PROPOSED CURRENT TRANSFORMER
AS APPROVED BY P.S.E.
PROPOSED REVENUE METERING.
METER ENCLOSURE SHALL BE
PROVIDED BY THE CONTRACTOR AND
SHALL MEET P.S.E STANDARDS.
GROUND CONNECTION POINT (TYPICAL).
SEE GROUNDING DETAILS ON DWG NO.
E08 FOR MORE INFORMATION.
#2/0 BARE COPPER GROUND
ELECTRODE CONDUCTOR TO
GROUND ELECTRODES PER N.E.C.
3/4" X 8' LONG COPPER GROUND
ROD (TYPICAL). INSTALL PER N.E.C.
SEE GROUNDING DETAILS ON DWG
NO. E08 FOR MORE INFORMATION.
P.S.E. PRIMARY SERVICE
WIRING FROM PROPOSED
SERVICE TRANSFORMER.
SEE DWG NO. C08 FOR
CONTINUATION.
PROPOSED PAD -MOUNTED SERVICE
TRANSFORMER. SEE DWG NO. C08 FOR
PROPOSED LOCATION. TRANSFORMER
AND TRANSFORMER PAD SHALL BE
PROVIDED BY P.S.E.
REBA
BUILDING
FOUNDATION.
1
INSIDE
PROPOSED CURRENT _
TRANSFORMER CABINET.
AUTOMATIC TRANSFER SWITCH.
SEE SPECIFICATIONS.
I
OUTSIDE
I I
i
i02 `
EXISTING UTILITY METER AND
WIRING TO BE REMOVED AND
RETURNED TO CITY.
I
EXISTING TRANSFORMER
PROVIDE AND INSTALL VAULT TO BE REUSED AFTER I
NEW VAULT LID PER REMOVAL OF EXISTING
RFI-014 TRANSFORMER BY PUGET I
® SOUND ENERGY.
� I
I
i
EXISTING JUNCTION BOX TO
BE REUSED. SEE DWG NO.
C08 FOR MORE INFORMATION.
104
p E
EXISTING SYSTEM
CONTRACTOR SHALL USE GROUND'
EXISTING CONDUIT TO PULL -'¢ ®----
PROPOSED CONDUCTORS.
I
INSIDE
I �
� I
i
90OA 3P ' I
TM
1000A
i
I
I•
105
1000A, 48OV, 30, 3W WITH NEUTRAL LUG, 65 KAIC WITHSTAND_
ONE -LINE DIAGRAM
NO SCALE
1O00A, 48OV, 30, 3W
NEUTRAL
K
900AT
1000AF
TB
POWER
METER
TB
4 K
600AT
600AF
�L EXISTING SWITCHBOARD.
800A 3P
TM
�A 08, �C I
G �B C
PROPOSED EG
CONNECTION CABLES.
SEE SPECIFICATIONS.
103
I �A B �C 20A
I
IGfN�'A B C
HEATER
M
10 kW
30A 3P
TM
MCC A
300AT 800A, 480V, 30, 3W
300AF
800AT
800AF
30AT
30AF
300A/3P
SSRVS
PROPOSED NORTH TALBOT GENERATOR
® BUILDING SWITCHBOARD.
900A 3P ! 20A/2P
TM ( J TM
I 5 kVA
! 48OV-240/120V
I I
E
i
i
102 s
SEE DWG NO. COB FOR CONDUIT AND
CONDUCTOR ROUTING TO EXISTING NORTH
TALBOT BOOSTER PUMP STATION.
SSRVS
LIGHTING
PANEL
480V -
240/120V
REVISED TO CONFORM
TO CONSTRUCTION RECORDS
ZYG'�' 4 11 01 2007
RH2 ENGINEERING INC. DATE
I
MCC B
600A, 48OV, 30, 3W
30A/2P 30OA/3P
SSRVS
SSRVS
250 HP 200 HP 125 HP 30 HP
15 kW
PUMP #1 PUMP #2 PUMP #3 PUMP #4
NORTH TALBOT BOOSTER PUMP STATION
NO SCALE
ELECTRICAL NOTES
LIGHTING PANEL WILL BE A 125 AMP, 120/240 VOLT, 1PH, 3 WIRE WITH 60 AMP BACK FED
MAIN BREAKER AND 18 POLE SPACES. PANELS AND BREAKERS TO BE 22KAIC.
