HomeMy WebLinkAboutWTR2703214.15ELECTRICAL EQUIPMENT LEGEND
ITEM
DESCRIPTION
MANUFACTURER
PART NO.
BY OTHERS
SURGE PROTECTIVE DEVICE - SURGE PROTECTIVE UNIT WITH
INNOVATIVE TECHNOLOGIES
PTXl60-lS101-SD-D
INTEGRAL DISCONNECT SWITCH IN A NEMA 4X ENCLOSURE..
OR EQUAL
CONDUIT AND WIRING PER MANUFACTURER'S RECOMMENDATIONS.
LIGHTING PANELBOARD - NEMA 1 ENCLOSURE, SERVICE ENTRANCE
SIEMENS
TYPE Pl
O
RATED, 200 AMP MAIN CIRCUIT BREAKER, 50 AMP BACK -FED
OR EQUAL
EMERGENCY GENERATOR CIRCUIT BREAKER, MECHANICAL INTERLOCK
BETWEEN MAIN CIRCUIT BREAKER AND EMERGENCY GENERATOR
CIRCUIT BREAKER, 240/120 VOLT, 10, 3 W, 30 CIRCUIT. MOUNT
TOP OF ENCLOSURE 6'-0" FROM FLOOR.
©
INTRUSION ALARM SWITCH - HEAVY DUTY INTRUSION ALARM SWITCH.
SQUARE D
TYPE C, CLASS
CONTRACTOR TO SELECT PLUNGER STYLE ACTUATOR.
9007 OR EQUAL
PHOTO ELECTRIC SMOKE DETECTOR - 24 VDC, WITH LOCAL AUDIBLE
SYSTEMS SENSOR
4WTAR-B OR
O
ALARM SIGNAL AND CONTACTS FOR REMOTE ANNUNCIATION
EQUAL
THROUGH FOUR WIRE CONNECTION TO TELEMETRY. INSTALL AT
HIGHEST POINT. WIRE PER MANUFACTURER'S INSTRUCTIONS. PROVIDE
I
ACCESSORIES AS NECESSARY TO COMPLETE A FUNCTIONAL CIRCUIT.
WALL MOUNTED COOLING THERMOSTAT - SNAP ACTION, SPDT LINE
HONEYWELL
T631C1103 OR
OE
VOLTAGE AIR SWITCH CONTROLLER. RANGE:30' - 100'F, SET AT
EQUAL
757. MOUNT 4 FEET ABOVE FINISHED FLOOR.
©
KEYED -SWITCH BOX. SEE SPECIFICATIONS DWG NO. E02 FOR MORE
INFORMATION.
H
O
RESERVOIR LEVEL TRANSMITTER - SEE SPECIFICATIONS AND DWG
NO. E04 FOR MORE INFORMATION.
I
O
RESERVOIR OVERFLOW LEVEL SWITCH - SEE SPECIFICATIONS AND
DWG NO. E04 FOR MORE INFORMATION.
L
O
LIGHTING LIMIT SWITCH - HEAVY DUTY LIMIT SWITCH. ONTRACTOR
SQUARE D
TYPE C, CLASS
TO SELECT PLUNGER STYLE ACTUATOR.
9007 OR EQUAL
O
FLOOD SWITCH - N.O. REED TYPE FLOAT SWITCH, 20 VA. SEE
OMEGA MODEL
LVN-20 OR EQUAL
DWG NO. E04 FOR DETAIL.
ON
TELEMETRY PANEL, "RTU"
REID INSTRUMENTS
REID INSTRUMENTS
OO
GENERATOR CONNECTION RECEPTACLE - 50 AMP, 120/240
VOLT, 1-PHASE, 3-WIRE, TWIST LOCK MALE RECEPTACLE,
GENERAL ELECTRIC
T050N OR EQUAL
MOUNT TOP OF ENCLOSURE 5'-0" FROM FINISHED GRADE.
* CONTRACTOR SHALL INSTALL ALL EQUIPMENT PROVIDED BY OTHERS.
FACILITY LIGHTING FIXTURE SCHEDULE
MANUFACTURER
* LAMP
TYPE
DESCRIPTION
NAME CATALOG NO.
QTY. CATALOG NO.
