GENERAL NOTES
1. ALL CONSTRUCTION AND MATERIALS SHALL CONFORM TO THE STANDARDS AND
REQUIREMENTS OF WSDOT INCLUDING THE STANDARD PLANS FOR ROAD AND BRIDGE
CONSTRUCTION OF THE STATE OF WASHINGTON AND THE 1998 STANDARDS FOR
ROAD, BRIDGE AND MUNICIPAL CONSTRUCTION FOR THE STATE OF WASHINGTON.
2. A COPY OF THESE APPROVED PLANS MUST BE ON THE JOB SITE WHENEVER
CONSTRUCTION IS IN PROGRESS.
3. ALL STORM DRAINAGE IMPROVEMENTS SHALL BE CONSTRUCTED IN ACCORDANCE WITH
THESE APPROVED PLANS. ANY DEVIATION FROM THESE PLANS WILL REQUIRE
APPROVAL FROM THE OWNER, ENGINEER AND APPROPRIATE PUBLIC AGENCIES.
4. IT SHALL BE THE SOLE RESPONSIBILITY OF THE CONTRACTOR TO OBTAIN STREET
USE AND ANY OTHER RELATED PERMITS PRIOR TO ANY CONSTRUCTION ACTIVITY,
5. ALL LOCATIONS OF EXISTING UTILITIES SHOWN HEREON HAVE BEEN ESTABLISHED BY
FIELD SURVEY OR OBTAINED FROM AVAILABLE RECORDS AND SHOULD THEREFOR BE
CONSIDERED APPROXIMATE ONLY AND NOT NECESSARILY COMPLETE. IT IS THE
SOLE RESPONSIBILITY OF THE CONTRACTOR TO INDEPENDENTLY VERIFY THE
ACCURACY OF ALL UTILITY LOCATIONS SHOWN AND TO FURTHER DISCOVER AND
AVOID ANY OF THE UTILITIES NOT SHOWN HEREON WHICH MAY BE AFFECTED BY THE
IMPLEMENTATION OF THIS PLAN. THE CONTRACTOR SHALL CONTACT THE
UNDERGROUND UTILITIES LOCATION SERVICE (1-800-424-5555) AT LEAST 48
HOURS PRIOR TO CONSTRUCTION. THE OWNER OR HIS REPRESENTATIVE AND THE
ENGINEER SHALL BE CONTACTED IMMEDIATELY IF A CONFLICT EXISTS.
6. ALL CATCH BASINS SHALL BE TYPE 1 UNLESS SPECIFIED OTHERWISE.
7. STORM DRAIN PIPE SHALL BE ANY OF THE FOLLOWING TYPES UNLESS SPECIFIED
OTHERWISE. ALL PIPE SPECIFICATIONS SHALL COMPLY WITH SECTION 9-05 OF THE
WSDOT/APWA SPECIFICATIONS.
A: UNREINFORCED CONCRETE (RC)
B: DUCTILE IRON CLASS 52
C: SMOOTH INTERIOR, DOUBLE WALL CORRUGATED POLYETHYLENE
8. SEWER PIPE SHALL BE PVC CONFORMING TO ASTM D3034 SDR35.
9. ALL RELEVANT NOTES AND STANDARD DETAILS IN THE CITY OF RENTON DRAFTING'
STANDARDS SHALL APPLY TO THIS CONTRACT.
WATER SYSTEM NOTES
1. All work materials shall be in conformance with the standards and specifications of
the City of Renton Utility Department and the latest edition of the WSDOT/APWA
Standards and Specifications, as approved by the City of Renton. A set of
approved plan shall be kept on site at all times during construction.
2. The hours of work in the street right-of-way shall be limited to 8:30 AM to 3:30
PM on weekdays unless otherwise approved in writing by the Department of Public
Works at (206) 235-2635. All street closures, partial or full, shall be approved
by the Department of Public Work 24 hours in advance. The Police Department,
Fire Department and 911 shall be notified 24 hours in advance.
3. All locations of existing utilities shown are approximate and it shall be the
contractor's responsibility to verify the true and correct location so as to avoid
damage or disturbance. For utility locate call 48-Hour Locators,
1-800-424-5555.
