NOTE:
1. TRANSFORMER DOORS NOT
SHOWN THIS DETAIL FOR CLARII
2. TRANSFORMER AT MT. OLIVE;
SITE MAY DIFFER FROM TYPE 01
TRANSFORMER SHOWN IN THIS
DETAIL.
EXISTING PRIMARY CONDUCTORS.
EXISTING PRIMARY CONDUIT.
PROPOSED SECONDARY
CONDUCTORS. SEE DWG NO.
E02 FOR CONDUCTOR SIZING.
PROPOSED SECONDARY
CONDUITS.
EXISTING CONDUIT TO SWITCHGEAR. SEE
AND CONDUCTORS DWG NO, CO3 FOR
TO PSE. CONTINUATION.
TRANSFORMER CONNECTION DETAIL
NOT TO SCALE
2'-6"
EXISTING CONDUIT FROM THE
EXISTING MT. OLIVET BOOSTER
PUMP STATION TRANSFORMER
(TYPICAL). CONTRACTOR SHALL
INTERCEPT EXISTING CONDUITS IN
ORDER TO REUSE EXISTING
SERVICE ENTRANCE CONDUITS AND
CONDUCTORS TO SUPPLY POWER
TO THE EXISTING MT. OLIVET
BOOSTER PUMP STATION.
2'-6"
PROPOSED UTILITY VAULT
MODEL NO. 3030-1-A OR EQUAL.
PROPOSED CONDUIT AND
CONDUCTORS TO THE MT, OLIVET
GENERATOR BUILDING (TYPICAL).
n
EXISTING CONDUIT TO BE
REMOVED.
EXISTING CONDUIT AND
CONDUCTORS TO THE
EXISTING MT. OLIVET
BOOSTER PUMP STATION.
PROPOSED CONDUCTORS. SEE
DWG NO. E02 FOR CONDUCTOR
SIZING.
CONDUIT INTERCEPTION DETAIL
NOT TO SCALE
8"W x 6"H x 1 /4" D SS.
PLATE. ATTACH PLATE TO C
CHANNEL USING 1 /4" SS STEEL
HARDWARE. SECURE IN A
MINIMUM OF TWO LOCATIONS.
CONDUIT TO RECEPTACLI
(TYPICAL;
BEARING PLATE. SECURE TO
FLOOR USING (4) 1/4" SS
CONCRETE ANCHORS,
RECEPTACLE FOR PORTABLE
GENERATOR POWER (TYPICAL).
MOUNT TOP OF RECEPTACLE
3'-0" ABOVE FINISHED FLOOR.
SECURE TO SS PLATE USING
1/4" SS HARDWARE. SECURE IN
A MINIMUM OF TWO LOCATIONS.
2" GALVANIZED CHANNEL.
PORTABLE GENERATOR
RECEPTACLE MOUNTING DETAIL
REMOTE FILL STATION DETAIL
NOT TO SCALE
3" BRASS BALL VALVE.
ITE FUEL FILL STATION.
SPECIFICATIONS FOR
INFORMATION.
ABOVE GRADE CARRIER PIPE
ELIMINATED AND REPLACED WITH
A 14 GA. GALVANIZED STEEL
SHROUD TO ENCLOSE
CONTAINMENT PIPE PER
RFI-066.
SCHEDULE 80
R PIPE FOR I
)ARY CONTAINMENT
3" FUEL LINE.
ORS ADDEC
REMOTE FILL
RMS PER
W 323932
TO EG FUEL TANK.
3" DIAMETER FUEL LINE, ENVIRON
GEOFLEX D DOUBLE WALL PIPING
OR EQUAL. PROVIDE WITH
6" PVC SCH. 80 CARRIER PIPE. / SHUTOFF VALVE AND ROUTE
PRo\AnF I INK ';FAI AT Al l �' THROUGH CARRIER PIPE.
CONCRETE PENETRATIONS.
ENGINE GENERATOR.
CONCRETE FLOOR.
1/2" OR LARGER FOAM CORE
PADDING FOR VIBRATION
PROTECTION. INSTALL BELOW
LINK SEAL.
FINISH WITH CMU CUT AT 45'.
MORTAR TO TOP OF WALL.
FULLY GROUTED
CMU BLOCK WALL
#5 VERT TYP
EACH END
UNDISTURBED NATIVE EARTH
REMOTE FILL STATIO
BLAN
A MII
INTERIC
PROPOSED 60C
ENGINE GENERA
DUAL WALL SUB —BASE FUEL
TANK. SEE SPECIFICATIONS
. •a ' .
FOR DETAILS.
+• :. ' 3" DIA, GEOFLEX D DOUBLE
' WALL FUEL PIPING OR EQUAL.
INSTALL FROM REMOTE FUEL
TANK TO STATIONARY ENGINE
#4 @ 12" O.C., EW,
TOP AND BOTTOM
3" TYP NATIVE OR STRUCTURAL FILL
�- COMPACTED TO 97% STANDARD
MIN 4" DEPTH OF CRUSHED
SURFACING COMPACTED TO 97%
STANDARD PROCTOR.
N SECTION
PROPOSED ALUMINIZED STEEL RAIN CAP
WITH STAINLESS STEEL MOUNTING
.A
:NT
'IPE
D TO
FROM
TINTS.
JLESS
ST BE
EARY
EXPIRES 3 19/2008
SIGNED: 07128106
EXPIRES 5 14 2008
SIGNED: 071281106
0
N r
Z O Uj
W
CA
fmn4w
ZW J
� W
(0PLO U
V
~z �
Va w
W J
� W
W
-�H2 ENGINv EKING. INC.
http://www.rh2.com
mailbox0rh2.com
1.800.720.8052
BELLINGHAM OFFICE
360.676.0836
454 West Horton Road
BOTHELL OFFICE
425.951.5400
12100 NE 195th Street, Suite 100
EAST WENATCHEE OFFIC
509.886.2900
300 Simon Street, Suite 5
PORT ORCHARD OFFICE
360.876.7960
600 Kitsap Street, Suite 101
REVISED TO CONFORM
FOR FUEL LINES. PROVIDE LINK SEAL TO CONSTRUCTION RECORDS ENGINEER: DAB E09
AT GENERATOR BUILDING FLOOR
PENETRATION. SEE DETAIL THIS SHEET.��� RENEWED: MM
��� �� 11 /01 /2007 DATE: NOV 2, 2007 1EEr Na.
STATIONARY ENGINE GENERATOR OBLIQUE 32
NOT TO SCALE RH2 ENGINEERING INC. DATE "CLIENT: REN
REVISED TO CONFORM TO CONSTRUCTION RECORDS
:MR
MLM
11/01/07
joB No.: 105-079
1 33
NO.
REVISION
BY
REVIEW
DATE
E'' ENAME: GEN—D—EO9
NOT TO SCALE
1" - 1'-0"