1. ALL WORK MATERIALS SHALL BE IN CONFORMANCE WITH THE STANDARDS AND SPECIFICATION OF THE CITY OF RENTON UTILITY
DEPARTMENT AND THE LATEST EDITION OF THE WSDOT/APWA STANDARDS AND SPECIFICATIONS.
2. ALL CONSTRUCTION SHALL BE IN ACCORDANCE WITH "STANDARD SPECIFICATIONS FOR MUNICIPAL PUBLIC WORKS CONSTRUCTION"
PREPARED BY WASHINGTON STATE CHAPTER AMERICAN PUBLIC WORKS ASSOCIATION, LATEST EDITION (APWA) AND CITY OF RENTON
STANDARD SPECIFICATIONS.
3. ALL LOCATIONS OF EXISTING UTILITIES SHOWN ARE APPROXIMATE AND IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY TO
VERIFY THE TRUE AND CORRECT LOCAT70N SO AS TO AVOID DAMAGE OR DISTURBANCE.
4. CONTRACTOR IS SOLELY RESPONSIBLE FOR THE MEANS, METHODS AND SEQUENCES OF CONSTRUCTION AND FOR THE SAFETY OF
WORKERS AND OTHERS ON THE CONSTRUC7ON SITE.
5. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO OBTAIN STREET USE AND ANY OTHER RELATED PERMITS PRIOR TO
ANY CONSTRUCTION.
6. PLANS APPROVED BY THE CITY OF RENTON, PUBLIC WORKS DEPARTMENT SHALL TAKE PRECEDENCE OVER ALL OTHER PLANS.
7. A COPY OF THESE APPROVED PLANS MUST BE ON THE JOB SITE WHENEVER CONSTRUCTION IS IN PROGRESS.
8. THE CONTRACTOR SHALL PROVIDE THE CITY OF RENTON WITH AN AS -BUILT DRAWING OF THE SANITARY SEWER SYSTEM, WHICH
HAS BEEN STAMPED AND SIGNED BY A LICENSED PROFESSIONAL ENGINEER OR LICENSED PROFESSIONAL SURVEYOR.
9. BACKFILL SHALL BE PLACED EQUALLY ON BOTH SIDES OF THE PIPE IN LAYERS WITH A LOOSE AVERAGE DEPTH OF 6 INCHES,
MAXIMUM DEPTH OF 8 INCHES, THOROUGHLY TAMPING EACH LAYER TO 95 PERCENT OF MAXIMUM DENSITY. THESE COMPACTED
LAYERS MUST EXTEND FOR ONE PIPE DIAMETER ON EACH SIDE OF THE PIPE OR TO THE SIDE OF THE TRENCH. MATERIALS TO
COMPLETE THE FILL OVER PIPE SHALL BE THE SAME AS DESCRIBED.
10. OPEN CUT ROAD CROSSINGS FOR UTILITY TRENCHES ON EXISTING TRAVELED ROADWAY SHALL BE BACKFILLED WITH CRUSHED
ROCK AND MECHANICALLY COMPACTED. CUTS INTO THE EXISTING ASPHALT SHALL BE NEATLINE CUT WITH SAW IN A CONTINUOUS
LINE. A TEMPORARY MIX PATCH MUST BE PLACED IMMEDIATELY AFTER BACKFILL AND COMPACTION. A PERMANENT HOT MIX
PATCH SHALL BE PLACED WITHIN 10 DAYS AND SHALL BE PER CITY OF RENTON CURRENT STANDARDS.
11. DATUM SHALL BE CITY OF RENTON, 1988 NAVD.
12. ALL DISTURBED AREAS SHALL BE SEEDED AND MULCHED OR OTHERWISE STABILIZED TO THE SATISFACTION OF THE
DEPARTMENT FOR THE PREVENTION OF ON -SITE EROSION AFTER THE COMPLETION OF CONSTRUCTION.
13. ALL PIPE AND APPURTENANCES SHALL BE LAID ON A PROPERLY PREPARED FOUNDATION IN ACCORDANCE WITH SECTION 7 OF
THE CURRENT STATE OF WASHINGTON STANDARD SPECIFICATIONS FOR ROAD AND BRIDGE CONSTRUCTION. THIS SHALL INCLUDE
NECESSARY LEVELING OF THE TRENCH BOTTOM OR THE TOP OF THE FOUNDATION MATERIAL, AS WELL AS PLACEMENT AND
COMPACTION OF REQUIRED BEDDING MATERIAL, TO UNIFORM GRADE SO THAT THE ENTIRE LENGTH OF THE PIPE WILL BE
SUPPORTED ON A UNIFORMLY DENSE, UNYIELDING BASE. PIPE BEDDING SHALL BE PEA GRAVEL 6 INCHES ABOVE AND BELOW THE
PIPE
14. SANITARY SEWER PIPE SHALL BE POLYVINYL CHLORIDE (PVC) RUBBER GASKETED ASTM D 3034, SDR 35, OR DUCTILE IRON
CLASS 50.
15. IN UNIMPROVED AREAS, MANHOLE TO EXTEND MINIMUM 6 INCHES AND MAXIMUM 12 INCHES ABOVE FINISHED GRADE. IN PAVED
AREA, COVER MUST SLOPE IN ALL DIRECTIONS TO MATCH PAVING.
3350 Monte Villa Parkway
Bothell, Washington 98021-6972
(425)951-4800
(425)951-4808
)acific.com
Planners Surveyors • Landscape Architects
Smlli3410.ai
NO.
7' MIN.
