GENERAL JOINT UTILITY TRENCH PLAN NOTES
0
.19
-01
0
N
EXISTING UNDERGROUND UTILITIES TO BE CONVERTED TO NEW UNDERGROUND
ALIGNMENT TO THE LIMITS SHOWN. CONTRACTOR SHALL PROVIDE ALL NECESSARY
COORDINATION, LAYOUT, SURVEYING, TRENCHING, EXCAVATION, BEDDING, BACKFILL
A.ND RESTORATION FOR THE FRANCHISE UTILITIES TO SUCCESSFULLY COMPLETE
THE CONVERSION. THE LAYOUT SHOWN IS APPROXIMATE AND A COMPILATION OF
TIDE DESIGNS BY PSE, COMCAST, CENTURYLINK, AND CITY OF RENTON. SEE
FRANCHISE UTILITY PLANS (VOLUME 4 OF 4) FOR DESIGNS BY PSE POWER, PSE
GAS, COMCAST, AND CENTURYLINK.
THE JOINT TRENCH LAYOUT, SWEEPS, VAULTS AND OTHER FEATURES SHOWN ARE
APPROXIMATE ADJUST AS NECESSARY TO MEET FRANCHISE UTILITY
REQUIREMENTS AND TO PROVIDE A COMPLETE, FUNCTIONING SYSTEM. ALL
CONDUIT MATERIALS, BENDS, VAULTS, AND OTHER MATERIALS INSTALLED BY THE
CONTRACTOR SHALL BE PER THE REQUIREMENTS AND SPECIFICATIONS OF THE
FRANCHISE UTILITIES.
PSE WILL FURNISH ALL VAULTS AND CONDUITS REQUIRED FOR THEIR ELECTRICAL
CONVERSION. PSE WILL FURNISH ALL CASING CONDUIT REQUIRED FOR THEIR GAS
CONVERSION.
THE CONTRACTOR WILL FURNISH AND INSTALL ALL VAULTS AND CONDUITS FOR
THE CITY OF RENTON.
COMCAST AND CENTURYLINK WILL FURNISH ALL VAULTS AND CONDUITS REQUIRED
FOR THEIR CONVERSION.
UNDERGROUND SERVICE CONNECTIONS FOR CENTURYLINK AND COMCAST SHALL BE
MADE BY THE FRANCHISE UTILITIES.
UNDERGROUND SERVICE CONNECTIONS FOR POWER SHALL BE MADE BY THE
PROPERTY OWNER FROM THE RIGHT—OF—WAY TO EXISTING PRIVATE METERS.
IHOP
VAULT SCHEDULE
8. CONSTRUCT JOINT UTILITY TRENCH PER THE TYPICAL TRENCH DETAILS, SECTIONS
AND PROFILE SHEETS 174-192. ADJUST THE HORIZONTAL ALIGNMENT AND
VERTICAL PROFILE AS NECESSARY TO AVOID CONFLICTS WITH EXISTING AND
PROPOSED UTILITIES AND ROADWAY FEATURES, WHILE MAINTAINING 3' MINIMUM
COVER OVER CONDUITS AND VERTICAL 12" MINIMUM CLEAR BETWEEN OTHER
UNDERGROUND UTILITIES. THE CONTRACTOR SHALL VERTICALLY TRANSITION THE
TRENCH DEPTH BY DEFLECTING JOINTS OR INSTALLING BENDS PER THE FRANCHISE
UTILITY REQUIREMENTS. SEE THE APPROXIMATE JOINT UTILITY TRENCH PROFILE TO
AID IN THE LAYOUT OF THE TRENCH, SHEETS 180-192.
9. CONTRACTOR SHALL SEQUENCE WORK TO ALLOW CONTINUED OPERATION OF ALL
EXISTING UTILITIES UNTIL NEW SYSTEM IS COMPLETE. ONCE NEW SYSTEM IS
COMPLETED, TESTED, APPROVED BY UTILITY OWNERS AND FULLY OPERATIONAL,
CONTRACTOR SHALL REMOVE EXISTING CONDUIT DUCT BANK AND EXISTING UTILITY
STRUCTURES NO LONGER IN USE.
10 INCLUDE ILLUMINATION AND SIGNAL CONDUIT IN JOINT TRENCH WHERE POSSIBLE.
SEE ILLUMINATION AND SIGNAL PLANS FOR CITY OF RENTON POWER AND FIBER
DESIGN.