4. All water main pipe to be cement lined ductile iron pipe conforming to AWWA C110
and C111 or latest revision, thickness Class 52. Cement mortar lining and seal
coating shall conform to AWWA C104 or latest revision. Pipe joints to be
push -on or mechanical joint. Bedding to be Class C. All ductile iron pipe shall
be polyethylene wrapped per ANSI/AWWA C105-77 Standards.
5. Cast iron and ductile iron fittings shall be cement lined, pressure rated as noted
on plans, and in accordance with ANSI/AWWA C110/A21.10-82. Cement lining shall
be in accordance with ANSI/AWWA C104/A21.4-85. If fittings are 3 inches to 12
inches in diameter and have mechanical joints, the fittings shall be in accordance
with either ANSI/AWWA C110/A21.10-82 or ANSI/AWWA C153/A21.53-84. 3 inch
to 12 inch diameter fittings which have mechanical joints and/or flanged joints
shall be in accordance with ANSI/AWWA C110/A21.10-82 or a combination of
ANSI/AWWA C110/A21.10-82 and ANSI/AWWA C153/A21.53-84 such that the
portion of the fitting with a mechanical joint(s), may be in accordance with
ANSI/AWWA C153/A21.53-84 and that portion of the fitting with flanged joint(s)
shall be in accordance with ANSI/AWWA C110/A21.10-82. Acceptance testing in
accordance with section 53-5.3 of ANSI/AWWA C153/A21.53-84 or with section
10-4.3 of ANSI/AWWA C110/A21.10-82 shall be obtained by the contractor and
transmitted to the owners.
6. Gate valves shall conform to AWWA C500 and shall be iron body,
bronzed -mounted, double disc with bronze wedging device and 0-ring stuffing box.
Valves shall be designed for a minimum water operating pressure of 200 psi.
Gate valves shall be Clow List 14, Mueller Company No. A2380, or M & H. All
valves 12" in diameter and larger, shall be installed in a vault. See water
standard detail for 12" Gate Valve Assembly Vault and 1" Bypass Installation.
7. Fire Hydrants shall be Corey type (opening with the pressure) conforming to AWWA
C-504-80 with a 6 inch inlet and a M.V.O. of 5 inches, two 2-1/2 inch hose
nozzles with national standard 7 inch, 60 degree V threads, O.D. thread 4.875 and
root diameter 4.6263, 1-1/4 inch pentagon operating nut opened by turning
counter clockwise (left).
B. All water mains 10 inches and small to maintain a minimum cover of 36 inches
below finished grade. All water mains 12 inches and larger shall be at a
minimum of 48 inches below finished grade. Where utility conflicts occur, water
mains are to be lowered to clear.
9. All water mains six (6) inches in diameter and larger shall be cleaned with pipe
cleaning "PIGS" prior to disinfection. The "Poly Pigs" shall be Girard Industries
Aqua Swab -AS or approved equal, 2lb/cu density foam with 90A durometer
urethane rubber coating on the rear of the "PIG" only. "PIGS" shall be cylinder
shaped with bullet nose or square end. The contractor will perform the operation.
9a. All water mains and services shall be pressure tested to a minimum of 200 psi or
150 psi over operating pressure, in accordance with the specifications of the City
of Renton and the Washington State Department of Health. All pressure testing
shall be done in the presence of a representative of the City of Renton.
9b. All water mains and services shall be disinfected by the injection of a 50 ppm
(Minimum concentration) chlorine/water solution. Dry Calcium Hypochlorite shall
NOT be placed in the pipe as laid. Chlorine shall be metered/injected in
accordance with Section 7-11.3(12)E or 7-11.3(12)F of the Standard Specifications
referenced in 1 above.
10. A preconstruction conference is required prior to any construction. A minimum
of 3 (three) working days notice is required for scheduling. Prior to scheduling
the precon a permit information sheet must be supplied to the Utility Engineer's
Office. Twenty-four hour notice will be required prior to starting new
construction.
w TIP -1' - hi.? _
NE SEC 31, TWP 23 N, RGE 5 EY4,
11. It shall be the contractor's responsibility to secure all necessary permits prior to
starting construction.
12. Installation of corporate stops, water services, lines and meters shall not be done
until all service agreements, meter applications, construction permits, and payment
of fees have been made to the City of Renton.
