HomeMy WebLinkAboutWTR2703239.30I NOTE:
CONTRACTOR SHALL PROVIDE A TOTAL OF 2 SIGNAL CABINETS.
CABINETS SHALL BE LOCATED AT THE FOLLOWING LOCATIONS-
- PROPOSED MT. OLIVET GENERATOR BUILDING.
- PROPOSED NORTH TALBOT GENERATOR BUILDING.
SEE SPECIFICATIONS FOR MORE INFORMATION.
CONTRACTOR SHALL INSTALL
TERMINAL BLOCKS IN PROPOSED
SIGNAL CABINET FOR CONNECTION
OF FIELD DEVICES TO THE
EXISTING TELEMETRY PANEL.
TB1
CONDUIT TO FIELD DEVICES
(TYPICAL).
CONDUIT TO EXISTING
TELEMETRY PANEL.
NEMA 12 TYPE ENCLOSURE WITH
BA.CKPAN, MOUNT ENCLOSURE
6'-0" FROM FINISHED FLOOR.
SIZE PANEL AS NECESSARY TO
CONTAIN ALL CONTROL SIGNALS.
TYPICAL SIGNAL CABINET
INTERIOR VIEW
NOT TO SCALE
------------
MT. OLIVET GENERATORBUILDING
SIGNAL CABINET
KEY LOCK HANDLE.
PIN, 7 WIRE PANEL MOUNTED RECEPTACLE
FOR SIGNALIZATION TO PORTABLE GENERATOR. SEE
- SPECIFICATIONS AND SIGNAL CABINET TERMINAL
BLOCK SET SCREW ASSIGNMENT TABLES THIS
SHEET FOR RECEPTACLE SOCKET ASSIGNMENTS.
TYPICAL SIGNAL CABINET
EXTERIOR VIEW
NOT TO SCALE
SCREW ASSIGNMENTS REVISED
PER RFI-042RO03
RECEPTACLE REVISED
l� FROM 10 PIN TO 7
PIN PER RFI-042.
MT. OLIVET SIGNAL CABINET TERMINAL BLOCK SET SCREW ASSIGNMENTS
SIGNAL ORIGIN
SIGNAL DESCRIPTION
SIGNAL CABINET
I
SIGNAL DESTINATION
! RECEPTACLE SOCKET
TB TERMINATION POINT
WELLS 1, 2 & 3 ATS
' ATS START
TB
§1
- SET SCREWS
1 & 2
STATIONARY
EG SET
WELLS 1, 2 & 3 ATS
ATS FAIL
TB
#1
- SET SCREWS
3 & 4
MT.
OLIVET BPS
TELEMETRY PANEL
MT. OLIVET ATS
ATS START
#3 &
TB
#1
- SET SCREWS
5 & 6
SIGNAL CABINET RECEPTACLE PLUG SOCKET
MT. OLIVET ATS
ATS FAIL
TB
#1
- SET SCREWS
7 & 8
MT.
OLIVET BPS
TELEMETRY PANEL
STATIONARY EG
EG RUN
TB
1
- SET SCREWS
9 & 10
MT.
OLIVET BPS
TELEMETRY PANEL
STATIONARY EG
EG FAIL
TB
#1
- SET SCREWS
11 & 12
MT.
OLIVET BPS
TELEMETRY PANEL
STATIONARY EG
EG TROUBLE
TB
#1
- SET SCREWS
13 & 14
MT.
OLIVET BPS
TELEMETRY PANEL
STATIONARY EG
EG LOW FUEL
TB
#1
- SET SCREWS
15 & 16
MT.
OLIVET BPS
TELEMETRY PANEL
STATIONARY EG
EG FUEL LEAK
TB
#1
- SET SCREWS
17 & 18
MT.
OLIVET BPS
TELEMETRY PANEL
STATIONARY EG
VENTILATION CALL
I
TB
#1
-SET SCREWS 19 & 20
VENTILATION
CON TROL PANEL 1
PORTABLE EG
EG RUN
#4
TB
#1
- SET SCREWS
21 & 22
MT.
