WATER NOTES & SPECIFICATIONS:
1, THESE NOTES SHALL APPEAR FOR PROJECTS FOR THE WATER UTILITY.
0
0
z
z
w
0
V)
0
0
0
a-
w
x
x
w
z
Z
W
J
Cn
LiJ
O
Z
8d
Q
V �cv
C ao
W
Go
�z10
�.�ko
L Wz
:cv
E �v
O d 0
_ o
04�00
05 WW00
zw�
�zx�
s OE
a zo
M W2
2. ALL
WORK MATERIAL
SHALL BE IN CONFORMANCE WITH THE STANDARDS AND SPECIFICATIONS OF
THE CITY OF RENTON PLANNING/BUILDING/PUBLIC
WORKS
DEPARTMENT AND THE 1996 EDITION OF THE WSDOT/APWA
STANDARDS AND SPECIFICATIONS,
AS APPROVED AND MODIFIED BY THE CITY OF
RENTON
IN THE RENTON
STANDARD PLANS & SPECIFICATIONS. A
SET OF APPROVED PLANS SHALL
BE KEPT ON SITE AT ALL TIMES DURING
CONSTRUCTION.
3. THE
HOURS OF WORK
IN THE STREET RIGHT OF WAY SHALL BE
LIMITED TO 8:30 AM TO 3:30 PM
ON WEEKDAYS UNLESS OTHERWISE APPROVED IN
WRITING
BY THE PUBLIC
WORKS DEPARTMENT AT (425) 430-7301.
THE POLICE DEPARTMENT, FIRE
DEPARTMENT, AND 911 SHALL BE NOTIFIED 24
HOURS
IN ADVANCE OF
ANY WORK IN THE RIGHT OF WAY.
4. ALL LOCATIONS OF EXISTING UTILITIES SHOWN ARE APPROXIMATE AND IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY TO VERIFY THE TRUE AND
CORRECT LOCATION SO AS TO AVOID DAMAGE OR DISTURBANCE. FOR UTILITY LOCATES CALL 48-HOUR LOCATORS 800-424-5555.
5. AN APPROVED TRAFFIC CONTROL PLAN IS REQUIRED TO BE SUBMITTED AT THE PRE -CONSTRUCTION MEETING.
6. ALL WATERMAIN PIPE IS TO BE CEMENT LINED DUCTILE IRON PIPE CONFORMING TO AWWA C110 AND C111 OR LATEST REVISION, THICKNESS CLASS
52. CEMENT MORTAR LINING AND SEAL COATING SHALL CONFORM TO AWWA C104 OR LATEST REVISION. PIPE JOINTS TO BE PUSH -ON OR
MECHANICAL JOINT BEDDING TO BE CLASS C. ALL DUCTILE IRON PIPE AND FITTINGS SHALL BE POLYETHYLENE WRAPPED PER ANSI/AWWA
C105/A21.5-93 STANDARDS.
7, CAST IRON AND DUCTILE IRON FITTINGS SHALL BE CEMENT LINED, PRESSURE RATED AS NOTED ON PLANS, AND IN ACCORDANCE WITH ANSI/AWWA
C110/A21.10-87. CEMENT LINING SHALL BE IN ACCORDANCE WITH ANSI/AWWA C104/421/4-90. IF FITTINGS ARE 3 TO 12 INCHES IN DIAMETER AND
HAVE MECHANICAL JOINTS, THE FITTINGS SHALL IN ACCORDANCE WITH EITHER ANSI/AWWA C110-A21.10-87 OR ANSI/AWWA C153/A21.53-94. THREE
(3) INCH TO 12 INCH DIAMETER FITTINGS, WHICH HAVE MECHANICAL JOINTS AND/OR FLANGED JOINTS, SHALL BE IN ACCORDANCE WITH ANSI/AWWA
C110/A21.10.87 OR A COMBINATION OF ANSI/AWWA C110/A21.10.87 AND ANSI/AWWA C153/A21.53-94 SUCH THAT THE PORTION OF THE FITTING WITH
A MECHANICAL JOINT(S) MAY BE WITH ANSI/AWWA C153/A21.53-94 AND THAT PORTION OF THE FITTING WITH FLANGED JOINT(S) SHALL BE IN
ACCORDANCE WITH AWWA C110/A21.10-87. ACCEPTANCE TESTING IN ACCORDANCE WITH SECTION 53.53 OF ANSI/AWWA SECTION 10-4.3 OF
ANSI/AWWA C110/A21.10-87 SHALL BE OBTAINED BY THE CONTRACTOR AND TRANSMITTED TO THE OWNER.