13. All connections to existing mains to be accomplished by the City of Renton, except
wet taps which may be made by approved wet tap contractors with prior approval
from the Department of Public Works. All necessary excavation and materials to
be supplied by the contractor and be on -site prior to City notifications.
14. Inspection will be accomplished by a representative of the City of Renton. It shall
be the contractor's responsibility to notify the Utility Department 24 hours in
I 'n II construction. The contractor as well as the Engineers
advance of backflll g a con g
shall keep as -built drawings.
15. Contractor to provide plugs and temporary blow -off assemblies for testing and
purity acceptance prior to tie-in.
16. All joint restraint systems (shackle rods, nuts, bolts, etc) shall be manufactured
by the Star Manufacturing Company of Columbus Ohio or equal approved in writing
by the Department of Public Works.
17. Asphalt and concrete street paving shall be sawcut to a minimum depth of two
inches. Oil mat streets may be spade cut. All surface concrete, pavement,
sidewalks, curb, gutters, and driveway approaches shall be sawcut to a minimum
depth of 2 inches or removed to an existing expansion joint.
18. A temporary cold mix asphalt patch shall be placed on the day of initial
excavation with a permanent, sealed patch to be placed, to City of Renton policy,
within ten days. Cali for subgrade inspection prior to placement of final patch.
Trenches will not be left open over night without prior written approval of the
Inspector.
19. For City projects such as telemetry conduit, the PVC pipe used shall be schedule
40 in unimproved areas and schedule 80 under improved areas. All chemical
process lines shall be schedule 80 PVC pipe.
TESTING DETAIL
- CT
12"02"TAPPING TEE (MJxFL)
12" TAPPING GATE VALVE (FL XMJ)
12" TEMPORARY PLUG (MJ) WITH 2-INCH TAP
AND 2-INCH BLOW -OFF ASSEMBLY
CONCRETE BLOCKING
FINAL CONNECTION DETAIL
IN 12" D.I. WATER LINE O NEW 12" D.I. WATER LINE
1
i
12"x12"VERTICAL CROSS(MJxFL) FOR POLYPIGGING AFTER ALL CLEANING BY POLYPIG, PRESSURE TESTING
AND DISINFECTION, REMOVE TEMPORAY BLOCK & BLOW -OFF
1-12" BLIND FLANGE ON TOP WITH 2" TAP AND 2" PLUG AND CONNECT TO VALVE WITH 12" D.I. SLEEVE (MJ) & D.I. SPOOLS
1-12" BLIND FLANGE ON BOTTOM FINAL CONNECTION BY CITY FORCES
1-12" PLUG(MJ) WITH 2"TAP & 2" BLOW -OFF
TEMPORARY BLOCK
4' 900 BEND(MJ)
c�
4'FLxMJ ADAPTOR J '
4'TEE(MJxFL) -
r- 4' POST INDICATOR VAi-VE (MJxMJ)
f PAINTED BLOC 2-3f4' SHACKLE RODS PER
CITY OF RENTON SPECIFICATIONS
13 LF 4' D,I. - 4' 90' BEND(M!)
�7._T
4'FLxMJ
ADAPTOR
LADDER WITH
4' TEE
(FL)
SUaPOR7 PARS
PE:n? ❑SHA
GENERAL NOTES,
(C3j o�o
ALL METERS AND BACK;LOW PREVENTION DEVICE COMBINATIONS ARE NOT
SHOWN OR INCLUDED IN "WE STANDARD OF DRAVINGS. 1F YOUR
-'AIL
PARTICULAR CDMBiNATION IS NOW SHOWN, AN APPROVED DRAWING WILL BE
'
REQUIRED BY THE UTILITY ENGINEERING DEPT. FOR ITS INSTALLATION.
EPDXY NON- SlIRINK-
`.
..
THE PRINCIPAL REOUIREM_NTS REGARDING VAULT SIZING ARE THE LENG'H
GROUT
• ?'-a'
y
DF FITTI>NGS OR THEIR CLEARANCE FROM T'NE VAULT 'WALLS, (WHICH,
PRFCA%J (AINCRETE VAULT WITH 2 3'x3' FANGED --'
STEEL PLATE COVER. OUTSIDE DIMENSIONS
4'-$`x7'-0`. (EUAL T] -IPE INC., OR CITILITY VAULT
WITH 57-7L-B, 2 3'x3' DIAMOND PLATE DOORS)
6',4' DR 3' GATE VALVE (FLx7! )
NC!N-I<ISING STEM WITH HAND WHEEL
EQUAL TO MUELLER CO. A-2380-6 ---
6' DR. 4' (FLxPE) CEMENT 3' 4•
LINED DUCTILE IRON PIPE
CLASS 52 3'-6' LONG
WITH COLLAR 20' FROM
P.E EDUAL TO THOSE
SUPPLIED BY PACIFIC 3'-2'
WATER WORKS CO. INC.
