HomeMy WebLinkAboutWTR2703214.16Y
z
Z
Q
U
PO c
CONCRETE RESERVOIR
c�
GRASS
CONCRETE PAD
WITH TANK
SUPPORT, (TYP.)
O O
GRASS
Q O
CONCRETE
VAULT
O
436
CONCRETE PAD W/
ELECTRICAL BOXES, TYP
GRAVEL
GRASS 438
CONCRETE PAD W/
ELECTRICAL BOX EXISTING
�TELEMETRY
HANDHOLE
GRAVR
A
4TE
7' CHAIN LINK
NE 12TH STREET
EXISTING SITE PLAN
20'
EXISTING PIPE TO BE
REMOVED
00 -
O
N
d
COLUMN
CONCRETE RESERVOIR
COLUMN
0
A�8 EXISTING GENERATOR
BUILDING
BUILDING
EASTERLY BROKEN EDGE
OF ASPHALT, ASPHALT
DISAPPEARS INTO GRAVEL
CONCRETE EXISTING 2" PVC TELEMETRY
oNDUIT
/ C
EXISTING TELEMETRY BUILDING
HANDHOLE
EXISTING BOOSTER, ----
STATION BUILDING
HIGHLANDS RESERVOIR
LEGEND
EXISTING
SYMBOLS
SURVEY
SYMBOL DESCRIPTION
QUARTER SECTION CORNER
O ENCASED CONCRETE MONMENT
SURFACE BRASS DISK MONUMENT
SURFACE FEATURES
SYMBOL DESCRIPTION
PP POWER POLE
EJB ELECTRICAL JUNCTION BOX
TJB TELEPHONE JUNCTION BOX
CONIFER TREE
HEDGE
WATER
SYMBOL DESCRIPTION
WATER VALVE
FH FIRE HYDRANT
LINETYPES
SURFACE FEATURES
LINETYPE DESCRIPTION
FENCE LINE
GRAVEL
CONCRETE
EXISTING STRUCTURE
UTILITIES
LINETYPE DESCRIPTION
UNDERGROUND POWER LINE
UNDERGROUND TELEPHONE LINE
UNDERGROUND TELEMETRY LINE
WATER LINE
PROPOSED
OBJECT DESCRIPTION
FITTINGS
WATER MAIN
' WATER MAIN WITH SHACKLE RODS
SENSING LINE
UNDERGROUND TELEMETRY LINE
UNDERGROUND POWER LINE
j HIGHLANDS RESERVOIR
SURVEY INFORMATION
VERTICAL DATUM: NAVD 1988
BENCHMARK: CITY OF RENTON MONUMENT #1843,
AT INTERSECTION OF NE 12TH STREET AND
MONROE AVENUE NE (TO THE NORTH), BRASS
PLUG IN CONCRETE, 1.25' DEEP.
ELEVATION = 425.15 FEET
UTILITIES SHOWN ARE BASED ON OBSERVATION OF
SURFACE FEATURES, PAINT MARKS APPLIED BY AN
UNDERGROUND UTILITY LOCATING SERVICE, AND
AVAILABLE RECORD DRAWINGS. FIELD LOCATIONS
MUST BE VERIFIED PRIOR TO ANY CONSTRUCTION.
CALL 1-800-424-5555 FOR THIS VERIFICATION.
THIS SURVEY MADE WITHOUT THE BENEFIT OF A
TITLE REPORT AND DOES NOT PURPORT TO
SHOW ALL ITEMS OF RECORD.
ELEVATION PRECISION: 0.05' HARD SURFACES
0.1' NON -HARD SURFACES
EXISTING CONDULET. CONTRACTOR SHALL INSTALL
PROPOSED CONDUCTORS TO EXISTING CONDULET.
CONTRACTOR SHALL CONNECT PROPOSED 1 1/2" GRC
CONDUIT TO EXISTING CONDULET. CONTRACTOR SHALL
INSTALL PROPOSED 1 1/2n GRC CONDUIT CONTAINING
PROPOSED FLOW METER CABLE'S, ALTITUDE VALVE
CONDUCTORS, AND FLOOD SWITCH CONDUCTORS
BETWEEN EXISTING CONDULET AND PROPOSED FLOW
METER TRANSMITTER LOCATED NEXT TO EXISTING
TELEMETRY PANEL AND THE TELEMETRY PANEL.
LOCATION OF PROPOSED FLOW METER TRANSMITTER.
CONTRACTOR SHALL INSTALL A JUNCTION BOX ABOVE
THE FLOW METER TRANSMITTER,TERMINATE PROPOSED
1 1/2" CONDUIT IN THE PROPOSED JUNCTION BOX.
