HomeMy WebLinkAboutWTR2703226.7Q of
(01
EXIST. SHACKLE RODS
RJ FOR 60'
NEWS 1�I. o EX. 12" D.I.
INSTALL POLYPIGGING
CROSS, RJxFL
TEMP. BLOWOFF
TESTING DETAIL
45' VERT, BENDS TIE SHACKLE RODS
TO NEW BEND
12" D.I. RJ
12" D.I. RJ� EX. 12" D.I.
(80,) - -
UPON COMPLETION OF TESTING, CLEANING &
DISINFECTION, REMOVE TEMP. BLOWOFF AND
BLOCK & CONNECT TO EXISTING W/ 2-12"
VERTICAL 45• BENDS, RJxRJ AND 2-12"
SPOOLS. CONNECT BOTTOM BEND TO EXIST.
SHACKLE RODS. FINAL CONNECTION BY CITY
FORCES.
FINAL CONNECTION
CONNECTION AT WILLIAMS AVENUE S.
AND S. 2ND STREET
NTS
(IE) EX. STORM
LDRAIN PIPE
(CROWN)
(IE) PROPOSED 12"
4" ETHAFOAM PAD WATER MAIN
EX. 6" SANITARY
SEWER SERVICE
EX. 8" SANITARY
SEWER MAIN
I
(CROWN)
NOTE:
PROPOSED WHERE MINIMAL
VERTICAL CLEARANCE IS
AVAILABLE BETWEEN UTILITIES.
UTILITY CROSSING DETAIL
NTS
FINISH GRADE ELEVATION
3 FT. MIN. COVER (10-INCH DIAMETER AND UNDER)
4 FT. MIN. COVER (12-INCH DIAMETER AND OVER)
UNLESS OTHERWISE APPROVED BY THE CITY OF RENTON
NEW WATER MAIN =f�OLYPIG
TEMPORARY 2" GALVANIZED PIPE
AND 2" GATE VALVE
INSTALL 2" PLUG ON TOP BLIND FLANGE
AFTER REMOVAL OF POLYPIG
NOTE:
SIZE OF THE VERTICAL CROSS SHALL BE THE SAME AS SIZE OF MAIN LINE.
VERTICAL CROSS (MJxFL)
ONE BLIND FLANGE ON TOP OF CROSS WITH 2" TAP & 2" TEMPORARY BLOW -OFF ASSEMBLY
(REMOVE BLOW -OFF ASSY. AND INSTALL 2" PLUG AFTER REMOVAL OF CLEANING "POLY -PIG")
ONE BLIND FLANGE ON BOTTOM OF CROSS
ONE PLUG (MJ) ON END OF CROSS
CONCRETE BLOCKING
ALL DEBRIS AND POLYPIGS SHALL BE REMOVED FROM SUMP OF VERTICAL CROSS BEFORE
DISINFECTION OF NEW WATER MAIN.
VERTICAL CROSS FOR POLYPIGGING STATION
NTS
X POLYPIGGIN13 CROSS
w. 8't SEE DETAIL
q
NEW 12" D.I.
0
CONNECT TO EX. 24" D.I.
1-24"x12 TAPPING TEE W/BLOCK
1-12" GATE VALVE, FLxMJ
1-12" MJ PLUG W/2" TAP
1-TEMPORARY BLOWOFF
j 1-TEMPORARY BLOCK
TESTING DETAIL
_ 0 12" D.I.
UPON COMPLETION OF TESTING
CLEANING & DISINFECTION,
REMOVE TEMPORARY BLOWOFFS
& BLOCKS AND CONNECT W/12"
SPOOLS & MJ SLEEVE. FINAL
CONNECTION BY CITY FORCES.
FINAL CONNECTION
CONNECTION AT WILLIAMS AVENUE S.
AND S. TOBIN ST.
NTS
c
i
i
DEPTH
AS REQ'D
u
TEMPORARY STREET RESTORATION NOTES
A) THE CONTRACTOR SHALL PATCH ALL TRENCH CUTS AT THE END OF EACH WORKING
DAY WITH A TEMPORARY ASPHALT PATCH, EXCEPT THE LAST SECTION OF THE TRENCH
WHICH MAY BE COVERED WITH STEEL SHEETS. TEMPORARY PATCHES SHALL BE
COMPACTED WITH A ROLLER COMPACTOR TO A DENSITY WHICH WILL PROVIDE A
SMOOTH, FIRM SURFACE FOR VEHICLES. THE PATCHES SHALL BE MAINTAINED
THROUGHOUT THE DURATION OF THE PROJECT TO PREVENT POT HOLING AND RUTS
FROM FORMING. ALL POTHOLES, RUTS AND BUMPS SHALL BE REPAIRED IF THE
DEFECT EXCEEDS AN INCH IN DEPTH OR HEIGHT.
