HomeMy WebLinkAboutWTR2703226.44" POST INDICATOR VALVE
(MJxMJ) PAINTED BLUE
2-3/4" SHACKLE RODS PER CITY
OF RENTON SPECIFICATIONS
4- 90- BEND (MJ)
TEE (MJ FL) 12" 13 LF 4" D.I. 4" 90- BEND (MJ)
1xr GATE VALVE (FLxMJ) 7'-0"
V 4" FLxMJ ADAPTOR
4" FLxMJ ADAPTOR LADDER WITH
SUPPORT BAR2'-4"
:.;Xi* PER OSHA
4" or 6" D.I.
FLOW • -
IN TO BUILDING
151L�,
! . �� M EPDXY NON -
SHRINK
GROUT 2' -4"
U 4* TEE (MJxFL)
WELDED STEEL COLLAR
TOUCH READ PIT LID SENSOR MOUNTED ON---/
STEEL PLATE COVER THROUGH 1-5/8" DIA.
DRILLED HOLE IN COVER.
PRECAST CONCRETE VAULT WITH 2 3"x3" HINGED STEEL
PLATE COVER. OUTSIDE DIMENSIONS 4'-8".7'-0".
(EQUAL TO PIPE INC., OR UTILITY VAULT WITH
57-7L-B, 2 3'.3' DIAMOND PLATE DOORS)
6",4" OR 3" GATE VALVE (FLxFL)
NON -RISING STEM WITH HAND WHEEL
EQUAL TO MUELLER CO. A-2380-6.
6" OR 4" (FLxPE) CEMENT LINED
DUCTILE IRON PIPE CLASS 52 3'-6"
LONG WITH COLLAR 20" FROM P.E.
EQUAL TO THOSE SUPPLIED BY PACIFIC
WATER WORKS CO. INC. 1- 3" F 4"
12" AROUND-
I
PRIVATE
JCITY
PIPING
PIPING
DEADMAN BLOCK
TEE
RTEYQUIRED WITH
_J(FL)
SHACKLING TO TEE
TOUCHREAD PITUD SENSOR
MOUNTED ON STEEL PLATE
COVER
•
TWO PIECE CAST IRON VALVE BOX,
EQUAL TO OLYMPIC FOUNDRY CO.
STANDARD 8" TOP SECTION, WITH
REGULAR BASE SECTION LENGTH TO FIT.
VALVE NUT EXTENSION IF REQUIRED
(DWG BR46/PAGE B090)
6", 4" OR 3" GATE VALVE
(FLxMJ) EQUAL TO MUELLER
CO. A-2380-20.
TC BUILDING --
4" Ill
CITY PRIVATE
PIPING I PIPING
6" OR 4" PExPE CEMENT
LINED DUCTILE IRON PIPE
CLASS 52. LENGTH TO FIT.
6",4' OR 3" COMPOUND WATER METER (FL)
EQUAL TO SENSUS SRH COMPOUND METER WITH
TOUCHREAD PITUD REGISTER & SENSOR WITH 4
WHEEL HIGH RESOLUTION (100 CUBIC FEET) /ADJUSTABLE STEEL \-6" OR 4" FLEXIBLE FLANGED
REGISTER. FOR 3" METER, REDUCE AT METER PIPE SUPPORT COUPLING ADAPTOR, ROMAC
WITH 4"X3" FI CONCENTRIC REDUCER. STANCHION BOLTED OR APPROVED EQUAL.
TO FLOOR
GENERAL NOTES
ALL METERS AND BACKFLOW PREVENTION DEVICE COMBINATIONS ARE
NOT SHOWN OR INCLUDED IN THE STANDARD DETAIL DRAWINGS. IF
YOUR PARTICULAR COMBINATION IS NOT SHOWN, AN APPROVED
DRAWING WILL BE REQUIRED BY THE UTILITY ENGINEERING DEPT. FOR
ITS INSTALLATION.