REMARKS
FLUORESCENT LIGHT FIXTURE, 120 VAC, 4' LONG, HIGH -IMPACT
Al
ACRYLIC LENS, MOLDED FIBERGLASS REINFORCED POLYESTER HOUSING,
LITHONIA
VRI 2 32 ARDP 120 CW
2
32WT8
(2)-32W LAMPS, ENERGY SAVING BALLAST, CEILING MOUNTED, U.L.
32 WATT
LISTED FOR DAMP LOCATIONS.
FLUORESCENT OUTDOOR AREA LIGHT - 42W, 120V BALLAST,
A2
DIE-CAST ALUMINUM HOUSING, POLYCARBONATE LENS; U.,L, LISTED
LITHONIA
TWH 2/42 120 PE LPI
2
42 WATT
PHOTO AND MOTION
FOR WET LOCATIONS. MOUNT BOTTOM OF FIXTURE 7 -2 FROM
FINISHED GRADE.
RESERVOIR ROOF METAL HALIDE POLE MOUNT OUTDOOR FLOOD
LIGHT:
A3
FIXTURE - 120V 20OW PULSE START, METAL HALIDE LAMP, STANDARD
LITHONIA
KFL3-20OM-HPN-120-TS-SCWA-LPI
1
200 WATT
DARK BRONZE FINISH, SUPER CWA PULSE START BALLAST. FURNISH
POLE:
METAL
WITH TENON SLIPFITTER FOR POLE MOUNTING TO SPECIFIED POLE AND
RSS-10-4B-T20
HALIDE
I
ON 10 FOOT TALL 4" ROUND POLE.
MARINE QUARTZ FLOODLIGHT - 50OW, 120 VAC, 11 7/16"
500 WATT
A4
H, 8 13/16" W, 6 15/16" D, COPPER FREE ALUMINUM,
PHOENIX
MS 500 QH
1
QUARTZ
MARINE RATED, U.L. LISTED FOR WET LOCATIONS.
HALOGEN
A5
OUTDOOR AREA POLE -MOUNTED FLOODLIGHT- QUARTZ LIGHT
HUBBELL
LIGHT:
QD-150W
150 WATT
FIXTURE, 120 VAC, 150 WATT, DIE-CAST ALUMINUM HOUSING,
LIGHTING
POLE:
1
QUARTZ
WITH CAST GUARD, ADJUSTABLE SWIVEL KNUCKLE. FURNISH
SSS-16-50-7-TA-B
WITH TENON SUPFITTER FOR POLE MOUNTING TO SPECIFIED POLE.
OUTDOOR LOW -MOUNT FLOODLIGHT- INCANDESCENT LIGHT FIXTURE,
A6
120 VAC, 150 WATT, DIE-CAST ALUMINUM HOUSING,
150 WATT
POLYCARBONATE LENS, U.L. LISTED FOR WET LOCATIONS, SURFACE
LITHONIA
KLI A 120 LPI BBW DBL
1
INCANDESCENT
j
MOUNT TO STAIRWAY RAILING PER DETAIL ON DWG NO. E06.
i
* NUMBER OF LAMPS PER FIXTURE
HAZEN RESERVOIR PANEL SCHEDULE
LOCATION: LIGHTING PANEL
SERVING: RESERVOIR
1
3
5
7
9
11
13
15
17
19
21
23
25
27
29
AB
11
)�200A
2
4
6
8
10
12
14
16
18
20
22
24
26
28
30
120/240
200
AMP
VOLTS 3 WIRE
MAIN
CIRCUIT DESCRIPTION
KVA
AMP
AMP
KVA
CIRCUIT DESCRIPTION
RESERVOIR LIGHTING
1.36
20
50
-
EMERGENCY GENERATOR
TVSS
4.71
30
2P
2P
20
0.50
TELEMETRY PANEL
VENTILATION FAN
0.35
20
20
0.25
ELECTRICAL BUILDING LIGHTING
ELECTRICAL BUILDING RECEPTACLES
0.70
20
20
0.70
RESFP'`nlP QFr'FPTACLE
SEINER RECEH i Ai,LL
OUTDOOR LIGHTING
MOTORIZED GATE OPERATOR
1.92
20
20
0.50
OUTDOOR LIGHTING CONTROL PNL
0.10
20
20
0.35
METER VAULT SUMP PUMP
0.70
20
20
1.92
SEISMIC CONTROL VALVE
SEISMIC VALVE VAULT SUMP PUMP
