HomeMy WebLinkAboutTED2703471.4C:)
CV
F_
W
LL1
w x
W
z _1
U
w
7 Q
0
Cif
a_
z
0
I-
Z
LLJ
rr
Water Utility Notes and Specifications
THESE NOTES SHALL APPEAR ON PROJECTS FOR THE WATER UTILITY.
1. All work material shall be in conformance with the standards and specifications of
the City of Renton Planning/Building/Public Works Department and the latest edition
of the WSDOT/APWA Standards and Specifications, as approved and modified by the
City of Renton in the Renton Standard Plans & Specifications. A set of approved
plans shall be kept on site at all times during construction.
2. The hours of work in the street right of way shall be limited to 8:30 AM to 3:30
PM on weekdays unless otherwise approved in writing by the Public Works
Department at (425) 430-7301. The Police Department, Fire Department, and 911
shall be notified 24 hours in advance of any work in the right of way.
3. All locations of existing utilities shown are approximate and it shall be the
contractor's responsibility to verify the true and correct location so as to avoid
damage or disturbance. For utility locates call 48-hour locators 800-424-5555.
4. An approved Traffic Control Plan is required to be submitted at the
Pre -Construction meeting.
5. All watermain pipe is to be cement lined ductile iron pipe conforming to AWWA
C110 and C111 or latest revision, thickness Class 52. Cement mortar lining and seal
coating shall conform to AWWA C104 or latest revision. Pipe joints to be push -on
or mechanical joint. Bedding to be Class C. All ductile iron pipe and fittings shall
be polyethylene wrapped per ANSI/AWWA C105/A21.5-93 Standards.
6. Cast iron and ductile iron fittings shall be cement lined, pressure rated as noted
on plans, and in accordance with ANSI/AWWA C110/A21.10-87. Cement lining shall
be in accordance with ANSI/AWWA C104/421 /4-90. If fittings are 3 to 12 inches in
diameter and have mechanical joints, the fittings shall in accordance with either
ANSI/AWWA C110-A21.10-87 or ANSI/AWWA C153/A21.53-94. Three (3) inch to 12
inch diameter fittings, which have mechanical joints and/or flanged joints, shall be in
accordance with ANSI/AWWA C110/A21.10.87 or a combination of ANSI/AWWA
C110/A21.10.87 and ANSI/AWWA C153/A21.53-94 such that the portion of the
fitting with a mechanical joint(s) may be with ANSI/AWWA C153/A21.53-94 and that
portion of the fitting with flanged joint(s) shall be in accordance with AWWA
C11O/A21.10-87. Acceptance testing in accordance with section 53.53 of
ANSI/AWWA section 10-4.3 of ANSI/AWWA C110/A21.10-87 shall be obtained by the
contractor and transmitted to the owner.
7. Gate valves shall be iron body, bronzed -mounted, double disc with bronze wedging
device and 0-ring stuffing box (AWWA C500) or of resilient seated type (AWWA
C509). Valves shall be designed for a minimum water operating pressure of 200
psi. Gate valves shall be Clow List 14, Mueller Company NO. A2380 or M & H.
8. Fire hydrants shall be Corey type (opening with the pressure) or compression type
(opening against pressure) conforming to AWWA C-502-85 with a 6 inch mechanical
joint inlet and a main valve opening (M.V.O.) of 5-1/4 inch, two 2-1/2 inch hose
nozzles with National Standard Threads 7-1/2 threads per inch and one 4 inch
pumper nozzle with the new Seattle Pattern 6 threads per inch, 60 degrees V.
Threads: outside diameter of male thread 4.875 and root diameter 4.6263.
Hydrants shall have a 1-1/4 inch pentagon operating nut opened by turning counter
clockwise (left).
9. The two 2-1/2 inch hose nozzles shall be fitted with cast iron threaded caps
with operating nut of the some design and proportions as the hydrant stem nut.
Caps shall be fitted with suitable neoprene gaskets for positive water tightness
under test pressures.
10. The 4 inch pumper nozzle shall be fitted with a Storz adapter, 4 inch Seattle
Thread x 5 inch Storz. Storz adapter shall be forged and/or extruded 6061-T6
aluminum alloy, hardcoat anodized. Threaded end portion shall have no lugs and
two set screws 180 degrees apart. Storz face to be metal, no gasket to weather.
Storz cap to have synthetic molded rubber gasket, and shall be attached to hydrant
adapter with 1 /8 inch, coated, stainless steel, aircraft cable.
11. Fire hydrants shall be pointed with two coats of point. Preservative paint
number 43-655 safety yellow or approved equal.
12. Pumper connection to face roadway assembly.
13. Fire hydrants shall be installed per City of Renton Standard Detail for fire
hydrants, latest revision.
