HomeMy WebLinkAboutWTR2703131.9SECTION 3, TOWNSHIP2 N®, RANGE 4 E, W.M. zz v 0 LLJ � w� o u LA L1.-4 �2 I� W � 1 my o 03 'c a ® "E 3Q v W N H Qd \c lie i • r o M � N a o a i Q 0 0 � W i x m i 0 M N 0 Li w 0 0 Z Ib CUT -IN AND INSTALL: TEMPORARY 8" CAP(MJ) TEMPORARY 2" B.O.V. ASSY. TEMPORARY BLOCK REMOVE EX. 8" D.I. W. TO NORTH, SEE PLAN �iiffiv♦ ♦ ♦ W WATER UTILITY NOTES AND SPECIFICATIONS 1. THESE NOTES SHALL APPEAR FOR PROJECTS FOR THE WATER UTILITY 2. ALL WORK MATERIAL SHALL BE IN CONFORMANCE WITH THE STANDARDS AND SPECIFICATIONS OF THE CITY OF RENTON PLANNING/BUILDING/PUBLIC WORKS DEPARTMENT AND THE 1996 EDITION OF THE WSDOT/APWA STANDARDS AND SPECIFICATIONS, AS APPROVED AND MODIFIED BY THE CITY OF RENTON IN THE RENTON STANDARD PLANS & SPECIFICATIONS. A SET OF APPROVED PLANS SHALL BE KEPT ON SITE AT ALL TIMES DURING CONSTRUCTION. 3, THE HOURS OF WORK IN THE STREET RIGHT OF WAY SHALL BE LIMITED TO 8:30 AM TO 3:30 PM ON WEEKDAYS UNLESS OTHERWISE APPROVED IN WRITING BY THE PUBLIC WORKS DEPARTMENT AT (425) 430-7301, THE POLICE DEPARTMENT, FIRE DEPARTMENT, AND 911 SHALL BE NOTIFIED 24 HOURS IN ADVANCE OF ANY WORK IN THE RIGHT OF WAY. 4, ALL LOCATIONS OF EXISTING UTILITIES SHOWN ARE APPROXIMATE AND IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY TO VERIFY THE TRUE AND CORRECT LOCATION SO AS TO AVOID DAMAGE OR DISTURBANCE. FOR UTILITY LOCATES CALL 48-HOUR LOCATORS 800-424-5555. 5. AN APPROVED TRAFFIC CONTROL PLAN IS REQUIRED TO BE SUBMITTED AT THE PRE -CONSTRUCTION MEETING. 6. ALL WATERMAIN PIPE IS TO BE CEMENT LINED DUCTILE IRON PIPE CONFORMING TO AWWA C110 AND C111 OR LATEST REVISION, THICKNESS CLASS 52. CEMENT MORTAR LINING AND SEAL COATING SHALL CONFORM TO AWWA C104 OR LATEST REVISION. PIPE JOINTS TO BE PUSH -ON OR MECHANICAL JOINT. BEDDING TO BE CLASS C. ALL DUCTILE IRON PIPE AND FITTINGS SHALL BE POLYETHYLENE WRAPPED PER ANSI/AWWA C105/A21.5-93 STANDARDS. 7. CAST IRON AND DUCTILE IRON FITTINGS SHALL BE CEMENT LINED, PRESSURE RATED AS NOTED ON PLANS, AND IN ACCORDANCE WITH AN C110/A21.10-87, CEMENT LINING SHALL BE IN ACCORDANCE WITH ANSI/AWWA C104/421 /4-90. IF FITTINGS ARE 3 TO 12 INCHES IN DIAMETER AND HAVE MECHANICAL JOINTS, THE FITTINGS SHALL IN ACCORDANCE WITH EITHER ANSI/AWWA C110-A21.10-87 OR ANSI/AWWA C153/A21.53-94. THREE (3) INCH TO 12 INCH DIAMETER FITTINGS, WHICH HAVE MECHANICAL JOINTS AND/OR FLANGED JOINTS, SHALL BE IN ACCORDANCE WITH ANSI/AWWA C110/A21.10.87 OR A COMBINATION OF ANSI/AWWA C110/A21.10.87 AND ANSI/AWWA C153/A21.53-94 SUCH THAT THE PORTION OF THE FITTING WITH A MECHANICAL JOINT(S) MAY BE WITH ANSI/AWWA C153/A21.53-94 AND THAT PORTION OF THE FITTING WITH FLANGED JOINTS) SHALL BE IN ACCORDANCE WITH AWWA C110/A21.10-87. ACCEPTANCE TESTING IN ACCORDANCE WITH SECTION 53.53 OF ANSI/AWWA SECTION 10-4.3 OF ANSI/AWWA C110/A21.1087 SHALL BE OBTAINED BY THE CONTRACTOR AND TRANSMITTED TO THE OWNER. 