0.70
20
20
SPARE
-
20
20
-
SPARE
SPARE
-
20
20
-
SPARE
SPARE
-
20
20
-
SPARE
SPACE
-
-
-
-
SPACE
SPACE
-
-
-
-
SPACE
SPACE
-
-
-
-
SPACE
CONNECTION LOAD: DEMAND: LIGHTING & MISC. LOAD DEMAND LOAD:
KVA AMPS KVA AMPS
POWER CONDUIT SCHEDULE
CIRCUIT
SOURCE
DESTINATION
TRADE SIZE
(QUANTITY) CONDUCTORS
NOTES
P1
UTILITY TRANSFORMER
UTILITY METER
2 1/2"
(2) - #3/0, (1) - #3/0 N
P2
UTILITY METER
LIGHTING PANELBOARD, "L"
2 1/2"
(2) - #3/0, (1) - #3/0 N
P3
LIGHTING PANELBOARD, "L"
GENERATOR CONNECTION RECEPTACLE
1"
(2) - #8, (1) - #8 N, (1) - #10 GRD
P4
LIGHTING PANELBOARD, "L"
TVSS
3/4"
(2) - #10, (1) - #10 N, (1) - #10 GRD
P6
LIGHTING PANELBOARD, "L"
TELEMETRY PANEL, "RTU"
COOLING THERMOSTA
EXHAUST FAN, "EF-1"
INTAKE LOUVER ACTUATOR, "LA-l"
1/2"
(2) - #12, (1) - #12 GRD
P7
LIGHTING PANELBOARD, "L"
1/2-
(2) - #12, (1) - #12 GRD
P8
COOLING THERMOSTAT
1/2"
(2) - #12, (1) - #12 GRD
i
P9
COOLING THERMOSTAT
1/2"
1/2"
(2) - #12, (1) - #12 GRD
(2) - #12, (1) - #12 GIRD
P10
LIGHTING PANELBOARD, "L"
ACCES `TF '"nT �''� An�� b r,"�
P11
OUTDOOR LIGHTING CONTROL PANEL
ACCE - GATE SITE LIGHTING AND MOTION DETECTOR
1"
(4) - #12, (1) - #12 GRD
P12
OUTDOOR LIGHTING CONTROL PANEL
PARKING AREA SITE LIGHTING
3/4"
(2) - #12, (1) - #12 GRD
13
LIGHTING PANELBOARD, "L"
RESERVOIR LIGHTING
1"
(2) - #12, (1) - #12 GRD
P13B
LIGHTING PANELBOARD, "L"
RESERVOIR RECEPTACLE
1"
(2) - #12, (1) - #12 GRD
P14
LIGHTING PANELBOARD, "L"
SEWER TELEMETRY RECEPTACLE
1/2"
(2) - #12, (1) - #12 GRD
RECEPTACLE LOCATED AT TOP OF RESERVOIR
P15
LIGHTING PANELBOARD, "L"
SEISMIC CONTROL PANEL
1/2"
(2) - #12, (1) - #12 GRD
P16
ACCESS GATE MOTORIZED OPERATOR
GATE ENTRY KEYPAD
1"
(4) - #14, (1) - #14 GRD
P17
LIGHTING PANELBOARD, 1"
METER VAULT SUMP PUMP
1/2"
(2) - #12, (1) - #12 GRD
P18
LIGHTING PANELBOARD, "L"
SEISMIC VALVE VAULT SUMP PUMP
1/2"
(2) - #12, (1) - #12 GRD
CONTROL CONDUIT SCHEDULE
CIRCUIT
SOURCE
DESTINATION
TRADE SIZE
(QUANTITY) CONDUCTORS
NOTES
C1
ELECTRICAL BLDG. INTRUSION SWITCH
TELEMETRY PANEL, "RTU"
1/2"
(2) - #14, (1) - #14 GRD
C2
ELECTRICAL BLDG. INTRUSION DISABLE
TELEMETRY PANEL, "RTU"
1/2"
(2) - #14, (1) - #14 GRD
C3
ELECTRICAL BLDG. SMOKE DETECTOR
TELEMETRY PANEL, "RTU"
1/2"
(4) - #14, (1) - #14 GRD
C4A
RESERVOIR TELEMETRY JUNC11ON BOX NO. 1
TELEMETRY PANEL, "RTU"
1/2"
(2) - #14, (1) - #14 GRD
CIRCUITS "C0" AND "C413" SHARE CONDUIT CONDUIT "C4"