FROM THE JUNCTION BOX INSTALL A 1" CONDUIT TO THE
FLOW METER TRANSMITTER AND TERMINATE THE FLOW
METER CABLES TO PROPOSED FLOW METER
TRANSMITTER. INSTALL A j" GRC CONDUIT CONTAINING
(2)—#12 AND (1)—#12 GROUND CONDUCTORS BETWEEN
THE FLOW METER TRANSMITTER AND THE PROPOSED
TELEMETRY PANEL. INSTALL A 1" GRC CONDUIT
CONTAINING (2) — 2—CONDUCTOR SHIELDED CABLES
AND (6)—#14 AND (1)—#14 GROUND CONDUCTORS' . =
BETWEEN THE FLOW METER TRANSMITTER AND THE r.
EXISTING TELEMETRY PANEL. TERMINATE CONDUCTORS
AT THE TELEMETRY PANEL AND THE FLOW METER f Y
TRANSMITTER. INSTALL A � CONDUIT CONTAINING _ -
(6)—#14 AND (1)—#14 GRID CONDUCTORS BETWEEN THE +.,.
JUNCTION BOX AND THE EXISTING TELEMETRY PANEL. _
TERMINATE THE PROPOSED CONDUCTORS IN THE
EXISTING TELEMETRY PANEL ><
SURFACE MOUNT INSTALL PROPOSED
1 1/2" CONDUIT TO EXISTING
BOOSTER STATION INTERIOR WALL.
4wo1
EXISTING TELEMETRY PANEL.
EXISTING BOOSTER STATION INTERIOR -
SOUTH WALL
NO SCALE
SURFACE MOUNT INSTALL
PROPOSED 1 1/2' CONDUIT TO ---
WALL ABOVE DOOR.
EAST WALL
NO SCALE
EXISTING 2" CONDUIT TO
EXISTING BOOSTER STATION
BUILDING. CONTRACTOR SHALL f;
INSTALL PROPOSED FLOW METER
CABLE'S, ALTITUDE VALVE s
CONDUCTORS, AND FLOOD i
SWITCH CONDUCTORS IN �r
EXISTING CONDUIT.
.:
EXISTING 2" CONDUIT BUILDING
PENETRATION FROM EXISTING
CONDUIT LEAVING EAST
%HANDHOLE.
fp EXISTING 2" PVC CONDUIT FROM
EXISTING WEST TELEMETRY
EXISTING BOOSTER STATION INTERIOR - NORTH WALL HANDHOLE
NO SCALE
EXISTING 2" PVC CONDUIT TO EAST TELEMETRY HANDHOLE.
CONTRACTOR SHALL INSTALL PROPOSED FLOW METER CABLE'S,
ALTITUDE VALVE CONDUCTORS, AND FLOOD SWITCH CONDUCTORS
IN EXISTING CONDUIT.
.:.
PROPOSED WEST
TELEMETRY
HANDHOLE.
CONTRACTOR SHALL
CONNECT PROPOSED
2" PVC COATED GRC
CONDUIT TO EXISTING
HANDHOLE
EXISTING WEST TELEM
NO SCALE
EXISTING WEST EAST TELEMETRY
EXISTING HAI
GENERATO -
BUILDING
H.
WA
IO/L/
�$BCIST-0 i
rO1VAL
SIGNED: 06129107
SIGNED: 06129107
's Y
W
H
N
C�
z
H
0 =
cn
�0-4
x
za
;4
F)
Z
a
z
W
w
Ir
°z
V
cS
C ENGINEE_
PLANNERS
EXISTING EAST TELEMETRY HANDHOLE S► E N T I S T SMw
NO SCALE RH2 ENGINEERING, INC:.
http://www.rh2.com
mailbox®rh2.com
1.800.720.8052
EXISTING BOOSTER BELLINGHAM OFFICE
STATION BUILDING 360.676.0836
454 West Horton Road
_OCATION OF EXISTING BOTHELL OFFICE
CELEMETRY PANEL ON SOUTH 425.951.5400
NALL OF EXISTING BOOSTER 12100 NE 195th Street, Suite 100
STATION INTERIOR
EAST WENATCHEE OFFICE
509.886.2900
300 Simon Street, Suite 5
PORT ORCHARD OFFICE
360.876.7960
600 Kitsop Street. "T
SCALE: SHOWN
FRW
Mm
0 1" 2"
DRAWING IS NOT TO SCA[F
A
EXISTING BOOSTER STATION BUILDING EXTERIOR
NO SCALE
IF BAR IS NOT 2" LONG
PLOT 20 DWG NO.
ENGINEER: C,DW C14
REVIEWED: MLM
DATE: SEP 14, 2009 SHEET NO.
REVISED TO CONFORM TO CONSTRUCTION RECORDS DY KJS 06/08/09 CLIENT: REN 33
ADDENDUM / ISSUED FOR CONSTRUCTION BTE MM 10/09/07 JOB No.: 105-049 34
NO. REVISION BY REVIEW DATE FILENAME HIGH—D—HOT