HVAC/PLUMBING LEGEND
24x12
=24xi2
DUCT — FIRST FIGURE IS SIDE SHOWN
12x12
12x12
------------------------
DUCT WITH ACOUSTICAL LINING
DIMENSIONS ARE NET FREE AREA
DIRECTION OF FLOW
INCLINED RISE (R) OR DROP (D),
ARROW IN DIRECTION OF AIR FLOW
SUPPLY DUCT — ELBOW UP OR DOWN
STANDARD BRANCH WITH SPLITTER DAMPER
RETURN DUCT — ELBOW UP OR DOWN
VD
VD=
MANUAL VOLUME DAMPER
-
STANDARD BRANCH WITH SPLITTER DAMPER
AND TURNING VANES
BD gD
BACK DRAFT DAMPER
FD
FD
FIRE DAMPER (PROVIDE ACCESS DOOR FOR
INSPECTION AND LINK REPLACEMENT.)
c T c
- EDn
ED
GRILLE AND REGISTER CONNECTION WITH
EXTRACTION DAMPER
CD
CONTROL DAMPER
AD
r___,Ap
AD
AD!---'
DUCT ACCESS DOOR
FC
FC
FLEXIBLE DUCT CONNECTION
��12 1?0 1 .x 00
CSD CSD
CEILING SUPPLY DIFFUSER INDICATING
NECK SIZE, THROW, & AIR QUANTITY
X
SUPPLY DUCT IN SECTION
z
EXHAUST OR RETURN DUCT IN SECTION
12x1
200
CER
I ; 1� 200
CER
CEILING EXHAUST OR RETURN REGISTER
INDICATING NECK SIZE, THROW, & AIR QUANTITY
OT
THERMOSTAT
�12xl
�0„`'
WSD
(�1�
�l
�00
WSD
WALL SUPPLY DIFFUSER INDICATING
NECK SIZE, THROW, & AIR QUANTITY
TS
TEMPERATURE SENSOR
12x120�12x1 200
WER WER
WALL EXHAUST OR RETURN REGISTER
INDICATING NECK SIZE, THROW, &AIR QUANTITY
HS
HAND SWITCH
M❑
FLOW METER
TURNING DUCT
WH
WATER HEATER
HB
HOSE BIBB
OI
INTERLOCK
GATE VALVE
OM
MOTOR
IOI
BALL VALVE
HVAC AND PLUMBING ABBREVIATIONS
FAN SCHEDULE
TAG NO.
LOCATION
AREA SERVED
TYPE
DRIVE
RPM
CFM
ESP (IN. W.C.)
HP
VOLTS/PHASE
NOTES
EF-1
CONTROL BUILDING
CONTROL
SIDEWALL
DIRECT
1550
650
0.25
1/8
120/1
1,2,3
BUILDING
EXHAUST
NOTES:
1. PROVIDE BACK DRAFT DAMPER.
2. ALL ONE —PHASE FRACTIONAL HP MOTORS TO BE FURNISHED WITH FACTORY —MOUNTED DISCONNECT SWITCHES.
3. THERMOSTAT —CONTROLLED.
ELECTRIC HEATER SCHEDULE
TAG NO.
LOCATION
AREA SERVED
TYPE
AIRFLOW
kW
VOLTS/
NOTES
(CFM)
PHASE
EH-1
CONTROL BUILDING
CONTROL BUILDING
UNIT
700
2
208/1
1
NOTES:
1. REMOTE THERMOSTAT CONTROLLED.
CONTROL DAMPER SCHEDULE
LOUVER
INTAKE/
AIRFLOW
WIDTH
HEIGHT
VOLTS/
TAG NO.
LOCATION
SERVED
EXHAUST
(CFM)
(IN)
(IN)
PHASE
CD-1
CONTROL BUILDING
L-1
INTAKE
650
24
24
120/1
LOUVER SCHEDULE
TAG NO.
LOCATION
AREA SERVED
INTAKE/
EXHAUST
AIRFLOW
(CFM)
WIDTH
(IN)
HEIGHT
(IN)
TYPE
L-1
CONTROL BUILDING
CONTROL BUILDING
INTAKE
650
24
24
6" ACOUSTIC
L-2
CONTROL BUILDING
CONTROL BUILDING
EXHAUST
650
24
24
6" ACOUSTIC
NOTES:
1. SEE SECTION 10.10200 FOR ADDITIONAL REQUIREMENTS.
650 CFM
L-2
BACKFLOW PREVENTER SCHEDULE
SIZE
PRESSURE
TAG NO.