UPON COMPLETION OF THE ELECTRICAL SYSTEM AT THE NORTH TALBOT GENERATOR BUILDING,
THE CONTRACTOR SHALL COORDINATE WITH PUGET SOUND ENERGY (P.S.E.) TO REMOVE THE
EXISTING PAD -MOUNT SERVICE TRANSFORMER LOCATED AT AND SERVING THE NORTH TALBOT
BOOSTER PUMP STATION. THE CONTRACTOR SHALL SCHEDULE THIS WORK WITH THE CITY 3
BUSINESS DAYS PRIOR TO REMOVING THE TRANSFORMER. A PORTABLE GENERATOR WILL BE
PROVIDED AND MAINTAINED AT THE NORTH TALBOT BOOSTER PUMP STATION BY THE CITY
DURING THE POWER OUTAGE. CONTRACTOR SHALL BE ALLOWED 3 BUSINESS DAYS TO
COMPLETE THE CONDUIT AND CONDUCTOR ROUTING FOR SUPPLY POWER TO THE BPS.
EXISTING CITY OWNED 500 kW GENERATOR CURRENTLY IS EQUIPPED WITH A CURBSIDE
EMERGENCY POWER CONNECTION PANEL WITH DOUBLE LUGS FOR EACH PHASE. CONTRACTOR
SHALL REMOVE THIS EMERGENCY POWER CONNECTION PANEL AND SHALL REPLACE IT WITH A
NEMA 4 STAINLESS STEEL ENCLOSURE WITH PARALLEL CROUSE-HINDS E0400-1687 POSI-LOK
RECEPTACLES. RECEPTACLES SHALL BE FEMALE. PANEL WITH CROUSE-HINDS POST-LOK
RECEPTACLES SHALL BE CONSTRUCTED BY SKYLINE ELECTRIC MANUFACTURING COMPANY OF
SEATTLE WASHINGTON MODEL NO. 59344. SEE ELECTRICAL EQUIPMENT LEGEND, ITEM C THIS
SHEET. CONTRACTOR SHALL RETURN THE EXISTING CONTROL PANEL TO THE CITY SHOP.
THE EXISTING 500 KW PORTABLE GENERATOR IS ALSO EQUIPPED WITH A POWER AND
TELEMETRY ENTRANCE ENCLOSURE. THIS ENCLOSURE CURRENTLY HAS THREE (3) 24" LONG
POWER CORDS WITH 125 VOLT, 20-AMP, 3-WIRE GROUNDED MALE CONNECTION PLUGS.
CONTRACTOR SHALL REMOVE EACH MALE CONNECTION PLUG AND REPLACE EXISTING POWER
CORDS WITH 25 FOOT LENGTH, 600 VOLT RATED, 20-AMP, 3-WIRE SO TYPE CORD AND
SHALL INSTALL THE EXISTING MALE CONNECTION PLUGS TO EACH END OF THE THREE (3)
PROPOSED POWER CORDS.
ADDITIONALLY, THIS ENCLOSURE CONTAINS A VANTAGE TECHNOLOGIES RECEPTACLE MOUNTED
IN THE POWER AND TELEMETRY ENTRANCE ENCLOSURE WITH THE FOLLOWING SOCKET
ASSIGNMENTS.
SOCKET 1 - COMMON
SOCKET 2 - LOW FUEL
SOCKET 3 - GROUND
SOCKET 4 - GENERATOR FAILURE
SOCKET 5 - GENERATOR TROUBLE
SOCKET 6 - GENERATOR RUN
SOCKET 7 - SPARE
CONTRACTOR SHALL WIRE SOCKET 2 TO THE EXISTING TANK RUPTURE LEAK DETECTOR.
SOCKETS 3 AND 6 SHALL BE WIRED FOR THE START SIGNAL FROM THE ATS AND THE
VENTILATION CALL RESPECTIVELY.
CONTRACTOR SHALL PROVIDE A 100 FOOT CABLE ASSEMBLY WITH PLUGS. THE CABLE
ASSEMBLY SHALL BE A VANTAGE TECHNOLOGIES PART. NO. V-70253-CA-1200. CABLE
ASSEMBLY WILL BE UTILIZED TO PLUG INTO A VANTAGE TECHNOLOGIES RECEPTACLE MOUNTED
IN THE SIGNAL CABINET. SEE SPECIFICATIONS FOR SIGNAL CABINET INFORMATION,
CONTRACTOR SHALL FIELD VERIFY TO ASSURE THAT THE GROUND AND NEUTRAL ON THE
EXISTING PORTABLE ENGINE GENERATOR IS NOT BONDED. IF BONDED, CONTRACTOR SHALL
REMOVE BONDING,
CONTRACTOR SHALL COORDINATE THIS WORK WITH THE CITY OF RENTON MAINTENANCE SHOP
AND SHALL GIVE THE CITY 1 WEEK NOTICE PRIOR TO MAKING CHANGES, CONTRACTOR WILL BE
GIVEN FIVE (5) WORKING DAYS TO COMPLETE WORK ON THE EXISTING GENERATOR.