8. GATE VALES SHALL BE IRON BODY, BRONZED -MOUNTED, DOUBLE DISC WITH BRONZE WEDGING DEVICE AND 0-RING STUFFING BOX (AWWA C500)
OR OF RESILIENT SEATED TYPE (AWWA C509). VALVES SHALL BE DESIGNED FOR A MINIMUM WATER OPERATING PRESSURE OF 200 PSI. GATE
VALVES SHALL BE CLOW LIST 14, MUELLER COMPANY NO. A2380 OR M & H.
9. FIRE HYDRANTS SHALL BE COREY TYPE (OPENING WITH THE PRESSURE) OR COMPRESSION TYPE (OPENING AGAINST PRESSURE) CONFORMING TO
AWWA C-502-85 WITH A 6 INCH MECHANICAL JOINT INLET AND A MAIN VALVE OPENING (M.V.O.) OF 5-1/4 INCH, TWO 2-1/2 INCH HOSE NOZZLES
WITH NATIONAL STANDARD THREADS 7-1/2 THREADS PER INCH AND ONE 4 INCH PUMPER NOZZLE WITH THE NEW SEATTLE PATTERN 6 THREADS PER
INCH, 60 DEGREES V. THREADS: OUTSIDE DIAMETER OF MALE THREAD 4.875 AND ROOT DIAMETER 4.6263. HYDRANTS SHALL HAVE A 1-1/4 INCH
PENTAGON OPERATING NUT OPENED BY TURNING COUNTER CLOCKWISE (LEFT).
10. THE TWO 2-1/2 INCH HOSE NOZZLES SHALL BE FITTED WITH CAST IRON THREADED CAPS WITH OPERATING NUT OF THE SAME DESIGN AND
PROPORTIONS AS THE HYDRANT STEM NUT. CAPS SHALL BE FITTED WITH SUITABLE NEOPRENE GASKETS FOR POSITIVE WATER TIGHTNESS UNDER
TEST PRESSURES.
11. THE 4 INCH PUMPER NOZZLE SHALL BE FITTED WITH A STORZ ADAPTER, 4 INCH SEATTLE THREAD X 5 INCH STORZ. STORZ ADAPTER SHALL BE
FORGED AND/OR EXTRUDED 6061-T6 ALUMINUM ALLOY, HARDCOAT ANODIZED. THREADED END PORTION SHALL HAVE NO LUGS AND TWO SET
SCREWS 180 DEGREES APART. STORZ FACE TO BE METAL, NO GASKET TO WEATHER. STORZ CAP TO HAVE SYNTHETIC MOLDED RUBBER GASKET,
AND SHALL BE ATTACHED TO HYDRANT ADAPTER WITH 1 /8 INCH, COATED, STAINLESS STEEL, AIRCRAFT CABLE.
12. FIRE HYDRANTS SHALL BE PAINTED WITH TWO COATS OF PAINT. PRESERVATIVE PAINT NUMBER 43-655 SAFETY YELLOW OR APPROVED EQUAL.
13. PUMPER CONNECTION TO FACE ROADWAY ASSEMBLY.
14. FIRE HYDRANTS SHALL BE INSTALLED PER CITY OF RENTON STANDARD DETAIL FOR FIRE HYDRANTS, LATEST REVISION.
15. ALL WATERMAINS 10 INCHES AND SMALLER TO MAINTAIN A MINIMUM COVER OF 36 INCHES BELOW FINISH GRADE. ALL WATERMAIN 12 INCHES AND
LARGER SHALL BE AT A MINIMUM OF 48 INCHES BELOW FINISH GRADE. WHERE UTILITY CONFLICTS OCCUR, WATERMAINS ARE TO BE LOWERED TO
CLEAR.
16. ALL WATERMAINS 6 INCHES AND LARGER IN DIAMETER SHALL BE CLEANED WITH PIPE CLEANING "PIGS" PRIOR TO DISINFECTION, THE "POLY PIGS"
SHALL BE GIRARD INDUSTRIES AQUA SWAB -AS OR APPROVED EQUAL, 2 LB/CU. FT. DENSITY FOAM WITH 90A DUROMETER URETHANE RUBBER
0
N
x
W"�
Z
��5
COATING ON THE REAR OF "PIG" ONLY.
