE MAXIMUM ALLOWABLE AREA TO BE USED FOR SPRINKLER SYSTEM RISERS AND BACKFLOW PREVENTERS. INSTALLATION MUST ALLOW FOR ALL REQUIRED MAINTENANCE ACCESS WITHIN CROSS HATCHED AREA SURVEYED: SCALE: VERTICAL: NAVD 1988, BM# 2123 BARGHAUSEN C.E. ELEVATION 45.11 FEET NONE HORIZONTAL: NAD 1983/1991 DESIGNED: REFER TO PROJECT SURVEY JRG DRAWN: DMD ONE INCH PERMIT COMMENTS RESUBM11TAL PACLAND 4 18 03 CHECKED: DATUM AT FULL SCALE JRG IF NOT ONE INCH REVISION BY DATE APPR APPROVED: SCALE ACCORDINGLY JRG I PLAN VIEW SPRINKLER RISER NTS 03.30.01 114, CITY OF RENTON Planning/Building/Public Works Dept. WALL POST INDICATOR VALVE WITH TAMPER SWITCH IN 12 O'CLOCK POSITION, TYP. VALVE TO BE CHAINED AND LOCKED. 2 1/2" X 6", 4—WAY "BOX STYLE" FIRE DEPARTMENT CONNECTION SAM'S CLUB #4835-00 901 SOUTH GRADY WA` RENTON, WA 98055 WATER DETAILS DATE: 2-07-03 FIELDBOOK: PAGE: DRAWING NO: C-7.3 SHEET: OF: SCANNED NOV ® 7 2003 ` t:: �, � - � 0 a C) %