8. GATE VALES SHALL BE IRON BODY, BRONZED -MOUNTED, DOUBLE DISC WITH BRONZE WEDGING DEVICE AND 0-RING STUFFING BOX (AWWA C500) OR OF RESILIENT SEATED TYPE (AWWA C509). VALVES SHALL BE DESIGNED FOR A MINIMUM WATER OPERATING PRESSURE OF 200 PSI, GATE VALVES SHALL BE CLOW LIST 14, MUELLER COMPANY NO. A2380 OR M & H. 9, FIRE HYDRANTS SHALL BE COREY TYPE (OPENING WITH THE PRESSURE) OR COMPRESSION TYPE (OPENING AGAINST PRESSURE) CONFORMING TO AWWA C-502-85 WITH A 6 INCH MECHANICAL JOINT INLET AND A MAIN VALVE OPENING (M.V.O.) OF 5-1/4 INCH, TWO 2-1/2 INCH HOSE NOZZLES WITH NATIONAL STANDARD THREADS 7-1/2 THREADS PER INCH AND ONE 4 INCH PUMPER NOZZLE WITH THE NEW SEATTLE PATTERN 6 THREADS PER INCH, 60 DEGREES V. THREADS: OUTSIDE DIAMETER OF MALE THREAD 4.875 AND ROOT DIAMETER 4.6263, HYDRANTS SHALL HAVE A 1-1/4 INCH PENTAGON OPERATING NUT OPENED BY TURNING COUNTER CLOCKWISE (LEFT). 10. THE TWO 2-112 INCH HOSE NOZZLES SHALL BE FITTED WITH CAST IRON THREADED CAPS WITH OPERATING NUT OF THE SAME DESIGN AND PROPORTIONS AS THE HYDRANT STEM NUT. CAPS SHALL BE FITTED WITH SUITABLE NEOPRENE GASKETS FOR POSITIVE WATER TIGHTNESS UNDER TEST PRESSURES. 11. THE 4 INCH PUMPER NOZZLE SHALL BE FITTED WITH A STORZ ADAPTER, 4 INCH SEATTLE THREAD X 5 INCH STORZ. STORZ ADAPTER SHALL BE FORGED AND/OR EXTRUDED 6061-T6 ALUMINUM ALLOY, HARDCOAT ANODIZED. THREADED END PORTION SHALL HAVE NO LUGS AND TWO SET STORZ FACE TO BE METAL, NO GASKET TO SCREWS 180 DEGREES APART. WEATHER. STORZ CAP TO HAVE SYNTHETIC MOLDED RUBBER GASKET, AND SHALL BE ATTACHED TO HYDRANT ADAPTER WITH 1/8 INCH, COATED, STAINLESS STEEL, AIRCRAFT CABLE. 12. FIRE HYDRANTS SHALL BE PAINTED WITH TWO COATS OF PAINT. PRESERVATIVE PAINT NUMBER 43-655 SAFETY YELLOW OR APPROVED EQUAL. **Fw- Al -lrt EX. 8" D.I. W. SUFFICIENT DISTANCE TO ALLOW FOR QED CONNECTION TO EXISTING MAIN, 10'± INSTALL: )RARY 8" PLUG (MJ) W/2" TAP TEMPORARY 2" B.O.V. ASSY. TEMPORARY BLOCK 8" VERTICAL 2 - 8" ONE W/2" TAP & 2" PLUG NEW WATER MAIN TESTING DETAIL 13, PUMPER CONNECTION TO FACE ROADWAY ASSEMBLY. 