THE PRINCIPAL REQUIREMENTS REGARDING VAULT SIZING ARE THE
LENGTH OF FITTINGS OR THEIR CLEARANCE FROM THE VAULT WALLS,
(WHICH CLEARANCE SHALL BE A MINIMUM OF 12- FROM THE ENDS AND
THE SIDE CLEARANCE SHOULD BE AS TYPICALLY SHOWN ON THE
VARIOUS STANDARD DETAILS).
NOTE: DEADMAN BLOCK SHALL BE DESIGNED AND INSTALLED SO IT
BEARS AGAINST SUFFICIENT UNDISTURBED EARTH SO AS TO SUPPORT
THE DESIGNED THRUST.
3 4" & 6" COMPOUND
METER SERVICE
- T7- ADOPTED
CITY OF RENTON
STANDARD PLANS
LST DATE:04/04
DWG. NAME: BR44
1-1 /2" AND 2" WATER SERVICE DETAIL a I a
Z Z
_J
IN UNIMPROVED RIGHT-OF-WAY
CAUTION; VALVE BOX SHOULD NOT REST ON PIPE. 10 11 12 INSTALL METER BOX AT
LATER COMPACTION IN AREA OF VALVE BOX COULD a PROPERTY LINE.
o 0
CAUSE THE BREAKAGE OF THE SERVICE.
10" MIN.
14" MAX
SP PAGE:B108
Z > C� . 9 36" MIN,
:2 J 4 3
- 0 rLEAVE EXPOSED COVER
CID U
7 12"
MIN
0 BY PASS NOT NEEDED
FOR IRRIGATION METERS
f
..........
0
1 2 3 7 13
5 CRUSHED ROCK BASE
TO SUPPORT VAULT,
MAIERIAL LIST FOR 2" SERVICE; METER LOCATED IN PLANTING STRIP BETWEEN CURB &SIDEWALK MATERIAL LIST FOR 1-1/2" SERVICE: METER LOCATED IN PLANTING STRIP BETWEEN CUB AND SIDEWALK 2" BRASS NIPPLE
1. 2* tapped tee. 1. 2* topped tee. (MIPT x MIPT)
2. 6' long X 2" brass nipple with threaded ends (MIPT). 2. 6" long X 2" brass nipple with threaded ends (MIPT),
CAST IRON OR
3. 2" double disc gate valve (full opening for tapping) with threaded ends, 3. 2" double disc gate valve (full opening for tapping) with threaded ends, square DUCTILE RON•
CONCRETE BLOCKS
square operating nut, and valve nut extension if required (dwg BR46/Page B090). operating nut, and valve nut extension if required (dwg BR46/page 8090). WATERMAIN.
4. Two piece cast iron valve box. Standard 8" top section with regular base section, 4. Two piece cast iron valve box. Standard 8* top section with regular base section, FOR SERVICE FROM EXISTING
length to fit, "lug" t ype cover. length to fit, "lug" type cover. WATERMAINS INSTALL 2" FORD
5. 2* brass Pushing (MIPT x FIPT). 5. 2" X 1-1/2" hex brass bushing (MIPT x FIPT). F202 STYLE SADDEL (IPT)
2 each 2 brass or bronze nipples 6" length, threaded ends. 2 each 1-1/2" brass or bronze nipples 6" length, threaded ends.
2 each 2"-90' brass or bronze elbows (FIPT x FIPT). 2 each 1-1/2"-90' brass or bronze elbows (FIPT x FIPT). ALTERNATE CONNECTION DETAIL
5. 2: (MIPT) x compression fitting, Ford C84-66 or equal. 6. 1-112(MIPT) x compression fitting, Ford C84-66 or equal.
7. 2soft copper tubing type "K , length to fit. 7. 1-1/2" soft copper tubing type "K , length to fit. FOR EXISTING MAINS
8. 2. pack -joint 90' ell, for Ford L44-77 or equal. 8. 1-1/2' pack -joint 90' ell, for Ford L44-77 or equal.