II
"zo
LL
Z
o
17. "PIGS" SHALL BE CYLINDER SHAPED WITH BULLET NOSE OR SQUARE END. THE CONTRACTOR WILL PERFORM THE CLEANING OPERATION,
c-
a?�
N
18. ALL WATERMAINS AND SERVICES SHALL BE PRESSURE TESTED TO A MINIMUM OF 200 PSI OR 150 PSI OVER OPERATING PRESSURE, IN
ACCORDANCE WITH THE SPECIFICATIONS OF THE CITY OF RENTON AND THE WASHINGTON STATE HEALTH DEPARTMENT. ALL PRESSURE TESTING SHALL
BE DONE IN THE PRESENCE OF A REPRESENTATIVE OF THE CITY OF RENTON. THE QUANTITY OF WATER LOST FROM THE MAIN SHALL NOT EXCEED
THE NUMBER OF GALLONS PER HOUR AS LISTED IN CITY OF RENTON STANDARD PLANS & SPECIFICATIONS 7-11.3(11). THE LOSS IN PRESSURE
SHALL NOT EXCEED 5 PSI DURING THE 2 HOUR TEST PERIOD.
_
Vi
o
cv
19. ALL WATERMAINS AND SERVICES SHALL BE DISINFECTED BY THE INJECTION OF A 50 PPM (MINIMUM CONCENTRATION) CHLORINE/WATER SOLUTION.
w
DRY CALCIUM HYPOCHLORITE SHALL NOT BE PLACED IN THE PIPE AS LAID. CHLORINE SHALL BE METERED/INJECTED IN ACCORDANCE WITH SECTION
N
_
'
7-11.3(12)E OR 7-11.3(12)F OF THE STANDARD SPECIFICATIONS REFERENCED ABOVE.
N
20. A PRE -CONSTRUCTION CONFERENCE IS REQUIRED PRIOR TO ANY CONSTRUCTION, A MINIMUM OF FIVE (5) WORKING DAYS NOTICE IS REQUIRED
FOR SCHEDULING.
Q
21. TWENTY-FOUR (24) HOURS NOTICE WILL BE REQUIRED PRIOR TO STARTING NEW CONSTRUCTION.
It
to
w
U0
�
<
0
22. IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY TO SECURE ALL NECESSARY PERMITS PRIOR TO STARTING CONSTRUCTION.
23. INSTALLATION OF CORPORATE STOPS, WATER SERVICES, LINES AND METERS SHALL NOT BE DONE UNTIL ALL SERVICE AGREEMENTS, METER
w
w
00
APPLICATIONS, CONSTRUCTION PERMITS, AND PAYMENT OF FEES HAVE BEEN MADE TO THE CITY OF RENTON.
24. ALL CONNECTION TO EXISTING MAINS IS TO BE ACCOMPLISHED BY THE CITY OF RENTON, EXCEPT WET TAPS, WHICH MAY BE MADE BY APPROVED
_T
WET TAP CONTRACTORS WITH PRIOR APPROVAL FROM THE PUBLIC WORKS DEPARTMENT. ALL NECESSARY EXCAVATION AND MATERIALS ARE TO BE
SUPPLIED BY THE CONTRACTOR AND BE ON -SITE PRIOR TO CITY NOTIFICATIONS,
25. INSPECTION WILL BE ACCOMPLISHED BY A REPRESENTATIVE OF THE CITY OF RENTON. IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY TO
NOTIFY DEVELOPMENT SERVICES TWENTY FOUR (24) HOURS IN ADVANCE OF BACKFILLING ALL CONSTRUCTION. THE CONTRACTOR, AS WELL AS THE
ENGINEERS, SHALL KEEP AS -BUILT DRAWINGS.
26. CONTRACTOR TO PROVIDE PLUGS AND TEMPORARY BLOW -OFF ASSEMBLIES FOR TESTING AND PURITY ACCEPTANCE PRIOR TO FINAL TIE-IN.
z
0
cn
27• ALL JOINT RESTRAINT SYSTEMS (SHACKLE RODS, NUTS, BOLTS, ETC.) SHALL BE AS MANUFACTURED BY THE STAR MANUFACTURING COMPANY OF
w
w
>
COLUMBUS OHIO, OR EQUAL, APPROVED IN WRITING BY THE PUBLIC WORKS DEPARTMENT,
w
WLi
28. ASPHALT AND CONCRETE STREET PAVING SHALL BE SAWCUT TO A MINIMUM DEPTH OF TWO (2) INCHES. OIL MAT STREETS MAY BE SPADE CUT.