OLIVET BPS
TELEMETRY PANEL
PORTABLE EG
EG FAIL
#2
TB
#1
- SET SCREWS
23 & 24
MT.
OLIVET BPS
TELEMETRY PANEL
PORTABLE EG
EG TROUBLE
#2
TB
J1
- SET SCREWS
25 & 26
MT.
OLIVET BPS
TELEMETRY PANEL
PORTABLE EG
EG LOW FUEL
2
TB
11
- SET SCREWS
27 & 28
MT,
OLIVET BPS
TELEMETRY PANEL
PORTABLE EG
EG FUEL LEAK
#2
TB
#1
- SET SCREWS
29 & 30
MT.
OLIVET BPS
TELEMETRY PANEL
PORTABLE EG
VENTILATION CALL
#5 & #7
TB
#2
- SET SCREWS
1 & 2
VENTILATION CONTROL PANEL
SMOKE DETECTOR
SMOKE ALARM
TB
#2
- SET SCREWS
3 & 4
MT.
OLIVET BPS
TELEMETRY PANEL
MT. OLIVET BPS TELEMETRY PANEL
12 VDC POWER
TB
#2
- SET SCREWS
5 & 6
SMOKE DETECTOR
OVERHEAD DOOR #1 INTRUSION SWITCH
INTRUSION
TB
#2
- SET SCREWS
7 & 8
MT.
OLIVET BPS
TELEMETRY PANEL
OVERHEAD DOOR #1 LIMIT SWITCH
DOOR FULLY OPEN INDICATION
TB
#2
- SET SCREWS 9 & 10
MT.
OLIVET BPS
TELEMETRY PANEL
OVERHEAD DOOR #2 INTRUSION SWITCH
INTRUSION
TB
#2
- SET SCREWS
11 & 12
MT.
OLIVET BPS
TELEMETRY PANEL
OVERHEAD DOOR #2 LIMIT SWITCH
DOOR FULLY OPEN INDICATION
TB
#2
- SET SCREWS
13 & 14
MT.
OLIVET BPS
TELEMETRY PANEL
MAN DOOR INTRUSION SWITCH
INTRUSION
TB
#2
- SET SCREWS
15 & 16
MT.
OLIVET BPS
TELEMETRY PANEL
PANIC BUTTON
PANIC ALARM
TB
2
- SET SCREWS
17 & 18
MT.
OLIVET BPS
TELEMETRY PANEL
MT. OLIVET BPS TELEMETRY PANEL
VENTILATION CALL
TB
#2
- SET SCREWS
19 & 20
MT.
OLIVET VENTILATION PANEL
INTRUSION DISABLE KEYED SWITCH BOX
INTRUSION DISABLE
TB
#2
- SET SCREWS
21 & 22
MT,
OLIVET BPS
TELEMETRY PANEL
BUILDING TEMPERATURE THERMISTOR
BUILDING TEMP 4-20 MA
TB
2
- SET SCREWS
23 & 24
MT.