3-1/2"
fC:
°
12" (TYP)
�c
0
MORTAR
FILLET
°
6
1%
1131
a
T7-
6" MIN.
(TYP)
REVISION
NEW A.C. PAVEMENT
MANHOLE FRAME AND COVER
SEE CITY OF RENTON STD. BR29
ADJUSTMENT (4" MIN.)
CONE
�.
'
RUBBER GASKETED JOINTS
°
IN ACCORDANCE WITH ASTM C-443
STEPS - 3/4" DEFORMED BAR
STEPS SHALL BE INCLUDED
CONCRETE RISER BY PIPE INC.,
OR APPROVED EQUAL.
r�
MAX. PIPE SIZE - 'E'
LADDER -STD. ALUMINUM
OR GALVANIZED STEEL
�- CONCRETE SHELF
PRECAST BASE SECTION
•
OR CAST IN SHELF.
I1'MIN.I 11'MIN.I
NOTES:
1. STEPS TO BE 3/4" 0 DEFORMED BAR GALVANIZED SAFETY
STEPS OR EQUAL.
2. STEPS ARE TO BE IN PLACE BEFORE MANHOLE SECTIONS
ARE INSTALLED.
3. CASTING TO BE PER CITY OF RETON STD. BR29.
4. MANHOLE SECTIONS TO BE OF REINFORCED PRECAST
CONCRETE.
5. ALL JOINTS SHALL BE GROUTED.
6. SANITARY SEWER MANHOLES SHALL HAVE ALL INTERIOR
SURFACES, INCLUDING CHANNELING, COATED (SEALED)
WITH A HIGH SOLIDS URETHANE COATING;
WASSER MC-CONSEAL OR APPROVED EQUAL;
COLOR OF COATING SHALL BE WHITE.
7. RUBBER GASKETED JOINTS SHALL BE IN CONFORMANCE
WITH ASTM C-443.
8. CHANNEL HEIGHT SHALL BE A MINIMUM OF 3/4 THE INSIDE
DIAMETER OF THE LARGEST PIPE.
9. CONNECTIONS TO MANHOLE SHALL BE MADE USING GPK
ADAPTOR, KOR-N-SEAL BOOTS OR APPROVED EQUAL.
W.B,
,c,
'D,
tE,
48 MH
48 196
MIN.
5 MIN
24 MIN,
21 I.D.
54" MH
54"
8" MIN.
5.5" MIN.
24" MIN.
24" I.D.
60���
60"
8" MIN.
6" MIN.
42" MIN.
30" I.D.
SANITARY SEWER MANHOLE TYP. DETAIL('_�,
SCALE: N.T.S. (RENTON DETAIL B 071) C1.14
--6-1/2" MIN. CSBC
95% OF MAX. DRY DENSITY
PER ASTM D1557
3" A.C. CLASS B
95% OF MAXIMUM
4' MIN. "' j DRY DENSITY PER
• : • • r ••'. ASTM D1557
.. ,
92% OF MAXIMUM
DRY DENSITY PER
ASTM D1557 a
..
\� a •. .: .
6" MIN
L-
SEE PIPE BEDDING + \ PIPE Z
DETAIL O.D. N
W
5�� E�
54" MIN. CL M_ -�t I CL
FOUNDA T70N LEVEL
*W MAX. NOTE, SHORING SHALL COMPLY
WITH THE REQUIREMENTS OF
SECTION 7- 08.3(1)B "SHORING"
*W MAX = 1.5 X PIPE I.D. + 18" MIN. OF THE 2002 WSDOT/APWA
FOR PIPE I.D. > 18"I.D. STANDARD SPECIFICATIONS
FOR 27" PIPE I.D., W MAX = 4'-10"
TRENCH DETAIL 2
SCALE: N.T.S. C1.14
SURVEYED:
DESIGNED:
HCS
DRAWN:
HCS
CHECKED:
SIRS.
BY DATE APPR APPROVED:
JTME
SCALE:
NTS
ONE INCH
AT FULL SCALE
IF NOT ONE INCH
SCALE ACCORDINGLY
VERTICAL: NAVD 1988
HORIZONTAL: NAD 1983/1991
DATUM
FOUNDATION
LEVEL
DETECTABLE ALTERNATE
MARKING TAPE VER77CAL TRENCH
W
ALTERNATE
� LAID-BACK
1RENCH
FLEXIBLE PIPE ERIAL
NOTES:
1. PROVIDE UNIFORM SUPPORT UNDER BARREL. 5. REFER TO STANDARD SPECIFICATIONS FOR
2. HAND TAMP UNDER HAUNCHES. FOUNDATION, BEDDING AND BACKFILL
3 COMPACT BEDDING MATERIAL TO 957. MAXIMUM MATERIAL REQUIREMENTS.
DENSITY EXCEPT DIRECTLY OVER PIPE. HAND 6. COMPLY WITH ALL SAFETY ORDERS RELATING
TAMP ONLY. TO TRENCH CONSTRUCTION.
4. REFER TO STANDARD SPECIFICATIONS FOR
CALCULA77ON OF TRENCH WIDTH, WHICH SHALL
BE THE MAXIMUM TRENCH WIDTH.
PIPE BEDDING DETAIL
SCALE. N. T. S.
MLRCITY OF
RENTON
Planning/Building/Public Works Dept.
Nzi57
EXPIRES: 08/28/07
3
C1.14
Checked for Compliance to City Standards
THE LANDING 11 /03/06
FIELDWOK:
HARVEST PARTNERS PAGE:
SANITARY SEWER NOTES & DRAWING NO:
DETAILS L
LOT V SHEET: C4.2 F.