B) AT THE END OF EACH WORKING WEEK, THE ENGINEER WILL INSPECT THE TEMPORARY
PATCHES. IF THE TEMPORARY PATCHES DO NOT PROVIDE AN ADEQUATE DRIVING
SURFACE, AS DETERMINED BY THE ENGINEER, THE CONTRACTOR SHALL INSTALL A
PERMANENT PATCH AS NOTED ON THE PAVEMENT RESTORATION DETAILS.
PAY LIMIT TRENCH BACKFILL, 3' MAINLINE, 2'
WATER SERVICES AND HYDRANT LATERALS
SEE PAVEMENT RESTORATION DETAILS AND
TEMPORARY STREET RESTORATION NOTES
FOR TRENCH PATCHING REQUIREMENTS
III �►
4IIIIIIIIIIIN
LANE LINE
MARKING 7,_8„
STANDARD VEHICLE WHEEL PATH
-3'-
MIN.
2" CLASS "B"
2" SAWCUT AND REMOVE
OR GRIND, SEAL
WITH AR4000W
* MINIMUM ACP CLASS 'E' SHALL BE:
** PRINCIPAL/MINOR/COLLECTOR ARTERIAL STREETS
& INDUSTRIAL ACCESS STREETS - 6" ACP CLASS 'E' OR `B'
RESIDENTIAL ACCESS STREETS - 2" ACP CLASS `E' OR 'B'
** NOTE: UPON REQUEST OF ENGINEER, NEW ROADWAY PAVEMENT
SECTION MAY BE DESIGNED USING AN APPROVED METHOD FOR
DETERMINING PAVEMENT THICKNESS.
C)Engineering Planning Surveying 3 PERMIT RESUBMITTAL
Penhallegon Associates Consulting Engineers, Inc. 2 PERMIT RESUBMITTAL
750 Sixth Street South <�rklond, WA 98033 www.pciceengrs.com 1 PERMIT RESUBMITTAL
C, S PH: (425) 827-2014 800-945-8408 FAX: (425) 827-5043
Kirkland Seattle N 0.
REVISION
4.5'
MIN.
is
I
2.5'
MIN.
SURVEYED:
DESIGNED:
FPH
3/3/05
FPH
JS
2/14/05
DBH
DRAWN:
JS
1/10/05
DBH
CHECKED:
BY
DATE
APPR
AF'PRD�ED:
SUBSEQUENT BACKFILL MATERIAL (NATIVE IF
APPROVED BY ENGINEER) OR IMPORT PER
SECTION 9-03.14(1) GRAVEL BORROW
12" D.I. WATER MAIN
WITH POLY WRAP
PIPE ZONE MATERIAL PER SECTION
9-03.12(3) GRAVEL BACKFILL FOR PIPE
ZONE BEDDING
EXCAVATION BACKFILL OF UNSUITA
FOUNDATION MATERIAL (IF NECESSARY)
DEPTH AS APPROVED BY ENGINEER.
MATERIAL SHALL MEET SECTION 9-03.9(1)
BALLAST.
WATER MAIN/WATER SERVICES
TYPICAL TRENCH BEDDING AND BACKFILL
NTS
V- ACP CLASS
MIN. `E' OR `B'
6" CRUSHED SURFACING
TOP COURSE
EDGE OF PAVEMENT,
EDGE OF CURB & GUTTER,
OR CENTER OF LANE LINE
CRUSHED ROCK, FLOWABLE FILL
OR AS REQUIRED BY ENGINEER
W I Ll , ! : �, AVE SO UTN
LANE WMM OVERLAY
FOR FLEMBLE PAVEMENT ONLY
_� ADOPTED
CITY OF RENTON
STANDARD PLANS
8 LST DATA: 12/96
BY APPR DWG. NAME: HR-05 SP PAGE: H032
SCALE:
1 M-20'-OM
ONE INCH
AT FULL SCALE
IF NOT ONE INCH
SCALE ACCORDINGLY
VERTICAL: NAVO 1988
HORIZONTAL: NAD 1983/1991
DATUM
RECOMMENDED FOR APPROVA
Bra.