- -
12' AROUND -11. : 16•
f'
INVI514SY5 - $RH �...1,.
('I W ITN T6%014A6110 PIT1r1111P 56N w
6',4' OR 3' COMPOUND WATER
MFTFR (FI ) FOJAL TO SENSES
COMPOUND METER. �-
REDJCE AT METER WI i I CONCRETE SUPPORT -
4"x3` FLxFL CONCENTRIC PAD> O� AD_RYI IA_iL>_
REDUCER PIPE SUPPORTS.
NOTES:
1. TAPPING TEES SHALL BE MADE OF CAST IRON, DUCTILE IRON OR
EPDXY -COATED STEEL.
2. WET -TAP SHALL BE DONE ONLY BY CITY -APPROVED
CONTRACTORS
12" WET TAP D ETAI L
NTS
CLEARANCE SHALL BE A MINIMUH OF Ic FROM THE ENDS AND THE SIDE
--^ .- -r•-r- DEADMAN B? OC ( CLDETAlI$j SHOULD BE AS TYPICALLY SHOWN ON THE VARIOUS STANDARD
---a.----- - RE'?UIRE D WITH
SHACKLING TO TEE NOTE, DEADMAN BLLICK SMALL RE DESiGNEr
AND INSTALLED SO IT BEARS AGAINST
SUFFICIENT UNDISTURBED EARTH SO AS TO
SUPPURT THE DESIGNED THRUST.
�V0X, PIECE CAST IRON VALVE BOX,
C a. QJ FOUAL TO OLYMPIC FOUNDRY CO.
�s`*�S•� STANDARD S' TOP SECTION, WITH
REGULAR BASE SECTION LENGTH
o? TO FIT,-
6', 4' OR 3' DATE VALVE
1 (FLxMJ) EOIUk- TO MUELLER
r-
CO. A-2380-20.
-�- 3",4" & 6" COMPOUND
14' " METER SERVICE
6' CI? 4' PF xI'[ CCMLNT LINED
DUCTIre- IRON PPE CLASS 52,
LENGTH TO FIT. ADOPTED l CITY Or RENTON 12/96
6' DR 4` FLEXIBLE F�ANC�ED � � +
CflUPLN i ADAPTOR., R]IMAC OR' '` Standard plan.
!1PPRCVED EQUAL, � LST DATE: 12!15f91
REVISION
DWG, NAME: BP44 SP PAGE; B108
1rJN ; BY A�'NR'
CITY OWNED
AND MAINTAINED PRIVATELY OWNED AND MAINTAINED
MAXIMUM PIPE LENGTH FROM PROPERTY LINE BUILDING WALL
TO DDCVA MUST NOT EXCEED 50 FEET
®� 4 CONCRETE BOLLARDS Z
O • 10 "
IWWW
5 FT. MAX.
Z 7 N
.� OEn
W
Z co
LLJ
_ Z
U
w 2 O
d W
0U? O
Qf� w 7 Z
a < w
3 V
O Z 24 INC y 48 INCH
91.
s � -
13 12 11 to Z
1- MAIN LINE TEE (MJ x FL) WITH CONCRETE BLOCKING Ix
(WATER MAIN LOCATED IN EASEMENT ON PRIVATE PROPERTY
SHALL NOT BE MORE THAN 50 FEET TO BUILDING)
2- BRANCH VALVE (FL x MJ) WITH VALVE BOX AND COVER C w
3- CLASS 52 DUCTILE IRON PIPE (4 INCH MINIMUM) Z
ALL PIPE AND FITTINGS SHALL BE RESTRAINED WITH SHACKLE RODS 9 rn
AND CONCRETE THRUST BLOCKS PER NFPA AND AWWA STANDARDS.
