HomeMy WebLinkAboutWTR2703530.17FLOW
TRANSMITTER
INSERT FOR TRAFFIC AREAS COVER STEEL ,
CONCRETE ONLY FOR N❑N-TRAFFIC
USE AREAS
STATION FLOOR
FLOW ELEMENT
FOGTITE GROUND
ROD BOX #SP-1
GROUNDING BUSHING OR EQUAL
(IF CONDUIT IS STEEL
• BURNDY GROUND CLAMP
CHASE FLOOR
GROUND ROD
PIPE CHASE
fPwni ITT Tn . r`rTmi-rI rn r'r1KIT)I ITT ..
SERVICE
EQUIPMENT FLOW METER
F TYPICAL INSTALLATION DETAIL
XE04 TYPICAL INSTALLATION DETAIL FOR EQUIPMENT IN PIPE CHASE
SHOWING C❑NCELED RACEWAYS IN FLOOR AND STUB UP UNDER
GROUND ROD DETAIL C EQUIPMENT. TYPICAL FOR ALL PIPE CHASE INSTALLATIONS SUCH AS
SCALE: NONE VAR PRESSURE TRANSMITTERS AND CONTROL VALVES
PRESSURE WALL
GAUGE
PRESSURE
XMTR WITH
DISPLAY
TEST
VALVE
WITH PLUG
tP BOX
4'x12' PVC NIPPLE
8' TO 3/4' ADAPTOR
FLOOR
GEMS SWITCH LS-1800 SERIES
MOUNT TO TRIP AT FLOOR ELEVATION
(❑R HI LEVEL)
rD) FLOOD SWITCH MOUNTING DETAIL
XE04
NTS
PRESSURE TRANSMITTER OR SWITCH
TYPICAL INSTALLATION DETAIL A
VAR
LIGHTING FIXTURE SCHEDULE
FIXTURE
M FG. CATA _OG #
LAMPS
DESCRIPTION
INDUSTRIAL 2 LAMP 1X4 FLOURESCENT - WET LOCATION, RECESSED MOUNTED. POWDER PAINTED STEEL
F1
LITH0N1A W RT
(2) LAMPS 32W
HOUSING, ALUMINUM DOOR FRAME, UL LISTED FOR WET LOCATIONS.
F2
COLUMBIA CSR
(2) LAMPS 32W
4' (2) LAMP FLUORESCENT W/5%o UPLIGHT, SURFACE MOUNT. DIE FORMED STEEL HOUSING,
INDUS--RIAL
F3
NIGHTBRITES
100W METAL
WALL MOUNTED 100W METAL HALIDE FIXTURE -OUTDOOR RATED 0-DEGREE BALLAST, 120V.
W LM TYPE
HALIDE
F4
MCPH[-BEN
2 HALOGEN
EMERGENCY WALL PACK, 2 LAMP W/ RECHARGEABLE BATTERY, VOLTMETER 120V.
SU SERIES
DIMMIT PLIMPSTATION LOADS
s
LOAD DESCRIPTION
DUTY
NO.
HP
EACH
KVA
EACH
Total
Duty
KVA
PLANT LOAD
NO. KVA
PUMP 1
1
150.0
144
144
1.25 180
:PUMP 2
1
15.0
17
17
1 17
:PUMP 3
1
15.0
17
17
1 17
PUMP 4
1
15.0
17
17
1 17
SITE LIGHTING
1
1
1
1 ? 1
HEAT
1
12
12
1 ' 12
MISC
1
8
8
1 8
Total
Duty
DESIGN TOTAL
KVA SUB -TOTAL'
216
KVA 252
AMPS @ 480V, 3P
-
260
AMPS 303
I
I
GENERATOR LOAD
NO. KVA ,_
1 144
1 17
1 17
1 1
1 12
1 8
GEN TOTAL
WX 216
AMPS' 260
CONDUIT & WIRE SCHEDULE
TAG #
CONDUIT
SIZE TYPE
WIRE DESCRIPTION
FROM
TO
NOTES
PRIM
4" *
PVC
PRIMARY CABLES
UTILITY SERVICE
UTILITY XFMR
UTILITY PRIMARY SERVICE
P-01SRV
(2) 4"
PVC
(2) 3 #350 & 1/OG
UTILITY XFMR
CT CABINET
SERVICE
P-02SRV
(2) 4"
PVC
(2) 3 #350 & 1/OG
CT CABINET
ATS
SERVICE ENTRANCE""
P-GEN
(2) 3
PVC
(2) 3-4/0 & #2G
GEN
ATS
P-01
1
PVC
3#10 & #10G
MCC
PUMP 1
P-02
11'
PVC
3#10 & #10G
MCC
PUMP 2
P-03
1"
PVC
3#10 & #10G
MCC
PUMP 3
P-04
3"
PVC
3-4/0 & #2G, 2#14
MCC
PUMP 4
C-MCP
3"
GRC
#14 & #12 AS REQUIRED
MCC
MCP
CONTROL / 120V
C-GEN
1"
PVC
#14 AS REQUIRED
MCP
GEN CONTROL PNL
S-MCP
1-1/2"
PGRC
3#16 TSP
MCC
MCP
S-LT
1-1/2"
PGRC
3#16 TSP & 10#14
RENTON TELEM PNL
MCP
RENTON INTERFACE
TEL
4" *
PVC *
6 PAIR TELEPHONE CABLE
TELEPHONE SERVICE
PUMP STATION
TELEPHONE "
NOTE: CONDUIT TYPE REFERS TO THE MOST PREVELENT TYPE USED FOR THAT TAG -TYPES MAY CHANGE - SEE SPECIFICATIONS SECTION 16110 FOR DETAIL
GRC= GALVANIZED RIGID STEEL, PGRC = PVC COATED GRC
* = PER UTILITY REQUIREMENTS
PANEL SCHEDULE
PNL NO. A 208Y/120V, 3PHASE
LOCATION: DIM MIT PS 100 AMP WITH 50AMP MAIN BREAKER
NO.
LOAD DESCRIPTION
TRIP
AMPS
TRIP
AMPS
LOAD DESCRIPTION
NO.
1
LIGHTS PUMP ROOM
0.6
20/1
20/1
0.8
REC - PUMP RM
2
3
LIGHTS PUMP ROOM
0.6
20/1
20/1
0.6
REC PUMP RM
4
5
LIGHTS - EXTERIOR
0.5
20/1
20/1
0.4
REC GEN RM
6
7
LIGHTS - GEN ROOM
0.4
20/1
20/1
0.2
REC PUMP RM -DEDICATED CKT
8
9
SPARE
20/1
2011
SPARE
10
11
SPARE
20/1
2011
0A
BATTERY CHARGER
12
13
SUPPLY FAN
0.7
20/1
20/1
0.5
CONTROL PANEL - MCP
14
15
SPARE
20/1
20/1
SPARE
16
17
CV-1
0.5
20/1
20/1
SPARE
18
19
CV-2
0.5
20/1
20/1
SPARE
20
21
CV-3
0.5
20/1
20/1
SPARE
22
23
CV-4
0.5
20/1
20/3
SPARE
24
25
CV-5
0.5
20/1
26
27
CV-6
0.5
20/1
28
29
SPARE
20/1
20/3
SPARE
30
31
SPARE
20/1
32
33
SPARE
20/1
34
35
SPARE
20/1
30/1
SPARE
36
5.8
2.6
FOLLETT ENGINEERING TOTAL KVA = 8.4
425-836-3333 AMPS @ 208V 3 PHASE = 23.3
W=3530
REVISION
AA3, l,. 2 - 3 5 0 %