9. 2" Customsetter with by-pass Ford VFH 77-12B x 17-3/16" or equal, with flanged 9. 1-1/2" Customsetter with by-pass Ford VFH 66-12B x 13-3/16" or equal, with flanged
angle valve and padlock wings on inlet, and angle check valve outlet, ball valve on angle valve and padlock wings on inlet, and angle check valve outlet, ball valve on
bypass with padlock wings. Customsetter shall have vertical inlet and outlet. bypass with padlock wings. Customsetter shall have vertical inlet and outlet. 1-1/2" & 2* WATER SERVICE DETAIL
10. Rigid meter spreader to be supplied and installed in meter setter by contractor. 10. Rigid meter spreader to be supplied and installed in meter setter by contractor. LOCATED IN PLANTING STI
11. Water meter shall be supplied and installed by City of Renton upon payment of all 11. Water meter shall be supplied and installed by City of Renton upon payment of all
related water meter
er fee and satisfactory pressure and purity tests. related water meter fee and satisfactory pressure and purity tests. BEEN CM & SIDEWALK
12- 17"x28" concrete meter box with 3/8" steel diamond -plate cover equal to Fog Tits 12. 17%28" concrete meter box with 3/8" steel diamond -plate cover equal to Fog Tits
Meter Seal Co. No, 2T. Meter box shall be double stacked. Meter Seal Co. No. 2T. Meter box shall be double stacked. ADOPTED
13. 2" coupling (compression x FIPT) with 2* plug (MIPT), Ford C-14-66 or equal. 13. 1-1/2" coupling (compression x FIPT) with 1-1/2" plug (MIPT), Ford C-14-66 ♦♦1I or FAR"M
The property owner is responsible for any necessary adaptation or extension of or equal. The property owner is responsible for any necessary adaptation
water service. or extension of water service. 8TANDAND PLUM
1 10/15/96 � nut LB! DAM 12/96
1 3/8/95 1 Material Ll.t. DCVAG
DWG. NAME: BR42 SP PAGE: B 107.1
1 DATE I REVISION I EYY 1APPR�
Engineering Planning Surveying
Penhallegon Associates Consulting Engineers, Inc.
750 Sixth Sreet South Kirkland, WA 98033 www.pcceengrs.com
PH: (425) 827-2014 1-800-945-8408 FAX: (425) 827-5043
Kirkland Seattle
PRECAST CONCRETE VAULT WITH 2 - Sx 3'
HINGED STEEL PLATE COVERS.
DIMENSIONS 4'-8" x 7'-0"
UTILITY VAULT CO. 57-7L-B OR EQUAL
0 INSTALL EPDXY NON -SHRINK GROUT (TYP.)
fk! 4: -4;
4" FL. x P.E. D.I. PIPE WITH
COLLAR 18- FROM P.E. �: r.Y T r
3'-4 LONG
4'
12" ALL AROUND
CONCRETE BLOCKING
ALL DOUBLE CHECK VALVE ASSEMBLIES SHALL INCLUDE PLAN
RESILIENT SEATED SHUTOFF VALVES AND TEST COCKS, AND APPROVED
CROSS- CONNECTION CONTROL ASSEMBLIES PER D.S.H.S. LATEST APPROVED LIST.
DOUBLE CHECK VALVE ASSEMBLY INCLUDES TWO RESILIENT SEATED SHUTOFF VALVES.
4"" FLANGED COUPLING ADAPTER
EQUAL TO ROMAC. 4" DUCTILE IRON CLASS 52 PIPE,
NOTE: CEMENT LINED, LENGTH TO FIT.