14. FIRE HYDRANTS SHALL BE INSTALLED PER CITY OF RENTON STANDARD DETAIL FOR FIRE HYDRANTS, LATEST REVISION. - F"$'GRADE 15, ALL WATERMAINS 10 INCHES AND SMALLER TO MAINTAIN A MINIMUM COVER OF 36 INCHES BELOW FINISH GRADE. ALL WATERMAIN 12 INCHES AND LARGER SHALL BE AT A MINIMUM OF 48 INCHES BELOW FINISH GRADE. n WHERE UTILITY CONFLICTS OCCUR, WATERMAINS ARE TO BE LOWERED TO ' � f, CLEAR. . NEW � �rLE �`1' 16. ALL WATERMAINS 6 INCHES AND LARGER IN DIAMETER SHALL BE WATERMAIN CLEANED WITH PIPE CLEANING "PIGS" PRIOR TO DISINFECTION. THE "POLY PIGS" SHALL BE GIRARD INDUSTRIES AQUA SWAB -AS OR APPROVED EQUAL iA r` LOQP D,OV TO EN�RUNF 2 LB/CU. FT, DENSITY FOAM WITH 90A DUROMETER URETHANE RUBBER PR WATER A' T �` PRO:4IaIE STACK IN <OF-I=1;R COATING ON THE REAR OF "PIG" ONLY. SERE LNE 10 METM i 17. "PIGS" SHALL BE CYLINDER SHAPED WITH BULLET NOSE OR SQUARE 1 v £4RP?DRATION 3TOP. FORD TAPEr.tO IaI? KI IC I. P!11_K ,"N? I,1{4F1I1DD) END. THE CONTRACTOR WILL PERFORM THE CLEANING OPERATION. fig„ F""' 18. ALL WATERMAINS AND SERVICES SHALL BE PRESSURE TESTED TO A MINIMUM OF 200 PSI OR 150 PSI OVER OPERATING PRESSURE, IN ACCORDANCE WITH THE SPECIFICATIONS OF THE CITY OF RENTON AND THE WASHINGTON STATE HEALTH DEPARTMENT. ALL PRESSURE TESTING SHALL BE DONE IN THE PRESENCE OF A REPRESENTATIVE OF THE CITY OF �isTlt.1 4 RENTON. THE QUANTITY OF WATER LOST FROM THE MAIN SHALL NOT I=^.IR:f EXCEED THE NUMBER OF GALLONS PER HOUR AS LISTED IN CITY OF-° RENTON STANDARD PLANS & SPECIFICATIONS 7-11.3(11), THE LOSS IN PRESSURE SHALL NOT EXCEED 5 PSI DURING THE 2 HOUR TEST PERIOD. ,;, 1 =' - I 19. ALL WATERMAINS AND SERVICES SHALL BE DISINFECTED BY THE FOR S ^: ACE FROM I >ngrc STEED Ii INJECTION OF A 50 PPM (MINIMUM CONCENTRATION) CHLORINE/WATER A,SEIETG £ CEMENT OR I WA -ER MANS SOLUTION. DRY CALCIUM HYPOCHLORITE SHALL NOT BE PLACED IN THE TAL SEVK1a LAf'F� �' ::cYK.� �A� PIPE AS LAID. CHLORINE SHALL BE METERED/INJECTED IN ACCORDANCE!AL T ' v "` WITH SECTION 7-11.3(12)E OR 7-11.3(12)F OF THE STANDARD SPECIFICATIONS REFERENCED ABOVE. N iTE: 'ME CENTFlt OF 'HE H(XE MUST BE AT 20. A PRE -CONSTRUCTION CONFERENCE IS REQUIRED PRIOR TO ANY LEST t FR01A tIN ERNEA Ri UNLESS CONSTRUCTION. A MINIMUM OF FIVE 5 WORKING DAYS NOTICE IS ( )N ' RIB SPACING ALUDY6 TFiv NOT TO IIAGAINST , C. EIN SIDE � CRE FOR SCHEDULING. -HAREQUIRED 21. TWENTY-FOUR (24) HOURS NOTICE WILL BE REQUIRED PRIOR TO ash ffiax fixazftA STARTING NEW CONSTRUCTION. 22. IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY TO SECURE ALL NECESSARY PERMITS PRIOR TO STARTING CONSTRUCTION, 23. INSTALLATION OF CORPORATE STOPS, WATER SERVICES, LINES AND METERS SHALL NOT BE DONE UNTIL ALL SERVICE AGREEMENTS, METER APPLICATIONS, CONSTRUCTION PERMITS, AND PAYMENT OF FEES HAVE BEEN MADE TO THE CITY OF RENTON. 