4- POST -INDICATOR VALVE (MJ) WITH TAMPER SWITCH W
5- 2-90' BENDS (FL x FL) WITH FLANGED DUCTILE IRON PIPE SPOOL
6- 18" LONG SPOOL (FL x PE) O 1
7- FLANGE COUPLING ADAPTOR
8- APPROVED DDCVA ON MAIN LINE IN HORIZONTAL POSITION ONLY. (n
(PER LATEST DEPT. OF HEALTH APPROVED LIST OF BACKFLOW PREVENTION DEVICES) ( W
BOTTOM OF DDCVA SHALL BE A MINIMUM OF 24 INCH ABOVE FLOOR LEVEL AND
NOT HIGHER THAN 3 FEET MAXIMUM. INSTALL 3 CONCRETE PADS OR ADJUSTABLE PIPE 4
SUPPORT COLUMNS UNDER DDCVA O
9- O.S & Y VALVES TO BE RESILIENT SEATED WITH TAMPER SWITCHES.
ADD WIRING IN ACCORDANCE WITH L & I
10- METERED 3/4 INCH BY-PASS DCVA - BY-PASS METER SHALL BE A 3/4 INCH
"SENSUS-ECR" SR POSITIVE DISPLACEMENT METER EQUIPPED WITH A REMOTE
READ SENSOR PLATE MOUNTED ON THE OUTSIDE OF THE BUILDING WALL.
11- SWING TYPE GRAVITY CHECK VALVE, FLANGE WITH BALL DRIP IN VAULT
12- 4"x 4" x 6" BULL, ELBOW, THREADED W4ft31131?2
13- UL LISTED FIRE DEPT. CONNECTION, UL LISTED BREAK AWAY CAPS, LOCATE WITHIN
50 FEET MAXIMUM OF A PUBLIC FIRE HYDRANT.
AFTER FIELD INSTALLATION, MAIN DDCVA AND BY-PASS DCVA MUST BE TESTED
SATISFACTORILY BY A DEPARTMENT OF HEALTH CERTIFIED BACKFLOW ASSEMBLY
TESTER. TEST REPORT MUST BE SUBMITTED TO CITY OF RENTON WATER UTILITY
ENGINEERING DEPARTMENT PRIOR TO ACTIVATION OF NEW LINE.
INSTALL BRASS PLUGS AT ALL TEST COCKS.
EDITED TEXT
REMOVED VALVES, EDITED TEXT
PERIMETERS OF MINIMUM CLEARANCES TO BE
PAINTED ON FLOOR IN WHITE ENAMEL PAINT
STRIPE, WITH 2 INCH STENCILED BLACK LETTERS
TO SAY: "DO NOT BLOCK ACCESS"
DDCVA MUST BE INSTALLED IMMEDIATELY AFTER
PIPE PENETRATION THROUGH BUILDING FLOOR SLAB.
ROOM IN WHICH DDCVA IS LOCATED SHALL:
A. HAVE FLOOR DRAIN CONNECTED TO THE SANITARY SEWER SYSTEM.
B. HAVE A HEATING SYSTEM (40' F MIN. TEMP.) NO HEAT TAPE
C. NOT BE USED FOR STORAGE AROUND THE DDCVA
D. HAVE CLEARLY DELINEATED ACCESS WAYS TO DDCVA AND PIV9.
A RIGHT -OF -ENTRY AGREEMENT MUST BE GRANTED TO THE
CITY OF RENTON FOR INSPECTION OF THE DDCVA
AIJD METER.
SEPARATE FIRE SPRINKLER PLANS INCLUDING INSTALLATION OF DDCVA
MIDST BE SUBMITTED TO RENTON FIRE PREVENTION DEPARTMENT FOR
REVIEW AND APPROVAL.
A SEPARATE FIRE SPRINKLER PERMIST IS REQUIRED.
24 INCH, MINIMUM -- -
36 INCH MAXIMUM
FINISH FLOOR LEVEL
ELEVATION VIEW OF DDCVA
INSIDE BUILDING INSTALLATION FOR
3 INCH AND LARGER
DETECTOR DOUBLE CHECK VALVE ASSEMBLY
*N�
IIR CITY OF RENTON
STANDARD PLANS
LST DATE:.
DWG. NAME:. SP PAGE:.
SHEET: 7 OF: 7