BY
BY
�_- CITY OF
RENTON
Planning/Building/Public Works Dept.
Gregg Zimmerman P.E., Administrator
WATER UTILITY GENERAL NOTES
1, ALL WORK MATERIALS SHALL BE IN CONFORMANCE WITH THE STANDARDS AND
SPECIFICATIONS OF THE CITY OF RENTON UTILITY DEPARTMENT AND THE LATEST
EDITION OF THE WSDOT/APWA STANDARDS AND SPECIFICATIONS, AS APPROVED
BY THE CITY OF RENTON. A SET OF APPROVED PLANS SHALL BE KEPT ON
SITE AT ALL TIMES DURING CONSTRUCTION.
2. THE HOURS OF WORK IN THE STREET RIGHT-OF-WAY SHALL BE LIMITED TO
8:30 AM TO 3:30 PM ON WEEKDAYS UNLESS OTHERWISE APPROVED IN WRITING
BY THE DEPARTMENT OF PUBLIC Wr)PKS AT 235-2635. ALL STREET
CLOSURES, PARTIAL OR FULL, SHALL BE APPROVED BY THE DEPARTMENT OF
PUBLIC WORKS 24 HOURS IN ADVANCE. THE POLICE DEPARTMENT, FIRE
DEPARTMENT, AND 911 SHALL BE NOTIFIED 24 HOURS IN ADVANCE.
3. ALL LOCATIONS OF EXISTING UTILITIES SHOWN ARE APPROXIMATE AND IT SHALL
BE THE CONTRACTOR'S RESPONSIBILITY TO VERIFY THE TRUE AND CORRECT
LOCATION SO AS TO AVOID DAMAGE OR DISTURBANCE. FOR UTILITY LOCATE
CALL UTILITIES UNDERGROUND LOCATION CENTER, 1-800-424-5555.
4. ALL WATER MAIN PIPE TO BE CEMENT LINED DUCTILE IRON PIPE CONFORMING
TO AWWA C110 AND C111 OR LATEST REVISION, THICKNESS CLASS 52 CEMENT
MORTAR LINING AND SEAL COATING SHALL CONFORM TO AWWA C104 OR
LATEST REVISION. PIPE JOINTS TO BE PUSH -ON OR MECHANICAL JOINT.
BEDDING TO BE CLASS C. ALL DUCTILE IRON PIPE INSTALLED SOUTH OF
SUNSET BLVD. (EMPIRE WAY, SR 900) AND WEST OF SR 167 (EAST VALLEY
FREEWAY) OR IN SOILS OF HIGH RESISTIVITY SHALL BE POLYETHYLENE WRAPPED
PER ANSI/AWWA C105-77 STANDARDS.
5. CAST IRON AND DUCTILE IRON FITTINGS SHALL BE CEMENT LINED, PRESSURE
RATED AS NOTED ON PLANS, AND IN ACCORDANCE WITH ANSI/AWWA
C110/A21.10-82. CEMENT LINING SHALL BE IN ACCORDANCE WITH ANSI/AWWA
C104/A21.4-85. IF FITTINGS ARE 3 INCHES TO 12 INCHES IN DIAMETER AND
HAVE MECHANICAL JOINTS, THE FITTINGS SHALL BE IN ACCORDANCE WITH
EITHER ANSI/AWWA C110/A21.10-82 OR ANSI AWWA C153/A21.53-84. 3-INCH
TO 12-INCH DIAMETER FITTINGS WHICH HAVE MECHANICAL JOINTS AND/OR
FLANGED JOINTS SHALL BE IN ACCORDANCE WITH ANSI/AWWA C110/A21.10.82
OR A COMBINATION OF ANSI/AWWA C110/A21.10.82 AND ANSI/AWWA
C153/A21.53-84 SUCH THAT THE PORTION OF THE FITTING WITH A
MECHANICAL JOINT(S), MAY BE IN ACCORDANCE WITH ANSI/AWWA
C153/A21.53-84 AND THAT PORTION OF THE FITTING WITH FLANGED JOINT(S)
SHALL BE IN ACCORDANCE WITH ANSI/AWWA C110/A21.10-82. ACCEPTANCE
TESTING IN ACCORDANCE WITH SECTION 53-5.3 OF ANSI/AWWA
C153/A21.53-84 OR WITH SECTION 10-13 OF ANSI/AWWA C110/A21.10-82
SHALL BE OBTAINED BY THE CONTRACTOR AND TRANSMITTED TO THE OWNER.