ALL SURFACE CONCRETE, PAVEMENT, SIDEWALKS, CURB, GUTTERS, AND DRIVEWAY APPROACHES SHALL BE SAWCUT TO A MINIMUM DEPTH OF TWO (2)
0-
a_
INCHES OR REMOVED TO AN EXISTING EXPANSION JOINT.
cn
o_
V)
o_
29. A TEMPORARY COLD MIX ASPHALT PATCH SHALL BE PLACED ON THE DAY OF INITIAL EXCAVATION WITH A PERMANENT, SEALED PATCH TO BE
`n
E�
LO
�1>
PLACED, TO CITY OF RENTON POLICY, WITHIN 10 DAYS. CALL FOR SUBGRADE INSPECTION PRIOR TO PLACEMENT OF FINAL PATCH.
cr
0
30. FOR CITY PROJECTS SUCH AS TELEMETRY CONDUIT, THE PVC PIPE USED SHALL BE ALL CHEMICAL PROCESS LINES SHALL BE SCHEDULE 80 PVC
PIPE. SCHEDULE 40 IN UNIMPROVED AREAS AND SCHEDULE 80 PVC PIPE UNDER IMPROVED AREAS.
FINISHED GRADE ELEVATION
3 FT MIN. COVER (10-INCH DIAMETER AND UNDER)
4 FT MIN. COVER (12-INCH DIAMETER AND OVER)
TEMPORARY 2"
GALVANIZED PIPE AND 2"
GATE VALVE
INSTALL 2" PLUG ON TOP
BLIND FLANGE AFTER
REMOVAL OF POLYPIG
NEW WATER MAIN
I:PO=G� p v p
`a.
VERTICAL CROSS FOR POLYPIGGING STATION:
SIZE OF VERTICAL CROSS SHALL BE THE SAME AS SIZE OF MAIN LINE
VERTICAL CROSS (MJxFL)
ONE BLIND FLANGE ON TOP OF CROSS WITH 2" TAP AND 2" TEMPORARY
BLOW -OFF ASSEMBLY
(REMOVE BLOW -OFF ASSEMBLY AND INSTALL 2' PLUG AFTER REMOVAL OF
CLEANING "POLY -PIG")
ONE BLIND FLANGE ON BOTOM OF CROSS
ONE PLUG (MJ) ON END OF CROSS
CONCRETE BLOCKING
ALL DEBRIS AND POLYPIGS SHALL BE REMOVED FROM SUMP OF VERTICAL
CROSS BEFORE DISINFECTION OF NEW WATER MAIN
WATER MAIN POLYPIGGING STATION
VERTICAL CROSS FOR POLYPIGGING
N.T.S.
FIRE HYDRANT SHALL BE COREY-TYPE EQUAL TO IOWA F-5110
OR COMPRESSION TYPE SUCH AS CLOW MEDALLION; M & H 929
AND MUELLER SUPER CENTURION 200 WITH 6" MECHANICAL JOINT
INLET WITH LUGS, 5-1/4" MAIN VALVE OPENING. TWO 2-1/2"
HOSE CONNECTIONS NATIONAL STANDARD THREADS. 4" PUMPER
CONNECTION CITY OF SEATTLE THREADS WITH A STORTZ
ADAPTOR, 4" SEATTLE THREAD X 5" STORTZ, ATTACHED WITH
1/8" STAINLESS STEEL CABLE. 1-1/4" PENTAGON OPERATING
NUT. FIRE HYDRANT TO BE PAINTED WITH TWO COATS OF PAINT.
PRESERVATIVE PAINT No. 43-655 SAFETY YELLOW OR APPROVED
EQUAL. PUMPER CONNECTION TO FACE ROADWAY ASSEMBLY. FIRE
HYDRANT EXTENSION TO BE USED IF REQUIRED.
CONCRETE BLOCKING
1' 1' 2.5' _4 1' 1'
MIN MIN MIN MINI MIN
2" CLASS 'B'
*2" TO 6"
CLASS 'E'
OR
CLASS 'B'
6.5' MIN.
2" DEPTH OF
GRIND OR SAWCUT AND REMOVE
* SEE DWG# HR-05 FOR MINIMUM STANDARDS
18" TO 20 BEHIND BACK OF
CURB OR 12" BEHIND BACK OF
SIDEWALK THAT IS ADJACENT TO
CURB
TWO-PIECE CAST IRON VALVE BOX WITH LUG TYPE COVER.
9e EQUAL TO OLYMPIC FOUNDRY CO. STANDARD 8" TOP SECTION
WITH REGULAR BASE SECTION LENGTH TO FIT. VALVE NUT
EXTENSION AS REQUIRED (SEE DWG BR46 / PAGE B090).
RAISED PAVEMENT MARKER TYPE 88
A8 STIMSONITE TWO-WAY BLUE.
42" MIN
BURY
-J
CONCRETE BLOCKING
CAST IRON TEE. WITH 6" FLANGE SIDE OUTLET.
