FIRE HYDRANT SHALL BE COREY-TYPE EQUAL TO IOWA F-5110
OR COMPRESSION TYPE SUCH AS CLOW MEDALLION; M do H 929
AND MUELLER SUPER CENTURION 200 WITH 6" MECHANICAL JOINT
INLET WITH LUGS.
5-V4" MAIN VALVE OPENING. TWO 2-1/2" HOSE CONNECTIONS
NA TTjiONAL STANDARD THREADS. 4" PUMPER CONNECTION CITY OF
SEATTLE THREADS WITH A STORTZ ADAPTOR, 4" SEATTLE THREAD
X 5" STORTZ, ATTACHED WITH 1 /8" STAINLESS STEEL CABLE.
1-I ; PENTAGON OPERATING NUT. FIRE HYDRANT TO BE
PAINTED WITH TWO COATS OF PAINT. PRESERVATIVE
PAINT No. 43-655 SAFETY YELLOW OR APPROVED EQUAL.
PUMPER CONNECTION TO FACE ROADWAY ASSEMBLY.
FIRE HYDRANT EXTENSION TO BE USED IF REQUIRED.
CONCRETE BLOCKING
RENTON PLACE DIVISION III
THE NORTHWEST QUARTER OF SECTION 18, T23N, RSE, W.M.
CITY OF RENTON, KING COUNTY, WASHINGTON
-18" TO 20" BEHIND BACK OF CURB
OR 12" BEHIND BACK OF SIDEWALK
THAT IS ADJACENT TO CURB
TWO-PIECE CAST IRON VALVE BOX WITH LUG TYPE COVER.
EQUAL TO OLYMPIC FOUNDRY CO. STANDARD 8" TOP SECTION WITH
REGULAR BASE SECTION LENGTH TO FIT. VALVE NUT EXTENSION
AS REQUIRED (SEE DWG BR46 / PAGE 8090).
RAISED PAVEMENT MARKER TYPE 88 A8
STIMSONITE TWO-WAY BLUE.
J CONCRETE BLOCKING
CAST IRON TEE. WITH 6" FLANGE SIDE OUTLET.
6" GATE VALVE (FL X MJ) AWWA C-509, RESILIENT SEAT
�- „1117 6" DUCTILE IRON PIPE, CLASS 52 CEMENT LINED, LENGTH TO FIT TWO 3/4"
STEEL TIE RODS. SEE STD DETAIL FOR TIE RODS,
16" x 8" x 4" MININUM
CONCRETE BLOCK
LEVEL ALL 6ROU1,10 UNDER HYDRANT 1 /3 CU. YD. WASHED DRAIN ROCK (3" TO 3/8")
MIN 3' RADIUS FIRE HYDRANT ASSEMBLY
- LEVEL ALL
5" STORTZ MIN 3' RADIUS GROUND
ONE MAN ROCK
1
6p
CUT JL
HYDRANT LOCATION IN CUT OR FILL
FIRE HYDRANT ASSEMBLY DETAIL
PRV STATION
SPLASH BLOCK SEE DETAIL SHEET
90' BEND
90' BEND WITH
WITH THRUST
THRUST BLOCK
BLOCK
ISOLATION - I- 2' MIN. -I 2' MIN ISOLATION
VALVE
4' MIN VALVE
FLOW
FLOW
Ll TEE WITH /IN TEE WITH
-LINE ZONE VALVE
THRUST
BLOCK ( THRUST BLOCK
(NORMALLY CLOSED)
STANDARD PRV STATION SITE PLAN
GENERAL
1.
NOTES
The concrete vault shall be either a precast vault made by Utility Vault
Co. or equal as specified in the Standard Details, or shall be cast -in -
place with 8" walls and slabs. All joints shall be sealed so vault will
remain watertight.
2.
The vault cover shall be three 3' x 3' spring loaded hinged steel plate,
lockable doors with recessed lift handles, as made by Utility Vault Co. or
approved equal.
3.
Pipe supports shall be approximately 8" to 10" square. They shall be
concrete block or poured -in -place concrete construction.
4.
The vault shall contain one ladder constructed of galvanized steel.
A detail plan of location and construction shall be submitted to City
prior to Installation.
5.
The exterior of the vault shall be sealed with two coats of ATCO
Bitumastic No. 2221.
6.
The interior walls and ceiling of the vault shall be painted with two
coats of Koppers Ramuc Utility Enamel not, or approved equal. The floor
shall not be painted.
7.
The piping and equipment in the vault shall be given a complete field coat
of InertRust Penetrating Primer No. 621 or approved equal. Two finish
coats of Torex 800 Enamel, or approved equal, shall be applied over the
field coated primer.
8.
The Standard PRV Station Site Plan shall be used for all new PRV station
construction except when limited right-of-way or existing buildings are
restrictive. In such cases, and with City approval, the in -line option
may be used.
9.
All isolation and zone valves outside the PRV station shall be provided
with a valve box when Valves are 10" in size or smaller or a valve chamber
when valves are 12" in size or larger.