11. CONTRACTOR TO INSTALL CENTURYLINK OVERSET VAULTS.
12. CONTRACTOR SHALL PRESERVE AND PROTECT ALL FACILITIES TO REMAIN.
�'x G IA 011-14-11 SURVEYED: KPG
0& _
�
` `05 was�rL DRAWN BY: SOD
�o N DESIGN BY: SOD
CHECK BY: JLF
�� 20320 w�
c �FcrsTf PROJ MGR: JF
�SSj�NAL E�G1
REVISION DESCRIPTION BY APP. DATE FILE: 0655DJUT01.dwg
753 9th Avenue N 2502 Jefferson Avenue
Seattle, WA 98109 Tacoma, WA 98402
(206) 286-1640 (253) 627-0720
www,kpg,com
C8
CONSTRUCTION NOTES
4" DIAMETER CONDUIT CENTURYLINK (2 CONDUIT)
2" DIAMETER CONDUIT—COMCAST (1 CONDUIT)
4" DIAMETER CONDUIT—PSE POWER (I CONDUIT)
END INSTALLATION OF 4" DIAMETER CONDUIT—PSE GAS
— APPROXIMATE STA 27+40, LT
rn�
o JOINT UTILITY TRENCH LEGEND
0
6, FOR JOINT UTILITY TRENCH LEGEND, SEE SHT 164.
®®
®®
ID
VAULT
FRANCHISE
UTILITY ID
OWNED BY
PROVIDED BY
INSTALLED BY
CONDUIT
IN/FROM LEFT
CONDUIT
OUT/TO RIGHT
P7
1—PH MP TRANSFORMER
V08
PSE
PSE
CONTRACTOR
12p
2-4"
Q8
264 TA
#919
CENTURYLINK
CENTURYLINK
CONTRACTOR
12q,13q
14q,15q,16q,17q
C6
2436 MEDIUM DUTY VAULT
—
COMCAST
COMCAST
CONTRACTOR
7c,8c,9c,50c
10c,11c
P8
THREE PHASE J—BOX
J13
PSE
PSE
CONTRACTOR
9p,10p,3-4" _
13p,14p
Q9
264 TA
#920
CENTURYLINK
CENTURYLINK
[CONTRACTOR
—
19q,20q
C7
2436 MEDIUM DUTY VAULT
—
COMCAST
COMCAST
CONTRACTOR
1001c
12c,13c,14c
P9
THREE PHASE J—BOX
J14
PSE
PSE
CONTRACTOR
13p,14p
15p,16p,17p
C8
17"00"
—
COMCAST
COMCAST
CONTRACTOR
—
19c
P35
INTERCEPT POINT
IP06
PSE
—
CONTRACTOR
15p
—
C37
17" 00"
—
COMCAST
COMCAST
CONTRACTOR
12c
—
P36
INTERCEPT POINT
IP07
PSE
—
CONTRACTOR
—
20p
P46
INTERCEPT POINT
IP05
PSE
—
CONTRACTOR
—
1-4"
P47
INTERCEPT POINT
IP05
PSE
—
CONTRACTOR
—
1-4"
P51
INTERCEPT POINT
IP05A
PSE
—
CONTRACTOR
—
1-4"
P63
REMOVE VAULT
J13A
PSE
—
CONTRACTOR
—
—
P64
REMOVE VAULT
J15
PSE
—
CONTRACTOR
—
—
P65
REMOVE VAULT
J17A
PSE
—
CONTRACTOR
—
—
CITY OF RENTON
BID
Public Works Department
DOCUMENTS APPROVED FOR CONSTRUCTION
DATE-/Z
0 5 10 20 40 60
SCALE IN FEET
T=3430108
CALL 2 DAYS
BEFORE YOU DIG
1-800-424-5555
CATEGORY
SHEET
RIGHT OF WAY PLANS
11
EXISTING CONDITIONS — _ _
SITr-PREPARATION & TESC PLAN
ALIGNMENT PLAN
59
I 73
85
ALIGNMENT PROFILE
97
DRAINAGE PLANS
108
DRAINAGE PROFILE
116-119
WATER PLAN
136
WATER PROFILE
150
JOINT UTILITY TRENCH PLAN
—
JOINT UTILITY TRENCH PROFILES
184
PROPERTY RESTORATION PLANS
199
CHANNELIZATION & SIGNING PLAN
221
ILLUMINATION PLANS
232
IRRIGATION PLAN
286
LANDSCAPE PLAN
298
RAINIER AVENUE S (SR 167)
S GRADY WAY TO S 2ND ST
JOINT UTILITY TRENCH PLAN
STA 24+50 TO STA 29+00
DRAWING NO. 168
PROJECT NO. TED403430
FED AID NO.-CM0167(048)
DATE: NOV 2011
SHEET NO. 168 OF 304