6" GATE VALVE (FL X MJ) AWWA C-509, RESILIENT SEAT
6" DUCTILE IRON PIPE, CLASS 52 CEMENT LINED, LENGTH TO FIT TWO
3/4" STEEL TIE RODS. SEE STD DETAIL FOR TIE RODS.
16"x8"x4"
MININUM CONCRETE 1 /3 CU. YD. WASHED DRAIN ROCK (3" TO 3/8")
BLOCK UNDER
HYDRANT
FIRE HYDRANT ASSEMBLY
N.T.S.
12"x 22"
CONCRETE METER
W
IN UNIMPROVED RIGHT OF WAY
W
BOX WITH
3/16" STEEL DIAMOND PLATE
?
INSTALL METER BOX AT
COVER EQUAL TO FOG TITE METER
PROPERTY LINE.
SEAL CO.
B-10 METER BOX.
w
W
6" MIN
0
0
FINISH GRADE
9" MAX
a
/ SIDEWALK
a
9"
='- 21 MIN
COVER
36" MIN COVER
2-1 /2°
NEW DUCTILE IRON L LOOP DOWN TO CENTERLINE
WATERMAIN OF WATER MAIN TO PROVIDE
SLACK IN COPPER SERVICE
LINE TO METER.
CORPORATION STOP. FORD TAPERED
THREAD (CC). PACK JOINT (3/4" F1000)
(1" F1000)
22-1/2'
.'f. -
_i"M:i
WATER METER TO BE 12" MIN
SUPPLIED BY THE CITY
TYPE "K" SOFT
COPPER TUBING
FORD COPPERSETTER
VH 72-15W-44-33G (FOR 5/8" x 3/4" METER)
VH 72-15W-44-44G (FOR 1" METER)
BOTH INLET AND OUTLET WITH PACK JOINT WITH GRIPPER.
PADLOCK WINGS ON KEY VALVE SINGLE CHECK VALVE
ON OUTLET.
ALL PACK -JOINT FITTINGS SHALL BE WITH GRIPPER.
IF SERVICE LINE TO HOUSE IS TO BE
INSTALLED IN THE FUTURE INSTALL
FORD C14-33 OR 44
FIDT x COMPRESSION COUPLING
3/4" OR 1" GALVANIZED PLUG
FOR SERVICE FROM EXISTING STEEL
EXISTING CAST IRON ASBESTOS CEMENT OR PVC WATER MAINS
OR DUCTILE IRON INSTALL DOUBLE STRAP SERVICE CLAMP
WATERMAIN EQUAL TO MUELLER CO.
3/4" & 1" WATER SERVICES DETAILS
RECOMMENDED
FOR APPROVAL
Ely
- -�
BY
B1
CHECKED FOR COMPLIANCE
nTO CITY STANDARDS
DATE
DATE
DATE
36" MIN
COVER
FACE OF CURB OR
EDGE OF PAVEMENT
2" CLASS 'B'
CENTER LINE OR
LANE LINE
6.5' MIN.
1' V 2.5' 1' 1'
MIN MIN MIN MIN MIN
\*ACP CLASS 'E' OR 'B'
6" CRUSHED
SURFACING TOP COURSE
CRUSHED ROCK,
FLOWABLE FILL
OR
AS REQUIRED BY ENGINEER
TYPICAL PATCH FOR FLEXIBLE
PAVEMENT WHEN PERPENDICULAR TO
ROADWAY CENTERLINE
CUT
LEVEL ALL
GROUND MIN 3'
RADIU
ONE MAN ROCK i
1
6
FILL
HYDRANT LOCATION IN CUT OR FILL
N.T.S.
Call
before you
1011198
1-800-42445555
AVOID CUTTING UNDERGROUND
UTILITY LINES. IT'S COSTLY
E
of
1133 1S
s jONA.LL
EXPIRES 11/30/04
NOTE:
EXISTING UTILITY LOCATIONS SHOWN HEREON ARE APPROXIMATE ONLY.
IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY TO DETERMINE THE
EXACT VERTICAL AND HORIZONTAL LOCATION OF ALL EXISTING UNDER-
GROUND UTILITIES PRIOR TO COMMENCING CONSTRUCTION. NO
REPRESENTATION IS MADE THAT ALL EXISTING UTILITIES ARE SHOWN
HEREON. THE ENGINEER ASSUMES NO RESPONSIBILITY FOR UTILITIES
NOT SHOWN OR UTILITIES NOT SHOWN IN THEIR PROPER LOCATION.
CALL BEFORE YOU DIG: 1-800-424-5555
UNDERGROUND SERVICE (USA)