LOCATION
TYPE
(INCHES)
RATING
NOTES
(PSI)
RPBA
CONTROL
REDUCED
1
175
1
BUILDING
PRESSURE
NOTES:
1. SEE SECTION 10.15400 FOR ADDITIONAL REQUIREMENTS.
AC
AIR CONDITIONING
F
FAN
NC
NORMALLY CLOSED
I I \IJ
AH
AIR HANDLING UNIT
FC
FAN COIL
NO
NORMALLY OPEN
SP=60 F
FD
FLOOR DRAIN
BD
BELT DRIVE
OSA
OUTSIDE AIR
BFP
BACKFLOW PREVENTER
GPM
GALLONS PER MINUTE
P
PUMP
BR
BOILER
I CONTROL BUILDING
CONTROL BUILDING
BTU
BRITISH THERMAL UNIT
H
HEATING
PD
PRESSURE DROP
HC
HEATING COIL
PROP
PROPELLER
I
CC
COOLING COIL
HOA
HAND/OFF/AUTO
PW
POTABLE WATER
CD
CONTORL DAMPER
HP
HORSEPOWER
RF
RETURN FAN
CENT
CENTRIFUGAL
HS
HAND SWITCH
RPBA
REDUCED PRESSURE BACKFLOW ASSEMBLY
CER
CEILING EXHAUST RETURN
HSPF
HEATING SEASONAL PROFICIENCY FACTOR
RPM
REVOLUTIONS PER MINUTE
CFM
CUBIC FEET PER MINUTE
HTG
HEATING
CH
CHILLER
HVAC
HEATING VENTILATING AIR CONDITIONING
SEER
L --------------
CHWS
CHILLED WATER SUPPLY
HWR
HEATING WATER RETURN
SP
STATIC PRESSURE/SET POINT
CHWR
CHILLED WATER RETURN
HWS
HEATING WATER SUPPLY
SQ. FT.
SQUARE FEET
CO
CLEAN OUT
CSD
CEILING SUPPLY DIFFUSER
IN.
INCHES
V
VENTILATING
CV
COEFFICIENT, VALVE FLOW
VD
VOLUME DAMPER
L
LOUVER
VTR
VENT —TO —ROOF
r-- I -------------
D
DRAIN
LAV
LAVATORY
VVT
VARIABLE VOLUME/TEMPERATURE
DB
DRY BULB
LBS
POUNDS
I / �
DH
LOSS IN FEET
LWT
LEAVING WATER TEMPERATURE
WB
WET BULB
I I
EER
ENERGY EFFICIENCY RATIO
MBH
BTU PER HOUR (THOUSANDS)
WC
WATER CLOSET
I 1
EF
EXHAUST FAN
MFGR.
MANUFACTURER
WER
WALL EXHAUST OR RETURN
ESP
EXTERNAL STATIC PRESSURE
WG
WATER GAUGE
I
EWT
ENTERING WATER TEMPERATURE
WH
WATER HEATER
I
WSD
WALL SUPPLY DIFFUSER
i
NOTES:
1. ELECTRICAL INSTALLATION BY THE ELECTRICAL CONTRACTOR IS LIMITED TO THE CONDUIT AND WIRE
NECESSARY TO PROVIDE POWER TO THE UNITS. THE CONTRACTOR SHALL PROVIDE AND INSTALL ALL
NECESSARY CONDUIT, WIRING, CONTROLS AND APPURTENANCES FOR A COMPLETE AND OPERABLE
HVAC SYSTEM.
2. ALL SPACE CONDITIONING EQUIPMENT SHALL MEET THE REQUIREMENTS OF THE WASHINGTON STATE
ENERGY CODE AND SECTION 10.15800.
3. PROVIDE PLUMBING AND DRAIN PIPING IN ACCORDANCE WITH SECTION 10.15400.
PROVIDE SERVICE CONNECTION AND METER IN ACCORDANCE WITH KING COUNTY WATER DISTRICT NO.
90 STANDARD DETAILS. SEE CIVIL DRAWINGS FOR LOCATION.
ROTFIHI LL
Roth Hill, LLC Tel 425.869.9448 www.rothhill.com
11130 NE 33rd Place, Suite 200 Bellevue, WA 98004
Kennedy/Jenks Consultants
32001 32nd Avenue South, Suite 100
Federal Way, WA 98001
Ph. 253-835-6400
Fax 253-952-3435
HVAC SCHEMATIC
SURVEYED: I SCALE:
DESIGNED:
DBT
DRAWN:
JW
t RECORD DRAWING RFB 20 12 JMF CHECKED: ONE INCH
RPR AT FULL SCALE
IF NOT ONE INCH
N 0. REVISION BY DATE A P P R APPROVED: SCALE ACCORDINGLY
1 I - - I
650 CFM
VERTICAL: NAVD 1988
HORIZONTAL- NAD 1983/1991
DATU M
S=347320
CITY OF
RENTON
Planning/Building/Public Works Dept
HOT BOX
PLUMBING SCHEMATIC
RECORD DRAWING
These Record Drawings have been prepared based on information provided
by the contractor and others. Kennedy/Jenks Consultants has not verified the
accuracy or completeness of information provided to them and does not
warrant the accuracy or completeness of these Record Drawings. Users of
these Record Drawings assume all risk of loss resulting from their use.
STONEGATE
LIFT STATION REPLACEMENT
HVAC AND PLUMBING
SCHEMATICS AND EQUIPMENT SCHEDULES
M
�0 �42 09
`SS'IONAL
DATE:
06-11-2010
PAGE:
DRAWING NO:
M1
art r S , -3 (+ -) -3 ao
20 42