ABBREVIATIONS
a
CIRCUIT BREAKER AUX. CONTACT,
FLEX
FLEXIBLE
NTS
NOT TO SCALE
CLOSED WHEN BREAKER IS CLOSED
FLUOR
FLUORESCENT
OH
OVERHEAD
A
AMMETER, AMPERES
FREQ
FREQUENCY
OT
OVER TEMPERATURE
AC
ALTERNATING CURRENT
FT
FEET, FOOT
OL
THERMAL OVERLOAD RELAY
A/D
ANALOG TO DIGITAL
FU
FUSE
PA
PUBLIC ADDRESS
ADJ
ADJUSTABLE
(F)
FUTURE
PB
PULLBOX
AF
AMPERE FRAME
FVNR
FULL VOLTAGE NON REVERSING
PE
PHOTOELECTRIC
AFD
ADJUSTABLE FREQUENCY DRIVE
FVR
FULL VOLTAGE REVERSING
PEC
PHOTOELECTRIC CELL
AFF
ABOVE FINISHED FLOOR
FWD
FORWARD
PF
POWER FACTOR
AFG
ABOVE FINISHED GRADE
GA
GAUGE
PFR
POWER FAIL RELAY
AIC
AMPERES INTERRUPTING CAPACITY
GALV
GALVANIZED
PH
PHASE
AL
ALUMINUM
GEN
GENERATOR
PLC
PROGRAMMABLE LOGIC CONTROLLER
ALT
ALTERNATOR
GFI
GROUND FAULT INTERRUPTER
A/M
AUTO/MANUAL CONTROLLER
G, GND
GROUND
PNL
PANEL
ANN
ANNUNCIATOR
GRS
GALVANIZED RIGID STEEL
PNLBD
PANELBOARD
APPROX
APPROXIMATE
H2O2
HYDROGEN PEROXIDE
PRI
PRIMARY
AS
AMMETER SWITCH
HH
HANDHOLE
PS
PRESSURE SWITCH
AT
AMMETER TRIP
HMI
HUMAN MACHINE INTERFACE
PSI
POUNDS PER SQUARE INCH
ATS
AUTOMATIC TRANSFER SWITCH
HOA
HAND -OFF -AUTOMATIC
PVC
POLYVINYL CHLORIDE
AUTO
AUTOMATIC
HOR
HAND -OFF -REMOTE
PWR
POWER
AUX
AUXILIARY
HORIZ
HORIZONTAL
(RL)
RELOCATE
AWG
AMERICAN WIRE GAGE
HP
HORSEPOWER
(RLD)
RELOCATED
b
CIRCUIT BREAKER AUX. CONTACT,
HPS
HIGH PRESSURE SODIUM
RCPT
RECEPTACLE
CLOSED WHEN BREAKER IS OPEN
HTR
HEATER
RCT
REPEAT CYCLE TIMER
BCG
BARE COPPER GROUND
HV
HIGH VOLTAGE
REQD
REQUIRED
BLDG
BUILDING
HZ
HERTZ (CYCLES PER SECOND)
RM
ROOM
C
CONDUIT, CONTACTOR
IND LT
INDICATING LIGHT
RPM
REVOLUTIONS PER MINUTE
CAB
CABINET
INCAND
INCANDESCENT
RT
RESET TIMER
CAP
CAPACITOR
INSTR
INSTRUMENT, INSTRUMENTATION
SCR
SILICON CONTROLLED RECTIFIER
CB
CIRCUIT BREAKER
1/0
INPUT/OUTPUT
SD
SMOKE DETECTOR
CC
CONTROL CABLE, CLOSING COIL
JB
JUNCTION BOX
SEC
SECONDS, SECONDARY
CHH
COMMUNICATION HANDHOLE
KA
KILOAMPERES
SECT
SECTION
CKT
CIRCUIT
KCMIL
THOUSANDS OF CIRCULAR MILS
SF
SUPPLY FAN/STATIC FILTER
CMH
COMMUNICATION MANHOLE
KV
KILOVOLTS
SHH
SIGNAL HANDHOLE
CO
CONDUIT ONLY
KVA
KILOVOLT AMPERES
SHT
SHEET
COMM