14. All watermains 10 inches and smaller to maintain a minimum cover of 36 inches
below finish grade. All watermain 12 inches and larger shall be at a minimum of 48
inches below finish grade. Where utility conflicts occur, watermains are to be
lowered to clear.
15. All watermains 6 inches and larger in diameter shall be cleaned with pipe
cleaning "PIGS" prior to disinfection. The "Poly pigs" shall be Girard Industries Aqua
Swab -AS or approved equal, 2 lb/cu. ft. density foam with 90A durometer urethane
rubber coating on the rear of "PIG" only.
16. "PIGS" shall be cylinder shaped with bullet nose or square end. The contractor
will perform the cleaning operation.
17. All watermains and services shall be pressure tested to a minimum of 200 psi
or 150 psi over operating pressure, in accordance with the specifications of the City
of Renton and the Washington State Health Department. All pressure testing shall
be done in the presence of a representative of the City of Renton. The quantity of
water lost from the main shall not exceed the number of gallons per hour as listed
in City of Renton Standard Plans & Specifications 7-11.3(11). The loss in pressure
shall not exceed 5 psi during the 2 hour test period.
18. All watermains and services shall be disinfected by the injection of a 50 ppm
(minimum concentration) chlorine/water solution. Dry Calcium Hypochlorite shall NOT
be placed in the pipe as laid. Chlorine shall be metered/injected in accordance with
Section 7-11.3(12)E or 7-11.3(12)F of the Standard Specifications referenced above.
19. A pre -construction conference is required prior to any construction. A minimum
of five (5) working days notice is required for scheduling.
20. Twenty-four (24) hours notice will be required prior to starting new construction.
21. It shall be the contractor's responsibility to secure all necessary permits prior to
starting construction.
22. installation of corporate stops, water services, lines and meters shall not be
done until all service agreements, meter applications, construction permits, and
payment of fees have been made to the City of Renton.
23. All connection to existing mains is to be accomplished by the City of Renton,
except wet taps, which may be made by approved wet tap contractors with prior
approval from the Public Works Department. All necessary excavation and materials
are to be supplied by the contractor and be on -site prior to City notifications.
23. All connection to existing mains is to be accomplished by the City of Renton,
except wet taps, which may be made by approved wet tap contractors with prior
approval from the Public Works Department. All necessary excavation and materials
are to be supplied by the contractor and be on -site prior to City notifications.
24. Inspection will be accomplished by a representative of the City of Renton. It
shall be the contractor's responsibility to notify Development Services twenty four
(24) hours in advance of backfilling all construction. The contractor, as well as the
engineers, shall keep as -built drawings.
25. Contractor to provide plugs and temporary blow -off assemblies for testing and
purity acceptance prior to final tie-in.
26. All joint restraint systems (shackle rods, nuts, bolts, etc.) shall be as
manufactured by the Star Manufacturing Company of Columbus Ohio, or equal,
approved in writing by the Public Works Department.
27. Asphalt and concrete street paving shall be sawcut to a minimum depth of two
(2) inches. Oil mat streets may be spade cut. All surface concrete, pavement,
sidewalks, curb, gutters, and driveway approaches shall be sawcut to a minimum
depth of two (2) inches or removed to an existing expansion joint.
28. A temporary cold mix asphalt patch shall be placed on the day of initial
excavation with a permanent, sealed patch to be placed, to City of Renton policy,
within 10 days. Cali for subgrade inspection prior to placement of final patch.
29. For City projects such as telemetry conduit, the PVC pipe used shall be All
chemical process lines shall be schedule 80 PVC pipe. Schedule 40 in unimproved
areas and schedule 80 PVC pipe under improved areas.
RECOMMENDED CONSTRUCTION SEQUENCE
1. Pre -construction meeting.
2. Flag or fence clearing limits.
3. Post sign with name and phone number of ESC supervisor.
4. install catch basin protection if required.
5. Grade and install construction entrance(s).
6. Install perimeter protection (silt fence, brush barrier, etc.).
7. Construct sediment ponds and traps.
8. Grade and stabilize construction roads.
9. Construct surface water controls (interceptor dikes, pipe slope
drains, etc.) simultaneously with clearing and grading for project
development.
10. Maintain erosion control measures in accordance with
Snohomish County standards and manufacturer's recommendations.
11. Relocate surface water controls and erosion control measures
or install new measures so that as site conditions change the
erosion and sediment control is always in accordance with the
Snohomish County Erosion and Sediment Control Standards.
12. Cover all areas that will be unworked for more than seven days
during the dry season or two days during the wet season with
straw, wood fiber mulch, compost, plastic sheeting or equivalent.
13. Stabilize all areas that reach final grade within seven days.
14. Seed or sod any areas to remain unworked for more than 30
days.