24. ALL CONNECTION TO EXISTING MAINS IS TO BE ACCOMPLISHED BY THE CITY OF RENTON, EXCEPT WET TAPS, WHICH MAY BE MADE BY APPROVED WET TAP CONTRACTORS WITH PRIOR APPROVAL FROM THE PUBLIC WORKS DEPARTMENT. ALL NECESSARY EXCAVATION AND MATERIALS ARE TO BE SUPPLIED BY THE CONTRACTOR AND BE ON -SITE PRIOR TO CITY NOTIFICATIONS. 25. INSPECTION WILL BE ACCOMPLISHED BY A REPRESENTATIVE OF THE CITY OF RENTON. IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY TO NOTIFY DEVELOPMENT SERVICES TWENTY FOUR (24) HOURS IN ADVANCE OF BACKFILHNG ALL CONSTRUCTION. THE CONTRACTOR, AS WELL AS THE ENGINEERS, SHALL KEEP AS -BUILT DRAWINGS. 26. CONTRACTOR TO PROVIDE PLUGS AND TEMPORARY BLOW -OFF ASSEMBLIES FOR TESTING AND PURITY ACCEPTANCE PRIOR TO FINAL TIE-IN. 27, ALL JOINT RESTRAINT SYSTEMS (SHACKLE RODS, NUTS, BOLTS, ETC.) SHALL BE AS MANUFACTURED BY THE STAR MANUFACTURING COMPANY OF COLUMBUS OHIO, OR EQUAL, APPROVED IN WRITING BY THE PUBLIC WORKS DEPARTMENT. 28. ASPHALT AND CONCRETE STREET PAVING SHALL BE SAWCUT TO A MINIMUM DEPTH OF TWO (2) INCHES. OIL MAT STREETS MAY BE SPADE CUT. ALL SURFACE CONCRETE, PAVEMENT, SIDEWALKS, CURB, GUTTERS, AND DRIVEWAY APPROACHES SHALL BE SAWCUT TO A MINIMUM DEPTH OF TWO (2) INCHES OR REMOVED TO AN EXISTING EXPANSION JOINT. 29, A TEMPORARY COLD MIX ASPHALT PATCH SHALL BE PLACED ON THE DAY OF INITIAL EXCAVATION WITH A PERMANENT, SEALED PATCH TO BE PLACED, TO CITY OF RENTON POLICY, WITHIN 10 DAYS. CALL FOR SUBGRADE INSPECTION PRIOR TO PLACEMENT OF FINAL PATCH. * 30, FOR CITY PROJECTS SUCH AS TELEMETRY CONDUIT, THE PVC PIPE USED SHALL BE ALL CHEMICAL PROCESS LINES SHALL BE SCHEDULE 80 PVC PIPE. SCHEDULE 40 IN UNIMPROVED AREAS AND SCHEDULE 80 PVC PIPE UNDER IMPROVED AREAS. 31. ALL NEW WATER MAIN SHALL BE POLYWRAPPED & BONDED FOR ELECTRICAL CONDUCTIVITY. FIRE HYDRANT SHALL BE COREY-TYPE EQUAL TO IOWA F-5110 OR COMPRESSION TYPE SUCH AS CLOW MEDALLION; M & H 929 AND MUELLER SUPER CENTURION 200 WITH 6" MECHANICAL. JOINT INLET WITH LUGS. 5-1/4" MAIN VALVE OPENING TWO 2-1/2" HOSE CONNECTIONS NATIONAL STANDARD THREADS. 4" PUMPER CONNECTION CITY OF SEATTLE THREADS WITH A STORTZ ADAPTER, 4" SEATTLE THREAD X 5" STORTZ, ATTACHED WITH 1/8" STAINLESS STEEL CABLE. 1-1/4" PENTAGON OPERATING NUT. FIRE HYDRANT TO BE PAINTED WITH TWO COATS OF PAINT. PRESERVATIVE PAINT No. 43-655 SAFETY YELLOW OR APPROVED EQUAL. PUMPER CONNECTION TO FACE ROADWAY ASSEMBLY. FIRE HYDRANT EXTENSION TO BE USED IF REQUIRED. CONCRETE BLOCKING REMOVE: SEW 8" D.I. W TEMPORARY 8" CAP(MJ) 36" MIN. COVER) TEMPORARY 2" B.O.V. ASSY. -)EE PLAN/PROFILE TEMPORARY BLOCK x24" PLA`-UC MCIFIR NOX EQUAI 10 MID TA E5 PLAS71C. !