COMMUNICATION
KVAR
KILOVOLT AMPERES REACTIVE
SIG
SIGNAL
COND
CONDUCTOR
KVARH
KILOVOLT AMPERES REACTIVE
SN
SOLID NEUTRAL
CONT
CONTINUED, CONTINUATION
HOURS
SPECS
SPECIFICATIONS
CPT
CONTROL POWER TRANSFORMER
KW
KILOWATTS
SPD
SURGE PROTECTIVE DEVICE
CID
CONTROL PANEL
KWH
KILOWATT HOURS
SPDT
SINGLE POLE DOUBLE THROW
CR
CONTROL RELAY
LP
LIGHTING PANEL
SS
STAINLESS STEEL
CS
CONTROL SWITCH
LPS
LOW PRESSURE SODIUM
SSS
SOLID STATE STARTER
CT
CURRENT TRANSFORMER
LTG
LIGHTING
SW
SWITCH
CWP
COLD WATER PIPE
LTS
LIGHTS
SWBD
SWITCHBOARD
DC
DIRECT CURRENT
(M)
MODIFIED
SWGR
SWITCHGEAR
DIA
DIAMETER
mA
MILLIAMPERES
SYNC
SYNCHRONIZING
DIAG
DIAGRAM
MAX
MAXIMUM
TB
TERMINAL BOX, TERMINAL BOARD
DISC
DISCONNECT
MCC
MOTOR CONTROL CENTER
TC
TELEPHONE CABINET
DISTR
DISTRIBUTION
MCP
MOTOR CIRCUIT PROTECTOR
TEL
TELEPHONE
DN
DOWN
MFR
MANUFACTURER
TEMP
TEMPERATURE
DP
DISTRIBUTION PANEL
MH
MANHOLE
TSP
TWISTED SHIELDED PAIR
DPDT
DOUBLE POLE DOUBLE THROW
MIN
MINIMUM
TYP
TYPICAL
DPST
DOUBLE POLE SINGLE THROW
MISC
MISCELLANEOUS
UG
UNDERGROUND
DWG
DRAWING
MOV
MOTOR OPERATED VALVE
UH
UNIT HEATER
(E)
EXISTING
MS
MOTOR STARTER
V
VOLTS
EA
EACH
MTD
MOUNTED
VA
VOLT-AMPERES
EF
EXHAUST FAN
MTG
MOUNTING
VFD
VARIABLE FREQUENCY DRIVE
EHH
ELECTRICAL HANDHOLE
MTS
MANUAL TRANSFER SWITCH
VAR
VOLT AMPERES REACTIVE
EL, ELEV
ELEVATION
(N)
NEW
VERT
VERTICAL
ELEC
ELECTRIC, ELECTRICAL
NC
NORMALLY CLOSED
VH
VAR -HOUR
ELEM
ELEMENTARY
NEC
NATIONAL ELECTRICAL CODE
VS
VOLTMETER SWITCH
EMERG
EMERGENCY
NEMA
NATIONAL ELECTRICAL
W
WIRE, WATTS
ENCL
ENCLOSURE
MANUFACTURER'S ASSOC.
WHIM
WATTHOUR METER
EQ
EQUAL
NEUT
NEUTRAL
WHDM
WATTHOUR DEMAND METER
EQPT
EQUIPMENT
NIC
NOT IN CONTRACT
WP
WEATHERPROOF
ETM
ELAPSED TIME METER
NO
NORMALLY OPEN, NUMBER
WT
WATERTIGHT
FDR
FEEDER
WTP
WATER TREATMENT PLANT
XFMR
TRANSFORMER
GENERAL NOTES:
G1. THESE DRAWINGS ARE
G2. THIS IS A GENERALIZED LEGEND
G4. INFORMATION SHOWN MAY NOT
DIAGRAMMATIC ONLY; EXACT
SHEET. THIS CONTRACT MAY
BE ALL INCLUSIVE. SEE ALSO
LOCATIONS OF ELECTRICAL
NOT USE ALL INFORMATION
ANSI C37.2, Y1.1, Y32.2, AND
EQUIPMENT SHALL BE DETERMINED
SHOWN.