6. GATE VALVES SHALL CONFORM TO AWWA C500 AND SHALL BE IRON BODY,
BRONZED -MOUNTED, DOUBLE DISC WITH BRONZE WEDGING DEVICE AND O-RING
STUFFING BOX. VALVES SHALL BE DESIGNED FOR A MINIMUM WATER
OPERATING PRESSURE OF 200 PSI. GATE VALVES SHALL BE CLOW LIST 14,
MUELLER COMPANY NO. A2380, OR M&H. ALL VALVES 12" IN DIAMETER AND
LARGER, SHALL BE INSTALLED IN A VAULT. SEE WATER STANDARD DETAIL FOR
12" GATE VALVE ASSEMBLY VAULT AND 1" BYPASS INSTALLATION.
7. FIRE HYDRANTS SHALL BE COREY TYPE (OPENING WITH THE PRESSURE)
CONFORMING TO AWWA C504-80 WITH A 6 INCH INLET AND A M.V.O. OF 5
INCHES, TWO 2-1/2 INCH HOSE NOZZLES WITH NATIONAL STANDARD 7 INCH,
60 DEGREES V. THREADS, O.D. THREAD 4.875 AND ROOT DIAMETER 4.6263,
1-1/4 INCH PENTAGON OPERATING NUT OPENED BY TURNING COUNTER
CLOCKWISE (LEFT).
8. ALL WATER MAIN 10 INCHES AND SMALLER TO MAINTAIN A MINIMUM COVER OF
36 INCHES BELOW FINISH GRADE. ALL WATER MAIN 12 INCHES AND LARGER
SHALL BE AT A MINIMUM OF 48 INCHES BELOW FINISH GRADE. WHERE UTILITY
CONFLICTS OCCUR, WATER MAINS ARE TO BE LOWERED TO CLEAR.
9. ALL WATER MAINS SIX (6) INCHES IN DIAMETER AND LARGER SHALL BE
CLEANED WITH PIPE CLEANING "PIGS" PRIOR TO DISINFECTION. THE "POLY
PIGS" SHALL BE GIRARD INDUSTRIES AQUA SWAB -AS OR APPROVED EQUAL, 2
LB/CU FT DENSITY FOAM WITH 90A DUROMETER URETHANE RUBBER COATING
ON THE REAR OF "PIG" ONLY. "PIGS" SHALL BE CYLINDER SHAPED WITH
BULLET NOSE OR SQUARE END. THE CITY WILL ASSIST THE CONTRACTOR WHO
WILL PERFORM THE CLEANING OPERATION.
9A. ALL WATER MAINS AND SERVICES SHALL BE PRESSURE TESTED TO A MINIMUM
OF 200 PSI OR 150 PSI OVER OPERATING PRESSURE IN ACCORDANCE WITH THE
SPECIFICATIONS OF THE CITY OF RENTON AND THE WASHINGTON STATE HEALTH
DEPARTMENT. ALL PRESSURE TESTING SHALL BE DONE IN THE PRESENCE OF A
REPRESENTATIVE OF THE CITY OF RENTON.
9B. ALL WATER MAINS AND SERVICES SHALL BE DISINFECTED BY THE INJECTION OF
A 50 PPM (MINIMUM CONCENTRATION) CHLORINE/WATER SOLUTION. DRY
CALCIUM HYPOCHLORITE SHALL NOT BE PLACED IN THE PIPE AS LAID.
CHLORINE SHALL BE METERED/INJECTED IN ACCORDANCE WITH SECTION
7-11.3(12)E OR 7-11.3(12)F OF THE STANDARD SPECIFICATIONS REFERENCED IN
1 ABOVE.
10. A PRECONSTRUCTION CONFERENCE IS REQUIRED PRIOR TO ANY CONSTRUCTION.
A MINIMUM OF THREE (3) WORKING DAYS NOTICE IS REQUIRED FOR SCHEDULING.