^,t SC,7 SE'' ' . MSOCr '32=i f olTFi 7 5' 'I110N CVCBLE SR0N Cok"ChD PLATE COVER 14x,:4" EXiAL TO WO AIES PLASTICS, IN'.. MSC.,O 1 ,2A- R WiTt- i - {` I HDIL.E r:3R 'I,'UCHRFA0 P1. LID ;SEE faL-VAR A -A) ---.-- s �1 f} � L; SIDEWALk ,15 MW MIN COVER REMOVE: TEMPORARY 8" PLUG (MJ) W/2" TAP INSTALL: \_TE RARY 2" B.O.V. ASSY. 8± LF 8" D.I. RARY BLOCK 11-1/4° BEND (MJxFL) 1 - 8" SLEEVE (MJ) NOTE: INSTALL NEW METER BOX BEHIND NEW SIDEWALK OR INSTALL COPPER PAST PROPERTYI TAILPIECE MINIMUM 1 NEW WATER MAIN CONNECTION DETAIL T T Y P} t wAr R 1 "L 36" AN ° COVER Tir F "K` SOFT -OF ;7_ IF SER1 4CE UNE TO HCAJS} sT f �-'3/4 - OR i" T;) ICE IN sTA€ I.€.iB N 1,4E F jiuru f ! A,°. ANIZE`D R54ALL FC'* C14-34 OR 44 �'DT1' s _.; x 0 I C N c� 1_ IN313 sCg?'�Fxi FiEt'2 R f �x3 4 ;TIRD vH 2 UN M•O.ONAI BRASS- 2146. OR §aI P .42. --3/4 OiIPERT ER �1t 1 sL vH72_15W-� McD"Nh.I,D BRAS4'..)W- C4 OR VUELLET,,' BOT4 m E ; - PAD,,-'C , ALLxs . tali €A f E',4, 1_7 2- 64 NEAREST AND FFL , t" OF PIT 3/,4 w & WATtir t 0ED t iP` Oil' i OF vw STA"AW PIANO 4 F: BR41-TR SP OAGE: R106 �-18" TO 20" BEHIND BACK OF CURB OR 12" BEHIND BACK OF SIDEWALK THAT IS ADJACENT TO CURB \y TWO-PIECE CAST IRON VALVE BOX WITH LUG TYPE COVER. ®o EQUAL TO OLYMPIC FOUNDRY CO. STANDARD 8 TOP SECTION WITH ® ! REGULAR BASE SECTION LENGTH TO FIT. VALVE NUT EXTENSION AS REQUIRED (SEE DWG BR46 / PAGE B090). MAX. MIN. 2� ! RAISED PAVEMENT MARKER TYPE 88 A8 STIMSONITE TWO-WAY BLUE. 42" MIN. CONCRETE BLOCKING BURY C_ CAST IRON TEE. WITH 6" FLANGE SIDE OUTLET. 6" GATE VALVE (FL X MJ) AWWA C-509, RESILIENT SEAT %w � 6" DUCTILE IRON PIPE, CLASS 52 CEMENT LINED, LENGTH TO FIT TWO 3/4" \ STEEL TIE RODS. SEE STD DETAIL FOR TIE RODS. 16" x 8" x 4" MLNIMUMJ \ CONCRETE BLOCK LEVEL ALL GROUND UNDER HYDRANT '---1/3 CU. YD. WASHED DRAIN ROCK (3" TO 3/8") MIN, 3' RADIUS FIRE HYDRANT ASSEMBLY LEVEL ALL GROUND 5" STORTZ MIN. 3' RADIUS 1 ONE MAN ROCK 6� CUT FILL FIRE HYDRANT ASSEMBLY DETAIL HYDRANT LOCATION IN CUT OR FILL ADOPTED CITY OF RENTON STANDARD PLANS 12/96 Add valve not extension. Reformat to U x17' DCV DT LST DATE: 12/96 5/18/995 Revised Pum er Port DCV DT 12/15/9 Corrected text & Changed paint color RTM IT DATE REVISION BY APPR DWG. NAME: BR24 SP PAGE: B102 CHECKED FOR COMPLIANCE TO CITY STANDARDS Date 3 -Z 7-0� Date 3 Date BY BY 2" BEEHIVE STRAINER 2" OPEN PATTERN, RETURN BEND 2" GALVANIZED IRON PIPE FIELD LOCATE 2" UNION 2" CLOSE NIPPLE 17"x28" CONCRETE METER BOX WITH 3/8" STEEL DIAMOND CUT OPENING AS REQUIRED, 18" SHORT NIPPLE 7 PLATE COVER EQUAL TO FOG-TITE METER SEAL