HomeMy WebLinkAboutWTR2703239.29CEI
H --o 0---
120 P
N— — — — — — — — —
HAND —AUTO SWITCH 1
2
3
4
CR2 CR4
HAND / AUTO
15A
BUILDING INTAKE
LOUVER
-----------------
15A
—
—� l r BUILDING EXHAUST
-- — -0 — ` T --�— M FAN
- - - - - - - - - - - - - - - ---
15A
_
GENERATOR
INTAKE LOUVER
----------------J
15A
GENERATOR
EXHAUST LOUVER
120 VAC
VENTILATION CALL
3
CR1
CR1
CR2
CR1 �,. �
PORTABLE EG AUXILIARY CONTACT
CR3
STATIONARY EG AUXILIARY CONTACT
CR3
CR4
NOTES:
1. THE MT. OLIVET GENERATOR BUILDING HAS
TWO OVERHEAD DOORS THAT SHALL OPEN
WHEN EITHER GENERATOR IS CALLED TO I
START FROM A SIGNAL FROM THE
GENERATORS.
2. LOUVERS ARE POWERED CLOSED.
_ V OVERHEAD
CR5-1 DOOR #1
i
INTAKE/EXHAUST —
MOTOR START
YJ OVERHEAD
VENTILATION CALL CR5-2 DOOR #2
FROM TELEMETRY L—
VENTILATION START
v
BUILDING EXHAUST
FAN REQUIRED
GENERATOR
RUNNING
GENERATOR
LOUVER CALL
OVERHEAD DOOR OPEN CALL
TR1 TIME DELAY RELAY, SET AT
5 SECONDS. /
9 W GENERATOR VENTILATION
SYSTEM REQUIRED
OVERHEAD DOOR NO.1 OVERHEAD DOOR NO. 2
TR1 FULLY OPEN FULLY OPEN
10 CR5 PROGRAMMABLE ONE SHOT RELAY (TRIGGER = POWER ON) WHEN
TR1 IS ENERGIZED AND THE OVERHEAD DOORS ARE CLOSED, RELAY
CR4 SHALL BE MOMENTARILY ENERGIZED FOR A USER ADJUSTABLE
TIME INITIALLY SET TO 0.5 SECONDS TO OPEN THE OVERHEAD DOOR.
i
MT. OLIVET VENTILATION & AUTOMATIC DOOR CONTROL LOGIC
TYPICA
5
6
7
8
CR4
NO SCALE
24 V
POWER SOURCE FROM OVERHEAD DOOR ACTUATOR
WALL MOUNTED OPEN/CLOSE PUSHBUTTON
CR5-1
RTU DOOR CLO`.
0
OVERHEAD DOOR
MOTOR ACTUATOR j
I E:
LABEL CR5 CONTACT AS FOLLOWS:
CR5-1 FOR OVERHEAD DOOR #1
CR5-2 FOR OVERHEAD DOOR #2
CALL FROM TELEMETRY
TO CLOSE DOOR
L MT. OLIVET OVERHEAD DOOR MOTOR ACTUATOR CONTROL LOGIC
L
NO SCALE
ON
120V
HAND SWITCH OFF — — —
AUTO PHOTO CELL CONTROL
LIGHTING CIRCUIT LOGIC DETAIL
NO SCALE
A2
N
SEE PLANS FOR NUMBER OF
OUTDOOR LIGHTS.
a
CB
H--1. --
120 P
N— — — — — — — — —
N— — — — — — — — —
120 P CB
H ---0 0---
HAND —AUTO SWITCH 14
2
3
4
CR2 CR3
HAND / AUTO
15A
BUILDING INTAKE
LOUVER
- - - - - - - - - - - - - - - - 'J
15A
__(::BUILDING EXHAUST
FAN
15_ A
GENERATOR
INTAKE LOUVER
----------------J
120 VAC
24 VAC
VENTILATION CALL
3, 5
CR1
INTAKE/EXHAUST
MOTOR START
VENTILATION CALL
FROM TELEMETRY
CR1 I
CR2 --� MOTOR START
CR1 '
W BUILDING EXHAUST
FAN REQUIRED
j PORTABLE EG AUXILIARY CONTACT
5 ---— CIR3 INTAKE LOUVER CALL
CR3
GENERATOR
VENTILATION A
SYSTEM REQUIRED
. TALBOT VENTILATION CONTROL LOGIC *.
NO SCALE
NO 1:
THE NORTH TALBOT GENERATOR BUILDING
HAS ONE OVERHEAD DOOR AND ONE ENGINE
GENERATOR INTAKE LOUVER, THE OVERHEAD
DOOR AT THE NORTH TALBOT GENERATOR
BUILDING WILL NOT BE WIRED TO OPEN WHEN
THE GENERATOR IS CALLED TO START.
SIZE PANEL AS NECESSARY VENTILATION CONTROL
TO CONTAIN VENTILATION PANEL LABEL, I_AQEL PER
CONTROL LOGIC DEVICES. SPECIFICATIONS.
VENTILA11ON & AUTOMATIC OVERHEAD DOOR
I I CONTROL PANEL i
HAND —AUTO SWITCH
(TYPICAL).
HAND AUTO SWITCH
BUILDING EXHAUST FAN REQUIRED
0
GENERATOR VENTILATION SYSTEM REQUIRED
0
VENTILATION CONTROL PANEL
FRONT VIEW
NOT TO SCALE
NORTH TALBOT LABEL SHALL
READ VENTILATION CONTROL
PANEL.
W-323929
REVISED TO CONFORM
TO CONSTRUCTION RECORDS
' // 11 /01 /2007
RH2 ENGINEERING INC. DATE
1
REVISED TO CONFORM TO CONSTRUCTION RECORDS
REVISED PER SUBMITTAL NO. 18 REVIEW COMMENTS
NO. REVISION
EXPIRES 3719 2008
SIGNED: 07128106
EXPIRES 5/14/2008
SIGNED. 071281106
Q
�,' �
R
1
1A;t
7.rv0
0 0
z
0
V
a
� V
0
C)c 0
z
W
W �I
i
i
SING, it4
I mailbox®rr.
1.800.720.8052
BELLINGHAM OFFICE
360.676.0836
^54 West Horton Rood
12100 NE 195th Street, Suite 100
WE NATCHEE OFFIC
-�86.2900
300 Simon Street, Suite 5
PORT ORCHARD OFFIC
360.876.7960
600 Kitsap Street, Suite 101
SCALE: SHOWN
0 i" 21'
DRAWING IS NOT TO SCALE
IF BAR IS NOT 2" LONG
PLOT: 1 DWG NO
ENGINEER: DJB E06
REVEWED: MM
DATE: NOV 2, 2007E=, `'
CMR MLM 11 /01 /07 : REN 29
CMR MLM 11 /21 /06 jOB NO.: 105-079 7
33
BY REVIEW DATE FILENAME: GEN—D—E06
Au W , '�231201