1. LOCATE VAULT IN PLANTING AREA NOT IN PAVING
2. 4" AND LARGER BENDS AND TEES TO BE CAST
IRON CEMENT LINED
3. TEMPORARY SUPPORT SHALL BE PROVIDED UNDER
VALVES AT THE TIME OF INSTALLATION TO CENTER
THE PIPE IN VAULT OPENING. AFTER COMPLETE
INSTALLATION REMOVE THE TEMPORARY SUPPORT
AND INSTALL CONCRETE SUPPORT PAD OR
ADJUSTABLE PIPE SUPPORT, 4" DCVA ASSMMLY
4. INSTALL GALVANIZED LADDER FOR ACCESS.
5. AFTER FIELD INSTALLATION, MAIN DDCVA AND
BY-PASS DCVA MUST BE TESTED SATISFACTORILY
BY A DEPT. OF HEALTH CERTIFIED BACKFLOW
ASSEMBLY TESTER. TEST REPORT TO BE SUBMITTED
TO CITY OF RENTON WATER UTILITY ENGINEERING
DEPT. PRIOR TO ACTIVATION OF NEW LINE.
6. INSTALL BRASS PLUGS AT ALL TEST COCKS ADOPTED
Crff or Fiat=
STA111111111M PLAW
Lff DIA 1 M96
12/96 REFORMAT TO 1 1"xl 7" JDCV DIRT
3/7/95 EDITED TEXT AND DIMENSIONS I DC I AG
FDATE I - REVISION I BY IAPPR'a DWI NAME: BR56A (MODIRED) SP PAGE: B098.1
PRECAST CONCRETE VAULT WITH 3 - 3'x 3'-
HINGED STEEL PLATE COVERS. DIMENSIONS
5'-8"x 11'-2"x 7'-2" EQUAL TO UTILITY
VAULT OR EQUAL
TOUCH READ PIT LID SENSOR
MOUNTED ON STEEL PLATE
COVER THROUGH 1-5/8- DIA.
DRILLED HOLE IN COVER.
THE BY-PASS ASSEMBLY SHALL BE
INCLUDED AS PART OF THE DETECTOR
DOUBLE CHECK VALVE ASSEMBLY.
5/8'x3/4" SENSUS SRII (TR/PL) METER
_1C
CITY PRIVATE
Z PIPING PIPING
TEE (MJ x FL)
3'-2"
O GATE VALVE (FL x MS)
5'- 8"
ONE EACH SIDE
4" ADAPTER, FL.x SCREWED
4"x4"x6" BULL HEAD TEE, FL.--\
6" PIPE FL.x FL.
2'-0" LONG -
18" FOR 10" ASSEMBLY
17 1/2" FOR 8" ASSEMBLY
18 1/2- FOR 6- ASSEMBLY
11'-
6" 90* BEND
3'- 0'
12" ALL AROUND 2'_ 6'-' 6
CONCRETE BLOCKING -
ALL DETECTOR DOUBLE CHECK VALVE
ASSEMBLIES SHALL INCLUDE RESILIENT
10", 8" OR 6" FL.x P.E. SEATED SHUTOFF VALVES AND TEST PLAN
I
PIPE WITH COLLAR 18 COCKS. AND APPROVED
FROM P.E.CROSS-CONNECTION CONTROL
10"- 3'-��- LONG ASSEMBLIES PER DEPARTMENT OF
8"- S-15 LONG HEALTH LATEST APPROVED LIST.
6"- 4'-0
" LONG
DOUBLE CHECK VALVE ASSEMBLY
INCLUDES TWO RESILIENT SEATED
SHUTOFF VALVES.
10% 8-, OR 6- FLANGED COUPLING
ADAPTER EQUAL TO ROMAC.
TOUCH READ PIT LID SENSOR MOUNTED
ON STEEL PLATE COVER THROUGH
1-5/8- DIA. DOLLED HOLE IN COVER.