PRIOR TO SCHEDULING THE PRECON A PERMIT INFORMATION SHEET MUST BE
SUPPLIED TO THE UTILITY ENGINEER'S OFFICE. TWENTY-FOUR HOUR NOTICE
WILL BE REQUIRED PRIOR TO STARTING NEW CONSTRUCTION.
11. IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY TO SECURE ALL NECESSARY
PERMITS PRIOR TO STARTING CONSTRUCTION.
12. INSTALLATION OF CORPORATE STOPS, WATER SERVICES, LINES AND METERS
SHALL NOT BE DONE UNTIL ALL SERVICE AGREEMENTS, METER APPLICATIONS,
CONSTRUCTION PERMITS, AND PAYMENT OF FEES HAVE BEEN MADE TO THE
CITY OF RENTON.
13. ALL CONNECTION TO EXISTING MAINS TO BE ACCOMPLISHED BY THE CITY OF
RENTON, EXCEPT WET TAPS WHICH MAY BE MADE BY APPROVED WET TAP
CONTRACTORS WITH PRIOR APPROVAL OF FROM THE DEPARTMENT OF PUBLIC
WORKS. ALL NECESSARY EXCAVATION AND MATERIALS TO BE SUPPLIED BY
THE CONTRACTOR AND BE ON -SITE PRIOR TO CITY NOTIFICATIONS.
14. INSPECTION WILL BE ACCOMPLISHED BY A REPRESENTATIVE OF THE CITY OF
RENTON. IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY TO NOTIFY THE
UTILITY DEPARTMENT 24 HOURS IN ADVANCE OF BACKFILLING ALL
CONSTRUCTION. THE CONTRACTOR, AS WELL AS THE ENGINEERS, SHALL KEEP
AS -BUILT DRAWINGS.
15, CONTRACTOR TO PROVIDE PLUGS AND TEMPORARY BLOW -OFF ASSEMBLIES FOR
TESTING AND PURITY ACCEPTANCE PRIOR TO FINAL TIE-IN.
16. ALL JOINT RESTRAINT SYSTEMS (SHACKLE RODS, NUTS, BOLTS, ETC.)
SHALL BE AS MANUFACTURED BY THE STAR MANUFACTURING COMPANY OF
COLUMBUS, OHIO OR EQUAL APPROVED IN WRITING BY THE DEPARTMENT OF
PUBLIC WORKS.
17. ASPHALT AND CONCRETE STREET PAVING SHALL BE SAWCUT TO A MINIMUM
DEPTH OF TWO INCHES. OIL MAT STREETS MAY BE SPADE CUT. ALL SURFACE
CONCRETE, PAVEMENT, SIDEWALKS, CURB, GUTTERS, AND DRIVEWAY
APPROACHES SHALL BE SAWCUT TO A MINIMUM DEPTH OF TWO INCHES OR
REMOVED TO AN EXISTING EXPANSION POINT.
18. A TEMPORARY COLD MIX ASPHALT PATCH SHALL BE PLACED ON THE DAY OF
INITIAL EXCAVATION WITH A PERMANENT, SEALED PATCH TO BE PLACED, TO
CITY OF RENTON POLICY, WITHIN TEN DAYS. CALL FOR SUBGRADE INSPECTION
PRIOR TO PLACEMENT OF FINAL PATCH. TRENCHES WILL NOT BE LEFT OPEN
OVER NIGHT WITHOUT PRIOR WRITTEN APPROVAL OF THE INSPECTOR.
19. FOR CITY PROJECTS SUCH AS TELEMETRY CONDUIT, THE PVC PIPE USED SHALL
BE SCHEDULE 40 IN UNIMPROVED AREAS AND SCHEDULE 80 UNDER IMPROVED
AREAS. ALL CHEMICAL PROCESS LINES SHALL BE SCHEDULE 80 PVC PIPE.
L PEIV,
�
4� �q of wAs�J�-�p� of was,�,r
DATE.
DATE Y31
DATE ! !
21792 16067
DATE I IST1✓'R �1�' , .,S�IS'1' ��''
ONAL I
EXPIRES 3/19/07 EXPIRES 07/20/06
DATE:
WATER MAIN REPLACEMENT
FIELDBOOK:
WILLIAMS AVENUE S. PAGE:
S. 2ND STREET TO S. RIVERSIDE DRIVE DRAWING NO:
NOTES & DETAILS C3.2
SHEET: 3 OF: 4
32•26SCANNED APR 2 2