CO. NO.2 AFTER INSTALLATION, GROUT 2" UNION /I METER BOX. FIELD LOCATE. AROUND PIPE. 2"x2"x2" TEE +: 2" 90° BEND WITH CLOSE NIPPLE�� �' • "�• '� "' BETWEEN BEND AND TEE ! r BRONZE GATE VALVE, SCREWED EQUAL TO RED -WHITE VALVE CORP. 2" 90° ELBOW FIG NO, 280 2" GALVANIZED IRON PIPE TO FIT /, 0 2-2" 90° BENDS WITH CLOSE NIPPLE BETWEEN BENDS 61 2" GALVANIZED IRON PIPE -�-�c® o aq°�o 0 0 0 ®° CLOSE NIPPLE 18" LONG 12' MIN. o 0 -' ®o ® .- 00 ® �� � CORPORATION STOP 90" BEND, I.P. THREAD 00 0 o o $ ? o,oa TO COPPER, EQUAL TO FORD FB 500. 2" GALVANIZED IRON PIPE TO FIT 2" CAP WITH 1/8" HOLE 2" 90° ELBOW FOR DRAIN. AIR AND VACUUM VALVE 2" ASSEMBLY - APCO NO. 1452C OR EQUAL. WASHED GRAVEL, PASSING 1-1/2" AND RETAINED ON 1/4" MESH FOR DRAIN NOTE: AIR AND VACUUM RELEASE VALVE ASSEMBLY SHALL BE INSTALLED AT HIGHEST POINT OF LINE. IF HIGH POINT FALLS IN A LOCATION WHERE ASSEMBLY CANNOT BE INSTALLED, PROVIDE ADDITIONAL DEPTH OF LINE TO CREATE A HIGH POINT AT A LOCATION WHERE ASSEMBLY CAN BE INSTALLED. WATER MAIN 2" CLOSE 2" 90° ELBOW- CONCRETE BLOCKING TWO PIECE CAST IRON VALVE EQUAL TO OLYMPIC FOUNDRY CO. STANDARD 8" TOP SECTION, WITH REGULAR BASE SECTION LENGTH TO FIT. 1111111111111 2" GATE VALVE, SCREWED 2" GALVANIZED- \\ PIPE 12" LONG 2" CLOSE NIPPL BETWEEN CAP OR PLUG AND 2" 90° ELBOW INSTALL 4 MIL POLYETHYLENE - PLASTIC COVER OVER WASHED GRAVEL. CUT HOLE FOR PIPE DOUDLE STRAP SERVICE CLAMP WITH 2" IPS TAP TO FIT, EQUAL TO MUELLER CO. 2" AIR & VACUUM RELEASE VALVE ASSEMBLY Y ADOPTED CITY OF RENTON 2 STANDARD PLANS LST DATE:12/96 DWG, NAME: BR51 SP PAGE: B095 IF ADDITIONAL ADJUSTMENT IS REQUIRED, INSTALL 2-2" CLOSE NIPPLE AND 2-2" 90° BEND, SCREWED AT THIS POINT. FIELD LOCATE CONCRETE METER BOX 2" CLOSE NIPPLE 2" 90° ELBOW 2" GALVANIZED PIPE AS REQUIRED PLAN VALVE NUT EXTENSION AS REQUIRED (SEE DWG BR46 / PAGE B090) i� GROUND LINE CONCRETE SIDEWALK 3" MAX. 18" MAX. 10 CU. FT. WASHED GRAVEL PASSING 1-1/2" AND RETAINED ON 1/4" MESH FOR DRAIN ELEVATION � I I DATE I REVISIO_N. a�o,����F 132&j� /ONA L EXPIRES 9 JAN 2006 i '--',MP NOT VALID UNLESS SIGNED & DATED 2-1/2" NST (HOSE) BLOW -OFF HYDRANT EQUAL TO #78 KUPFERLE FOUNDRY CO. 2"x2"x2" TEE 2" CLOSE NIPPLE BETWEEN TEE AND 90° ELBOW. 2" 90° ELBOW 2" GALVANIZED PIPE 18" LONG PERMANENT 2" BLOW -OFF ASSEMBLY 2" CAP WITH 1/8" (FOR 8" MAINS AND SMALLER) TAP FOR DRAIN ADOPTED C17 OF RENTON STANDARD PLANS _ IST DATE:12/96 BY APPR' DWG. NAME: BR25A SP PAGE: B105 BY A&W DALEY-MORROW-POBLETE, INC. T26 AUBURN WAY N- AUBURN, WASHINGTON 98002 PHONE: 253333-2200, FAX: 253-333-22U6 incorporate CANNED OCT 0 8