12 96 REFORMAT TO 11"x17"
DATE RI
-A/J*
PRV STATION SITE PLAN
SPLASI'
THRUST
RESTRAIN
COLLAR
FLOW -
WATER MAIN
FIRE HYDRANT ASSEMBLY DETAIL
Y
-0
�
ADOPTED
CITY OF RENTON
♦( ♦
STANDARD PLANS
F N O LST DATE: 12/96
DWG. NAME: BR24 SP PAGE: B102
PRV STATION
SEE DETAIL SHEET
„�
FLANGE FOR FUTURE
BY-PASS (MJxMJxFL)
PRV STATION SITE PLAN IN -LINE OPTION
TRUST
:STRAINT
JLLAR
FLOW
10. Pressure gouges shall be provided on both inlet and outlet pipes in the
PRV vault. Secondary gauges shall be mounted on the ceiling in easy view
to be read from outside the vault. Gauges shall read from 0-300 psi.
Gauge installation shall include petcock between pipe and gauge.
11. Joints on all valves and fittings outside the vault shall be mechanical
joints unless otherwise specified. Joints on valves and fittings inside
vault shall be flanged or screwed as specified.
12. Vault drain shall be piped to the nearest storm drain sewer or open
drainage ditch in lieu thereof. If no storm drain or drainage ditch is
available, vault shall be constructed with a sump on the outlet side of
the vault. A sump pump shall be installed and the discharge from the pump
released onto a concrete pad outside the vault.
13. Cut 3" thick x 5" wide ethafoom 220 or equal to a length necessary to fit
the size of pipe installed and compressed Into place. The contractor
shall make sure the foam is compacted tightly between pipe and vault wall
with no voids. Lightly grout interior around pipe.
14. Pipe extending through vault shall be ductile iron, class 53,
cement lined.
STANDARD PRV STATION SITE PLAN
AND PRV STATION SITE PLAN
IN -LINE OPTION
Y_ a ADOPTED
V/ � CITY OF RENTON
. .
STANDARD PLANS
F N O LST DATE: 12/96
ocv oat DWG. NAME: BR53 SP PAGE: B098
BY PR
FLOW DUCTILE IRON PIPE
1 - (FL x PE) 36" MIN. LENGTH
I- 24" MIN.
4" THICK CONCRETE
SPLASH BLOCK
THRUST RESTRAINT COLLAR FOR
IN-UNE PRV OPTION. SEE DETAIL.
BEEHIVE STRAINER-,
2" -
12" -1
a" �
36" FOR PIPES
I
10" do SMALLER,
48" FOR PIPES
12" do LARGER
FLOWrr
4" MIN.
UTILITY VAULT CO. VAULT FLOW
OR APPROVED EQUAL
THRUST BLOCK (TYP.)
UNDISTURBED SOIL
a -
it 10 El
INSTALL NON -SHRINK
EPDXY GROUT
rc
12 9 11 °
_----THRUST RESTRAINT COLLAR FOR
• IN -LINE PRV OPTION. SEE DETAIL
PRV VAULT - PLAN VIEW
i3 UTILITY VAULT CO. VAULT
OR APPROVED EQUAL
13 4" MIN.
UTILITY VAULT CO. VAULT
OR APPROVED EQUAL
153.30 FINISH GRADE
GALVANIZED u
11- 12 n STEEL I
,✓ (1l LADDER
'all 10NNIIIIII1111
2" TYP.
FLOW
149.47
12" MIN
6 0 S.D. S
PRV VAULT - ELEVATION 2 1.0%
INLET t OUT-
LET PIPE
SIZE (IN)
O
PREV SIZE
(IN
O
AUZILLARY
W� V SIZE
(6'I)
O
TEE
)
SIZE M)
O
ISOLATION GATE VALVE
O FLANGED
SIZE IN) ADAPTOR
O©
0.1. PIPE CL 52
(FL x P�
1H M)
O
GATE VALVE, MON. TEE k
SEND SIZE (1N
®000
PRESSURE
RE11EF VALVE
SIZE (IN)
0
UILITY VAULT CO. VAULT
NOOEL N0.
(OR APPROVED EQUAL)
0
UTILITY VAULT CO.
VM1LT COVER (011�
0 MC6 (ORAPPROVED E )
AL
0
6
6
1-1/2
Gx4
6
36
1-1/2 (SE)
1-1/2 (SE)
5106-LA
3-332P
8
8
2
8x4
8
24
2 (SE)
2 (SE)
5106-LA
3-332P
10
10
2-1/2
10xe
10
24
2-1/2 (SE)
2-1/2. (SE)
612-4A
3-332P
12
12
1 3
12.0
12
16
3 (SE)
3 (SE)
612-L.A
3-332P
14
14
14x4
14
24
4
4 (FL)
814-LA
3-332P
to
18
[:::!4
16x4
16
18
4 NO U ON
4 (FL)
814-LA
3-332P
12 96
REFORMAT TO 11'x17"
DATE
I REVISION
PRESSURE REDUCING VALVE
RIGID FLEXIBLE
(D.I., CONC.) (CPEP, CMP, PVC)
PROVIDE NEAT, STRAIGHT LINE WHERE
MATCHING EXISTING PAVEMENT,
TACK do SEAL EDGES 3' COMPACTED THICKNESS ASPHALT
CONCRETE PAVEMENT -CLASS 'B"
EXISTING SECTI«� STRUCTURAL
BACKFILL PAVED AREAS
AND WITHIN R.O.W. CRUSHED
SURFACING TOP COURSE,
W.S.D.O.T. 9-03.9(3) 95%
COMPACTION, 6" MAXIMUM
LIFTS. UNPAVED AREAS NATIVE
MATERIAL OR GRAVEL BACKFILL
FOR PIPE BEDDING 90%
COMPACTION, 12' MAX. LIFT
8'TYP
j d d
0 0
4 C
d '
' MIN.