OLIVET BPS
TELEMETRY PANEL
SPARE
TB
#2
- SET SCREWS 25 & 26
SPARE
ITB
#2
- SET SCREWS
27 & 281
SPARE
JTB
#2
- SET SCREWS 29 & 30
NORTH TALBOT SIGNAL CABINET TERMINAL BLOCK SET SCREW ASSIGNMENTS
ORIGIN
SIGNAL DESCRIPTION
SIGNAL CABINET
DESTINATION
RECEPTACLE SOCKET #
TB TERMINATION POINT
NORTH TALBOT ATS
ATS START
#3 & #6
TB
#1 -
SET SCREWS 1 & 2
SIGNAL CABINET RECEPTACLE PLUG SOCKET
NORTH TALBOT ATS
ATS FAIL
TB
#1 -
SET SCREWS 3 & 4
NORTH
TALBOT BPS ELEME7Y PANEL
PORTABLE EG
EG RUN
#4
TB
#1 -
SET SCREWS 5 & 6
NORTH
TALBOT BPS TELEMETRY PANEL
PORTABLE EG
EG FAIL
#2
TB
#1 -
SET SCREWS 7 & 8
NORTH
TALBOT BPS TELEMETRY PANEL
PORTABLE EG
EG TROUBLE
#2
TB
#1
- SET SCREWS 9 & 10
NORTH
TALBOT BPS TELEMETRY PANEL
PORTABLE EG
EG LOW FUEL
12
TB
#1 -
SET SCREWS 11 & 12
NORTH
TALBOT BPS TELEMETRY PANEL
PORTABLE EG
EG FUEL LEAK
#2
TB
#1 -
SET SCREWS 13 & 14
NORTH
TALBOT BPS TELEMETRY PANEL
PORTABLE EG
VENTILATION CALL
15 & #7
TB
#1 -
SET SCREWS 15 & 16
NORTH
TALBOT BPS TELEMETRY PANEL
SMOKE DETECTOR
SMOKE ALARM
TB
#1
- SET SCREWS 17 & 18
NORTH
TALBOT BPS TELEMETRY PANEL
NORTH TALBOT BPS TELEMETRY PANEL
12 VDC POWER
TB
#2
- SET SCREWS 1 & 2
SMOKE
DETECTOR FOR POWER TO DETECTOR
DOOR INTRUSION SWITCHES
INTRUSION
TB
#2
- SET SCREWS 3 & 4
NORTH
TALBOT BPS TELEMETRY PANEL
PANIC BUTTON
PANIC ALARM
TB
#2
- SET SCREWS 5 & 6
NORTH
TALBOI BPS TELEMETRY PANEL
NORTH TALBOT BPS TELEMETRY PANEL
VENTILATION CALL
TB
#2
- SET SCREWS 7 & 8
VENTILATION CONTROL PANEL
INTRUSION DISABLE KEYED SWITCH BOX
INTRUSION DISABLE
TB
#2
- SET SCREWS 9 & 10
NORTH
TALBOT BPS TELEMETRY PANEL
BUILDING TEMPERATURE THERMISTOR
BUILDING TEMP 4-20 mA
TB
#2
- SET SCREWS 11 & 12
NORTH
TALBOT BPS TELEMETRY PANEL
SPARE
TB
#2
- SET SCREWS 13 & 14
SPARE
TB
#2
- SET SCREWS 15 & 16
SPARE
ITB
#2
- SET SCREWS 17 & 18
SCREW ASSIGNMENTS REVISED
PER RFI-042RO03 A
MT. OLIVET GENERATOR BUILDING PANEL SCHEDULE
LOCATION: LIGHTING PANEL
SERVING: GENERATOR BUILDING
AB
I !
1 I 2
3 4
5 6
7 8
9 10
1 i `�12
13 14
15 16
17 18
120/240
60 AMP
VOLTS 3 WIRE
MAIN
CIRCUIT DESCRIPTION
KVA
AMP�60A
AMP
KVA
CIRCUIT DESCRIPTION
GFI RECP CKT. #1, 120V
0.5
20
20
0.$
INTERIOR LIGHTING, 120V
GFI RECP CKT. #2, 120V
0.5
20
20
1 0.3
EXTERIOR LIGHT, 120V
VENTILATION PANEL, (MOTOR PWR)
0.5
20
20
0.5
WALL MOUNTED BATTERY CHARGER, 120V
VENTILATION PANEL, (CTRL LOGIC)
0.2
20
20
0.5
BATTERY CHARGER RECEPTACLE, 120V
OVERHEAD DOORS CKT 11, 120V
1.75
20
20
1.75
OVERHEAD DOORS, CKT #2, 120V