Y32.9.
IN THE FIELD BY THE ENGINEER.
G5. VERIFY ALL COLOR
THE INSTALLATION OF ALL
G3. NOTIFY THE ENGINEER
REQUIREMENTS BEFORE
EQUIPMENT SHOWN ON THESE
IMMEDIATELY IF CONFLICTS IN
ORDERING MATERIALS.
DRAWINGS OR DESCRIBED IN THE
EQUIPMENT LOCATIONS ARE
SPECIFICATIONS SHALL CONFORM TO
DISCOVERED OR IF PROBLEMS
G6. REFER TO THE MECHANICAL
THE REQUIREMENTS SET FORTH IN
ARISE DUE TO FIELD CONDITIONS,
DRAWINGS FOR CERTAIN
THE LATEST EDITIONS OF ALL
LACK OF INFORMATION OR ANY
CONTROL DIAGRAMS AND
APPLICABLE CODES AND UTILITY
OTHER REASON. NO PAYMENT
EXACT LOCATIONS OF
COMPANY STANDARDS. CONTACT
WILL BE MADE FOR CHANGES
MECHANICAL EQUIPMENT AND
THE UTILITY COMPANY
WHICH HAVE NOT BEEN
FOR CERTAIN CONNECTIONS TO
REPRESENTATIVES AND VERIFY
FAVORABLY REVIEWED BY THE
BE MADE TO ELECTRICAL
THEIR REQUIREMENTS
ENGINEER.
CIRCUITS.
PLAN NOTES:
P1. CONDUIT SIZE AND FILL SHALL BE AS INDICATED
WHERE NO SIZE IS SHOWN, THE CONDUIT SHALL
BE SIZED IN ACCORDANCE WITH THE EDITION OF
THE NATIONAL ELECTRICAL CODE ADOPTED BY
THE AUTHORITY HAVING CODE ENFORCEMENT
JURISDICTION. WHERE NO FILL IS INDICATED,
THE FILL SHALL BE 2#12. PROVIDE 3/16 INCH
NYLON PULL ROPE IN EACH EMPTY CONDUIT.
P2. CONDUIT AND WIRE LAYOUT FOR
LIGHTING AND RECEPTACLES NOT
SHOWN. PROVIDE PER NEC.
P3. LETTERS ADJACENT TO A LIGHT FIXTURE
INDICATE CIRCUIT INFORMATION. THE FIRST
LETTER DENOTES THE FIXTURE TYPE PER THE
FIXTURE SCHEDULE. PANEL AND CIRCUIT
IDENTIFICATION IS SHOWN IN BRACKETS. THE
SWITCH IDENTIFICATION IS SHOWN AS A LOWER
CASE LETTER.
P4. NUMBER OF CIRCLES DOES NOT
REPRESENT THE NUMBER OF CONDUITS
IN THE ENCASEMENT.