" PER WSDOT STD.
NOTE:
SUBMERSIBLE PUMP 12VDC WARREN-RUPP
SPA 1-1/2 E WHERE STORM DRAIN IS ABOVE
FLOOR ELEVATION OF PRV VAULT.
PLAN FOR ELECTRICAL CONDUIT SHALL BE
SUBMITTED FOR SPECIFIC USAGE.
PRESSURE SETTINGS
IN = 149.6
OUT = 65.2
PRV VAULT - SECTION
PRESSURE REDUCING VALVE
Y p ADOPTED
U� ClT1r OF RENTON
♦�
STANDARD PLANS
F N O LST DATE: 12/96
DER T
'PR DWG. NAME: BR52 SP PAGE: B097
I�t-3I2309
RECORD NOTE
THESE RECORD DRAWINGS HAVE BEEN PREPARED BASED ON INFORMATION SUBMiTTE[
IN PART, BY OTHERS. MILE THIS INFORMATION IS BELIEVED TO BE RELIABLE, AHBL
IS NOT RESPONSIBLE FOR ITS ACCURACY, OR ERROR OR OMISSIONS WHICH MAY
HAVE BEEN INCORPORATED INTO THIS DOCUMENT AS A RESULT. THOSE RELYING
ON THIS RECORD DOCUMENT ARE ADVISED TO OBTAIN INDEPENDENT VERIFICATION
OF ITS ACCURACY BEFORE APPLYING IT FOR ANY PURPOSE.
PIPE BEDDING PER WSDOT -
9-0116 95% COMPACTION 1.5 X I.D. + 18" a¢ '
PIPE AS SPECIFIED
24" MIN. ON PLAN OR SPECS. W .
NOTES:
1. NATIVE BACKFILL MATERIAL AT UNPAVED AREAS SHALL NOT HAVE PARTICLE SIZE
GREATER THAN 1" WITHIN 6" OF THE PIPE OR THE CONTRACTOR HAS THE
OPTION TO USE GRAVEL BACKFILL PIPE BEDDING CONFORMING TO 9-03.12 (3).
BEDDING BACKFILL PIPE 1:,V.
N TRENCHES TYP. FLEXIBLE rEkA f {
PAVEMENT RESTORATION r
NOT TO SCALE 025MID13
RECOMMENDED
FOR APPROVAL
BY
BY
BY
CALL 48 HOURS 1 AS -BUILT
BEFORE YOU DIG
1-"800-424-5555
NO.
CHECKED FOR COMPLIANCE
TO CITY STANDARDS
DATE
DATE
DATE
MW 3/ 2/04
REVISION
BY I APPR. I DATE
comer
OF WAS/J j� O
29010
�SSIONAL �Gti �'Y
EXPIRES 6
REUSE OF DOCUMENTS
THIS DOCUMENT HAS 6EQ1 SIGNED ELECTRONICALLY IN
ACCORDANCE WITH WAC 196-23-070 AND CHAPTER
19.34 RCW. UNAUTHORIZED ALTERATION OF ANY OF THE
14FORMATION ON THIS DOCUMENT WILL INVALIDATE THE
DOCUMENT, NY CERTIFICATION AND SIGNATURE.
THE IDEAS AND DESIGNS INCORPORATED HEREIN, AS AN
INSTRUMENT OF PROFESSIONAL SERVICE, IS THE
PROPERTY OF AHOL AND IS NOT TO BE USED, IN WHOLE
OR IN PART, FOR ANY OTHER PRQECT WITHOUT THE
WRITTEN AUTHORIZATION OF AH&.
Q
W
0
0
Cn
W
O
Z
W
Q
i
L1J
V) U)
LJJ
Z Ld
ZF 3 3'
3
JU > o-
LLJ
.4 Q
:D Egg
V) LJ V)
ry
Ir
LiIQ�
Eli UZ
Z ®� to o a
�ZZt
W J
CITY OF
RENTON
N oQ
DEPARTMENT OF PUBLIC WORKS
o
O3
WATER NOTES &
DETAILS
19
z m
0
m 21
o
o
O o
DESIGNED:
DATE: 3/12/04
FILE NAME: 77��_�?�
DRAWN:
M
PAGE:_
CHECKED:
SCALE: AS SHOWN
FIELD BOOK:_
0��
APPROVED:
DIRE rGR OF PUM-IC WORKS
SHEET: 19 OF: 19