GENERATOR SHALL BE RETURNED IN WORKING OPERATION BEFORE PSE TRANSFORMER CHANGE
CAN TAKE PLACE.
4� CONTRACTOR SHALL REMOVE BONDING JUMPER BETWEEN THE NEUTRAL AND GROUND BUS
BARS IN ORDER TO COMPLY WITH WAC 296-46B-250(2),
ELECTRICAL EQUIPMENT LEGEND
ITEM
DESCRIPTION
MANUFACTURER
PART NO.
SURGE PROTECTIVE DEVICE WITH INTERNAL
INNOVATIVE TECHNOLOGIES
VG160-3Y201-SD
I ®
SURGE RATED FUSES. CONDUIT AND WIRING
PER MANUFACTURER'S RECOMMENDATIONS.
EMERGENCY GENERATOR RECEPTACLE PANEL
CROUSE-HINDS (OR APPROVED
E0400-1662
TYPICAL OF TWO IN PARALLEL. COMPLETED
EQUAL)
©
ASSEMBLY SHALL HAVE A MINIMUM
I
CAPACITY OF 800 AMPS. RECEPTACLES
SHALL BE MALE.
NEMA 4 STAINLESS STEEL ENCLOSURE WITH
SKYLINE ELECTRIC
59344
[
PARALLEL CROUSE-HINDS E0400-1687 AMP
MANUFACTURING
�
{ �:J
POST-LOK RECEPTACLES. RECEPTACLES
SHALL BE FEMALE, ENCLOSURE SHALL BE
i
MOUNTED CURBSIDE.
BUILDING LOAD
CALCULATION
North Talbot BPS Load
Generator Building Heating Load
Miscellaneous Load
I
852 A x 1.00
18 A x 1.25 =
6 A x 1.25 m
I
= 852 amps
22.5 amps
7.5 amps
TOTAL
882.0 amps
CONDUCTOR/CONDUIT SCHEDULE
100
(4) 3" CONDUITS. EACH CONDUIT SHALL CONTAIN (3)-#250 MCM AND
NEUTRAL. INSTALL CONDUIT AND CONDUCTORS PER NEC.
(1)-#250 MCM
101
(1) 1 1/4" CONDUIT. CONDUIT SHALL CONTAIN (13)-#14 CONDUCTORS..
102
(3) 3" CONDUITS. EACH CONDUIT SHALL CONTAIN (3)-#350 MCM AND
INSTALL CONDUIT AND CONDUCTORS PER NEC.
(1)-2/0 GROUND.
103
(1) 1/2" CONDUIT. CONDUIT SHALL CONTAIN (3)-#12 AND (1)-#12 GROUND.
104
EXISTING CONDUIT. INSTALL (3)-#350 MCM AND (1)-#2/0 GROUND.
105
(3) 3" CONDUITS. EACH CONDUIT SHALL CONTAIN (3)-#300 MCM AND
INSTALL CONDUIT AND CONDUCTORS PER NEC.
(1)-2/0 GROUND.
' i06
(4) 3" CONDUITS. EACH CONDUIT SHALL CONTAIN (3)-#250 MCM AND
INSTALL CONDUIT AND CONDUCTORS PER NEC.
(1)-2/0 GROUND.
REVISED TO CONFORM TO CONSTRUCTION RECORDS
REVISED PER ELECTRICAL INSPECTOR COMMENTS
REVISED PER ENGINEER
NO, REVISION
EXPIRES 3 19 2008
SIGNED. 07128106
EXPIRES 5/14/2008
SIGNED. 07128106
vil
;� LERING, I N r
http: //www.rh2.com
mailbox®rh2.com
1.800.720.8052
BELLINGHAM OFFICE
360.676.0836
54 West Horton Road
TELL OFFICE
425.951.5400
12100 NE 195th St t S it 100
ree , e
'JATCHEE OFFIC
50'
300 Simon Street, Suite 5
PORT ORCHARD OFFICE
360.876.7960
600 Kitsop Street, Suite 101
SHOWN
0 1" 2"
DRAWING IS NOT TO SCALE
!F BAR IS NOT 2" LONG