C4B
RESERVOIR TELEMETRY JUNCTION BOX NO. 1
TELEMETRY PANEL, "RTU"
1/2"
(2) - #14, (1) - #14 GRD
CIRCUITS "C4A" AND "C4B" SHARE CONDUIT CONDUIT "C4"
C5
RESERVOIR VANDAL SHIELD INTRUSION SWITCH
TELEMETRY PANEL, "RTU"
1/2"
(2) - #14, (1) - #14 GRD
C6
SEISMIC CONTROL PANEL
TELEMETRY PANEL, "RTU"
1"
(12) - #14, (1) - #14 GRD
C7
RESERVOIR ACCESS HATCH INTRUSION SWITCH
RESERVOIR TELEMETRY JUNCTION BOX NO. 2
1/2"
(2) - #14, (1) - #14 GRD
C8
RESERVOIR OVERFLOW SWITCH
RESERVOIR TELEMETRY JUNCTION BOX NO, 2
1"
MANUFACTURER FLOAT CABLE
C9
SEISMIC CONTROL PANEL
SEISMIC VALVE SOLENOID AND LIMIT SWITCH
1 1/4"
(3) - #6, (3) - #14, (1) - #6 GRD
C10
SEISMIC VALVE VAULT FLOOD SWITCH
TELEMETRY PANEL, "RTU"
1/2"
(2) - #14, (1) - #14 GRD
C11A
RESERVOIR TELEMETRY JUNCTION BOX NO, 2
RESERVOIR TELEMETRY JUNCTION BOX NO. 1
1/2"
(2) - #14, (1) - #14 GRD
CIRCUITS "CllA" AND "CllB" SHARE CONDUIT CONDUIT "Cll"
C11B
RESERVOIR TELEMETRY JUNCTION BOX NO. 2
RESERVOIR TELEMETRY JUNCTION BOX NO. 1
1/2"
(2) - #14, (1) - #14 GRD
CIRCUITS "CllA" AND "CllB" SHARE CONDUIT CONDUIT "C1l"
INSTRUMENTATION CONDUIT SCHEDULE
CIRCUIT
SOURCE
DESTINATION
TRADE SIZE'
(QUANTITY) rONDINICTORS
NOTES
J1
RESERVOIR TELEMETRY JUNCTION BOX N0. 1
TELEMETRY PANEL, "RTU"
3/4"
-- - -
-'ABLE
JUNCTION BOX LOCATED ON RAILING AT TOP OF RESERVOIR. SEE DWG N0. E03.
J2A
INLET FLOW METER
TELEMETRY PANEL, "RTU"
2 1/2"
(1)-2-CONDUCTOR SHIELDED CABLE
CIRCUITS "J2A", "J2B", "J2C", "J21)", AND "J2E" SHARE CONDUIT CONDUIT "J2"
J2B
INLET FLOW METER (TOTALIZER AND POWER)
TELEMETRY PANEL, "RTU"
2 1/2"
(4) - #14, (1) - #14 GRD
CIRCUITS "J2A", "J2B", "J2C", "J21)", AND "J2E" SHARE CONDUIT CONDUIT "J2"
J2C
OUTLET FLOW METER
TELEMETRY PANEL, "RTU"
2 1/2"
(l)-2-CONDUCTOR SHIELDED CABLE
CIRCUITS "J2A", "J2B", "J2C", "J2D", AND "J2E" SHARE CONDUIT CONDUIT "J2"
J2D
OUTLET FLOW METER (TOTALIZER AND POWER)
TELEMETRY PANEL, "RTU"
2 1/2"
(4) - #14, (1) - #14 GRID
CIRCUITS "J2A", "J2B", "J2C", "J21)", AND "J2E" SHARE CONDUIT CONDUIT "J2"
J2E
METER VAULT FLOOD SWITCH
TELEMETRY PANEL, "RTU"
2 1/2"
(2) - #14, (1) - #14 GRD
CIRCUITS "J2A", "J2B", "J2C", "J2D", AND "J2E" SHARE CONDUIT CONDUIT "J2"
J3
RESERVOIR LEVEL TRANSMITTER
RESERVOIR TELEMETRY JUNCTION BOX NO, 2
1"
MANUFACTURER LEVEL TRANSDUCER CABLE
J4
STUB -UP ALONG INSIDE BUILDING WALL
SPARE CONDUIT HANDHOLE
(2)-2"
PULL CORD (EACH)
(2) SPARE CONDUITS.