15. Upon completion of the project, all disturbed areas must be
stabilized and best management practices removed if appropriate.
2' MIN
uy f
L 3.5'
�9 1
f
(SETTLE DEPTH)
1.5' MIN.
FLAT BOTTOM (STORAGE
NOTE: TRAP MAY BE FORMED BY BERM OR BY
PARTIAL OR COMPLETE EXCAVATION
SEDIMENT TRAP CROSS SECTION
NTS
`- 1.5' SEDIMENT STORAGE
2' SETTING DEPTH & 1' DEPTH OF
2"-4" ROCK, 1' DEPTH OF
3/4"-1/2" WASHED GRAVEL.
I►��►r_.
PERFORM MAINTENANCE AFTER EACH STORM EVENT AS DEFINED
IN THE DRAINGAGE PLAN,
1, SIZE THE BELOW GRATE INLET DEVICE (BGID) FOR THE
STORM WATER STRUCTURE IT WILL SERVICE.
2. THE BGID SHALL HAVE A BUILT-IN HIGH-FL❑W RELIEF
SYSTEM (OVERFLOW BYPASS),
3, THE RETRIEVAL SYSTEM MUST ALLOW REMOVAL OF THE
BGID WITHOUT SPILLING THE COLLECTED MATERIAL,
GEOT
rn A Tr
Ff
IS❑METRIC VIEW
CATCH BASIN PROTECTION DETAIL
NTS
JOINTS IN FILTER FABRIC SHALL BE SPLICED
AT POSTS. USE STAPLES, WIRE RINGS, OR
EQUIVALENT TO ATTACH FABRIC TO POSTS.
2"x2" BY 14 Go. WIRE OR
EQUIVALENT, IF STANDARD
STRENGTH FABRIC USED
FILTER FABRIC
TRIEVAL SYSTEM 6' MAX. I MINIMUM 4"x4" TRENCH
LJ L1\
BACKFILL TRENCH WITH
NATIVE SOIL OR 3/4"-1.5"
POST SPACING MAY BE INCREASED WASHED GRAVEL
TO 8' IF WIRE BACKING IS USED
2"x4" WOOD POSTS, STEEL FENCE
NOTE: FILTER FABRIC FENCES SHALL BE POSTS, REBAR, OR EQUIVALENT
INSTALLED ALONG CONTOUR WHENEVER POSSIBLE
ERFLOW BYPASS
TRIM GE❑TEXTILE
OVERFLOW BYPASS
SEDIMENT AND DEBRIS
4' MIN. •FILTER FABRIC FENCING
1' MIN. OVERFLOW
1' MIN, a 0
a 1' MIN.
OVERFLOW SPILLWAY 6' MIN
WIDTH
1'-3/4" TO 1.5" RIPRAP
WASHED GRAVEL 1'-2" TO 4" ROCK
NOTE: MAY BE CONSTRUCTED BY
EXCAVATION OR BY BUILDING A BERM
SEDIMENT TRAP OUTLET
NTS
DISCHARGE TO STABILIZED
CONVEYANCE, OUTLET OR
LEVEL SPREADER
THIS SET OF PLANS SUPERSEDES ALL PREVIOUS P
No, Date
1 1 5/5/O8
Revision
RESPONSE TO CITY COMMENTS
DETAIL: SILT FENCE
N.T.S.
.•
W'
z
N
DRIVEWAYS SHALL BE PAVED TO THE EDGE
OF R-O-W PRIOR TO INSTALLATION OF THE
)ONSTRUCTION ENTRANCE TO AVOID
)AMAGING OF THE ROADWAY
T IS RECOMMENDED THAT THE
:NTRANCE BE CROWNED SO THAT
RUNOFF DRAINS OFF THE PAD
i
PROVIDE FULL WIDTH OF
INGRESS/EGRESS AREA
DETAIL: STABILIZED CONSTRUCTION ENTRANCE
N.T.S.
�e4`�®P R OFFSS.
e `
CHECKED FOR COMPLIANCE
• '•;CPES
m � : �;° TO CITY STANDARDS
;�A Robert C. Elslip �.
®� No. 2330�T-
Date �
SE Date
Date
SW 1/4, SE 1/4, SEC II R TWN 23N, RGE SE, W.M. Date
PROJECT: Renton Triplexes
��. II
By E3RA Inc. " Renton, WA
CRL 9802 29th Ave. W.;: SHEET TITLE: Details and Notes
Suite B102
C
Everett, WA 98204
425-356-3372 f;F DESIGNER: CRL
425-356-3374 fax k DRAWN BY: CRL
www.e3ra.com 7; - CHECKED BY- RCE
.tea
DATE: 5/5/08
JOB NO- T07250
SCALE: As Shown
SHEET: 6
FILE: phrent.dwg