ROTFIHI
Roth Hill, LLC Tel 425.869.9448 www.rothhill.com
11130 NE 33rd Place, Suite 200 Bellevue, WA 98004
Kennedy/Jenks Consultants
32001 32nd Avenue South, Suite 100
Federal Way, WA 98001
Ph. 253-835-6400
Fax 253-952-3435
PLAN SYMBOLS
OH OVERHEAD POWER LINE
UNDERGROUND CONDUIT
UNDERGROUND DUCT LINE
(CONCRETE ENCASEMENT)
01 NOTE P4
UNDERGROUND DIRECT
BURIAL CONDUITS
NOTE P4
O
MULTIPLE CONDUIT RUN
CONDUIT CONCEALED IN
FLOOR
- - - - - - - - CONDUIT CONCEALED IN
WALL & CEILING
CONDUIT EXPOSED
CALLOUT INDICATING CONDUIT
3/4"C-3#12, SIZE, NUMBER OF WIRES AND
1#12G WIRE SIZE
CALLOUT INDICATING CONDUIT
100 PER SCHEDULE
CONDUIT RUN, HATCH MARKS
INDICATE NO. OF #12 CONDUCTORS
NO HATCH MARKS IS 2#12
UNLESS OTHERWISE NOTED
CONDUIT RUN, HATCH MARKS
#10 INDICATE NUMBER OF CONDUCTORS
III CALLOUT INDICATES
CONDUCTOR SIZE
HOME RUN TO PANELBOARD
OR AS INDICATED
FLEXIBLE CONDUIT
CONDUIT RUN, BROKEN AND
CONTINUED ON SAME SHEET
OR AS NOTED
CONDUIT WITH SEAL FITTING
] CAP ON CONDUIT STUB
OPEN CIRCLE DENOTES UPWARD
CONDUIT RISER
SOLID CIRCLE DENOTES DOWNWARD
CONDUIT RISER
INDICATES REMOVAL
F FIRE ALARM CONDUIT
T TELEPHONE CONDUIT
T/D TELEPHONE/DATA CONDUIT
SURFACE MOUNTED PANELBOARD
FLUSH MOUNTED PANELBOARD
O MOTOR
DISCONNECT SWITCH
COMBINATION MOTOR STARTER AND
DISCONNECT SWITCH
SMS MANUAL MOTOR STARTER
❑e CONTROL STATION
�— EQUIPMENT MOUNTING STAND
GROUND ROD AND BOX
® INSTRUMENT
❑D MAGNETIC DOOR HOLDER
K] INTRUSION REMOTE KEY PAD
O INTRUSION DOOR SWITCH
SAP SECURITY ALARM PANEL
S SECURITY ALARM CONDUIT
PA PUBLIC ADDRESS INDOOR SPEAKER
�PAJ PUBLIC ADDRESS OUTDOOR SPEAKER
PA PUBLIC ADDRESS CONDUIT
S* SINGLE POLE SWITCH
�k 2= 2 POLE, 3= 3 WAY, 4= 4 WAY,
K = KEY OPERATED
WP = WEATHERPROOF
D = DIMMER
P = SWITCH WITH PILOT LIGHT
Sab
SINGLE POLE SWITCH (NOTE P3)
Sab
DUAL RELAY WALL SWITCH INFRARED
OCCUPANCY SENSOR
O FLUORESCENT FIXTURE
(NOTE P3)
O FLUORESCENT FIXTURE WITH
NIGHT LIGHTING (UNSWITCHED)
OR FLUORESCENT FIXTURE WITH
SELF-CONTAINED EMERGENCY
BALLAST/BATTERY
❑ WALL/CEILING MOUNTED FIXTURE
j �( WALL/CEILING MOUNTED FIXTURE
' N� �1,� NIGHT LIGHTING (UNSWITCHED)
0-0 POLE MOUNTED FIXTURE
WALL/CEILING MOUNTED EXIT
b ®b LIGHT - DIRECTIONAL ARROW
WHERE INDICATED, SHADED AREA
INDICATES ILLUMINATED FACE
EMERGENCY LIGHT WITH SELF
CONTAINED BATTERY
A(LX-X)a LIGHT FIXTURE IDENTIFICATION
(NOTE P3)
IO
SINGLE RECEPTACLE, 120V
H�
SINGLE RECEPTACLE, 208V OR 240V
DUPLEX WALL RECEPTACLE, 120V
WP = WEATHERPROOF
G = GROUNDED
IG = ISOLATED GROUND
GF = GROUND FAULT INTERRUPTER
DOUBLE DUPLEX WALL RECEPTACLE
120V
DUPLEX FLOOR RECEPTACLE, 120V
MULTI -OUTLET ASSEMBLY
WITH DUPLEX RECEPTACLE,
120V. SPACING AS NOTED,
MOUNTING HEIGHT AS NOTED.