18" FOR 10" ASSEMBLY 17
1/2" FOR 8- ASSEMBLY 18
1/2" FOR 6- ASSEMBLY -
5/8"x3/4" INVENSYS -
TR-PL METER
6" MIN, DRAIN TO DAYLIGHT OR
STORM DRAIN SYSTEM WITH
CATCH BASIN OR MANHOLE
COMPACTED FOUNDATION END VIEW
NOTE: GRAVEL
1. LOCATE VAULT IN PLANTING AREA, NOT IN PAVING.
2. 4" AND LARGER BENDS AND TEES TO BE CAST IRON CEMENT LINED.
3. TEMPORARY SUPPORT SHALL BE PROVIDED UNDER VALVES AT THE
TIME OF INSTALLATION TO CENTER THE PIPE IN VAULT OPENING. AFTER
COMPLETE INSTALLATION REMOVE THE TEMPORARY SUPPORT AND
INSTALL ADJUSTABLE PIPE SUPPORT.
4. INSTALL GALVANIZED LADDER FOR ACCESS.
5. AFTER FIELD INSTALLATION, MAIN DDCVA AND BY-PASS DCVA MUST BE
TESTED SATISFACTORILY BY A DEPT. OF HEALTH CERTIFIED BACKFLOW
ASSEMBLY TESTER. TEST REPORT TO BE SUBMITTED TO CITY OF RENTON
WATER UTILITY ENGINEERING DEPT. PRIOR TO ACTIVATION OF NEW LINE.
6.1 INSTALL BRASS PLUGS AT ALL TEST COCKS
I DATE I V�y
6" 90' BEND FL.--"
'--GALVANIZED STEEL
LADDER
4"x 2 1/2" FIRE DEPARTMENT DOUBLE
CONNECTION FOR STAND PIPE WITH
BREAKABLE CAST IRON HOSE CAPS.
ONE EACH SIDE EQUAL TO GRINNEL
FIG. 1682 WITH HOSE CAPS FIG. 1333.
6" SWING TYPE GRAVITY OPERATED
CHECK VALVE, FL. EQUAL TO
MUELLER CO. A-2600-6 WITH BALL
DRIP VALVE AT BOTTOM
INSTALL EPDXY NON -SHRINK
GROUT (TYP.)
PIPE, FL.x FL. 3'0" LONG
6"& 8" ASSEMBLY. 6" SHORT
RADIUS 90* BEND FL.
10" ASSEMBLY 90' 8"X6-
FREDUCING BEND FL.
TO BUILDING
DEADMAN
BLOCK
REQUIRED.
10", 8", 6" FL x MJ ADAPTOR
10" ASSEMBLY 10"x10*x8"TEE FL.
8" ASSEMBLY 8"XI81"x6" TEE, FL. 6"
ASSEMBLY 6'x6"x6" TEE, FL.
10-, 8-, OR 15- GATE VALVE, FL.x MJ,
WITH INDICATOR POST. INDICATOR
POST VALVE SAME SIZE AS DOUBLE
CHECK VALVE (MUELLER CO. OR
EQUAL).
10-, 8-, OR 6- DUCTILE IRON
CLASS 52 NIPPLE PIPE,
CEMENT LINED, LENGTH TO FIT,
ADJUSTABLE STEEL PIPE SUPPORT,
STANCHIONS BOLTED TO FLOOR.
io", a* & a* DDcv Assmmy
6- STANDPIPE W/4 2-1/2- NOZZLE
CROSS CONNECTION/BACKFWW
PROTECTION ASSEMY
ADOPTED
Ciff or REHM
grANDIM FLM
Lff DAM 04/04
DWI NAME: BR56 SP PAGE: 8099
�iEc�o��.�s No F�ePerm�
� Pw�
RECOMMENDED FOR APPROVAL
DATE
41/
DATE )7LO S,
DATE
By DATE
CITY OF
RENTON
Planning/Building/Public Works Dept.
Gregg Zimmerman P.E., Administrator
Call
before you
Dig.
1-800-424-5555
UNDERGROUND SERVICE (USA)
SCANNED APR 2 2