I REMOTE FILL STATION 120V
0.2
20
20
1 -
SPARE
SPARE
-
1 20
20
-
SPARE
SPARE
-
20
-
-
SPACE
I SPACE
, -
I -
-
-
SPACE
CONNECTION LOAD: DEMAND: LIGHTING & MISC. LOAD DEMAND LOAD:
7.5 KVA 31.25 AMPS 7.5 KVA 31.25 AMPS
i NORTH TALBOT GENERATOR BUILDING PANEL SCHEDULE
LOCA T ION: SWITCHBOARD
SERVING: GENERATOR BUILDING
SECTION
3
AB
60A
1 2
3 -r' 4
5 6
7 6
9 -10
11 12
13 j 4
15 16
17 1 S
120/240
100
VOLTS 3 WIRE
AMP MAIN
CIRCUIT DESCRIPTION
KVA
AMP
AMP
KVA
CIRCUIT DESCRIPTION
IINTERIOR LIGHTING, 120V
0.6
20
20
0.3
EXTERIOR LIGHT, 120V
GFI RECP CKT. #1, 120V
0.5
20
20
0.5
GFI RECP CKT. #2, 120V
I VENTILATION PANEL, (MOTOR PWR)
0.4
20
20
0.2
EG LIGHTING RECEPTACLE
I VENTILATION PANEL, (CTRL LOGIC)
0.2
20
30
2.5
DEDICATED EG BLOCK HEATER CKT
1OVERHEAD DOOR
' 0.8
20
20
0.5
DEDICATED BATTERY CHARGER CKT
ARE
-
20
20
-
SPARE
SPARE
20
20
-
SPARE
;SPACE
-
-
-
I -
SPACE j
!SPACE
-
-
-
-
SPACE
CONNECTION LOAD: DEMAND: LIGHTING LOAD DEMAND LOAD:
L7 3 KVA 30.4 AMPS 7.3 KVA 30.4 AMPS
FACILITY LIGHTING FIXTURE SCHEDULE
MANUFACTURER
* LAMP
TYPE
DESCRIPTION
NAME CATALOG NO.
QTY. CATALOG NO,
REMARKS
Al
FLUORESCENT LIGHT FIXTURE, 120 VAC, 4' LONG, HIGH -IMPACT
ACRYLIC LENS, MOLDED FIBERGLASS REINFORCED POLYESTER HOUSING,
(2)-32W LAMPS, ENERGY SAVING BALLAST, CEILING MOUNTED, U.L.
( LITHONIA
VRI 2 32 ARDP 120 CW
2
32WT8
32 WATT
I
LISTED FOR DAMP LOCATIONS.
FLUORESCENT OUTDOOR AREA LIGHT - 42W, 12OV BALLAST,
A2
DIE-CAST ALUMINUM HOUSING, POLYCARBONATE LENS, U.L. LISTED
FOR WET LOCATIONS. MOUNT TOP OF FIXTURE 8'-6" FROM FINISHED
LiTHONIA
= TWH 2/42 120 PE LPI
1
I 42 WATT
PHOTOCELL CONTROL
GRADE.
i
w 41P
313430
REVISED TO CONFORM
TO CONSTRUCTION RECORDS
� � s
11 /01 /2007
RH2 ENGINEERING INC. DATE
REVISED TO CONFORM TO CONSTRUCTION RECORDS CMR MLM
N0. REVISION BY REVIEW
11/01/07
DATE
SIGNED: 07128106
EXPIRES 5 14/2008
SIGNED.- 07,/28/06
Y
i
� AT
J
Q
14.0 U_
U
O W
J
W
cn
O
ZZ Ill
,J W
W J
U m
C)c 2
W
Z z
m
� Q
J
Q
Z
0
U)
lvw
kill 0 wu
RH2 ENGIK:i:, _'RING. INC.
http: //www.rh2.com
mailbox0rh2.com
1, 800.720.8052
BELLINGHAM OFFICE
360.676.0836
454 West Horton Road
425.95 .5400
12100 NE 195th Street, Suite 100
FAST WENATCHEE OFFIC
509.886.2900
300 Simon Street, Suite 5
PORT ORCHARD OFFICE
360.876.7960
600 Kitsap Street, Suite 101
C ■ OT
I 65*�vw*R*R
DRAWING -7 O SCALE
IF BAR IS NOT 2" i ONG
PLOT:
I
ENGINEER: DJB E 10
REVIEWS : MM
DATE: NOV 2, 2007
cuE . REN 30
jai NO.: 105-079
T!LENAME: GEN-D-E10
b
CD
CD
W
0
0
W
N
0
W
N
W