J5
STUB -UP ALONG INSIDE BUILDING WALL
SPARE CONDUIT HANDHOLE
(3)-3"
PULL CORD (EACH)
(3) SPARE CONDUITS.
J6
STUB -UP ALONG INSIDE BUILDING WALL
STUB -UP ALONG UTILITY POLE
4"
PULL CORD
RESERVE FOR RENTON INFORMATION SERVICE DEPARTMENT
J7
SPARE CONDUIT HANDHOLE
STUB -UP BELOW GATE ENTRY KEYPAD AND CAP
2"
PULL CORD
RESERVE FOR FUTURE WATER DEPARTMENT SURVEILLANCE.
J8
STUB -UP ALONG INSIDE BUILDING WALL
TOP OF RESERVOIR
(2)-2"
PULL CORD (EACH)
RESERVE FOR FUTURE WATER DEPARTMENT SURVEILLANCE
J9
STUB -UP ALONG INSIDE BUILDING WALL
TOP OF RESERVOIR
(2)-2"
PULL CORD (EACH)
RESERVE FOR RENTON INFORMATION SERVICE DEPARTMENT.
IS DEPARTMENT CONDUIT SYSTEM
(2)-3"
ALL CONDUIT ROUTES MUST CONTAIN A MINIMUM OF 24" DIAMETER SWEEPS.
J10
RESERVOIR TELEMETRY JUNCTION BOX NO. 2
RESERVOIR TELEMETRY JUNCTION BOX NO. 1
3/4"
(1)-2-CONDUCTOR SHIELDED CABLE
JUNCTION BOX LOCATED ON RAILING AT TOP OF RESERVOIR. SEE DWG NO. E04.
VENTILATOR SCHEDULE
NO. FLOW FLOWRATE BACKDRAFT DAMPER MANUFACTURER MODEL ACCESSORIES
EF-1 EXHAUST 410 SCFM YES ACME ENGINEERING F0098 BACK GUARD
LOUVER AND DAMPER SCHEDULE
NO. FLOW FLOW RATE (SCFM) MANUFACTURER DAMPER, LOUVER DIMENSIONS ACCESSORIES* NOTES
LA-1 INTAKE 410 POTTORFF CD42, EFD-445 12" X 12" MOUNTING SLEEVE, MOTORIZED ACTUATOR DAMPER TO OPEN ON EF-1 STARTUP
LA-2 EXHAUST 410 POTTORFF CD42, EFD-445 12" X 12" MOUNTING SLEEVE, MOTORIZED ACTUATOR DAMPER TO OPEN ON EF-1 STARTUP
* MOUNTING SLEEVES DEPTH SHOULD BE 18" MAX.
Wm321438
REVISED TO CONFORM
7 rTR CORDS
06/08/09
RH ENGINEERING INC. DATE
REVISED TO CONFORM TO CONSTRUCTION RECORDS
ADDENDUM / ISSUED FOR CONSTRUCTION
NO. REVISION
H.
WA
6727
6727_. 1
WAT. 'p-
SIGNED: 06129107
SIGNED: 06129107
z
0
FNI
Z04
W
Oz
�z
V
0
cf)
W
J
D
0
W
U
cn
J
Q
V
w
J
W
1 ENGINEERS 1
RH2 ENGINEERING. INC.
http: /J/www.rh2 com
mailbox@rh2.com
1.800.720.8052
BELL.INGHAM OFFICE
360.E 76.0836
454 West Horton Road
BOTHELI. OFFICE
425, 951.5400
12100 NE 195th Street, Suite 100
EAST WENATCHEE OFFICE
509,886.2900
300 Simon Street, Suite 5
PORT ORCHARD OFFICE
360.876.7960
600 Kitsop Street, Suite 101
SHOWN
;446N44;�;1_
1
DRAWING IS NOT1 SCALE
IF BAR IS NOT 2" LONG
PLOT: 1 DWG N0,
ENGINEER: GMR E05
REVIEWED: MLM
DATE: SEP 14, 2009 SHEET NO.
DY
KJS
06/08/09
CLIENT: REN
BTE
MM
10/09/07
JOB No.: 105-049
734
BY
REVIEW
DATE
FILENAME: HAZEN-D-ELEC04
a8: 0- :3 14 3T