SD RECEPTACLE, 480V
I_ O WALL/CEILING MOUNTED
'��J JUNCTION BOX
FLOOR RECESS MOUNTED
JUNCTION BOX
ST THERMOSTAT, WALL MOUNTED
Q WALL TELEPHONE OUTLET
® FLOOR TELEPHONE OUTLET
T WALL TELEPHONE/DATA OUTLET
u FLOOR TELEPHONE/DATA OUTLET
r LTJ FIRE ALARM PULL STATION
MF FIRE ALARM HORN
`ice FIRE ALARM HORN WITH VISUAL
OHEAT DETECTOR
OSMOKE DETECTOR
EOL END OF LINE RESISTOR
FACP FIRE ALARM CONTROL PANEL
CR CARD READER
0 ❑ ELEC MANHOLE/ELEC HANDHOLE
EMH EHH
❑ ❑ SIGNAL HANDHOLE/TEL HANDHOLE
SHH THH
SINGLE LINE SYMBOLS
GROUND CONNECTION
0�0 SWITCH, 3 POLE EXCEPT WHERE NOTED.
RATING IN AMPERES AS NOTED
AUTOMATIC TRANSFER SWITCH
3 POLE, RATING AS NOTED
ST SHUNT TRIP
® FUSE
o�o FUSE CUTOUT
CIRCUIT BREAKER, 3 POLE EXCEPT WHERE
° MCP ° )OOOAT NOTED. RATING IN AMPERES AS NOTED.
IF TWO RATINGS APPEAR (EG. 100/625) THEN
0 OOAT 0 OOOAF DEVICE IS MCP; NUMERATOR IS CONTINUOUS
CURRENT RATING & DENOMINATOR IS
INSTANTANEOUS TRIP SETTING.
POWER CIRCUIT BREAKER
DRAWOUT ABOVE 1500V RATING AS NOTED
SURGE ARRESTER
SCURRENT TRANSFORMER
VOLTAGE TRANSFORMER
UI)i POWER OR DISTRIBUTION TRANSFORMER
RATING AS NOTED
100 MOTOR. NUMBER INDICATES HORSEPOWER
OGEN GENERATOR
O CONTROL PACKAGE PROVIDED WITH
THE DRIVEN EQUIPMENT
BUS STAB ON MCC OR SWITCHGEAR,
u CORD & PLUG CONNECTION FOR MOTORS
o �Cro THERMAL OVERLOAD
* A — AMMETER
O V — VOLTMETER
WH — WATTHOUR METER
GS — GROUND FAULT SENSOR
AS AMMETER SWITCH
VS VOLTMETER SWITCH
127 ELEMENTARY ELEMENTARY DIAGRAM NUMBER
K KIRK KEY INTERLOCK
POWER RECEPTACLE
FOR PORTABLE EQUIPMENT
# RELAY DEVICE FUNCTION,
# PER ANSI NUMBER C37.2
TERMINATOR / POTHEAD
—}— SPLICE, TERMINATION
T 2 MOTOR STARTER. NUMBER INDICATES NEMA SIZE
,T` CAPACITOR — KVAR INDICATED
AFD * AFD — ADJUSTABLE FREQUENCY DRIVE
SSS — SOLID STATE STARTER
CALLOUT INDICATING CONDUIT
100 PER SCHEDULE
P001 CALLOUT INDICATING CIRCUIT NUMBER
PER SCHEDULE
SPD SURGE PROTECTIVE DEVICE
SURVEYED: SCALE:
VERTICAL: NAVD 1988
- - HORIZONTAL: NAD 1983/1991
DESIGNED:
VAB
DRAWN:
LMM ONE INCH
i RECORD DRAWING RFB 20 1 PAR CHECKED: DATUM
PAR AT FULL SCALE
IF NOT ONE INCH
NO. REVISION BY DATE AP P R APPROVED: SCALE ACCORDINGLY
ELEMENTARY DIAGRAM SYMBOLS
CROSS REFERENCE TO
® FUSE. RATING IN AMPERES ANOTHER DIAGRAM
NORMALLY OPEN CONTACT
M MOTOR ETM ELAPSED TIME METER ON THE OTHER DIAGRAM
1)_ 2-2, 3, 0, 0
/1 7
* * CONTROL DEVICE COIL. PREFIX NUMBER, CIR - S
WHEN USED, DISTINGUISHES BETWEEN SPARE CONTACTS ON RELAY.
DEVICES OF THE SAME TYPE. IF OMITTED, THEN THE SPEC.
REQUIREMENTS REGARDING
ALT - ALTERNATOR LR - LATCH RELAY SPARE CONTACTS APPLY.
CR - CONTROL RELAY SV - SOLENOID VALVE NORMALLY CLOSED CONTACT
GR - GENERAL RELAY PR - PROBE RELAY ON THIS DIAGRAM
ISR - INTRINSICALLY SAFE TR -
TIMING RELAY
RELAY
INDICATING LIGHT
o *
PUSH -TO -TEST INDICATING LIGHT
1 f0
* COLORS:
A - AMBER R
- RED
B - BLUE N
- NEON
C - CLEAR W
- WHITE
G - GREEN Y
- YELLOW
0N OFF
SINGLE POLE SWITCH
EMERGENCY PUSHBUTTON
0 0
�Q PUSHBUTTON,
0 0 NORMALLY OPEN / CLOSED
0 -0
o% vI SWITCH,
° ISO 1-POLE / 3-POLE
I
0�0
MULTI —POSITION SELECTOR SWITCH
0
H 0 A
HAND -OFF -AUTOMATIC SWITCH
I` I X-INDICATES CONTACTS CLOSED
I I I
S0 1 0->K-
H1 H3 H2 H4
X1 X2
SENSING SWITCHES
CLOSE ON
SENSED VARIABLE
RISING
FALLING
FLOW
LEVEL
O-Z
PRESSURE
TEMPERATURE
LIMIT SWITCHES
V
CLOSE ON REACHING LIMIT
0__j6
CLOSE ON LEAVING LIMIT
TIMED CONTACTS
SYMBOL
NORMAL
OPEN TO
CLOSED
CLOSED TO
OPEN
0-f
OPEN
DELAYED
INSTANTANEOUS
CLOSED
INSTANTANEOUS
DELAYED
OPEN
INSTANTANEOUS
DELAYED
CLOSED
DELAYED
INSTANTANEOUS
HAND -OFF -REMOTE SWITCH ELEMENTARY DIAGRAM NOTES:
X-INDICATES CONTACTS CLOSED E1. UNDERLINED WORDS SHOWN AT A PUSHBUTTON,
LIGHT, SELECTOR SWITCH, ETC. INDICATE THE
LEGEND PLATE REQUIREMENT FOR THAT
PARTICULAR DEVICE. ANY ADDITIONAL
NAMEPLATES ARE INDICATED ON ELEVATIONS WITH
THE REQUIRED NAMEPLATE INSCRIPTIONS.
TERMINAL
E2• "NORMAL" STATUS OF SWITCHES OR
CONTACTS IS THE SHELF POSITION.
E3. NUMBERS AND LETTERS IDENTIFY DEVICE.
CONTROL POWER TRANSFORMER
MOTOR HEATER MOTOR HEATER
o I o
0
4--, CIRCUIT BREAKER,
o ° I ° 1—POLE / 3—POLE
0
GROUND CONNECTION
CONTACT,
NORMALLY OPEN / CLOSED
BUS STAB ON MCC; CORD & PLUG
CONNECTION FOR MOTORS
OL
OjXro THERMAL OVERLOAD
g BELL �1 HORN S=347329
RECORD DRAWING
These Record Drawings have been prepared based on information provideti
by the contractor and others. Kennedy/Jenks Consultants has not verified the
accuracy or completeness of information provided to them and does not
warrant the accuracy or completeness of these Record Drawings. Users of
these Record Drawings assume all risk of loss resulting from their use.
�31892
�QVAL �
DATE:
'4R STONEGATE 05-24-2010
CITY OF LIFT STATION REPLACEMENT
FlELDBOOK:
RENT 0 N PAGE:
DRAWING NO:
Planning/Building/Public Works Dept. ELECTRICAL ABBREVIATIONS AND SYMBOLS El
SHEET: OF:
29 42